KLEFR 6931 Digital Power Meters, Power Factor Meter User Manual

September 21, 2024
KLEFR

6931 Digital Power Meters, Power Factor Meter

Product Information

Specifications

  • Product Name: PRO1 Series MID
  • Type: Single phase energy meter
  • User Manual: KLEFR 6931, 6933 & 6934 KLEFR
    6941, 6943 & 6944 Version 2.19-1

Product Usage Instructions

Safety Instructions

Warning: Failure to observe the instructions
can result in death, serious injury, or material damage.

Caution: There is a hazard of electric shock,
and failure to take necessary safety precautions may result in
death, serious injury, or material damage.

Qualified Personnel: Installation and operation
of the device must be performed only by qualified personnel who are
authorized and knowledgeable about electrical equipment and
circuits.

Intended Purpose: The device should only be
used for specified application cases as mentioned in the catalog
and user manual.

Proper Handling: Ensure proper transport,
storage, installation, connection, operation, and maintenance of
the product. Be aware that certain parts of the meter might carry
dangerous voltages during operation.

Certificates

The product conforms to European Standard EN 45014 and other
relevant standards. It meets the requirements of Directive
2014/32/EU.

Specifications

  • Casing: PC flame-resistant plastic

FAQ

What are the recommended safety precautions for using the

energy meter?

Always ensure that qualified personnel handle the installation
and operation of the device. Follow the safety instructions
provided in the user manual to prevent any accidents or damage.

Can the energy meter be used for applications not specified in

the user manual?

No, the device should only be used for the application cases
specified in the catalog and user manual to ensure proper
functionality and safety.

PRO1 Series MID
Single phase energy meter
User manual KLEFR 6931, 6933 & 6934 KLEFR 6941, 6943 & 6944 Version 2.19-1

1 Index
1 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 3 Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 4 Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 5.2 Basic errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5.3 Infrared specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5.4 M-bus communication specifications (M-bus version only) . . . . . . . . . . . . . . . . . . . . .9 5.5 RS485 communication specifications (Modbus version only). . . . . . . . . . . . . . . . . . . . .9 5.6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.7 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7.1 Energy flow indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7.2 Reactive energy indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7.3 Tariff indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 7.4 Reading the meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 7.5 LCD display of the meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 7.6 Scrolling function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 7.7 Button scroll . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 7.8 Backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 7.9 Resettable day counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 7.10 S0 output rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 7.11 Calculation code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 7.12 Modbus/M-bus ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 7.13 Baud rate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 7.14 Parity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 7.15 Power down counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 7.16 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 7.17 CT ratio setting (PRO380-CT only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 8.1 Errors / Diagnostics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 8.2 Technical support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Appendix 1 – Multi tariff function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 A1.1 How to switch between T1 and T2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Appendix 2 – M-bus version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 A2.1 Communicating via the M-bus output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 A2.2 M-bus register map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Appendix 3 – Modbus version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 A3.1 Communicating via the Modbus output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 A3.2 Modbus register map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Appendix 4 – Infrared PC software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
KLEFR – 693-4x – Three phase – 3

2 Safety instructions
Information for your own safety This manual does not contain all of the safety measures for operation of this meter because special operating conditions, local code requirements or local regulations may necessitate further measures. However, it does contain information which must be adhered to for your own personal safety and to avoid material damage. This information is highlighted by a warning triangle with an exclamation mark or a lightning bolt depending on the degree of actual or potential danger:
Warning This means that failure to observe the instruction can result in death, serious injury or considerable material damage.
Caution This means hazard of electric shock and failure to take the necessary safety precautions will result in death, serious injury or considerable material damage.
Qualified personnel Installation and operation of the device described in this manual may only be performed by qualified personnel. Only people that are authorized to install, connect and use this device, who have the proper knowledge about labeling and grounding electrical equipment and circuits and can do so in accordance with local (safety)regulations, are considered qualified personnel in this manual.
Use for the intended purpose This device may only be used for the application cases specified in the catalog and the user manual and only in connection with devices and components recommended and approved by KLEFR.
Proper handling The prerequisites for perfect, reliable operation of the product are proper transport, storage, installation and connection, as well as proper operation and maintenance. During its operation certain parts of the meter might carry dangerous voltages.
· Only use insulated tools suitable for the voltages this meter is used for. · Do not connect while the circuit is connected to a power or current source. · Only place the meter in a dry environment. · The meter is intended to be installed in a Mechanical Environment M1′, with Shock and Vibrations of low significan- ce and Electromagnetic EnvironmentE2′, as per 2014/32/EC Directive. The meter is intended for indoor use. The meter shall be installed inside a suitable IP rated enclosure, in accordance with local codes and regulations. · Do not mount the meter in an explosive area or exposed to dust, mildew and/or insects. · Make sure the used wires are suitable for the maximum current of this meter. · Make sure the AC wires are connected correctly before activating the current/voltage to the meter. · Do not touch the meter’s connection clamps directly with your bare hands, with metal, blank wire or other conducting material as you will risk an electric shock that could cause possible injury, serious injury or death. · Make sure the protection covers are replaced after installation. · Maintenance and repair of the meter should only be carried out by qualified personnel. · Never break any seals (if present on this meter) to open the front cover as this might influence the functionality or accuracy of the meter, and will void all warranty. · Do not drop, or allow physical impact to the meter as there are high precision components inside that may break and affect the meter measurement negatively. · All clamps should be properly tightened. · Make sure the wires fit properly in the connection clamps. · If the wires are too thin it will cause a bad contact which can spark causing damage to the meter and its surroundings.
4 – KLEFR – 693-4x – Three phase

