TROTEC TAC 5000 Professional Air Cleaner Instructions
- June 3, 2024
- TROTEC
Table of Contents
TROTEC TAC 5000 Professional Air Cleaner
You can download the current version of the instructions and the EU declaration of conformity via the following link:
TAC 5000
https://hub.trotec.com/?id=42770
TAC 6500
https://hub.trotec.com/?id=42771
Symbols
-
Warning of electrical voltage
This symbol indicates dangers to the life and health of persons due to electrical voltage. -
Warning
This signal word indicates a hazard with an average risk level that, if not avoided, can result in serious injury or death. -
Caution
This signal word indicates a hazard with a low-risk level which, if not avoided, can result in minor or moderate injury. -
Note
This signal word indicates important information (e.g. material damage), but does not indicate hazards. -
Info
Information marked with this symbol helps you to carry out your tasks quickly and safely. -
Follow the manual
Information marked with this symbol indicates that the instructions must be observed.
Safety
Read this manual carefully before starting or using the device. Always store the manual in the immediate vicinity of the device or its site of use.
Warning
Read all safety warnings and all instructions. Failure to follow the warnings
and instructions may result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future reference.
-
Do not use the device in potentially explosive rooms or areas and do not install it there.
-
Do not use the device in aggressive atmosphere.
-
Only put up the device in an upright, stable position on firm ground.
-
Let the device dry out after a wet clean. Do not operate it when wet.
-
Do not use the device with wet or damp hands.
-
Do not expose the device to directly squirting water.
-
Never insert any objects or limbs into the device.
-
Do not cover the device during operation.
-
Do not sit on the device.
-
This appliance is not a toy. Keep away from children and animals. Do not leave the device unattended during operation.
-
Check accessories and connection parts for possible damage prior to every use of the device. Do not use any defective devices or device parts.
-
Ensure that all electric cables outside of the device are protected from damage (e.g. caused by animals). Never use the device if electric cables or the power connection are damaged!
-
The mains connection must correspond to the specifications in the Technical annex.
-
Insert the mains plug into a properly fused mains socket.
-
Observe the technical data when selecting extensions to the power cable. Completely unroll the extension cable. Avoid electrical overload.
-
Before carrying out maintenance, care or repair work on the device, remove the mains plug from the mains socket. Hold onto the mains plug while doing so.
-
Switch the device off and disconnect the power cable from the mains socket when the device is not in use.
-
Do not under any circumstances use the device if you detect damages on the mains plug or power cable.
If the power cable is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Defective power cables pose a serious health risk! -
When positioning the device, observe the minimum distances from walls and other objects as well as the storage and operating conditions specified in the Technical annex.
-
Make sure that the air inlet and outlet are not obstructed.
-
Make sure that there are no loose items or dirt located in the immediate surroundings of air inlet and air outlet.
-
Do not remove any safety signs, stickers or labels from the device. Keep all safety signs, stickers and labels in legible condition.
-
Make sure that the suction side is kept free of dirt and loose objects.
-
Dispose of replaced filters properly, especially after filtering substances hazardous to health.
-
Never use the device as a storage place or footstep.
Intended use
Only use the device to clean atmospheric air from non-conducting and non-
combustible dusts, fogs or suspended matter whilst using the appropriate
filter classes and adhering to the technical data.
The device is intended to be used in commercial areas.
Foreseeable misuse
- Do not place the device on wet or flooded ground.
- Do not place any objects, e.g. clothing, on the device.
- Do not use the device out of doors.
- Do not use the device to siphon off vapors or fluids.
- Any use other than the intended use is regarded as a reasonably foreseeable misuse.
- Any unauthorised modifications, alterations or structural changes to the device are forbidden.
Personnel qualifications
People who use this device must:
- be aware of the dangers that occur when working with electrically driven air cleaners.
- have read and understood the instructions, especially the Safety chapter.
Electrically skilled person
Electrically skilled personnel must be able to read and understand electric
circuit diagrams, to put electrical systems into service and to maintain them,
to wire control cabinets, to ensure the functionality of electrical
components, and to identify possible hazards from electrical and electronic
systems.
