Schneider Electric Galaxy VS Panel for Two USB Devices Installation Guide
- August 17, 2024
- Schneider Electric
Table of Contents
Galaxy VS Panel for Two USB Devices
“`html
Specifications
Product: Galaxy VS, Easy UPS 3S, and Easy UPS
3M
EMC: Electromagnetic compatibility
Safety Measures:
-
Persons will be in danger or seriously injured if these
instructions are not followed. -
Equipment may be damaged if these instructions are not
followed.
Product Usage Instructions
Electromagnetic Compatibility
Ensure that the product is compliant with electromagnetic
compatibility standards to prevent interference with other
devices.
Safety Measures
Follow all safety instructions carefully to avoid any risks or
injuries during installation and operation of the UPS system.
Additional Safety Measures After Installation
Continue to adhere to safety precautions even after the
installation process to maintain a secure operating
environment.
Electrical Safety
This guide contains essential safety instructions for the proper
installation and maintenance of the UPS system. Failure to comply
may result in serious injury.
FAQ
Q: What should I do if I encounter difficulties during
installation?
A: If you face any challenges during installation, refer to the
user manual for troubleshooting steps or contact customer support
for assistance.
Q: Can the UPS system be used outdoors?
A: It is recommended to use the UPS system indoors to protect it
from environmental factors that may affect its performance.
“`
Vægmonteret parallelt vedligeholdelsesbypasspanel til to UPSenheder
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M Installation
GVSBPAR10K30H, GVSBPAR40K50H, GVSBPAR60K120H De seneste opdateringer er
tilgængelige på Schneider Electrics hjemmeside 10/2023
www.se.com
Juridiske oplysninger
Oplysningerne i dette dokument indeholder generelle beskrivelser, tekniske
egenskaber og/eller anbefalinger vedrørende produkter/løsninger.
Dette dokument er ikke beregnet som erstatning for en detaljeret undersøgelse
eller en drifts- og stedspecifik udvikling eller skematisk plan. Det skal ikke
anvendes til at afgøre, om produkterne/løsningerne er egnede eller pålidelige
til specifikke brugerapplikationer. Det påhviler enhver sådan bruger at
foretage eller lade en professionel ekspert efter eget valg (integrator,
specificator eller lignende) foretage en passende og omfattende risikoanalyse,
evaluering og afprøvning af produkterne/ løsningerne i forbindelse med den
relevante specifikke anvendelse eller brug heraf.
Schneider Electrics brand og alle varemærker tilhørende Schneider Electric SE
og dets datterselskaber, der henvises til i denne vejledning, tilhører
Schneider Electric SE eller dets datterselskaber. Alle andre brands kan være
varemærker tilhørende deres respektive ejer.
Dette dokument og indholdet af den er beskyttet i henhold til gældende love om
ophavsret og stilles kun til rådighed til oplysning. Ingen del af dette
dokument må gengives eller transmitteres i nogen form eller på nogen måde
(elektronisk, mekanisk, ved fotokopiering, optagelse eller på anden måde) til
noget formål uden forudgående skriftlig tilladelse fra Schneider Electric.
Schneider Electric tildeler ingen rettigheder eller licens til kommerciel brug
af dokumentet eller dets indhold, bortset fra en ikke-eksklusiv og personlig
licens til at referere til den på en “som den er og forefindes”-basis.
Schneider Electric forbeholder sig ret til at foretage ændringer eller
opdateringer med hensyn til eller i indholdet af dette dokument eller dets
format til enhver tid uden varsel.
I det omfang, gældende lov tillader dette, påtager Schneider Electric og dets
datterselskaber sig ikke ansvar for eventuelle fejl eller udeladelser i
informationsindholdet i dette materiale eller for konsekvenser, der måtte
opstå som følge eller resultat af brugen af oplysningerne heri.
Indholdsfortegnelse
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
……………………………………………………………………………….5
Elektromagnetisk kompatibilitet ………………………………………………………….6
Sikkerhedsforanstaltninger ………………………………………………………………..6
Yderligere sikkerhedsforanstaltninger efter installation………………………..8
Elsikkerhed ………………………………………………………………………………9
Specifikationer ………………………………………………………………………………. 10
Anbefalede kabelstørrelser for Galaxy VS ………………………………………….. 11 Anbefalet
beskyttelse før indgangen på udstyret/UPS’en for Galaxy VS
……………………………………………………………………………………………..13 Anbefalede kabelstørrelser til Easy
UPS 3S og Easy UPS 3M………………….15 Anbefalet beskyttelse før indgangen til Easy
UPS 3S og Easy UPS 3M…………………………………………………………………………………………….. 17 Specifikationer
for drejningsmoment ………………………………………………….19 Forsendelsesvægt og -mål for
parallelt vedligeholdelsesbypasspanel …………………………………………………………..19 Vægt og mål
for parallelt vedligeholdelsesbypasspanel ………………………….19 Afstand
……………………………………………………………………………………….20 Overholdelse af regler og standarder
…………………………………………………20 Miljø …………………………………………………………………………………………..20
Enstregsdiagram …………………………………………………………………………..21
Installationsprocedure for Galaxy VS …………………………………………….25
Installationsprocedure for Easy UPS 3S og Easy UPS 3M …………….26 Monter det
parallelle vedligeholdelsesbypasspanel på
væggen…………………………………………………………………………………………. 27 Klargør til kabler
…………………………………………………………………………….30 Fjern den neutrale
jumper………………………………………………………………31 Tilslut strømkablerne på GVSBPAR10K30H
………………………………….33 Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPSsystem
…………………………………………………………………………………………..34 Tilslut strømkablerne på GVSBPAR40K50H
til et 3:3 UPSsystem …………………………………………………………………………………………..37 Tilslut
strømkablerne på GVSBPAR60K120H til et 3:1 UPSsystem
…………………………………………………………………………………………..38 Tilslut strømkablerne på GVSBPAR60K120H
til et 3:3 UPSsystem …………………………………………………………………………………………..41 Slut
signalkablerne til Galaxy VS UPS-enheder …………………………….43 Slut signalkablerne
til Easy UPS 3S og Easy UPS 3M …………………..45 Tilføj oversatte sikkerhedslabels
på produktet ……………………………….49 Tag det parallelle vedligeholdelsesbypasspanel ud
af drift eller flyt det til en ny placering………………………………………………………………..50
990-91216D-004
3
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
Læs disse instrukser grundigt, og kig på udstyret, så du bliver fortrolig med
det, før du forsøger at installere, betjene, efterse eller vedligeholde det.