Exclusion of liability We have checked the contents of this manual and every effort has been made to ensure that the descriptions are as accurate as possible. However, deviations from the description cannot be completely ruled out, so that no liability can be accepted for any errors or omissions in the information given. The data in this manual are checked regularly and the necessary corrections will be included in subsequent editions. If you have any suggestions, please do not hesitate to contact us. Subject to technical modifications without notice. Copyright Copyright Klefr December 2017. It is prohibited to pass on or copy this document or to use or disclose its contents without express permission of Klefr. Any duplication is a violation of the law and subject to criminal and civil penalties. All rights reserved, particularly for pending or approved patent awards or registered trademarks.
KLEFR – 693-4x – Three phase – 5

3 Foreword
Thank you for purchasing this energy meter. Although we produce this device according to international standards and our quality inspection is very accurate it’s still possible that this device shows a defect or failure for which we do apologize. Under normal conditions your product should give you years of trouble free operation. In case there is a problem with the energy meter you should contact your distributor immediately. Most of our energy meters are sealed with a special seal. Once this seal is broken there is no possibility to claim any warranty. Therefore NEVER open an energy meter or break the seal of the device. The limited warranty is 5 years after production date, divided into various periods., after production, and only valid for production faults.
6 – KLEFR – 693-4x – Three phase

4 Certificates

This declaration of Conformity is suitable to the European Standard EN 45014 General Criteria for Supplier’s Declaration of Conformity. The basis for the criteria has been found in international documentation, particularly in ISO / IEC, Guide 22, 1982, Information on manufacturer’s Declaration of Conformity with standards or other technical specifications

We, Inepro Metering BV
(supplier’s name)

Pondweg 7 2153 PK Nieuw-Vennep The Netherlands

(supplier’s address)

declare under our sole responsibility that the product:

6931 6933 6934

6941 6943 6944

Three phase DIN rail Watt Hour meter
(Name, type or model, batch or serial number, possibly source and number of items) to which this declaration relates in conformity with the following European harmonized and published standards at date of this declaration:
EN 50470
(Title and or number and date of issue of the applied standard(s)) Following the provisions of the Directives (if applicable):
N/A

Nieuw-Vennep, 2017, September 5
Place and date of issue
D. van der Vaart
Name of responsible for CE-marking

Declaration of Conformity
We Inepro Metering BV
Of Inepro Metering BV
Pondweg 7 2153 PK Nieuw Vennep
The Netherlands
Ensure and declare that the apparatus: 6931, 6933, 6934, 6941, 6943 and 6944
With the measurement range 230V/400V, 5(100)A, 50Hz, 10.000imp/kWh (direct)
230V/400V, 1,5(6)A, 50Hz, 10.000imp/kWh (CT) are in conformity with the type as described in the EC-type examination certificate T11175 and 11176 and satisfy the appropriate requirements of the Directive 2014/32/EU
September 5, 2017
Daan van der Vaart
KLEFR – 693-4x – Three phase – 7

5 Specifications

Casing

PC flame resistant plastic

Nominal voltage (Un)

230/400V AC (3~)

Operational voltage

3*230/400V ±20%

Insulation capabilities:

– AC voltage withstand

4KV for 1 minute

– Impulse voltage withstand

6KV ­ 1,2S waveform

Basic current (Ib)

5A (1,5A for CT version)

Maximum rated current (Imax)

100A (6A for CT version)

Operational current range

0,4%Ib-Imax

Overcurrent withstand

30Imax for 0,01s

Operational frequency range

45-60Hz

Internal power consumption

2W/Phase – 10VA/Phase (active – reactive)

Test output flash rate (RED LED)

10.000 imp/kWh

Pulse output rate

10.000/2.000/1.000/100/10/1/0,1/0,01 imp/kWh

Pulse width

– 10.000 pulses

o 0 ­ 4.999W 40ms

o 5.000 ­ 9.999W 20ms

o 10.000 ­ 19.999W 10ms

o 20.000 ­ 39.999W 5ms

o > 40.000W 2,5ms

– 2.000 pulses

o 0 ­ 46.799 20ms

o 46.800 15ms

– 1.000 pulses

o Fixed pulse width 30ms

– 100 pulses

o < 50.000W 40ms

o > 50.000W 20ms

– Other pulses

o Always 40ms

Data store

The data can be stored for more than 10 years without power

5 .1 Performance criteria

Operating humidity

75%

Storage humidity

95%

Operating temperature range DC version

-40°C – +70°C

Operating temperature range CT version

-25°C – +70°C

International standard

EN50470-1/3

Accuracy class

B (=1% accuracy)

Protection against penetration

of dust and water

IP51

Insulating encased meter of

protective class

II

5 .2 Basic errors
0,05Ib 0,1Ib
0,1Ib – Imax 0,2Ib – Imax

Cos = 1 Cos = 0,5L Cos= 0,8C Cos = 1 Cos = 0,5L Cos = 0,8C

±1,5% ±1,5% ±1,5% ±1,0% ±1,0% ±1,0%

5.3 Infrared specification
Infrared wavelengths Communication distance Protocol
8 – KLEFR – 693-4x – Three phase

900- 1000nm Direct contact IEC62056-21:2002 (IEC1107)

5.4 M-bus communication specifications (M-bus version only)

Bus type

M-bus

Baud rate

300, 600, 1200, 2400, 4800 and 9600 (default)

Range

1000m

Downlink signal

Master to slave. Voltage modulation

Uplink signal

Slave to master. Current modulation

Cable

JYSTY (nx2x0,8)

Protocol

EN13757-3

Unit loads

± 2

Max. number of meters

64 per bus*

5.5 RS485 communication specifications (Modbus version only)

Bus type

RS485

Protocol

MODBUS RTU with 16 bit CRC

Baud rate

1200, 2400, 4800 and 9600 (default)

Address range

1-247 user settable

Maximum bus load

60 meters per bus*

Range

1000m

*Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate, the smaller the number of meters which can be used) and the circumstances under which the meters are installed.