Instructed person
Instructed persons have been informed of the tasks they were entrusted with as
well as of potential hazards resulting from inappropriate behavior. They are
allowed to operate and transport the device and perform simple maintenance
activities (cleaning the housing, and cleaning the fan).
The device is to be maintained and looked after by instructed personnel.
Residual risks
-
Warning of electrical voltage
Work on the electrical components must only be carried out by an authorised specialist company! -
Warning of electrical voltage
Before any work on the device, remove the mains plug from the mains socket!
Do not touch the mains plug with wet or damp hands. Hold onto the mains plug while pulling the power cable out of the mains socket. -
Warning
Dangers can occur at the device when it is used by untrained people in an unprofessional or improper way! Observe the personnel qualifications! -
Warning
The device is not a toy and does not belong in the hands of children. -
Warning
Risk of suffocation!
Do not leave the packaging lying around. Children may use it as a dangerous toy. -
Caution
Risk of injury from parts being whirled up!
Before switching the device on, make sure that there are no loose parts (clothing, hair …) located near the air inlet or outlet! -
Note
Do not operate the device without an air filter inserted into the air inlet!
Without the air filter, the inside of the device will be heavily contaminated. This could reduce the performance and result in damage to the device. -
Note
Do not use abrasive cleaners or solvents to clean the device.
Behavior in the event of an emergency
- Switch the device off.
- In an emergency, disconnect the device from the mains feed-in: Hold onto the mains plug while pulling the power cable out of the mains socket.
- Do not reconnect a defective device to the mains.
Information about the device
Device description
Air cleaners are used to filter the room air. On building sites and renovation
areas high concentrations of dust can arise, for instance when using angle
grinders or during blasting, chiseling or demolition operations as well as
when mixing dry mortar or tile cement.
Depending on the inserted filter, the air cleaners of the TAC series serve to eliminate various dusts, e.g. from asbestos, building rubble, quartz, flour, wood, etc., but also mould spores, paint particles and mineral fibres in the air, possibly arising during the above-mentioned operations. This dust is to be vacuumed off as close as possible to the point of origin in order to reduce the pollution of the breathing air to a minimum. Depending on the used filter quality it is permissible to employ the device for the separation of quartziferous mineral dust, wood dust, lead-containing dust, artificial mineral fibres or high-temperature fibres.
The air cleaners TAC 5000 and TAC 6500 come equipped with a sensor-supported Flowmatic control for the automatic retention of the preselected air volume.
Application as a vacuum generator for mould remediation and asbestos abatement is also a possibility. In case of other hazardous substances there are additional requirements; hence observe the corresponding Technical Rules for Hazardous Substances (TRGS) or the country-specific regulations.
The device is suited for:
- producing a vacuum in a room, e.g. in heavily contaminated spaces;
- air purification in workspaces via air circulation, e.g. indoor building sites, workshops etc.;
- producing overpressure in a room, e.g. cleanroom;
- supplying filtered fresh air.
The device is structured as follows:
- housing with stacking aid
- adjustable fan for air transport
- filter monitoring for air volume flow
The device may be equipped with various filters. It provides the user with the possibility of configuring both the filter quality and the filter chain arrangement for the respective field of application. The filters must be selected according to the area of application. The device is approvable for asbestos abatement as per TRGS 519, dust class H.
Info
The filters are not included in the scope of delivery! Choose the filters
according to the area of application from our filter range. Insert the
selected filters prior to the initial start-up.
Device depiction
No. | Designation |
---|---|
1 | stacking/push handle |
2 | air intake opening with hose/pipe connection |
3 | shock protection |
4 | swivel castor with brake (rubber, non-marking) |
5 | forklift pocket |
6 | wheel (rubber, non-marking) |
7 | hinged cover |
8 | sliding cover |
9 | control panel |
10 | telescopic slide |
11 | lifting handle |
12 | tensioning frame |
13 | pre-filter box |
14 | main filter box |
15 | fan box |
16 | cable storage compartment |
Transport and storage
Note
If you store or transport the device improperly, the device may be damaged.