De følgende sikkerhedsmeddelelser kan optræde i denne manual eller på udstyret
for at advare om mulige farer. De kan også henlede opmærksomheden på
oplysninger, der tydeliggør eller forenkler en procedure.
Hvis dette symbol føjes til en sikkerhedsmeddelelse med overskriften “Fare”
eller “Advarsel”, betyder det, at der er risiko for farlig elektricitet, som
kan medføre personskade, såfremt instruktionerne ikke følges.
Dette er symbolet for sikkerhedsadvarsler. Det bruges til at advare dig om
mulige farer for personskade. Adlyd alle sikkerhedsmeddelelser med dette
symbol for at undgå risiko for kvæstelse eller død.
FARE
FARE angiver faretruende situationer, som vil medføre dødsfald eller alvorlige
personskader, hvis de ikke undgås.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
ADVARSEL
ADVARSEL angiver faretruende situationer, som kan medføre dødsfald eller
alvorlige personskader, hvis de ikke undgås.
Personer kan komme i livsfare eller alvorligt til skade, eller udstyr kan
blive beskadiget, hvis disse instrukser ikke overholdes.
FORSIGTIG
FORSIGTIG angiver faretruende situationer, som kan medføre mindre eller
moderate personskader, hvis de ikke undgås. Personer kan komme til skade,
eller udstyr kan blive beskadiget, hvis disse instrukser ikke overholdes.
BEMÆRK
BEMÆRK bruges om aktiviteter, som ikke relaterer til personskader. Symbolet
for sikkerhedsadvarsler bliver ikke brugt til denne type sikkerhedsmeddelelse.
Udstyr kan blive beskadiget, hvis disse instrukser ikke overholdes.
Bemærk
Elektrisk udstyr bør kun installeres, bruges, efterses og vedligeholdes af
kvalificeret personale. Schneider Electric fralægger sig ethvert ansvar for
konsekvenser, som skyldes brugen af dette materiale.
En kvalificeret person er én, som har færdigheder og viden, som knytter sig
til konstruktionen, installationen og betjeningen af elektrisk udstyr.
Personen er
990-91216D-004
5
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
desuden sikkerhedsuddannet til at genkende og undgå de farer, som det
indebærer.
Jvf. IEC 62040-1: “Uninterruptible power systems (UPS) — Part 1: Safety
Requirements” skal dette udstyr, herunder adgang til batterier, inspiceres,
installeres og vedligeholdes af en faglært person.
Den faglærte person er en person med relevant uddannelse og erfaring, der gør
ham eller hende i stand til at opfatte risici og undgå farer, som udstyret kan
skabe (reference IEC 62040-1, afsnit 3.102).
Elektromagnetisk kompatibilitet
BEMÆRK
RISIKO FOR ELEKTROMAGNETISK INTERFERENS Dette er et UPS-produkt i kategori C2.
I et beboelsesområde kan dette produkt udsende radiostøj, hvor brugeren evt.
selv skal tage yderligere forholdsregler. Udstyr kan blive beskadiget, hvis
disse instrukser ikke overholdes.
Sikkerhedsforanstaltninger
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Læs alle instruktioner i installationsmanualen, før du installerer eller
arbejder på dette produkt.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Installer ikke produktet, før alt byggearbejde er afsluttet, og
installationslokalet er rengjort.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Produktet skal installeres i henhold til de specifikationer og krav, som er
defineret af Schneider Electric. Det drejer sig især om de eksterne og interne
beskyttelsesanordninger (indgangsafbrydere, batteriafbrydere, kabler, osv.) og
miljøkrav. Schneider Electric fralægger sig ethvert ansvar, hvis disse krav
ikke overholdes.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
6
990-91216D-004
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
UPS-systemet skal installeres i henhold til gældende regler. Installer
UPSsystemet i henhold til: · IEC 60364 (herunder 60364-4-41 beskyttelse mod
elektrisk stød, 60364-4-
42 beskyttelse mod termisk påvirkning og 60364-4-43 beskyttelse mod
overstrøm), eller · NEC NFPA 70 eller · Canadian Electrical Code (C22.1, Part
- afhængigt af de gældende standarder i dit lokalområde.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser ikke overholdes.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER · Installer produktet i et temperaturkontrolleret indendørs miljø uden
strømførende forurening og fugt. · Produktet skal installeres på en ikke- brændbar, jævn og solid overflade (f.
eks. beton), som kan bære systemets vægt. Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser ikke overholdes.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Produktet er ikke beregnet til og må derfor ikke installeres i følgende usædvanlige driftsmiljøer: · Skadelige dampe · Eksplosive støv- eller gasblandinger, ætsende gasser samt lednings- eller
strålevarme fra andre kilder · Fugt, slidende støv, damp eller i et meget fugtigt miljø · Svamp, insekter, skadedyr · Saltholdig luft eller urent kølemiddel · Forureningsgrader over 2 i henhold til IEC 60664-1 · Usædvanlige vibrationer, stød eller vipning · Direkte sollys, varmekilder eller stærke elektromagnetiske felter Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser ikke overholdes.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Undlad at bore eller udskære huller til kabler eller kabelgennemføring, når forskruningspladerne er monteret, og undlad at bore eller udskære huller tæt på UPS-systemet.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser ikke overholdes.
990-91216D-004
7
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
ADVARSEL
FARE FOR LYSBUER Foretag ikke mekaniske ændringer i produktet (herunder at
fjerne skabsdele og bore/udskære huller), som ikke er beskrevet i
installationsmanualen.