5 .6 Dimensions
Height Width Depth Max. diameter power connection clamps
Weight

92,4 mm 70 mm 63 mm 25mm2 (Flex core) 35 mm2
(Solid copper) 0,39 Kg (net)

63mm

92,4mm 45mm

70mm

47,8mm

KLEFR – 693-4x – Three phase – 9

5 .7 Connection diagram

Klefr 693x Direct connected – 3P 4W

L1 (in) Phase 1 input – L1 (out) Phase 1 output L2 (in) Phase 2 input – L2 (out) Phase 2 output L3 (in) Phase 3 input – L3 (out) Phase 3 output N (in) Neutral input – N (out) neutral output 10/11 not used 12/13 not used 14/15 not used 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)

Klefr 693x Direct connected – 3P 3W Open Delta (Aron)
L1 (in) Phase 1 input – L1 (out) Phase 1 output L2 (in) Phase 2 input – L2 (out) Phase 2 output L3 (in) Phase 3 input – L3 (out) Phase 3 output N (in) not used – N (out) not used 10/11 not used 12/13 to be connected to 16/17 14/15 not used 16/17 to be connected to 12/13 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)

Klefr 693x Direct connected – 3P 3W Delta

L1 (in) Phase 1 input – L1 (out) Phase 1 output L2 (in) Phase 2 input – L2 (out) Phase 2 output L3 (in) Phase 3 input – L3 (out) Phase 3 output N (in) not used – N (out) not used 10/11 not used 12/13 not used 14/15 not used 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)

Klefr 693x Direct connected – 1P 2W – Single phase

10 – KLEFR – 693-4x – Three phase

L1 (in) Phase 1 input – L1 (out) Phase 1 output L2 (in) not used – L2 (out) not used L3 (in) not used – L3 (out) not used N (in) Neutral input – N (out) neutral output 10/11 not used 12/13 not used 14/15 not used 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)

Klefr 694x CT – 3P 4W Klefr 694x – 3P 3W Open Delta (Aron) Klefr 694x – 3P 3W Delta Klefr 694x – 1P 2W – Single phase

CT1 (in) Phase 1 input – CT1 (out) Phase 1 output CT2 (in) Phase 2 input – CT2 (out) Phase 2 output CT3 (in) Phase 3 input – CT3 (out) Phase 3 output UN (in) Neutral input – UN (out) neutral output 10/11 Phase 1 – UL1 12/13 Phase 2 – UL2 14/15 Phase 3 – UL3 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)
CT1 (in) Phase 1 input – CT1 (out) Phase 1 output CT2 (in) not used – CT2 (out) not used CT3 (in) Phase 3 input – CT3 (out) Phase 3 output UN (in) not used – UN (out) not used 10/11 Phase 1 – UL1 12 Phase 2 – UL2 13 to be connected to 17 14/15 Phase 3 – UL3 17 to be connected to 13 (16 not used) 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)
CT1 (in) Phase 1 input – CT1 (out) Phase 1 output CT2 (in) Phase 2 input – CT2 (out) Phase 2 output CT3 (in) Phase 3 input – CT3 (out) Phase 3 output UN (in) not used – UN (out) not used 10/11 Phase 1 – UL1 12/13 Phase 2 – UL2 14/15 Phase 3 – UL3 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)
CT1 (in) Phase 1 input – CT1 (out) Phase 1 output CT2 (in) not used – CT2 (out) not used CT3 (in) not used – CT3 (out) not used UN (in) Neutral input – UN (out) neutral output 10/11 Phase 1 – UL1 12/13 not used 14/15 not used 16/17 not used 18/19 Forward pulse output contact (S0) 20/21 Reverse pulse output contact (S0) 22/23 M-bus / Modbus communication contact 24/25 External tariff input (230V)
KLEFR – 693-4x – Three phase – 11

6 Installation
Caution
· Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before working on it.
· Always use a properly rated voltage sensing device to confirm that power is off.
Warning
· The installation should be performed by qualified personnel familiar with applicable codes and regulations. · Use insulated tools to install the device. · A fuse, thermal cut-off or single-pole circuit breaker should be fitted on the supply line and not on the neutral
line.
· The connecting wire, connecting the device to the outside circuit, should be sized in accordance with local regulations for the maximum amount of the current breaker or other overcurrent protection devices used in the circuit.
· An external switch or a circuit-breaker should be installed on the supply wires, which will be used to disconnect the meter and the device supplying energy. It is recommended that this switch or circuit-breaker is placed near the meter because that is more convenient for the operator. The switch or circuit-breaker should comply with the specifications of the building’s electrical design and all local regulations.
· An external fuse or thermal cut-off used as an overcurrent protection device for the meter must be installed on the supply side wires. It’s recommended that this protection device is also placed near the meter for the convenience of the operator. The overcurrent protection device should comply with the specifications of the building’s electrical design and all local regulations.
· This meter can be installed indoor, or outdoor enclosed in a meter box which is sufficiently protected, in accordance with local codes and regulations.
· To prevent tampering, an enclosure with a lock or a similar device can be used. · The meter has to be installed against a fire resistant wall. · The meter has to be installed in a well-ventilated and dry place. · The meter has to be installed in a protective box if the meter is exposed to dust or other contaminants. · The meter can be installed and used after being tested and can be sealed afterwards. · The device can be installed on a 35mm DIN rail. · The meter should be installed on a location where the meter can be read easily. · In case the meter is installed in an area with frequent surges for example due to thunderstorms, welding
machines, inverters etc., the meter is required to be protected with a Surge Protection Device. · The device should be sealed immediately after installing it in order to prevent tampering.
12 – KLEFR – 693-4x – Three phase