Note the information regarding the transport and storage of the device.
Transport
Before transporting the device, observe the following:
- Switch the device off.
- Hold onto the mains plug while pulling the power cable out of the mains socket.
- Do not use the power cable to drag the device.
After transporting the device, proceed as follows:
- Set up the device in an upright position after transport.
Storage
When the device is not being used, observe the following storage conditions:
- dry and protected from frost and heat
- in an upright position where it is protected from dust and direct sunlight
- with a cover to protect it from invasive dust, if necessary
Assembly and start-up
Scope of delivery
- 1 x Device
- 1 x Manual
Unpacking the device
- Open the cardboard box and take the device out.
- Completely remove the packaging.
- Fully unwind the power cable. Make sure that the power cable is not damaged and that you do not damage it during unwinding.
Assembly
Sliding covers
Please proceed as follows to open the sliding covers (8):
- Pull the stacking handles (1) up and fold them down.
- Pull the sliding covers (8) outwards with a jerk and shove it apart all the way to the stop.
Please proceed as follows to close the sliding covers (8):
- Push the sliding covers (8) together until they lock in place.
- Tilt the stacking handles (1) up and lock them in place.
Hinged covers
In order to open the hinged covers (7), swing them up until they are held in
place by the magnets.
Proceed in reverse order to close the hinged covers.
Inserting the filters
Info
The filters are not included in the scope of delivery! Choose the filters
according to the area of application from our filter range. Insert the
selected filters prior to the initial start-up.
Prior to start-up, the filter chain of the device must be configured according to the desired field of application. For this, two filter boxes are available.
- Open the sliding cover (8).
- Pull out the tensioning frame (12) towards the top.
- Remove further boxes from the device as required.
Note
For all filter installations always observe the correct flow direction
according to the direction of the air current (airflow direction: from back to
front)!
Note that the main filter is locked at the bottom of the housing. The lock is located under the tensioning frame (12) and the prefilter (13).
Configuration
The TAC series is equipped with a Vario-shift function. This means that the
filter elements can be variably arranged for all application scenarios and in
line with the regulations.
- The building site configuration for the separation of suspended matter as per DIN EN 60335-2-69 to dust class H; the main priority with these applications has the filtering of dust particles dangerous to health, to some extent even carcinogenic. The entire filter ladder has to be operated at pressure to prevent unfiltered air from escaping even in case of leakages when sucking off this dust. This means that the fan is to be positioned downstream of the main filter! Both are to be braced using tensioning elements on the unit side so that the high-efficiency particulate air filter does not come into contact with polluted air at the outlet during the entire operating time and the risk of leaks is minimized!
- The cleanroom configuration for the separation of suspended matter as per DIN EN 1822-1:1998 to filter class H14 (in case of a substantially reduced air volume filters with higher filtration efficiencies are also an option); as a rule, air from a polluted area is fed to a cleanroom, e. g. as fresh air supply. The applicable regulations usually demand that the filtered air may only come into contact with a clean air pipe/duct operated at overpressure. Therefore, the fan is to be positioned upstream of the main filter! Here, too, the elements are to be braced as stated for the building site configuration!
- Generic configuration for air purification applications filtering coarse dust or fine particulates as per DIN EN 779 to filter class F9; these applications do not require any particular fan position. For reasons of simplified filter change management, it is recommended for the fan to be the last element to be incorporated and braced.
Note
For the individual configurations it is important to make sure that the air
hoses (marked a, b, c, d) and the dummy plug (23) are connected to the
measuring points (marked A, B, C, D, E) according to the box arrangement (pre-
filter = 1 + main filter = 2 + fan = 3). Otherwise, the filter monitoring will
not be working!
Example:
Start-up
When positioning the device, observe the minimum distance from walls or other
objects as described in the chapter Technical annex.