Personer kan komme i livsfare eller alvorligt til skade, eller udstyr kan
blive beskadiget, hvis disse instrukser ikke overholdes.
BEMÆRK
FARE FOR OVEROPHEDNING Respekter pladskravene omkring produktet, og tildæk
ikke ventilationsåbningerne, når produktet er i drift.
Udstyr kan blive beskadiget, hvis disse instrukser ikke overholdes.
Yderligere sikkerhedsforanstaltninger efter installation
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Installer ikke UPS-systemet, før alt byggearbejde er afsluttet, og
installationslokalet er rengjort. Hvis der er behov for yderligere
byggearbejde i installationslokalet, efter at produktet er installeret, skal
produktet slukkes og dækkes til med den beskyttelsespose, det blev leveret i.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
8
990-91216D-004
Vigtige sikkerhedsanvisninger GEM DISSE ANVISNINGER
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Elsikkerhed
Denne vejledning indeholder vigtige sikkerhedsanvisninger, som skal overholdes
under installation og vedligeholdelse af UPS-systemet.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
· Det elektriske udstyr må kun installeres, bruges, efterses og vedligeholdes
af kvalificeret personale.
· Anvend passende, personligt beskyttelsesudstyr (PPE), og følg praksis for
sikkert elarbejde.
· Frakoblingsenheder for vekselstrøm og jævnstrøm skal leveres af andre og
være lettilgængelige, og frakoblingsenhedens funktion skal være markeret.
· Afbryd al strømforsyning til UPS-systemet, før du arbejder på eller inde i
det.
· Kontrollér, om der er farlig spænding mellem nogen af terminalerne, herunder
beskyttelsesjordingen, før du arbejder på UPS-systemet.
· UPS-systemet indeholder en intern energikilde. Der kan være farlig spænding
til stede, også når enheden ikke er tilkoblet hovedforsyningen. Før
installation eller eftersyn af UPS-systemet skal du sikre, at enhederne er
SLUKKEDE, og at både hovedforsyningen og batterierne er frakoblet. Vent fem
minutter, før du åbner UPS-systemet, så kondensatorerne får tid til at aflade.
· UPS-systemet skal have korrekt jordforbindelse, og jordforbindelsen skal
etableres først på grund af høj afledningsstrøm.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
Hvis UPS-indgangen er forbundet gennem eksterne isoleringsenheder, som efter
åbning isolerer den neutrale indgangsforbindelse, eller hvis den automatiske
tilbagekoblingsisolering er ekstern i forhold til udstyret eller forbundet til
et ITstrømfordelingssystem, skal brugeren fastgøre en mærkat med følgende
tekst (eller tilsvarende på et sprog, der er udbredt i det land, hvor UPS-
systemet er installeret) på UPS-indgangsterminalerne, på alle primære
strømisoleringer installeret uden for UPS-området og på eksterne
adgangspunkter mellem disse isoleringsenheder og UPS-systemet:
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Risiko for spændingstilbagekobling. Før der arbejdes på dette kredsløb: Isoler
UPS-systemet, og kontrollér, om der er farlig spænding mellem samtlige
terminaler, herunder beskyttelsesjordingen.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
990-91216D-004
9
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Specifikationer
Specifikationer
BEMÆRK: Maksimal kortslutningsklassificering: 10 kA RMS symmetrisk.
Til et 1+1 parallelsystem for redundans kan det parallelle
vedligeholdelsesbypasspanel forsyne en last på op til 120 kW/kVA så længe den
neutrale strøm (250 A) ikke overstiges:
· ved 380 V opnås den maksimale neutrale strømkapacitet med en ikke-lineær
last på 95 kVA.
· ved 400 V opnås den maksimale neutrale strømkapacitet med en ikke-lineær
last på 100 kVA.
Til et 2+0 parallelsystem for kapacitet kan det parallelle
vedligeholdelsesbypasspanel forsyne en last på op til 240 kW/kVA så længe den
neutrale strøm (500 A) ikke overstiges:
· ved 380 V opnås den maksimale neutrale strømkapacitet med en ikke-lineær
last på 190 kVA.
· ved 400 V opnås den maksimale neutrale strømkapacitet med en ikke-lineær
last på 200 kVA.
10
990-91216D-004
Specifikationer
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Anbefalede kabelstørrelser for Galaxy VS
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Al ledningsinstallation skal overholde gældende regler for elinstallationer.
· Den maksimalt tilladte størrelse for indgangskabler og lastkabler er 35 mm2
og den maksimalt tilladte størrelse for UPS-indgangskabler og UPSudgangskabler
er 16 mm2 for GVSBPAR10K30H.
· Den maksimalt tilladte størrelse for indgangskabler og lastkabler er 70 mm2
og den maksimalt tilladte størrelse for UPS-indgangskabler og UPSudgangskabler
er 25 mm2 for GVSBPAR40K50H.
· Den maksimalt tilladte størrelse for indgangskabler og lastkabler er 185 mm2
og den maksimalt tilladte størrelse for UPS-indgangskabler og UPSudgangskabler
er 50 mm2 for GVSBPAR60K120H.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
Kobber
BEMÆRK: Overstrømsbeskyttelse skal leveres af andre.
I denne manual er kabelstørrelser baseret på tabel B.52.5 i IEC 60364-5-52 med
følgende angivelser:
· 90 °C strømledere
· Omgivelsestemperatur på 30 °C
· Brug af strømledere af kobber eller aluminium
· Installationsmetode C
PE-størrelse er baseret på tabel 54.2 i IEC 60364-4-54.
Hvis omgivelsestemperaturen er over 30 °C, skal der vælges større strømledere
i overensstemmelse med IEC’s korrektionsfaktorer. Aluminiumskabler anbefales
ikke ved omgivelsestemperaturer på over 30 °C.