7 Operation
7.1 Energy flow indication
The red LED on the front panel indicates the power flow measured by the meter. When power flows, the LED will flash. The faster the LED flashes, the more power flows. For this meter, the LED will flash 10.000 times per kWh. The first display indication of the meter is either FW (forward) or RV (reverse). This page (shown below) indicates per phase the direction of the energy. In this picture phase 1 and 2 are forward and phase 3 is reverse.
7 .2 Reactive energy indication
The display will show kvarh to indicate the meter is measuring reactive energy.
7.3 Tariff indication
The tariff LED will be powered off for T1 or powered on for T2.
7 .4 Reading the meter
A red LED on the front panel indicates the consumption measured by the meter. When power is consumed, the LED will flash. The faster the LED flashes, the more power is consumed. For this meter, the LED will flash 10.000 times per kW. The meter is equipped with an 8 digit LCD. For the energy consumption the meter will display 99999.99 kWh and switch to 999999.9 kWh when over this value and so on.
7 .5 LCD display of the meter
The LCD is a multifunctional display, it has two rows to indicate the status of the meter. The top row shows the value, while the bottom row shows the units, phase and/or direction.
KLEFR – 693-4x – Three phase – 13

7 .6 Scrolling function
7 .6 .1 Automatic scroll Every 10 seconds the meter will display the next programmed data page (depending on the setting). 7 .6 .2 Change scrolling time by button
· Scroll with the buttons to Program mode 2. · Hold the right button for 3 seconds to enter the menu. · Scroll to LCD page LCD cycle time (rt xx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select the new value 1-30 seconds. · Confirm the new scrolling time by holding both buttons for 3 seconds. · The LCD will show SET OK when the setting is confirmed. 7 .6 .3 Add/remove registers to/from automatic scroll · Scroll to the register that you would like to add or remove. · Hold the right button for 5 seconds to add or remove. · The LCD will show OK in or OK out.
Only the registers in the sub-menu after: Current direction, Total active energy, Total reactive energy, Active power and Program mode 1 can be added or removed to/from the automatic scroll. Total active energy cannot be removed.
14 – KLEFR – 693-4x – Three phase

7 .7 Button scroll
By pressing the button for 1, 3 or 5 seconds you will go through all data pages one by one.
Set CT ratio (CT version only) NOTE: CT ratio has to be programmed before use. Once programmed the CT ratio cannot be changed. Wrong CT ratio can cause wrong billing charges.
Select secondary current /1 or /5. Confirm by holding both buttons for 3 seconds. Select the 4 digit primary current (0001-9995). Confirm each digit by holding both buttons for 3 seconds. The CT ratio is set when the last digit is confirmed

Total active energy

Total active power

Automatic scroll: default 10 seconds

KLEFR 6933, 6934, 6943 & 6944 KLEFR 6934, 6944

Button scroll: press the buttons for less than 3 seconds to scroll. After 30 seconds of no interaction the meter goes back to automatic scroll mode.

Current direction Total active energy
Total reactive energy
Total active power

Hold the right button for 3 seconds to enter the next menu. Hold the left button for 3 seconds to go back.
Display Shows:

Current direction

Comb. active status word Serial number

Total active energy

T1 active energy

Total RV active energy

T1 RV active energy

L2 total active energy

L2 FW active energy

T2 active energy T2 RV active energy L2 RV active energy

Total reactive energy

T1 reactive energy

T2 reactive energy

Total RV reactive energy

T1 RV reactive energy

T2 RV reactive energy

L2 total reactive energy

L2 FW reactive energy

L2 RV reactive energy

Total active power

L1 active power

L2 active power

Checksum

Checksum

Total FW active energy

T1 FW active energy

L1 total active energy

L1 FW active energy

L3 total active energy

L3 FW active energy

Total FW reactive energy

T1 FW reactive energy

L1 total reactive energy

L1 FW reactive energy

L3 total reactive energy

L3 FW reactive energy

L3 active power

Total apparent power

T2 FW active energy L1 RV active energy L3 RV active energy
T2 FW reactive energy L1 RV reactive energy L3 RV reactive energy
L1 apparent power

L2 apparent power

L3 apparent power

Total COS

L1 COS

L2 COS

L3 COS

Grid frequency

or

L2 Voltage

Total reactive power L3 Voltage

L1 reactive power L1 Current

L2 reactive power L2 Current

L3 reactive power L3 Current

L1 Voltage

Hold the right button for 5 seconds to add or remove from the automatic scroll.
Display Shows:
or

Resettable kWh
Program mode 1 (Read only)

Resettable kWh

Hold the right button for 5 seconds to reset.

CT rate (CT version only) Forward S0 output

Baud rate

Resettable kWh

Reverse S0 output Backlight

Calculation code Parity

Modbus/M-bus ID Power down counter

LCD cycle time

Program mode 2 (Write)
Program mode 3 (Write: Password
protected)

Modbus/M-bus ID

Scroll with the buttons to
select 3 digits. Confirm each digit by holding both buttons
for 3 seconds.

LCD cycle time

Scroll with the buttons to
select 1-30. Hold both buttons for 3 seconds to confirm.

Forward S0 output

Reverse S0 output

Calculation code

Baud rate

Hold the right button for 3 seconds and enter 4 digit password to enter program mode.

Scroll with the buttons to select 10.000/2.000/ 1.000/100/10/1/0,1/0,01.
Hold both buttons for 3 seconds to confirm.

