Innowater PH Wireless Option Instruction Manual
- September 27, 2024
- Innowater
Table of Contents
PH Wireless Option
“`html
Specifications:
-
Model: pH Wireless Option 05-2024
-
Power Supply: 230 VAC
-
Operating Mode: Alternating periods of 2 minutes operating and
2 minutes pause -
Calibration: Required before first use and periodically
thereafter
Product Usage Instructions:
Installation:
pH Wireless Pump Installation:
1. Install the pump on the wall using the supplied bracket.
2. Use the bracket to mark the locations of the holes in the
wall before screwing it to the pump.
3. Connect the power cable to a 230 VAC socket.
Injection Installation:
1. Install the injection using the clamp saddle provided in the
return pipe after other equipment.
2. Connect one end of the rigid opaque PVC tubing to the
injector connector and the other end to the pump outlet
fitting.
Suction Installation:
1. Connect one end of the transparent flexible tubing to the
suction inlet of the pump and the other end to the filter-suction
stainer fitting.
2. Submerge the suction stainer in the acid tank.
Acid Container Placement:
We recommend placing the acid tank away from metallic and
electronic equipment to avoid damage from fumes.
Operating:
Pump Operation:
The pump works in alternating periods of 2 minutes operating and
2 minutes pause. During pauses, data reception continues but the
pump remains at rest.
Probe Calibration:
The pH probes require calibration before first use and
periodically thereafter. Calibration involves measuring probe
responses in buffer solutions to calculate pH accurately.
FAQ:
Q: How often should I calibrate the pH
probe?
A: The pH probe should be calibrated before
first use and then periodically as per the product manual
instructions.
Q: Can I place the acid tank in the same room as other
pool equipment?
A: It is strongly recommended not to place the
acid tank in the same room as metallic or electronic pool equipment
due to fumes that can cause damage.
“`
manual pH Wireless option
05-2024
WARNINGS
DESCRIPTION
INSTALLATION
OPERATING
CONFIGURATION AND CALIBRATION 1 Activation of the pH functions 2. Set points
3. pH4 calibration 4. pH7 calibration 5. Factory calibration 6. Radio output
7. Initial dosage delay 8. Dosing alarm
Page
1
2
3
4
5 5 5 6 7 7 8 9 9
WARNINGS
The pH function allows you to measure the pH of your pool and dose acid for an
automatic correction. However, pH probes are subject to wear, their response
deteriorates with time, moreover they are a delicate component that can be
easily damaged. Likewise, like any device, the pH measurement system can
suffer a failure that causes an incorrect pH reading. For all these reasons,
you must periodically carry out a MANUAL pH CHECK using approved means to
ensure that the pH is within the accepted limits.
INNOWATER TRATAMIENTOS INTERGRALES DEL AGUA S.L. declines all responsibility
for material and personal damage caused by an excessive or insufficient dosage
of acid or due to its handling.
ATTENTION! Acid is corrosive and can seriously damage eyes and skin. Oxidants
(hypochlorite) are harmful and can seriously damage the eyes, skin and
respiratory tract. When reacting with other compounds they can produce very
dangerous poisonous gases. Wear appropriate personal protective equipment when
handling chemical containers or dosing equipment.
The device must be connected to a suitable earth conductor and protected by a
30 mA max. differential switch.
Never open the device under voltage. Danger due to 230 VAC voltage.
All manipulation inside the equipment must be carried out by a qualified
professional staff.
1
pH Wireless Option
DESCRIPTION The pH function allows you to measure the pH thanks to a probe
connected to the chlorinator and correct its value using the pH Wireless acid
dosing pump. When the function is activated (see section 1, page 6) the pH
value is shown on the main screen of the chlorinator. The communication
between the chlorinator and the pump is wireless, which allows the latter to
be installed anywhere and the acid tank to be placed in a suitable place. All
control and measurement functions are carried out in the chlorinator and are
configured in menu 6 pH Function. To reach this menu, press the MENU key from
the chlorinator keypad and scroll with the help of the arrows to menu 6.
5
1
2
1. Connection for suction tube
3 4
2. Connection for injection tube
3. Priming push button
4. Main 230 VAC cable
5. Data reception blue LED indicator
pH Wireless Option
2
INSTALLATION
pH Wireless pump. Install the pump on the wall using the supplied bracket.
Before screwing it to the pump, use the bracket to mark the locations of the
holes in the wall that you will need to make. Choose a place near the
injection site. You can choose the place freely and at some distance from the
chlorinator since the pump does not need any wired connection to the
chlorinator. Connect the power cable to a 230 VAC socket.
Installation of the pH probe Install the saddle supplied before the
chlorinator cell and as far away from it as possible. Choose a section of the
pipe that does not empty when the filter pump stops because the probes
deteriorate if they are not plunged in water. Screw the probe holder into the
saddle, insert the probe into it and tighten its locking screw. Connect the
probe cable to the BNC connector on the bottom of the chlorinator marked with
a blue washer. Before using the pH function, proceed to calibrate the probe
(see sections 3 and 4). The pH and redox probes require calibration before
their first use and, subsequently, be calibrated from time to time. This is
necessary because the sensitivity of each probe is different and also
inevitably varies with time.
