**HITACHI RAK-VJ25PHAT Split Type Air Conditioner Instruction Manual
**
SAFETY PRECAUTION
- Read the safety precautions carefully before operating the unit.
- The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ………. Incorrect methods of installation may cause death or serious injury.
CAUTION ………. Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of the unit as described in the user’ s guide. Ask a customer to keep this installation manual together with the instruction manual.
WARNING
- Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the installation work yourself.
- Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause water leakage, electric shock and fire.
- Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may collapse and impose danger.
- Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and fire may occur due to the use of low quality wire or improper work.
- Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the terminal base. Improper insertion and loose contact may cause over heating and fire.
- Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or stronger vibration may occur.
- Be sure to use the specified piping set for R32. Otherwise, this may result in broken copper pipes or faults.
- When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant( R32) does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
- Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
- After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
- Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
- Be sure to connect the earth line from the power supply wire to the outdoor unit and between the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the telephone unit. Improper earthing may cause electric shocks.
- When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe. If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
- When installing the unit, be sure to install the refrigerant pipe before starting the compressor. If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
- The electric cables should neither be reworked nor added. Make sure to use an exclusive circuit breaker. Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
- Make sure to connect cables to terminal properly and terminal cover should close firmly. Otherwise, over heating at terminal contact, fire or electric shock might occur.
- Make sure that there is no dust on any connected points of electric cables and fix firmly. Otherwise, fire or electric shock might occur.
CAUTION
-
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
-
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
-
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your fu niture.
-
An IEC approved power cord should be used. Power cord type: NYM.
THE CHOICE OF MOUNTING SITE
(Please note the following matters and obtain permission from customer before installation.)
WARNING
The unit should be mounted at stable, non-vibratory location which can provide full support to the unit.
CAUTION
-
No nearby heat source and no obstruction near the air outlet is allowed.
-
The clearance distances from top, right and left are specified in figure below.
-
The location must be convenient for water drainage and pipe connection with the Outdoor unit.
-
No nearby leakage risk of flammable gas, and no nearby source of vapor
or oil smoke. -
To avoid interference from noise, please place the unit and its remote controller at least 1m from the radio and television.
-
To avoid any error in signal transmission from the remote controller, please put the controller far away from high- frequency machines and high power wireless systems.
-
The installation height should be at least 2300 mm or more from the floor.
-
The distance from the air outlet to the fire alarm must be at least 1500mm and there must be no fire alarm in the front direction of the indoor unit.
Figure showing the Installation of Indoor Unit.
Direction of Piping
There are 4 directions allowed, namely, horizontally piping from right,horizontally piping from left, vertically down from right.
NO. | Item | Qty |
---|---|---|
1 | Hanger | 1 |
2 | Screw for Hanger | 5 |
3 | AAA size Battery | 2 |
4 | Remote Controller | 1 |
5 | Screw for Remote | |
Controller Holder | 2 | |
6 | Insulation sheet | 1 |
7 | Binding band | 2 |
8 | Air purifying filter | 2 |
9 | C-case | 2 |
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe
from the left side as shown in below. Be sure to plug in the drain hose until
the insulating material folds upon itself
Please use pliers to pull out the drain cap. (This is an easier way to remove the drain cap).
CAUTION
Insufficient insert may result in water leakage
- Push the pipe deeply until the insulating section of the drain hose end gets over the rib at the indoor unit side
- Remove low cover
- Insert drain cap up to the
- Please use hexagonal wrench key(Φ4mm) to insert the drain cap. (This is an easier way to install the drain cap.)
CAUTION
- The rubber strap used for fixing the insulator should not be tied with great force.Otherwise,this will damage heat insulation and causes water condensation.
- Please pull the lower part of the Indoor unit outwards to check if the unit is hooked onto the hanger. Improper installation may cause vibration and noise.
- Transform the piping while holding down the lower portion of pipe-support by hand.
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
- The refrigerating pipe should be adjusted to fit into the hole on the wall and then ready for further connection.
- The terminals of 2 connected pipes must be covered with insulator used for terminal connection. Then the pipes are wrapped with insulation pipe.