Scroll with the buttons to select 10.000/2.000/ 1.000/100/10/1/0,1/0,01.
Hold both buttons for 3 seconds to confirm.

Scroll with the buttons to select 01(F)/04(R)/ 05(F+R)/06(R-F)/09(F-R)/ 10(F-R)/11(F-R). NOTE: Calculation code 10 can only be set once! Hold both buttons for 3 seconds to confirm.

Scroll with the buttons to select 300/600/ 1200/4800/9600.
Hold both buttons for 3 seconds to confirm.

Power down counter

Program password

Hold both buttons for 3 seconds to confirm.

Select the new 4 digit password by choosing each digit (0-9).
Confirm each digit by holding both buttons for 3 seconds.

Backlight Parity

Scroll with the buttons to
select on/off/button. Hold both buttons for 3 seconds to confirm.

Scroll with the buttons to select even/none/odd.

Hold both buttons for 3 seconds to confirm.

Hold the right button for 5 seconds to enter program mode.

KLEFR – 693-4x – Three phase – 15

7 .8 Backlight
The meter is equipped with a blue backlight. The backlight can be set to always on, off or button mode.
7 .8 .1 Change the backlight setting · Scroll with the buttons to Program mode 2. · Hold the right button for 3 seconds to enter the menu. · Scroll to LCD page Backlight setting (bL xx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select button/on/off. · Confirm the new setting by holding both buttons for 3 seconds. · The LCD will show SET OK when the setting is confirmed.
7 .9 Resettable day counter
The meter is equipped with a day counter for consumed energy. This is the energy forward calculated and can be reset to zero by the user.
7 .9 .1 How to reset the day counter back to 0 · Scroll to register Resettable kWh in the main menu. · Hold the right button for 3 seconds to enter the menu. · The value starts blinking: hold the right button for 5 seconds to reset. · The LCD will show SET OK when the value is reset.
7 .10 S0 output rate
The energy meter is equipped with two pulse outputs (forward and reverse) which are optically isolated from the inside circuit. It generates pulses in proportion to the measured consumption for purpose of remote reading or accuracy testing. The pulse output is a polarity dependent, open-collector transistor output requiring an external voltage source for correct operation. For this external voltage source, the voltage (Ui) should be lower than 27V DC. The maximum switching current (Imax) is 100mA. To connect the impulse output, connect 5-27V DC to connector 18/20 (collector), and the signal wire (S) to connector 19/21 (emitter).
7 .10 .1 How to change the S0 output rate · Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to confirm each digit. · Scroll to LCD page S0 output (S0 xxxxxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select 10.000/2.000/1.000/100/10/1/0,1/0,01. · Confirm the new setting by holding both buttons for 3 seconds. · The LCD will show SET OK when the setting is confirmed.
16 – KLEFR – 693-4x – Three phase

7 .11 Calculation code
The meter allows you to display the total energy (usage) shown on the display in accordance to different calculation methods. You can use the following calculation methods for total energy:

Code C-01 C-04 C-05 C-06 C-09 C-10* C-11

Total (active) energy Forward only Reverse only Forward + Reverse Reverse – Forward Forward – Reverse Forward – Reverse Forward – Reverse

Example of flow through the meter

L1

+5 kWh

L2

+5 kWh

L3

-12 kWh

LCD reading and calculation of total energy

Code

C-01

C-04

C-05

C-06

C-09

Total

10

-12

22

-22

-2

Forward

10

10

10

10

10

Reverse

-12

-12

12

-12

-12

*Meters ordered or set afterwards to C-10 cannot be set to another calculation mode.

C-10* -2 0 -2

C-11 -2 10 -12

Code Forward Reverse

C-01 10

C-04 12

S0 output per code

C-05

C-06

10

10

12

12

C-09 10 12

C-10 0 2

C-11 0 2

7 .11 .1 How to change the calculation code
· Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds
to confirm each digit. · Scroll to LCD page Calculation code (Code-xx). · Hold the right button for 5 seconds to enter program mode. The value starts blinking:
select 01/04/05/06/09/10/11. · Confirm the new setting by holding both buttons for 3 seconds. · The LCD will show OK when the setting is confirmed.

KLEFR – 693-4x – Three phase – 17

7 .12 Modbus/M-bus ID
The Modbus ID can be set from 001 to 247, the default Modbus ID is 001. The M-bus ID can be set from 000 to 250, the default M-bus ID is 000.
7 .12 .1 How to change the Modbus/M-bus ID · Scroll with the buttons to Program mode 2. · Hold the right button for 3 seconds to enter the menu. · Scroll to LCD page Modbus/M-bus ID (addr xxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select 3 digits (Modbus: 001-247 or M-bus: 000-250). Confirm each digit by holding both buttons for 3 seconds. · The LCD will show OK when the setting is confirmed.
7 .13 Baud rate
The Modbus baud rate can be set from 1200 to 9600. The M-bus baud rate can be set from 300 to 9600.
7 .13 .1 How to change the baud rate · Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to confirm each digit. · Scroll to LCD page Baud rate (bd xxxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select 9600/4800/2400/1200/600/300. · Confirm the new setting by holding both buttons for 3 seconds. · The LCD will show OK when the setting is confirmed.
7 .14 Parity
The Modbus parity can be set to even, none or odd. The M-bus parity is always even.
7 .14 .1 How to change the parity · Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to confirm each digit. · Scroll to LCD page Parity (PAr xxxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select even/none/odd. · Confirm the new setting by holding both buttons for 3 seconds. · The LCD will show OK when the setting is confirmed.
18 – KLEFR – 693-4x – Three phase