BEMÆRK: Nullederen er dimensioneret til 1,73 gange fasestrøm i tilfælde af
højt harmonisk indhold fra ikke-lineær last. Hvis der ikke forventes nogen
eller kun lave harmoniske strømme, kan nullederen dimensioneres som
faselederen.
Kommerciel reference Parallelsystemtype
GVSBPAR10K30H Kapacitet (2+0)
Klassifikation af parallelsystem
20 kW 40 kW
Indgangsfaser (mm2) 6
16
Indgangs-PE (mm2) 6
16
Indgang N (mm2)
10
35
UPS-indgang (mm2) 6
6
UPS-udgang (mm2) 6
6
UPS PE (mm2)
6
6
UPS N (mm2)
6
10
Last (mm2)
6
16
Last PE (mm2)
6
16
Last N (mm2)
10
35
60 kW
35 16 2 x 16 10 10 10 16 25 16 2 x 16
Redundans (1+1) 10 kW 20 kW
6
6
6
6
6
10
6
6
6
6
6
6
6
10
6
6
6
6
6
10
30 kW
10 10 16 10 10 10 16 10 10 16
GVSBPAR40K50H
Kapacitet (2+0) 80 kW 100 kW
Redundans (1+1) 40 kW 50 kW
50 25 2 x 50 16 16 16 2 x 16 50 25 2 x 50
70 35 2 x 70 25 16 16 2 x 16 70 35 2 x 70
16 16 35 16 16 16 2 x 16 16 16 35
25 16 50 25 16 16 2 x 16 16 16 50
990-91216D-004
11
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Specifikationer
Kobber
Kommerciel reference Parallelsystemtype
GVSBPAR60K120H Kapacitet (2+0)
Klassifikation af parallelsystem
120 kW
160 kW
Indgangsfaser (mm2) 95
120
Indgangs-PE (mm2) 50
70
Indgang N (mm2)
120
2 x 120
UPS-indgang (mm2) 35
50
UPS-udgang (mm2) 25
50
UPS PE (mm2)
25
25
UPS N (mm2)
50
95
Last (mm2)
95
120
Last PE (mm2)
50
70
Last N (mm2)
120
2 x 120
200 kW
185 95 2 x 150 2 x 25 2 x 25 35 3 x 35 185 95 2 x 150
240 kW
2 x 120 120 3 x 150 2 x 50 2 x 35 50 3 x 35 2 x 95 95 3 x 150
Redundans (1+1)
60 kW
80 kW
35
50
25
25
50
95
35
50
25
50
25
25
50
2 x 50
25
50
16
25
50
95
100 kW
70 35 120 2 x 25 2 x 25 35 3 x 35 70 35 120
120 kW
95 50 120 2 x 50 2 x 35 50 3 x 35 95 50 120
Aluminium
Kommerciel reference Parallelsystemtype
GVSBPAR10K30H Kapacitet (2+0)
Klassifikation af parallelsystem
20 kW 40 kW
Indgangsfaser (mm2) 6
25
Indgangs-PE (mm2) 6
16
Indgang N (mm2)
2 x 16 2 x 16
UPS-indgang (mm2) 6
6
UPS-udgang (mm2) 6
6
UPS PE (mm2)
6
6
UPS N (mm2)
6
16
Last (mm2)
6
16
Last PE (mm2)
6
16
Last N (mm2)
16
2 x 16
60 kW
IR IR IR IR IR IR IR IR IR IR
Redundans (1+1) 10 kW 20 kW
6
6
6
6
6
16
6
6
6
6
6
6
6
16
6
6
6
6
6
2 x 16
30 kW
IR IR IR IR IR IR IR IR IR IR
GVSBPAR40K50H
Kapacitet (2+0) 80 kW 100 kW
Redundans (1+1) 40 kW 50 kW
70
IR
35
IR
2 x 70 IR
25
IR
16
IR
16
IR
2 x 16 IR
70
IR
35
IR
2 x 70 IR
25
IR
16
IR
50
IR
25
IR
16
IR
16
IR
2 x 16 IR
16
IR
16
IR
50
IR
Aluminium
Kommerciel reference Parallelsystemtype
GVSBPAR60K120H Kapacitet (2+0)
Klassifikation af parallelsystem
120 kW
160 kW
Indgangsfaser (mm2) 150
185
Indgangs-PE (mm2) 95
95
Indgang N (mm2)
185
2 x 120
UPS-indgang (mm2) 50
2 x 35
UPS-udgang (mm2) 50
2 x 35
UPS PE (mm2)
25
35
UPS N (mm2)
2 x 35
3 x 35
200 kW
2 x 120 150 3 x 150 2 x 50 2 x 35 50 3 x 50
240 kW
IR IR IR IR IR IR IR
Redundans (1+1)
60 kW
80 kW
50 25 70 50 50 25 2 x 35
70 70 150 2 x 35 2 x 35 35 3 x 35
100 kW
95 50 185 2 x 50 2 x 35 50 3 x 50
120 kW
IR IR IR IR IR IR IR
12
990-91216D-004
Specifikationer
Aluminium (Fortsat)
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Last (mm2) Last PE (mm2) Last N (mm2)
GVSBPAR60K120H
Kapacitet (2+0)
120 kW
160 kW
120
185
70
95
185
2 x 120
200 kW
2 x 120 120 4 x 95
240 kW
IR IR IR
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Redundans (1+1)
60 kW
80 kW
50
70
25
35
70
150
100 kW
95 50 185
120 kW
IR IR IR
Anbefalet beskyttelse før indgangen på udstyret/UPS’en for Galaxy VS
Indgang
BEMÆRK: Ved lokale direktiver, som kræver 4-polede afbrydere: Hvis nullederen forventes at bære en høj strøm, skal afbryderen være klassificeret i henhold til den forventede neutrale strøm pga. linje-neutral, ikke-lineær last.