Injection. Install the injection thanks to the clamp saddle provided in the
return pipe after all other equipment (pump, filter, heater, chlorinator,
etc…) It should be the last element on the return line. Connect one end of the
rigid opaque PVC tubing to the injector connector. Connect the other end to
the injection pump outlet fitting (2) .
Suction Connect one end of the transparent flexible tubing to the suction
inlet fitting of the pump (1) and the other end of the tubing to the filter-
suction stainer fitting. Submerge the suction stainer in the acid tank.
Acid container. We strongly recommend you not to place the acid tank in the
same room than the filter and the salt chlorinator. The fumes that emanate
from it will quickly destroy any metallic element and electronic equipment. .
3
pH Wireless Option
OPERATING
Commissioning. Once all the elements have been installed (pH electrode,
injection/suction tubings, level probe) press the priming pump button (3) to
activate the pump until the acid in the tuve has reached the injection point.
Next, activate the pH function in the MAIN MENU – 6 Config. of pH and proceed
to the establishment of the set points and the calibration of the probe as
detailed in the following paragraph. When activating the function, the
chlorinator will permanently send a dosage signal to the pump that will depend
on the measured pH and the established set points. The further the pH is from
the lower set point, the higher the dosing volume and the higher the pump
speed.
NOTE: The pump works alternating periods of 2 min operating and 2 min pause.
During a pause period the pump will continue to receive data (flashing blue
led) but will remain at rest regardless of the current calculated dosage.
Calibration of the probe The pH probes require a calibration before their
first use and be subsequently calibrated periodically. This is so because
probes can have different responses and also because the response of the same
probe inevitably varies with time.
The calibration consists of measuring the response of the probe by introducing
it into two buffer solutions and recording this response in order to be able
to calculate the pH of any other solution, in our case, the pH of the pool
water.
The calibration of the probe is carried out using the two supplied buffer
solutions (pH4 and pH7) and entering the submenus 3 Cal pH4 and 4 Cal pH7
respectively. See points 3 and 4.
Data reception indicator (blue LED). As soon as you have activated the pH
function, the chlorinator will start sending dosing data to the pump and the
blue led (5) will flash every second indicating that it is receiving data from
the chlorinator. Whenever the pH function is active, the
transmission/reception of data will take place even when the dosage is 0% or
the pump is in a pause period. If the pump does not receive data, which can be
indicated by the blue led (5) not flashing, it will stop dosing after a few
seconds. The manual priming of the pump (4) continues to be enabled even if
the pump does not receive data from the chlorinator. See point 6 for channel
configuration.
pH Wireless Option
4
CONFIGURATION AND CALIBRATION
All functions related to the pH option are in MENU 6 Config. pH. To access it,
press the MENU key from the chlorinator main screen and scroll with the help
of the arrows to menu 6.
MAIN MENU 6 Ph Config.
OK
pH Config.
1 Activation
Press OK to enter the pH configuration submenu. Use the arrows to scroll through the different functions.
1. Activation of the pH functions.
OK
pH Config. 1 Activation pH
pH Config ON
Choose ON or OFF with the help of the arrows to activate or desactivate the
function. Press OK to accept or MENU to exit.
When the pH function is activated:
– The bottom line of the screen permanently shows the pH measurement and the
acid dosage calculated based on pH value and the established set points.
– The chlorinator continuously sends control data to the pump via radio and
the blue light on the pump flashes every second indicating data reception. The
signal will alternate pause periods for the pump every two minutes during
which it will send 0% command. See point 6 to change or check the transmission
channel.
When the pH function is NOT activated, the probe is not read, the main screen
does not show the pH value and the radio signal is not transmitted.
2. Set points
pH Config 2 Set points.
OK
pH = 7.0 10% pH > 9.0 90%
The acid dosage is determined at each moment by the two established set points (screen on the right). The following example shows the calculation of the dosage (blue trace) based on these points:
5
pH Wireless Option
– When the pH is below the lower set point, the pump does not dose acid.
– When the pH is between both points, the acid dosage follows the linear
function defined by both points. In the example, if the pH is 8.0, the pump
will dose at 50%.
– When the pH is above the upper set point, the pump will dose the constant
volume set for that point, which in the example is 90%.
You can set both set points and choose the percentage for each of them. To do
this, use the MENU key to place the cursor on the parameter to be modified and
press the arrows < or > to change its value. Press OK to save the data and
exit the sub-menu.