7 .15 Power down counter
The power down counter registers the number of times that the meter has been turned off.
7 .15 .1 How to reset the power down counter · Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to confirm each digit. · Scroll to LCD page Power down counter (P00 – xxxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: hold both buttons for 3 seconds to reset. · The LCD will show OK when the value is reset.
7 .16 Password
Program mode 3 is protected with a password. The default password is 0000.
7 .16 .1 How to change the password · Scroll with the buttons to Program mode 3. · Hold the right button for 3 seconds to enter the menu. · Enter the 4 digit password: scroll with the buttons and select each digit 0-9, hold the right button for 3 seconds to confirm each digit. · Scroll to LCD page Password (PAS _xxxx). · Hold the right button for 5 seconds to enter program mode. · The value starts blinking: select each digit 0-9, confirm each digit by holding both buttons for 3 seconds. · The LCD will show OK when the setting is confirmed.
7.17 CT ratio setting (CT version only) NOTE! CT ratio has to be programmed before use. Once programmed the CT ratio cannot be changed. A wrong CT ratio can cause wrong billing charges.
7 .17 .1 How to set the CT ratio · Turn on the meter: display shows SEt Ct – Ctx 0005. · Select secondary current /1 or /5. · Hold both buttons for 3 seconds to confirm. · Select the 4 digit primary current (0001-9999). · Confirm each digit by holding both buttons for 3 seconds. · The CT ratio is set and stored when the last digit is confirmed.
KLEFR – 693-4x – Three phase – 19

8 Troubleshooting

Caution
· During repair and maintenance, do not touch the meter connecting clamps directly with your bare hands, with metal, blank wire or other conducting material as that will cause an electric shock and possibly cause injury, serious injury or even death.
· Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it before opening the protection cover and working on it.
· Turn off and lock all power supply to the energy meter and the equipment to which it is installed before opening the protection cover to prevent the hazard of electric shock.

Warning
· Maintenance or repair should only be performed by qualified personnel familiar with applicable codes and regulations.
· Use insulated tools to maintain or repair the meter. · Make sure the protection cover is in place after maintenance or repair. · The case is sealed, failure to observe this instruction can result in damage to the meter.

Problem

Possible cause

Check/solution

The red consumption LED is not There is no load connected to the Connect a load to the meter. Check

flashing (PULSE LED).

meter. The load on the line is very low. with an Ohm-meter if the load value

is very low.

The register doesn’t count.

There is almost no load connected to Check if the red consumption LED is

the meter.

flashing.

No pulse output.

The pulse output is not supplied with Check the external voltage source

DC power. The pulse output is not (Ui) is 5-27V DC with a voltage meter.

connected correctly.

Check if the connection is correct: the

5-27V DC should be connected to the

collector connection (pin 18/20+) and

the signal wire (S) to the emitter con-

nection (pin 19/21-).

The pulse output rate is wrong.

Is the correct pulse rate set via the Download or request the software

infrared software or in Program mode and use the infrared eye which can

3?

be bought seperately.

If none of the above works, please contact technical support

20 – KLEFR – 693-4x – Three phase

8 .1 Errors / Diagnostics display
The meter is equipped with a display field that shows errors and diagnostics. It consists of the character S followed by 2 + 3 digits. The meaning of each digit is as follows: · First digit: Program status (0 fail / 1 passed) · Second digit: Eeprom status (0 fail / 1 passed) · Third digit: Phase A status (0 not available / 1 available) · Fourth digit: Phase B status (0 not available / 1 available) · Fifth digit: Phase C status (0 not available / 1 available) If the first or second digit shows a 0 (zero); then please return the meter, as the meter is malfunctioning. If the third, fourth or fifth digit shows a 0 (zero); please check the wiring for power issues.
8 .2 Technical support
For questions about one of our products please contact: · Email: support@klefr.com · Website: www.klefr.com
KLEFR – 693-4x – Three phase – 21

Appendix 1 – Multi tariff function
A1 .1 How to switch between T1 and T2
The meter is equipped with 2 tariff functionality which need to be activated by an external voltage connected to the terminals 23/24. This is an AC voltage between 23 and 24:
22 – KLEFR – 693-4x – Three phase

Appendix 2 – M-bus version
A2 .1 Communicating via the M-bus output
The Klefr 6933 and 6943 are equipped with an M-bus port, the data can be read out via this port. The communication protocol conforms to the EN13757-3 standard. The meter can communicate with your PC. In order to read out the meter registers first install and configure the PC software. Use an M-bus level converter to connect the PC and the meter. The cable should be connected to terminals 22 and 23. The default communication address of the meter is 00. The defaults for M-bus communication are:
· Baud rate 9600 · 8 data bits · Even parity · 1 stop bit
The secondary addressing (253/FD) is preset to the last 8 digits of the serial number printed on the side of the meter. However this can be changed to a more convenient number through IR or M-bus communication. The baud rate can be lowered to values 4800, 2400, 1200, 600 and 300 baud. Data, parity and stop bit cannot be changed. For the registers used in the meter and how to interpreted the data, please use the M-bus register map on the next page. More detailed information on M-Bus can be found: www.m-bus.com
KLEFR – 693-4x – Three phase – 23

A2 .2 M-bus register map

M-bus command
REQ_UD2 10 5B xx
Serial number Manufacturer ID Version Medium Acces number Status Signature

Contents

M-bus register header DIF

M-bus register VIF

Header

REQ UD2

10 5B 00 5B 16

Datablocks:

Total active energy

0C

04

Total active energy T1

8C10

04

Total active energy T2

8C20

04

Total forward active energy 1C

04

Forward active energy T1

9C10

04

Forward active energy T2

9C20

04

Total reverse active energy 2C

04

Reverse active energy T1

AC10

04

Reverse active energy T2

AC20

04

Checksum

Default Baudrate Databits Parity Stopbit Address Broadcast primary address

9600 8 Even 1 00 FE (only for read)