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Afbrydertype In (A) Ir (A) Im (A)
GVSBPAR10K30H
Kapacitet (2+0)
20 kW
40 kW
LV429674 40 40 500 (fast)
LV429671 80 80 640 (fast)
60 kW
LV430671 125 125 1250 (fast)
Redundans (1+1)
10 kW
20 kW
LV429676 25 20 300 (fast)
LV429674 40 40 500 (fast)
30 kW
LV429672 63 63
Indgang
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Afbrydertype In (A) Ir (A) Im (A)
GVSBPAR40K50H
Kapacitet (2+0) 80 kW
LV430670 160 160 1250 (fast)
100 kW
LV431671 200 200 5-10 x In
Redundans (1+1) 40 kW
LV429671 80 80 640 (fast)
50 kW
LV429670 100 100 800 (fast)
Indgang
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Afbrydertype In (A)
GVSBPAR60K120H
Kapacitet (2+0)
120 kW
160 kW
LV431670 250
LV432695 320
200 kW
LV432695 400
240 kW
LV432895 500
Redundans (1+1)
60 kW
80 kW
LV430671 125
LV430670 160
100 kW
LV431671 200
120 kW
LV431670 250
990-91216D-004
13
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Indgang (Fortsat)
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Ir (A) Im (A) / Isd (A)
GVSBPAR60K120H
Kapacitet (2+0)
120 kW
160 kW
250 5-10 x In
1 1,5-10
200 kW 0,94
240 kW
Redundans (1+1)
60 kW
80 kW
125
160
1250 (fast)
Specifikationer
100 kW
200 5-10 x In
120 kW 250
14
990-91216D-004
Specifikationer
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Anbefalede kabelstørrelser til Easy UPS 3S og Easy UPS 3M
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Al ledningsinstallation skal overholde gældende regler for elinstallationer.
· Den maksimalt tilladte størrelse for indgangskabler/bypasskabler og
lastkabler er 70 mm2, og den maksimalt tilladte størrelse for
UPSindgangskabler/UPS-bypasskabler og UPS-udgangskabler er 25 mm2 for
GVSBPAR40K50H.
· Den maksimalt tilladte størrelse for indgangskabler/bypasskabler og
lastkabler er 185 mm2, og den maksimalt tilladte størrelse for
UPSindgangskabler/UPS-bypasskabler og UPS-udgangskablerer 50 mm2 for
GVSBPAR60K120H.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
BEMÆRK: Overstrømsbeskyttelse skal leveres af andre.
I denne manual er kabelstørrelser baseret på tabel B.52.5 i IEC 60364-5-52 med
følgende angivelser:
· 90 °C strømledere
· Omgivelsestemperatur på 30 °C
· Brug af strømledere af kobber eller aluminium
· Installationsmetode C
PE-størrelse er baseret på tabel 54.2 i IEC 60364-4-54.
Hvis omgivelsestemperaturen er over 30 °C, skal der vælges større strømledere
i overensstemmelse med IEC’s korrektionsfaktorer. Aluminiumskabler anbefales
ikke ved omgivelsestemperaturer på over 30 °C.
BEMÆRK: Nullederen er dimensioneret til 1,73 gange fasestrøm i tilfælde af
højt harmonisk indhold fra ikke-lineær last. Hvis der ikke forventes nogen
eller kun lave harmoniske strømme, kan nullederen dimensioneres som
faselederen.
Easy UPS 3S – 3:1 UPS-system
Kommerciel reference Parallelsystemtype
GVSBPAR40K50H Kapacitet (2+0) Redundans (1
+1)
Klassifikation af parallelsystem
20
30
10
15
kVA
kVA
kVA
kVA
System med Indgangsfaser (mm2) 35
50
16
25
en
forsyningskil- Indgang N (mm2)
35
50
16
25
de
Indgangs-PE (mm2) 16
25
16
16
System med Bypass-faser (mm2) 35
50
16
25
to
forsyningskil- Bypass N (mm2)
35
50
16
25
der
Bypass-PE (mm2)
16
25
16
16
Last (mm2)
35
50
16
25
Last N (mm2)
35
50
16
25
Last PE (mm2)
16
25
16
16
UPS-indgang (mm2)
16
25
16
25
GVSBPAR60K120H Kapacitet (2+0)
20
30
40
kVA
kVA
kVA
35
50
2 x 35
35
50
2 x 35
16
25
35
35
50
2 x 35
35
50
2 x 35
16
25
35
35
50
2 x 35
35
50
2 x 35
16
25
35
16
25
35
60 kVA 2 x 70 2 x 70 70 2 x 70 2 x 70 70 2 x 70 2 x 70 70 50
Redundans (1 +1)
20
30
kVA
kVA
35
50
35
50
16
25
35
50
35
50
16
25
35
50
35
50
16
25
35
50
990-91216D-004
15
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Specifikationer
Kommerciel reference Parallelsystemtype
Klassifikation af parallelsystem
/UPS bypass (mm2) UPS-udgang (mm2) UPS N (mm2) UPS PE (mm2)
GVSBPAR40K50H Kapacitet (2+0) Redundans (1
+1)
GVSBPAR60K120H Kapacitet (2+0)
Redundans (1 +1)
20
30
10
15
20
30
40
60
20
30
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
16
25
16
25
16
25
35
50
35
50
16
25
16
25
16
25
35
50
35
50
16
16
16
16
16
16
16
25
16
25
Easy UPS 3S – 3:3 UPS-system
Kommerciel reference Parallelsystemtype
GVSBPAR40K50H Kapacitet (2+0)
Redundans (1+1)
Klassifikation af parallelsystem
20
30
40
60
80
10
15
20
30
40
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
kVA
System med Indgangsfaser (mm2) 10
16
25
35
50
6
6
10
16
25
en
forsyningskil- Indgang N (mm2)