- Connect the connecting cord after removing low cover. (Refer to “CONNECTION OF POWER CORD”)
- After adjustment, fit the connecting cord and pipes into the space available under the unit. Use holder to hold them tight. Pipe Connecting cord Drain hose
- Be sure to cut the extra binding band. (Otherwise, it may result in abnormal noise or dewfall.)
THE CONNECTION OF REFRIGERATING PIPE DURING THE INSTALLATION OF INDOOR UNIT
The refrigerating pipes and connecting cord transform and are attached
The end of the refrigerating pipes are at locations marked with “ ” symbol. (Refer to installation hanger drawing)
Installation
Hang the indoor unit onto the hanger. Use the temporary stand at the back of the Indoor unit to push its lower part 15cm forwards.
- Place the drain hose through the hole on the wall.
- Wrap the refrigerating pipes with insulation pipe after connecting refrigerating pipe.
- Connect the connecting cord after removing low cover.
- After adjustment, the connecting cord and refrigerating pipes are placed into the space available under the Indoor unit.
- The projection of Indoor unit must hook to the hanger.
INSTALLATION OF REFRIGERATING PIPES AND AIR REMOVAL
Preparation of Pipe
Use a pipe cutter to cut the copper pipe and remove burr.
CAUTION
- Remove burr and jagged edge will cause leakage.
- Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
- Before flaring, please put on the flare nut.
O uter Diameter (Ø) | A (mm) Rigid Flaring Tool |
---|---|
For R410A,R32 too | For R22 tool |
6,35 (1/4″) | 0 – 0,5 |
9,52 (3/8″) | 0 – 0,5 |
Pipe Connection
CAUTION
- In case of removing flare nut of a indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Free from water into the piping when working.
- Be sure to tighten the flare nut to the specified torque with a torque wrench. If the flare nut is overtightened, the nut may be split after a long period has passed, and may cause a refrigerant leak.
- Please be careful when bending the copper pipe.
- Screw in manually while adjusting the center. After that, use a torque wrench to tighten the connection.
Gas leakage inspection
Please use gas leakage detector to check if leakage occurs at connection of Flare nut as shown in below. If gas leakage occurs, further tighten the connection to stop leakage.
CONNECTION OF POWER CORD
Detail of Cutting the Connecting Cord
WARNING
- Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the cord band.
- Secure the connecting cord along the coated part of the wire using the cord band. Do not exert pressure on the wire as this may cause overheating or fire.
Wiring of The Indoor Unit
- For wire connection of the Indoor unit, you need to remove the front cover, the low cover under the body of the unit and terminal cover.
- Remove the cover from the terminal base and screw the cable.
After remove the screw and terminal cover, and put the connecting cords and fix the terminal cover with screw.
Method to remove the low cover
Pull at the 1 and 2 in the directions as shown by arrows to remove the cover.
How to connect the optional parts(H-LINK RAC Adapter, Dry contact, Wired Remote Controller, Run status and alarm output)
- For cable connection to control P.W.B., you need to remove front cover and electrical box cover. Each connecting location is as below.
- Please check and confirm manuals attached to each optional parts for more connection details. Y
- Please check service manual about how to set from remote controller. ou can refer to this installation manual how to remove and re-attach the front cover. Please
- Please do the operation test after the connection. be careful not to damage lead wires by edge of plate when connecting the optional parts
Installation of Hanger , Wall Penetration and Installation of Protection
Pipe
CAUTION
The draining of the water container inside the Indoor unit can be done from the left. Therefore the hanger must be fixed horizontally or slightly tilted towards the side of drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Procedures of Installation and Precautions
- Drill holes on wall.
- Push plug into the holes.
- Fix the hanger on wall
- Drill holes on wall.(As shown below)
- Push plug into the holes.(As shown below)
Installation Of Remote Controller
-
The remote controller can be placed in its holder which is fixed on
wall or beam. -
To operate the remote controller at its holder, please ensure that the unit can receive signal transmitted from the controller at the place where the holder is to be fixed.The unit will beep when signal is received from eht yb nekaew si noissimsnart langis ehT .rellortnoc etomer eht fluorescent
esaelp ,redloh lortnoc etomer eht fo noitallatsni eht gnirud ,eroferehT .thgil
switch on the light, even during day time, to determine the mounting location of the holder.