CRC settings without checksum

Start byte REQ UD2

2

Start byte write commands 5

CRC type

SUM

Terminating symbol

16

HEX

Low byte first

1 byte

CRC settings with checksum

No CRC

Response
68 xx xx 68 08 xx 72
00 00 00 00 25 CD 01 02 02 00 00 00

Remarks
68 [data length] 68 08 [address] 72 [header] [datablocks] [checksum] 16
00000000 INM Version Electricity Number of accesses 00 = OK 02 = error Always 00 00

68 4B 4B 68 08 00 72 68 xx xx [Data length] 68 08 xx [Address] 72

14 48 60 01 23 80 35 00 91 67 24 01 46 13 69 00 56 34 12 00 90 78 56 00 68 34 91 00 67 45 23 00 01 89 67 00 7C 16

01604814 Energy 10 (Wh) =16048,14kWh 00358023 Energy 10 (Wh) = 3580,23 kWh 01246791 Energy 10 (Wh) = 12467,91kWh 00691346 Energy 10 (Wh) = 6913,46 kWh 00123456 Energy 10 (Wh) = 1234,56 kWh 00567890 Energy 10 (Wh) = 5678,9 kWh 00913468 Energy 10 (Wh) = 9134,68 kWh 00234567 Energy 10 (Wh) = 2345,67 kWh 00678901 Energy 10 (Wh) = 6789,01 kWh xx 16

24 – KLEFR – 693-4x – Three phase

Write

Contents

Command part 1 Address Command part 2 New value

Response

Baudrate

68 03 03 68 53

01

BB

E5 (new Baud 2400)

Primary address

68 06 06 68 53

01

51 01 7A

01

E5 (new id 01)

Secondary address

68 09 09 68 53

01

51 0C 79

15 01 23 45 E5 (new address 1501 2345)

Tariff mode

68 08 08 68 53

01

51 09 7C 01 54

02

E5 (tariff 2)

Combined code

68 07 07 68 53

01

51 09 FD 3A

05

E5 (combined code 05)

S0 rate

68 0A 0A 68 53

01

51 0C FD 3A 00 00 01 00

E5 (S0 rate 100)

Resettable kWh

68 09 09 68 53

01

51 0C 04

00 00 00 00

E5

Reset power down counter 68 08 08 68 53

01

51 0A FD 60

00 00

E5

Remarks B8 = 300; B9 = 600; BA = 1200; BB = 2400; BC = 4800; BD = 9600
000 – 247 write in HEX 4 bytes BCD same as read
T1 = 01 ; T2=02 01, 04, 05, 06, 09, 10 and 11 10.000 / 2.000 / 1.000 / 100 / 10 / 1 / 0,1 / 0,01 Value is ignored, always set to 0 Value is ignored, always reset to 0

SND NKE

10 40

01

E5

Can be send to primary or secondary address and resets all communication values

Selecting slave by secondary addressing 68 0B 0B 68 53 FD 52 Input Remarks

Serial number aa aa aa aa 01 00 07 13 13070001

Manufacturer ID bb bb 25 CD –

Generation version cc 01 Major version of the software

Medium dd 02 Electricity

KLEFR – 693-4x – Three phase – 25

Appendix 3 – Modbus version
A3 .1 Communicating via the Modbus output
The meter can communicate with your PC. In order to read out the meter registers first install and configure the PC software. Use an RS485 level converter to connect the PC and the meter. The cable should be connected to terminals 22 and 23. The default communication address of the meter is 01. The PRO380-Mod can be connected for Modbus communication. The Modbus implementation used is Modbus basic (standard). This means the following:
· Baud rate 9600 · 8 data bits · Even parity · 1 stop bit The baud rate can be lowered to values 4800, 2400, 1200, 600 and 300. The parity can be set to none or odd. Data and stopbit cannot be changed.
When connecting the meter through a serial converter (RS485) for testing, please be aware that because of not implementing the complete Modbus infrastructure, there will be a need to put an additional resistor (120 ohms/ 0,25 watts) across the terminals (22 & 23) on the meter side. For the registers used in the meter and how to interpreted the data, please use the Modbus register map on the next pages. More info on Modbus can be found: Physical: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf Protocol: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b3.pdf
26 – KLEFR – 693-4x – Three phase

A3 .2 Modbus register map

Reg. address
4000 4002 4003 4004 4005 4007 4009 400B 400C 400D 400F 4010 4011 4012 4013 4014 4015 4016 4017 4018 4019 401A 401B 401D 401F

Content
Serial number Meter code Modbus ID Baud rate Protocol version Software version Hardware version Meter amps CT ratio S0 output rate Calculation code LCD cycle time Parity setting Current direction L2 Current direction L3 Current direction Error code* Power down counter Present quadrant L1 Quadrant L2 Quadrant L3 Quadrant Checksum Active status word CT mode

Reg. address
5000 5002 5004 5006 5008 500A 500C 500E 5010 5012 5014 5016 5018 501A 501C 501E 5020 5022 5024 5026 5028 502A 502C 502E 5030

Content
Voltage L1 Voltage L2 Voltage L3 Voltage Grid frequency Current L1 Current L2 Current L3 Current Total active power L1 Active power L2 Active power L3 Active power Total reactive power L1 Reactive power L2 Reactive power L3 Reactive power Total apparent power L1 Apparent power L2 Apparent Power L3 Apparent Power Power factor L1 Power factor L2 Power factor L3 Power factor

Reg. address
6000 6002 6004 6006

Content
Total active energy T1 Total active energy T2 Total active energy L1 Total active energy

Function code 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

Register length
2 1 1 1 2 2 2 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1

Unit Data type

HEX

HEX

Signed

Signed

Float ABCD

Float ABCD

Float ABCD

A

Signed

A

HEX

imp/kWh Float ABCD

Signed

sec.