2 x 10 2 x 16 2 x 25 2 x 25 2 x 50 6
6
10
16
25
de
Indgangs-PE (mm2) 10
16
16
16
25
6
6
10
16
16
System med Bypass-faser (mm2) 10
16
25
25
50
6
6
10
16
25
to
forsyningskil- Bypass N (mm2)
2 x 10 2 x 16 2 x 25 2 x 25 2 x 50 6
6
10
16
25
der
Bypass-PE (mm2)
10
16
16
16
25
6
6
10
16
16
Last (mm2)
10
16
25
25
50
6
6
10
16
25
Last N (mm2)
2 x 10 2 x 16 2 x 25 2 x 25 2 x 50 6
6
10
16
25
Last PE (mm2)
10
16
16
16
25
6
6
10
16
16
UPS-indgang (mm2) /UPS bypass (mm2)
6
6
10
16
25
6
6
10
16
25
UPS-udgang (mm2)
6
6
10
16
25
6
6
10
16
25
UPS N (mm2)
6
6
10
16
25
6
6
10
16
25
UPS PE (mm2)
6
6
10
16
16
6
6
10
16
16
Easy UPS 3M – 3:3 UPS-system
Kommerciel reference Parallelsystemtype
GVSBPAR60K120H Kapacitet (2+0)
Klassifikation af parallelsystem
120 kVA
System med en forsyningskilde
Indgangsfaser (mm2) Indgang N (mm2) Indgangs-PE (mm2)
95 2 x 95 50
System med to forsyningskilder
Bypass-faser (mm2) Bypass N (mm2) Bypass-PE (mm2)
95 2 x 95 50
Last (mm2)
95
Last N (mm2)
2 x 95
160 kVA 120 2 x 120 70 120 2 x 120 70 120 2 x 120
Redundans (1+1) 60 kVA 35 2 x 25 16 35 2 x 25 16 25 2 x 25
80 kVA 50 2 x 50 25 50 2 x 50 25 50 2 x 50
16
990-91216D-004
Specifikationer
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem Last PE (mm2) UPS-indgang (mm2) /UPS bypass (mm2) UPS-udgang (mm2) UPS N (mm2) UPS PE (mm2)
GVSBPAR60K120H Kapacitet (2+0) 120 kVA 50 35
160 kVA 70 50
25 2 x 25 16
50 2 x 50 25
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Redundans (1+1) 60 kVA 16 35
25 2 x 25 16
80 kVA 25 50
50 2 x 50 25
Anbefalet beskyttelse før indgangen til Easy UPS 3S og Easy UPS 3M
Easy UPS 3S – 3:1 UPS-system
Indgang/Bypass (kun til systemer med to forsyningskilder)
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem
Afbrydertype
In (A) Ir (A) Im (A)
GVSBPAR40K50H
GVSBPAR60K120H
Kapacitet (2+0) 20 kVA 30 kVA
Redundans (1+1) 10 kVA 15 kVA
Kapacitet (2+0) 20 kVA 30 kVA
40 kVA
60 kVA
C120HC-100A/ NSX100F 100A TM100D C10F3TM100
CompactNSX160F 160A TM160D C16F3TM160
iC65HC-50A/ C60HC-50A
Fast
160
Fast
Fast/100 144
Fast
Fast
Fast
Fast
C120HC-80A / NSX100F 80A TM80D C10F3TM080
C120HC-100A/ NSX100F 100A TM100D C10F3TM100
CompactNSX160F 160A TM160D C16F3TM160
CompactNSX250F TM200D C25F3TM200
NSX400N mic2.3 ( C40N32D400
Fast
Fast
160
250
400
Fast/80 Fast/100 144
200
280
Fast
Fast
Fast
5~10*In Io =
1,5~10
Redundans (1+1) 20 kVA 30 kVA
C120HC-100A/ NSX100F 100A TM100D C10F3TM100
CompactNSX160F 160A TM160D C16F3TM160
Fast/100 160
Fast/100 144
Fast
Fast
990-91216D-004
17
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Specifikationer
Easy UPS 3S – 3:3 UPS-system
Indgang
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem
Afbrydertype
In (A) Ir (A) Im (A)
GVSBPAR40K50H
Kapacitet (2+0) 20 kVA 30 kVA
iC65HC-40A / C60HC-40A
iC65HC-63A / C60HC-63A /C120HC-63A
Fast
Fast
Fast
Fast
Fast
Fast
40 kVA
60 kVA
80 kVA
Redundans (1+1) 10 kVA 15 kVA
C120HC-80A / NSX100F 80A TM80D C10F3TM080
Compact NSX160F TM125D ( C16F3TM125)
Compact NSX160F TM160D ( C16F3TM160)
iC65HC-20A / C60HC-20A
Fast/80 125
160
Fast
Fast/80 125
160
Fast
Fast
Fast
Fast
Fast
iC65HC-32A / C60HC-32A
Fast Fast Fast
20 kVA
iC65HC-40A / C60HC-40A
Fast Fast Fast
30 kVA 40 kVA
iC65HC-63A / C60HC-63A /C120HC-63A
C120HC-80A / NSX100F 80A TM80D C10F3TM080
Fast
Fast/80
Fast
Fast/80
Fast
Fast
Bypass (Kun til systemer med to forsyningskilder)
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem
Afbrydertype
In (A) Ir (A) Im (A)
GVSBPAR40K50H
Kapacitet (2+0) 20 kVA 30 kVA
iC65HC-40A / C60HC-40A
iC65HC-63A / C60HC-63A /C120HC-63A
Fast
Fast
Fast
Fast
Fast
Fast
40 kVA
60 kVA
80 kVA
Redundans (1+1) 10 kVA 15 kVA
C120HC-80A / NSX100F 80A TM80D C10F3TM080
Fast/80
Compact NSX100F TM100D (C10F3TM100)
100
Compact NSX160F TM160D (C16F3TM160)
160
iC65HC-20A / C60HC-20A
Fast
Fast/80 100
144
Fast
Fast
Fast
Fast
Fast
iC65HC-32A / C60HC-32A
Fast Fast Fast
20 kVA
iC65HC-40A / C60HC-40A
Fast Fast Fast
30 kVA 40 kVA
iC65HC-63A / C60HC-63A /C120HC-63A
Fast
C120HC-80A / NSX100F 80A TM80D C10F3TM080
Fast/80
Fast
Fast/80
Fast
Fast
Easy UPS 3M – 3:3 UPS-system
Indgang/Bypass (kun til systemer med to forsyningskilder)
Kommerciel reference Parallelsystemtype Klassifikation af parallelsystem
Afbrydertype
Io (A) Ir (A) Isd (A)
GVSBPAR60K120H
Kapacitet (2+0) 120 kVA
NSX250N mic2.2 (C25N32D250) 250 200 1,5-10
160 kVA
NSX400N mic2.3 (C40N32D400) 400 280 1,5-10
Redundans (1+1) 60 kVA
80 kVA
Compact NSX160F TM125D (C16F3TM125)
125
125
800 (fast)
Compact NSX160F TM160D (C16F3TM160)