WARNING
Be sure that the wire is not in contact with any metal in the wall. Please use
the protection pipe as wire passing through the hollow part of the wall so as
to prevent the possibility of damaged by mouse. Unless it seals completely,any
air with high humidity flows from outdoor and any dew may drop.
Installation Of The Indoor Unit
Cutting Low Cover bush
While installing the pipe from the right, left or bottom side, use a knife to
cut openings as shown in figure. Then smoothen the edges of openings with a
file.
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
- Connect connecting cord.
- Pull out the pipe, connecting cord and drain hose
Installation
Insert the pipe through the wall hole.
- The upper part of the Indoor unit is hanged on the hanger.
- The projection at the lower part of the Indoor unit is hooked onto the hanger.
Heat Insulation and Finish of the Piping
- The connected terminals should be completed sealed with heat insulator and then tied up with rubber strap.
- Do not tie the terminals with the tape too tight. If any clearance or over-tightening may cause condensation.
- Please tie the pipe and power line together with vinyl tape as shown in the figure showing the installation of Indoor and Outdoor units.
- To enhance the heat insulation and to prevent water condensation, please cover the outdoor part of the drain hose and pipe with insulation pipe.
- Completely seal any gap with putty.
Installation of Drain Hose
CAUTION
Be sure that the drain hose is not loosely connected bend or proper condition
like left figure.
CAUTION
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor unit
during installation. (Careless may result in water leakage.)
HOW TO REMOVE INDOOR UNIT
Push up the [PUSH] sections at the bottom of the indoor unit and pull the bottom plate towards you. Then the claws are released from the stationary plate. (The [PUSH] sections are indicated by 2 arrows in the right figure)
HOW TO REMOVE OR ATTACH THE FRONT COVER
How to remove the front cover
- Push the end of the right-side arm outward to release the tab.
- Move the left-side arm outward to release the left tab, and then pull the panel towards you
- Remove the filters.
- After removing 1 screw, then remove the 2 screws, pull the center of the front cover towards you and release the
- Pull the side faces (lower sections) of the front cover towards you as shown in the figure and remove the cover.
How to Attach the Front Cover
- After installing the front cover onto the unit, hook three claws at upper side of the cover securely. Then, push the center of the front cover to lock the claws.
- Tighten the 2
- Assemble the cover of electric box, then tighten the screw. screws.
- Install the filter.
- Insert the shaft of the left arm along the step on the unit into the hole.
- Securely insert the shaft of the right arm along the step on the unit into the hole.
- Make sure that the front panel is securely attached, and then close the front panel.
CAUTION
Remove and attach the front cover to the direction as shown in the figure to
ensure no damage occurs to the ECO sensor
- Please mount the Outdoor unit of stable ground to prevent vibration and increase of noise level.
- Decide the location for piping after sorting out the different types of pipe available.
- When removing side cover, please pull the handle after undoing the hook by pulling it downward.
CAUTION Do not touch the suction port, bottom surface,or aluminum fin of the outdoor unit.Failure to do so may cause an injur
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
- There is holes on the base of Outdoor unit for condensed water to exhaust.
- In order to flow condensed water to the drain, the unit is installed on a stand or a block so that the unit is 100mm above the ground as shown figure. Join the drain pipe to one hole.
- After installation, check whether the drain pipe clings to the base firmly.
- Install the outdoor unit horizontally and make sure that condensate drains away.
- In case of using in chilly area pecially, in case that there are many snows by very cold in chilly area, condensed water freezes dna tfeL(.tinu fo mottob eht ta epip niard eht dna hsub ehtevomer esaelp ,esac siht nI .niard ot ton tluser yam dna esab eht no center near discharge portion of air, each 1 place).It becomes smooth drain.Ensure that the distance from the drain hole to the ground is 250 mm or more
- A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit breaker, the danger of electric shock exists.
- Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire if flammable gas leaks around it.
- Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your furniture.
- An IEC approved power cord should be used. Power cord type: NYM.