The total amount of acid injected is determined by the value of the
established production percentages. The more correction your pool needs, the
higher these percentages should be. To compensate for the delay in the pH
measurement due to the filtration circuit, you can set a slightly higher lower
set point so that the acid dosing stops before reaching the desired pH. For
example, to get a pH of 7.0 and avoid overdosing, set the dosing cutoff to a
slightly higher value:
pH = 7,2 0%
As each pool requires more or less acid and is more or less reactive to
dosing, at the beginning at least, you may need to correct the set points
several times.
3. pH4 calibration
pH Wireless Option
6
pH Config 3 pH4 Calib
OK
pH4 Calibration
4.34 Cal 4.00
Pressing OK you will enter the submenu 3 Cal pH 4 and you will find the screen shown above on the right. The value on the left of the screen shows the pH measured by the probe. The value to the right of Cal indicates the buffer solution valule used. You can change this value with the arrows to adjust it to the buffer solution you are using. Please note that the pH of the solution is temperature dependent as shown on its label.
Insert the probe into the pH4 buffer solution, move it slightly and wait for a stable reading value to be reached.
Once the reading value has stabilized press the OK key to save the calibration or MENU to exit without saving the calibration. If you press OK, one of the following two screens will appear momentarily:
pH4 calibration OK
pH4 calibration ERROR
The screen on the left indicates that the entered calibration values are
consistent and the calibration has been saved. The screen on the right
indicates that the probe measurement is too far from the actual buffer
solution value entered and that the calibration has not been saved.
4. Ph7 calibration
pH Config. 4 pH7 Calib.
OK
pH7 calibration
7.12 Cal 7.00
Remove the probe from the pH4 buffer solution, rinse its bottom with clean water and gently shake it to remove excess water (do not rub the probe with a cloth or paper). Then go to menu 4 Calib. pH7 and repeat the above process but with the buffer solution pH7.
5. Factory calibration
pH Config
OK
5 Factory calib.
Factory calib.? yes:OK exit:MENU
Using this function, you can reset the default value of a calibration that corresponds
7
pH Wireless Option
approximately to the theoretical measurement of a new probe. This function can be useful in some situations to correct or diagnose troubleshoots or if you do not have buffer solutions. Press OK to restore factory calibration or MENU to exit
Factory cal?
OK
yes:OK exit:MENU
Factory pH calibration OK
6. Radio output
pH Config. 6 Radio output
OK
pH 7.40 Dos 20%
TX 20 Channel 07
This function allows you to view the transmission status and change the channel.
pH 7.40
Current pH value measured by the probe
Dos 20%
Dosage calculated based on set points.
If the initial dosage delay is enabled and active (see point 7.) the indication DELAY will appear.
During a pause period of the pump (see point 1.) the indication PAUSE will appear.
TX 20
Command sent to the pump. Flashing of this parameter every second indicates transmission in progress.
Canal 07
Current transmission channel.
Note: The command sent to the pump can, in certain circumstances, be zero even though the calculated dosage is not zero. These circumstances are:
·
Initial delay activated (See point 7.)
·
Pump rest period (every two minutes)
·
Dosage alarm activated and maximum time reached (see point 8.)
If you have interference problems with other equipment that may be installed nearby, you can
choose a different channel:
In the menu Radio output, choose a diferente channel using the arrows.
Push the priming botón of the Wireless pump (3)
Press OK
The communication channel will change on the chlorinator and on the pump. The blue light on the pump will flash again indicating that it is receiving data from the chlorinator. NOTE: If the pump priming button is not held down when you press OK, the pump will not change channels and will stop receiving data.
pH Wireless Option
8
7. Initial dosage delay
pH Config. 7 Dosing delay
OK
Delay
ON
Time 30 min
Probes take some time to generate a valid answer after being disconnected.
This function allows you to set a delay period after powering up the device
during which the dosage remains on standby, thus avoiding incorrect dosage. We
recommend that you always activate a delay time of at least 15 min.
Place the cursor (MENU key) under the word OFF and use the arrows to activate
(ON) or desactivate (OFF) the dosing delay. Place the cursor under the word
min and use the arrows to set the desired delay time in minutes after power
on. Press OK to save and exit.
When the delay is active, after turning on the device, in the Radio Output
Menu of the pH Function (see point 6.) DELAY will be indicated.
8. pH dosing alarm
pH Config 8 Dosing alarm
OK
Dos. alarm OFF
Time
20 min
The pH dosing alarm allows recording the accumulated dosing time without reaching the programmed lower set point and triggering an alarm to interrupt dosing when a certain dosing time is reached. This can be useful to avoid overfeeding, indicate a lack of acid in the tank or to detect possible problems with the probe or injection.
Place the cursor (MENU key) under the word OFF and use the arrows to activate (ON) or deactivate (OFF) the alarm. Place the cursor under the word min and use the arrows to set the maximum dosing time in minutes. Press OK to save and exit.
If the function is activated and the maximum set dosing time is reached, the following screen will appear and dosing will be interrupted:
DOS. pH EXCEEDED Resume? = OK
Press OK to continue. The dosing counter will reset and dosing will continue
normally.
9