160
160
1250 (fast)
18
990-91216D-004
Specifikationer
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Specifikationer for drejningsmoment
Boltstørrelse M4 M5 M6 M8 M10 M12
Drejningsmoment 1,7 Nm 2,2 Nm 5 Nm 17,5 Nm 30 Nm 50 Nm
Forsendelsesvægt og -mål for parallelt vedligeholdelsesbypasspanel
Kommerciel reference GVSBPAR10K30H GVSBPAR40K50H GVSBPAR60K120H
Vægt i kg 56 96 120
Højde i mm1 500 580 500
Bredde i mm 800 800 1000
Dybde i mm1 1200 1200 1200
Vægt og mål for parallelt vedligeholdelsesbypasspanel
Kommerciel reference GVSBPAR10K30H GVSBPAR40K50H GVSBPAR60K120H
Vægt i kg 35 86 110
Højde i mm 700 850 1000
Bredde i mm 650 750 900
Dybde i mm 210 250 280
1. Produktet transporteres i vandret position, så forsendelseshøjden og -dybden er anderledes i forhold til det udpakkede produkt.
990-91216D-004
19
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Afstand
Specifikationer
BEMÆRK: Afstandsmålene angives udelukkende af hensyn til luftgennemstrømning og tilgængelighed ved servicearbejde. Undersøg, om der er flere sikkerheds- og standardkrav, som gælder i lokalområdet.
Overholdelse af regler og standarder
Sikkerhed
IEC 62040-1: 2017, Udgave 2.0, Uninterruptible Power Systems (UPS) Del 1: Sikkerhedskrav
Ydeevne
IEC 62040-3: 2011-03, 2. udgave af Uninterruptible Power Systems (UPS) Del 3: Metode til specificering af krav for ydeevne og test
Miljø
IEC 62040-4: 2013-04, 1. udgave af Uninterruptible Power Systems (UPS) Del 4: Miljøaspekter krav og rapportering
Mærker Jordingssystem
CE TN-C, TN-S, TT
Overspændingskate- OVCIII gori
Beskyttelsesklasse I
Forureningsgrad
2
Miljø
Temperatur Relativ luftfugtighed Højde
Drift 0 °C til 40 °C 5-95 %, ikke kondenserende 0-3000 m
Opbevaring -25 °C til 55 °C 10-80 %, ikke kondenserende
20
990-91216D-004
Specifikationer
Beskyttelsesklasse Farve
Drift IP20 RAL 9003, glansniveau 85 %
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M Opbevaring
Enstregsdiagram
Galaxy VS-enstregsdiagrammer
UIB1 UIB2 MBB IMB UOB1 UOB2 BB
Enhedsindgangsafbryder til UPS 1 Enhedsindgangsafbryder til UPS 2 Vedligeholdelsesbypassafbryder Intern vedligeholdelsesafbryder Enhedsudgangsafbryder til UPS 1 Enhedsudgangsafbryder til UPS 2 Batteriafbryder
Det parallelle vedligeholdelsesbypasspanel bruges i systemer med én
forsyningskilde til at sætte to UPS-enheder i parallel for enten kapacitet
eller redundans.
BEMÆRK: Den interne vedligeholdelsesafbryder IMB i UPS-enheden kan ikke
bruges i et system med et parallelt vedligeholdelsesbypasspanel, og den
interne vedligeholdelsesafbryder IMB skal aflåses i åben position med
hængelås.
990-91216D-004
21
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M Galaxy VS parallelsystem én forsyningskilde
Specifikationer
22
990-91216D-004
Specifikationer
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Easy UPS 3S- og Easy UPS 3M-enstregsdiagrammer
BEMÆRK: Den interne MBB i Easy UPS 3S/3M kan ikke bruges i et system med et parallelt vedligeholdelsesbypasspanel, og den interne MBB skal aflåses i åben position med hængelås. Brug kun Ext. MBB i det parallelle vedligeholdelsesbypasspanel til vedligeholdelsesbypassdrift.
UIB SSIB MBB UOB Ext. UIB1/Ext. SSIB1
Ext. UIB2/Ext. SSIB2
Ext. MBB Ext. UOB1 Ext. UOB2 BB
Enhedsindgangsafbryder
Indgangsafbryder til den statiske switch
Intern vedligeholdelsesbypassafbryder
Enhedsudgangsafbryder
Ekstern enhedsindgangsafbryder/ekstern indgangsafbryder til den statiske
switch til UPS 1 Ekstern enhedsindgangsafbryder/ekstern indgangsafbryder til
den statiske switch til UPS 2 Ekstern vedligeholdelsesbypassafbryder
Ekstern enhedsudgangsafbryder til UPS 1
Ekstern enhedsudgangsafbryder til UPS 2
Batteriafbryder
Easy UPS 3S og Easy UPS 3M Parallelsystem en forsyningskilde
990-91216D-004
23
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M Easy UPS 3S og Easy UPS 3M Parallelsystem to forsyningskilder
Specifikationer
24
990-91216D-004
Installationsprocedure for Galaxy VS
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Installationsprocedure for Galaxy VS
1. Monter det parallelle vedligeholdelsesbypasspanel på væggen, side 27.
2. Klargør til kabler, side 30.
3. Kun i de lande, hvor det kræves: Fjern den neutrale jumper, side 31.
4. Gør et af følgende: Tilslut strømkablerne på GVSBPAR10K30H, side 33
eller Tilslut strømkablerne på GVSBPAR40K50H til et 3:3 UPS-system, side 37
eller Tilslut strømkablerne på GVSBPAR60K120H til et 3:3 UPS-system, side
41.