- Before restarting the device, check the condition of the power cable. If there are doubts as to the sound condition, contact customer service.
- Only put up the device in an upright, stable position on firm ground.
- Do not create tripping hazards when laying the power cable or other electric cables, especially when positioning the device in the middle of the room. Use cable bridges.
- Make sure that extension cables are completely unrolled.
- Position the device near the source of air contamination.
- When positioning the device, keep a sufficient distance to heat sources.
- Make sure that no curtains or other objects interfere with the airflow.
- Make sure that the air inlet and outlet are not obstructed.
Installation of the device in the room, the air of which is to be purified
- When positioning the device, make sure it is located in the center of the room the air which is to be cleaned. Alternatively, you can also position the device near the source of air contamination.
- Prior to the operation, you have to ensure that the filters have been installed in the device as desired.
- The device works in recirculation mode, this means that the contaminated air enters the air cleaner via the air inlet opening and is blown out through the air outlet opening in a purified state.
Air purification in the sealed area via air circulation:
Installation of the device outside of the room, the air of which is to be
purified
The device can be connected in either recirculation or ventilation mode.
- In recirculation mode, the air to be cleaned is led via a hose from the room into the air inlet opening of the device. The purified air is fed through another hose from the air outlet opening and back into the room.
- In ventilation mode, the air to be cleaned is led via a hose from the room into the air inlet opening of the device. This creates a slight negative pressure in the room. Clean, fresh air flows in from outside.
Installation variants for maintaining the pressure:
When connecting hoses, the following must be observed:
- The used pipes and hoses must be designed for the available static compression of the fans. They should preferably be laid in a straight line and at full length. 7.6 m of air hose each can be connected to the air inlet and air outlet openings of the device.
- There ought to be a minimum distance of 1 m between air inlet and air outlet opening.
Connecting the power cable
- Insert the mains plug into a properly fused mains socket.
Operation
Operating elements
No. | Designation | Meaning |
---|---|---|
17 | power button | For switching the device on or off |
18 | filter 1 warning light | Indication of required coarse or fine filter |
change
19| filter 2 warning light| Indication of required HEPA or bag filter change
20| air volume control dial| For setting the desired air volume
21| operating hours counter| Indication of operating hours
22| Flowmatic with display| Indication of the air volume (volumetric flow)
Switching the device on
Once you have positioned the device as described in the Start-up chapter, you
can switch it on.
- Make sure that neither the air inlet nor the air outlet opening is covered.
- Turn the air volume control dial (20) counter-clockwise to the lowest level.
- Press the power button (17).
- The power button (17) lights up.
Adjusting the air volume
By use of the stepless air volume control dial (20) you can adjust the fan
speed and thus regulate the air volume conveyed by the device.
Shutdown
Warning of electrical voltage
Do not touch the mains plug with wet or damp hands.
- Switch off the device.
- Hold onto the mains plug while pulling the power cable out of the mains socket.
- Clean the device according to the Maintenance chapter.
- Store the device according to the Transport and storage chapter.
Available accessories
Warning
Only use accessories and additional equipment specified in the instructions.
Using insertion tools or accessories other than those specified in the instructions may cause a risk of injury.
Designation | Article number TAC 5000 | Article number TAC 6500 |
---|---|---|
G4 Z-line filter | 7.160.000.448 | 7.160.000.454 |
F7 pleated filter cartridge | 7.160.000.449 | 7.160.000.476 |
F7 bag filter | 7.160.000.450 | 7.160.000.477 |
H13 HEPA filter approved for dust class H | 7.160.000.451 | 7.160.000.478 |
Spray paint filter | 7.160.000.452 | 7.160.000.479 |
Air transport hose
Tronect SP-T, length 7.6 m
| 6.100.001.212| 6.100.001.214
Errors and faults
The device has been checked for proper functioning several times during
production. If malfunctions occur nonetheless, check the device according to
the following list.
The device does not start:
- Check the power connection.
- Check the power cable and mains plug for damage.
- Check the on-site fusing.