HEX

Signed

ASCII

ASCII

ASCII

Signed

Signed

Signed

Signed

Signed

Signed

HEX

HEX

A

Signed

Function code 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03 03

Register length
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Unit
V V V V Hz A A A A kW kW kW kW kvar kvar kvar kvar kVA kVA kVA kVA –

Data type
Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD

Function code 03 03 03 03

Register length
2 2 2 2

Unit
kWh kWh kWh kWh

Data type
Float ABCD Float ABCD Float ABCD Float ABCD

KLEFR – 693-4x – Three phase – 27

6008

L2 Total active energy

03

2

600A

L3 Total active energy

03

2

600C

Forward active energy

03

2

600E

T1 Forward active energy

03

2

6010

T2 Forward active energy

03

2

6012

L1 Forward active energy

03

2

6014

L2 Forward active energy

03

2

6016

L3 Forward active energy

03

2

6018

Reverse active energy

03

2

601A

T1 Reverse active energy

03

2

601C

T2 Reverse Active Energy

03

2

601E

L1 Reverse active energy

03

2

6020

L2 Reverse active energy

03

2

6022

L3 Reverse active energy

03

2

6024

Total reactive energy

03

2

6026

T1 Total reactive energy

03

2

6028

T2 Total reactive energy

03

2

602A

L1 Total reactive energy

03

2

602C

L2 Total reactive energy

03

2

602E

L3 Total reactive energy

03

2

6030

Forward reactive energy

03

2

6032

T1 Forward reactive energy 03

2

6034

T2 Forward reactive energy 03

2

6036

L1 Forward reactive energy

03

2

6038

L2 Forward reactive energy

03

2

603A

L3 Forward reactive energy

03

2

603C

Reverse reactive energy

03

2

603E

T1 Reverse reactive energy

03

2

6040

T2 Reverse reactive energy

03

2

6042

L1 Reverse reactive energy

03

2

6044

L2 Reverse reactive energy

03

2

6046

L3 Reverse reactive energy

03

2

6048

Tariff

03

1

6049

Resettable day counter

03

2

kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kvarh kWh

Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Float ABCD Signed Float ABCD

Write Reg. address 4003 Command: 4004 Command: 400D
Command:
400F Command: 4010 Command: 4011 Command: 4016 Command: 6048
Command:
6049 Command:

Content

Function code Register length Unit Data type

Modbus ID

06

1

Signed

01 06 4003 000A (new ID: 10)

01~247 – 01 default – 00 broadcast

Baud rate

06

1

Signed

01 06 4004 25 80 (new Baudrate: 9600)

300 – 600 – 1200 – 4800 – 9600

S0 output rate

10

2

imp/kWh Float ABCD

01 10 400D 0002 04 41 20 00 00 (new S0: 10)

10.000 – 2.000 – 1.000 – 100 – 10 – 1 – 0,1 – 0,01

Calculation code

06

1

Signed

01 06 400F 000A (new code: 10 F-R)

01, 04, 05, 06, 09, 10, 11

LCD cycle time

06

1

sec.

HEX

01 06 4010 0025 (new time: 25 sec.)

01~30

Parity setting

06

1

Signed

01 06 4011 0002 (new parity: none)

01: even – 02: none – 03: odd

Power down counter

06

1

Signed

01 06 4016 0000

Reset to 0

Tariff

06

1

Signed

01 06 6048 0002 (new tariff: 2)

01: T1 – 02: T2 – 11: T1 not saved 12: T2 not saved

Resettable day counter

10

1

kWh

Float ABCD

01 10 6049 0002 04 0000 0000

Reset to 0

*Single phase only

28 – KLEFR – 693-4x – Three phase

Appendix 4 – Infrared PC software
All KLEFR meters are capable to be read out and configured by IR. The standard used is IRDA (IEC62056-21:2002 (IEC1107)). IR converter and accompanying software are sold separately. Please contact your dealer. You can download the infrared software from www.klefr.com.
Infrared PC software
Connect the meter to the PC using the KLEFR Infrared eye and bracket. 1. Open the KLEFR IR software program and select KLEFR 693/4x.
1
KLEFR – 693-4x – Three phase – 29

Connect the meter
1. Select the correct COM port. 2. Press Connect. 3. Click on Read meter address. 4. The serial number of the connected meter will appear under meter address.

1

2

3

4

30 – KLEFR – 693-4x – Three phase

Read single data
1. Select the value that you would like to read, in the dropdown menu under Read meter – Single data. 2. Press Read. 3. The meter data will be displayed under Return data – Meter data.

1

2

3

KLEFR – 693-4x – Three phase – 31

Read multi data
1. Press select. 2. Select the values that you would like to read. 3. Press Read. 4. The meter data will be displayed under Return data – Meter data.

4

1

3

2

32 – KLEFR – 693-4x – Three phase

Meter data settings
1. Select the register that you would like to program. 2. Select the new value. 3. Press Setting. 4. The software will show Set success when the setting is confirmed.

1

2

3

4

KLEFR – 693-4x – Three phase – 33

Save mode
1. Select the register that you would like to program. 2. Select the new value. 3. Press Add to save mode. – Select the next register that you would like to program and add to save mode. 4. Press Show save mode. 5. The save mode will be displayed under Return data – Save mode item. 6. Press Write save mode to meter to write the new values to the meter. 7. The software will show Set success when the setting is confirmed.
5
1 2 3 4 6
7
34 – KLEFR – 693-4x – Three phase

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals