PHILIPS dynalite DDC116 Driver Controller
Specifications
-
Electrical:
- Supply Type: Single-Phase 100-277 VAC
- Supply Voltage: 0.5 A
- DyNet DC Output Voltage: 12 VDC
- DyNet DC Output Current: 200 mA
- Switched Output: 1 x 20 A
- Output Channel Ratings: III
-
Control:
- Serial Ports: 1 x RS-485, DyNet
- Supported Protocols: DMX Rx, 1 x AUX/UL924
- User Controls: 1 x service switch
- Indicators: 1 x service LED
-
Physical:
-
Dimensions (H x W x D): 4.40 x 4.33 x 1.69 in (112 x 110 x 43
mm) -
Packed Weight: 0.6 lb (0.27 kg)
-
Construction: Polycarbonate
-
-
Environment:
- Operating Temperature: 0 to 90%
- Relative Humidity: Non-condensing
- Ingress Protection Rating: IP20 II
-
Compliance:
- Certification: UL/cUL, FCC, ICES, RoHS Plenum UL 2043
Product Usage Instructions
Installation and Setup:
- Ensure power is turned off before installation.
- Mount the DDC116 load controller in a suitable junction box using standard wiring schemes.
- Connect the supply and load wires according to the specified conductor sizes.
- Connect control outputs to the desired lighting circuits.
PHILIPS dynalite DDC116 Driver Controller
- Use the provided user controls to configure the control channels and settings.
- Monitor the status indicators for device online/offline information.
- For advanced diagnostics, utilize the Philips Dynalite System Manager.
FAQ
-
Q: Can the DDC116 control both 0-10V and DALI lighting circuits simultaneously?
A: Yes, the DDC116 load controller can intelligently control both 0-10V and DALI broadcast lighting circuits. -
Q: What is the maximum switched output rating of the DDC116?
A: The DDC116 has a switched output rating of 20 A. -
Q: Is the DDC116 suitable for outdoor installation?
A: No, the DDC116 is designed for indoor installation only.
Speed up your lighting control design and installations
The Philips Dynalite DDC116 load controller provides intelligent networked
control of 0-10V and DALI broadcast lighting circuits, delivering the
flexibility to easily scale your projects from room-based controls to complete
building-wide networked controls.
The compact plenum-rated design is compatible with standard junction box
wiring schemes, reducing your installation effort and project costs.
DDC116
Speed up your lighting control design and installations
- Incorporates one relay output and one signal dimmer output – Provides dimming control of 0-10 V or DALI broadcast drivers and transformers.
- Driver standby power elimination – Internal relay automatically isolates the lighting power circuit when driver is dimmed to 0%.
- UL924 Input – Integrates seamlessly with compatible emergency systems.
- Flexible mounting solution – UL 2043 / Chicago plenum-rated plastic enclosure designed for mounting directly onto a junction box.
- Inbuilt diagnostic functionality – Features Device Online/Offline status indication.
- Easy to install and configure – Reduced installation complexity and project costs.
- Flexible deployment – Suitable for room-based applications or integration across multiple spaces.
- Standalone operation – Single-button configuration assigns the DDC116 to one of five preconfigured lighting zones, enabling individual zone control via the Philips Dynalite range of user interfaces and sensors, without the need for commissioning or head-end software.
- Networked operation – Seamless connectivity to the rest of the Dynalite system enables a range of expanded functionality such as automated scheduling, head-end software monitoring and management, and network gateway integration to third-party systems including BACnet, OPC UA, and others.
Dimensions
Specifications
Due to continuous improvements and innovations, specifications may change without notice.
Electrical
- Supply Type Single-Phase
- Supply Voltage 100-277 VAC
- Supply Current 0.5 A
- DyNet DC Output Voltage 12 VDC
- DyNet DC Output Current 200 mA
- Switched Output 1 x 20 A
- Output Channel Ratings (See Page 4)
- IEC Overvoltage Category III
Control
- Serial Ports 1 x RS-485
- Supported Protocols DyNet
- DMX Rx
- DMX Rx Channels 1
- Dry Contact Inputs 1 x AUX/UL924
- Control Channel Outputs 1(0-10 V or DALI Broadcast)
- User Controls 1 x service switch
- Indicators 1 x service LED
- Diagnostic Functions* Device online/offline status
Philips Dynalite System Manager required for analyzing diagnostic data.
The availability of some diagnostics is dependent on driver type.
Physical
- Dimensions (H x W x D) 4.40 x 4.33 x 1.69 in (112 x 110 x 43 mm)
- Packed Weight 0.6 lb (0.27 kg)
- Construction Polycarbonate
- Serial 1 x 3-way cage clamp terminal (common ground) 2 x RJ45
- Dry Contact 1 x 2-way cage clamp terminal (common ground)
- Cage Clamp Terminal Conductor Size #24-16 AWG (0.2-1.5 mm2)
- Supply/Load 4 x fly lead
- Line IN, Earth, Neutral, Line OUT
- Supply Conductor Size 12 AWG (2.5 mm2)
- Control Output 2 x fly lead
- V+/DA+, V-/DA-
- Control Output Conductor Size 18 AWG (0.75 mm2)
- Fly Lead Length 7.87 in (200 mm)
Environment
- Operating Temperature 32° to 113°F ambient (0° to 45°C)
- Storage/Transport Temperature -13° to 185°F ambient (-25° to 85°C)
- Relative Humidity 0 to 90% non-condensing
- Ingress Protection Rating IP20
- IEC Pollution Degree II
Compliance
- Certification UL/cUL, FCC, ICES, RoHS
- Plenum UL 2043
For indoor installation only
Electrical
Control Channel Ratings
- DALI Broadcast Channel
- Guaranteed Current 100 mA
- Maximum Current 250 mA
- Maximum Drivers 40
- Insulation Basic
- 0-10 V Channel
- Current
- Sink 100 mA
- Source 100 mA
Output Channel Ratings
- Load Type Maximum Rating per Output CH1
- General Use* 20 A, 277 VAC
- Electronic Driver 16 A, 277 VAC
- Pilot Duty
- 6 A, 120 VAC
- 3A, 140 VAC
- 2.6 A, 277 VAC
- Motor
- 16 FLA (1 HP), 120 VAC
- 14.5 FLA (2 ½ HP), 240 VAC
- 14.1 FLA (3 HP), 277 VAC
To avoid electrical overload, the total external connected load must not
exceed the output rating.
Controlled receptacle (plug load)
Ordering Code
- Product Philips 12NC
- DDC116-UL 913703376709
© 2024 Signify Holding.
All rights reserved. Specifications are subject to change without notice. No
representation or warranty as to the accuracy or completeness of the
information included herein is given and any liability for any action in
reliance thereon is disclaimed. Philips and the Philips Shield Emblem are
registered trademarks of Koninklijke Philips N.V. All other trademarks are
owned by Signify Holding or their respective owners.
www.dynalite.com
Revision 06 – 2024-05-03
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>