- Wait for 10 minutes before restarting the device. If the device is not starting, have the electrics checked by a specialist company or by Trotec.
The device is loud or vibrates:
- Check whether the device is set up in a stable and upright position.
The device gets very warm, is loud or is losing performance:
- Check the air inlets and air filters for dirt. Remove external dirt.
The device gives off an unpleasant odour:
- Smoke, e.g. dense tobacco smoke, odours, and contaminations may be in the air. Ventilate the room.
The device still does not operate correctly after these checks:
Please contact customer service. If necessary, bring the device to an
authorised specialist electrical company or to Trotec for repair.
Maintenance
Note
All service activities other than those specified in the maintenance table may
only be performed by a specialist company authorized by Trotec.
Activities required before starting maintenance
Warning of electrical voltage
Do not touch the mains plug with wet or damp hands.
- Switch the device off.
- Hold onto the mains plug while pulling the power cable out of the mains socket.
Warning of electrical voltage
Tasks which require the device to be opened must only be carried out by
authorised specialist companies or by Trotec.
Cleaning the housing
Clean the housing with a soft, damp and lint-free cloth. Make sure that no
moisture enters the housing. Protect electrical components from moisture. Do
not use any aggressive cleaning agents such as cleaning sprays, solvents,
alcohol-based or abrasive cleaners to dampen the cloth.
Visual inspection of the inside of the device for dirt
- Remove the air filters.
- Use a torch to illuminate the openings of the device.
- Check the inside of the device for dirt.
- If you see a thick layer of dust, clean the inside of the device with a vacuum cleaner.
- Reinsert the air filters.
Filter change
The filters must be replaced when the filter change warning light for filter 1
(18) or filter 2 (19) lights up during operation and an acoustic signal is
emitted.
- Detach air hose A from the measuring point.
- Pull out the tensioning frame (12) towards the top.
- Pull the pre-filter box (13) out of the device in an upward motion and remove the filters from the box.
- If required, also loosen the clasp and the locking lever on the filter boxes.
- Disconnect the air hoses B and C from the measuring points.
- Move the main filter box (14) a little sideways.
- Pull the main filter box (14) out of the device in an upward motion and remove the filters from the box.
- For assembling the filter boxes please proceed in reverse order.
Lubricating the telescopic slides
The covers’ telescopic slides (10) are to be lubricated after cleaning or as
needed.
Technical annex
Technical data
Parameter | Value |
---|---|
Model | TAC 5000 |
Article number | 1.580.000.125 |
Max. amount of air | 4500 m3/h |
The recommended amount of air for dust class H
Room size
with filter surface H13
| 2500 m3/h
170 m3
18 m2
| 3000 m3/h
200 m3
26 m2
Dust class
(as per DIN 60335-2-69)
| dust class H (transmittance ≤ 0.005 %) for substances with a max. allowable concentration of ≤ 0.1 mg/m3,
carcinogenic hazardous substances as per GefStoffV § 11 (Ordinance on Hazardous Substances), TRGS 905 or 906 (Technical Rules for Hazardous Substances), approvable for asbestos abatement as per TRGS 519
Motor power| 1270 W| 1400 W
Mains connection| 1/N/PE ~ 230 V / 50-60 Hz| 1/N/PE ~ 230 V / 50-60 Hz
Nominal current| 4.8 A| 5.5 A
Connection cable| CEE 7/7, cable length 2.5 m
rubber conduit (H05RR-F) length = 2.5 m
Air transport hose connector inlet/outlet side| 400 mm| 450 mm
Sound level (at a distance of 1 m)| 68 dB(A)| 68 dB (A)
Dimensions
(length x width x height)
| 1252 x 690 x 926 mm| 1252 x 790 x 1026 mm
Weight| 113 kg| 131 kg
Recommendation for filter combinations specific to the application and
corresponding room size suitability| TAC 5000| TAC 6500
---|---|---
| suitable for rooms sized up to 1)
Fields of application| Filter combination| m3| m2| m3| m2
Coarse dust 2) (≤ 3 ACH6))| G4| 1.200| 480| 1.400| 560
Fine particulates 3) (≤ 3 ACH6))| G4 + F7 to F9| 600| 240| 750| 300
Suspended matter 4) (≤ 3 ACH6))| G4 + H13| 150| 60| 200| 80
Hygienic areas 5) (≤ 3 ACH6))| G4 + H13| 110| 44| 135| 54
- With an assumed room height of 3 m; 2) Typical coarse dust tasks: sawing,
filing; 3) Typical fine dust tasks: restoration works with materials
containing minerals or glass wool; 4) Typical suspended matter tasks:
grinding, asbestos abatement or mould remediation, mineral dusts etc.; 5) H13
downstream; 6) Air exchange per hour.