CAUTION
- Selecting the installation location: Suitable location that will reduce the impact from rain and direct sun that may affect the unit performance. Besides,ventilation must be good and clear of obstruction .
- The air blown out of the unit should not point directly to animals or plants.
- The clearances of the unit from top, left, right and front are specified in figure below . At least three of the above sides must be open air .
- Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood.
- Do not install at a location where there is flammable gas,steam, oil and smoke.
- The location must be convenient for water drainage. eht morf yawam 1 tsael ta droc gnitcennoc sti dna tinu roodtuO eht ecalP antenna or signal line of television, radio or telephone. This is to avoid noise interference
Figure showing the Installation of Outdoor Unit.
Names of Outdoor Components
No | Item | Qty |
---|---|---|
1 | Drain Pipe |
| 1
2| Bush
| 2
The refrigerating machine oil is easily affected by moisture. Use caution to
prevent water from entering the cycle. The difference in height between the
indoor and outdoor unit should be kept below 15m. The connecting pipe, no
matter big or small, should all be insulated with insulation pipe and then
wrapped with vinyl tape. (The insulator will deteriorate if it is not wrapped
with tape).
The connection of insulated drain hose. Inner diameter 16mm Please use
insulated drain hose for the indoor piping (commercial product)
For outdoor unit installation,allow at least 2 sides of space around the unit to ensure ventilation flue.
About the outdoor unit:
- When “Stop” is selected during operation of the indoor unit, the fan of the outdoor unit continues turning for 10 to 60 seconds to cool the electric parts down.
- In heating operation, condensate or water due to defrosting will flow. Do not cover the drain port of the outdoor unit because such water may freeze in the chilly area.
- When the outdoor unit is hung on the ceiling, install the bush and drain pipe on the drain port and drain water.
Preparation of Pipe
Use a pipe cutter to cut the copper pipe and remove burr.
CAUTION
- Remove burr and jagged edge will cause leakage.
- Point the side to be trimmed downwards during trimming to prevent copper chips from entering the pipe.
Before flaring, please put on the flare nut.
Please use exclusive tool for refrigerant R410
Pipe Connection
CAUTION
- In case of removing flare nut of a indoor unit, first remove a nut of small diameter side, or a seal cap of big diameter side will fly out. Free from water into the piping when working.
- Be sure to tighten the flare nut to the specified torque with a torque wrench. If the flare nut is overtightened, the nut may be split after a long period has passed, and may cause a refrigerant leak
- Please be careful when bending the copper pipe.
- Screw in manually while adjusting the center. After that, use a torquewrench to tighten the connection
| Outer diameter of pipe (ø| Torque N·m (kgf·cm)
---|---|---
Small diameter side| 6.35 (1/4″)| 13.7-18.6 (140 – 190)
Large diameter side| 9.52 (3/8″)| 34.3-44.1 (350 – 450)
Valve head ca| Small diameter side| 6.35 (1/4″)| 19.6-24.5 (200 – 250)
Large diameter side| 9.52 (3/8″)| 19.6-24.5 (200 – 250)
Valve core cap| 12.3-15.7 (125 – 160)
Remove of Air From The Pipe And Gas Leakage Inspection
Procedures of using Vacuum Pump for Air Removal
- As shown in right figure, remove the cap of valve core. Then, connect the charge hose. Remove the cap of valve head. Connect the vacuum pump adapter to the vacuum pump and connect the charge hose to the adapter
- Fully tighter the “Hi” shuttle of the manifold valve and completely unscrew the “Lo” shuttle. Run the vacuum pump for about 10-15 minutes, then completely tighten the “Lo” shuttle and switch off the vacuum pump. Loosen the spindle of the service valve with small diameter by 1/4 turn and tighten the spindle immediately after 5 to 6 seconds. Remove the charging hose from the service valve.
- Completely unscrew the spindle of the service valve (at 2 places) in anticlockwise direction to allow the flow of refrigerant (using Hexagonal Wrench key).
- Tighten the cap of valve head. Check the cap’s periphery if there is any gas leakage. The task is then completed.
Gas leakage inspection
Please use gas leakage detector to check if leakage occurs at connection of
Flare nut as shown on the right. If gas leakage occurs, further tighten the
connection to stop leakage.
Procedures of Wiring
Detail of Cutting the Connecting Cord
WARNING
- The naked part of the wire core should be 10mm fix it to the terminal tightly. Then try to pull the individual wire to check if the contact is tight. Improper insertion may burn the terminal.
- Be sure to use only wire specified for the use of air-conditioner.
- Please refer to the manual for wire connection and the wiring technique should meet the standard of the electrical installation.
- There is an AC voltage drop between the LN terminal if the power is on. Therefore, be sure to remove the plug from its socket.
- Please exchange the blown-out fuse after making sure the right connection.
WARNING
- Leave some space in the connecting cord for maintenance purpose and be sure to secure it with the cord band.
- Secure the connecting cord along the coated part of the wire using the cord band.Do not exert pressure on the wire as this may cause overheating or fire
Wiring of the Outdoor Unit
Please remove the side cover for wire connection.
WARNING
- If you cannot attach the side plate due to the connection cord, please press the connecting cord in the direction to the front panel to fix it.
- Be sure that the hooks of the side cover fixed in certainly. Otherwise water leakage may occur and this causes short circuit or faults.
- The connecting cord should not touch to service valve and pipes. (it becomes high temperature in heating operation.)
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must be completed. To make the wiring capacity proper, use the wire gauge list below for the wiring from house distribution fuse box to the outdoor unit in consideration of the blocked rotor current.
- Investigate the power supply capacity and other electrical conditions at the installing location. Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary electrical work etc. The electrical work includes the wiring work up the outdoor unit. In localities where electrical conditions are poor, use of a voltage regulation is recommended.
- Install outdoor for the room air conditioner within the reaching range of the line cord
IMPORTANT
Fuse Capacity
RAC-VJ25/35PHAT 15A time delay fuse
Power Source And Operation Test
WARNING
-
Never remodel the power plug nor extend the long-distance cord.
-
Keep additional length for the power cord and do not render the plug under external force as this may cause poor contact.
-
The power cable easily generates heat. Do not bring the cable together
with a wire or vinyl tie. -
Do not fix the power cord with U-shape nail.
Operation test
-
Please be sure to measure the supply voltage before operation test.
-
Please ensure that the air conditioner is in normal operating condition
during the operation test- Operate with Cooling Mode(in summer) or Heating Mode(in winter).
- Press Temperature Button on the remote controller to set the desired temperature to 16.0 for Cooling Mode or 32.0 for Heating Mode. Set the desired fan speed to ” “(High).
- Operate the air conditioner for 20 minutes at least and make sure that the air from the air conditioner is cool or warm.
- Press On/Off Button on the remote controller and make sure that the air conditioner stops the operation.
-
If the indication lamps of the indoor unit flash with sounding of the buzzer during the operation test, perform a check following the procedures below.
Indication lamps flashing
mode| What to check
---|---
All indication lamps flash
three times repeatedly| Make sure that the spindles of both service valves are
open. (Outdoor fan might operate for near 15 minutes after the operation stop
for remove the protection. For the reoperation at that case, do it after
outdoor fan will stop.)
- Befor the check and the reoperation, reset the power supply by turning off and on the circuit breaker only after
- waiting for at least 5 mintes; or
- pressing the Temporary Switch Button only once while the power is OFF.
CAUTION
-
Don’t operate for over 5 minutes with the situation that the spindle of
the service valve is closed. This will cause the defect. -
Don’t operate by Cool Mode or Dry Mode with the door and windows opened, (the room humidity is always above 80%) for a long period of time. Water will condense and drip down occasionally. This will wet your furniture
-
Explain to your customer the proper operation procedures as described in the user’ s manual.
-
If the indoor unit won’t operate, check the cable for correct connection.
-
Turn on the lamp in the room where the indoor unit is installed and check the remote controller for normal operation.
Refrigerant
MODEL| Refrigerant
(kg)| GWP| t CO2 eq.
---|---|---|---
RAC-VJ25PHATRAC-VJ35PHAT| R 32:0.980| 675| 0.662