Optional equipment| TAC 5000| TAC 6500
---|---|---
Guiding wheels with pneumatic tyres, traceless| on request| on request
Trestle rollers (instead of guiding wheels)| on request| on request
Fork pockets for forklifts| on request| on request
Performance charts
A | Fan |
---|---|
B | The recommended amount of air for dust class H |
C | With G4+H13 filter combination (approval for dust class H) and air |
transport hose
D| With G4+F7 filter combination and air transport hose
E| With G4 filter and air transport hose
With spray paint filter and air transport hose
F| Without filter, with air transport hose*
- Connected to the pressure side, standard length 7.6 m, laid with one 90° arc. When the air hose is laid stretched and arc-free, an increase of air volume by up to 25 % is possible!
Disposal
The icon with the crossed-out waste bin on waste electrical or electronic equipment stipulates that this equipment must not be disposed of with the household waste at the end of its life. You will find collection points for free return of waste electrical and electronic equipment in your vicinity. The addresses can be obtained from your municipality or local administration. You can also find out about other return options that apply to many EU countries on the website https://hub.trotec.com/?id=45090. Otherwise, please contact an official recycling center for electronic and electrical equipment authorized for your country.
The separate collection of waste electrical and electronic equipment aims to enable the re-use, recycling, and other forms of recovery of waste equipment as well as to prevent negative effects on the environment and human health caused by the disposal of hazardous substances potentially contained in the equipment.
Declaration of conformity
Declaration of conformity in accordance with the EC Machinery Directive 2006/42/EC, Annex II, Part 1, Section A.
We – Trotec GmbH – declare in sole responsibility that the product designated
below was developed, constructed, and produced in compliance with the
requirements of the
EC Machinery Directive in version 2006/42/EC.
- Product model/Product:
- TAC 5000
- TAC 6500
- Product type: air cleaner
- Year of manufacture as of: 2019
- Relevant EU directives:
- 2011/65/EU: 01/07/ 2011
- 2014/30/EU: 29/03/2014
Applied harmonised standards:
- EN ISO 12100:2010
- EN ISO 13849-1:2015
- EN ISO 13857:2008
- EN ISO 14118:2018
- EN 55011:2009
- EN 60204-1:2006
- EN 60335-1:2012/AC:2014
- EN 60335-2-65:2003/A1:2008
- EN 60335-2-65:2003/A11:2012
- EN 61000-6-1:2007
- EN 61000-6-3:2007+A11:2011+AC:2012
Applied national standards and technical specifications:
Manufacturer and name of the authorised representative of the technical
documentation:
Trotec GmbH
Grebbener Straße 7, D-52525 Heinsberg
Phone: +49 2452 962-400
E-mail: info@trotec.de
Place and date of issue:
Heinsberg, 30.09.2013
Detlef von der Lieck, Managing Director
Trotec GmbH
Grebbener Str. 7 D-52525 Heinsberg
+49 2452 962-400
+49 2452 962-200
info@trotec.com
www.trotec.com.
References
- The Trotec Group: best conditions for your success - TROTEC
- TAC 5000 professional air cleaner - TROTEC
- TAC 6500 professional air cleaner - TROTEC
- WEEE-Annahmestellen | Interzero - zero waste solutions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>