5. Slut signalkablerne til Galaxy VS UPS-enheder, side 43.
6. Tilføj oversatte sikkerhedslabels på produktet, side 49.
For at flytte eller tage vedligeholdelsesbypasspanelet ud af drift efter
installationen, se Tag det parallelle vedligeholdelsesbypasspanel ud af drift
eller flyt det til en ny placering, side 50.
990-91216D-004
25
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Installationsprocedure for Easy UPS 3S og Easy UPS 3M
Installationsprocedure for Easy UPS 3S og Easy UPS 3M
Én forsyningskilde
To forsyningskilder
1. Monter det parallelle vedligeholdelsesbypasspanel på væggen, side 27.
2. Klargør til kabler, side 30.
3. Fjern den neutrale jumper, side 31.
4. Gør et af følgende: Tilslut strømkablerne på GVSBPAR40K50H til et 3:1
UPS-system, side 34 eller Tilslut strømkablerne på GVSBPAR40K50H til et 3:3
UPS-system, side 37 eller Tilslut strømkablerne på GVSBPAR60K120H til et 3:1
UPS-system, side 38 eller Tilslut strømkablerne på GVSBPAR60K120H til et 3:3
UPS-system, side 41.
5. Slut signalkablerne til Easy UPS 3S og Easy UPS 3M, side 45.
6. Tilføj oversatte sikkerhedslabels på produktet, side 49.
For at flytte eller tage vedligeholdelsesbypasspanelet ud af drift efter
installationen, se Tag det parallelle vedligeholdelsesbypasspanel ud af drift
eller flyt det til en ny placering, side 50.
26
990-91216D-004
Monter det parallelle vedligeholdelsesbypasspanel på væggen
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Monter det parallelle vedligeholdelsesbypasspanel på væggen
FORSIGTIG
RISIKO FOR PERSONSKADE ELLER BESKADIGELSE AF UDSTYR
· Monter det parallelle vedligeholdelsesbypasspanel på en væg eller et rack,
som er strukturelt stabil, og som kan understøtte enhedens vægt.
· Brug passende udstyr til væg-/racktypen.
Personer kan komme til skade, eller udstyr kan blive beskadiget, hvis disse
instrukser ikke overholdes.
990-91216D-004
27
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Monter det parallelle vedligeholdelsesbypasspanel på væggen
1. Mål og afmærk placeringen af de fire monteringshuller på væggen.
GVSBPAR10K30H
GVSBPAR40K50H
GVSBPAR60K120H
2. Bor huller på hvert af de fire afmærkede steder, og monter forankringsboltene.
28
990-91216D-004
Monter det parallelle vedligeholdelsesbypasspanel på væggen
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
3. Fjern skruerne, og åbn den indre dør i det parallelle vedligeholdelsesbypasspanel.
4. Monter det parallelle vedligeholdelsesbypasspanel på væggen
990-91216D-004
29
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Klargør til kabler
Klargør til kabler
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER Undlad at bore/udskære
huller, når forskruningspladerne er monteret, og undlad at bore/udskære huller
tæt på skabet. Personer vil komme i livsfare eller alvorligt til skade, hvis
disse instrukser ikke overholdes.
1. Fjern de nederste forskruningsplader.
2. Bor eller udskær huller til strømkabler og signalkabler eller
kabelgennemføringer i forskruningspladerne. UPS-indgang (A), indgang (B), last
(C), UPS-udgang (D).
3. Installer kabelgennemføringer (hvis relevant), og monter
forskruningspladerne igen.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Sørg for, at der ikke er nogen skarpe kanter, som kan beskadige kablerne.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
30
990-91216D-004
Fjern den neutrale jumper
Fjern den neutrale jumper
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
BEMÆRK: Den neutrale jumper udgør en fastboltet forbindelse for den neutrale
forbindelse, så denne ikke afbrydes, når de 4-polede afbrydere åbnes. BEMÆRK:
Fjern kun de neutrale jumpere i en Galaxy VS-installation, hvis det er et
lokalt krav. Fjernelse af de neutrale jumpere er en valgmulighed for en Galaxy
VS-installation. BEMÆRK: Fjern altid de neutrale jumpere i en Easy UPS 3S-
installation og i en Easy UPS 3M-installation. Fjernelse af de neutrale
jumpere er obligatorisk i en Easy UPS 3S-installation og i en Easy UPS 3M-
installation.
1. Fjern de neutrale jumpere (kabel og/eller busbar) mellem UOB1 og UOB2. Sæt
skruerne i igen de samme steder.
2. Fjern de neutrale jumpere på MBB (kabel eller busbar).
GVSBPAR10K30H
990-91216D-004
31
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M GVSBPAR40K50H
Fjern den neutrale jumper
GVSBPAR60K120H
32
990-91216D-004
Tilslut strømkablerne på GVSBPAR10K30H
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR10K30H
1. Slut PE-kablerne til PE-busbaren.
2. Tilslut indgangskablerne fra hovedforsyningen.
3. Tilslut UPS-indgangskablerne fra UPS 1. 4. Tilslut UPS-indgangskablerne
fra UPS 2. 5. Tilslut UPS-udgangskablerne fra UPS 1. 6. Tilslut UPS-
udgangskablerne fra UPS 2. 7. Tilslut lastkablerne. 8. Fastgør kablerne til
kabelaflastningen med kabelbindere (medfølger) som
vist.
990-91216D-004
33
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPSsystem
Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPS-system
1. Slut PE-kablerne til PE-busbaren.
34
990-91216D-004
Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPSsystem
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
2. Tilslut indgangskablerne/bypasskablerne fra hovedforsyningen.
Én forsyningskilde
990-91216D-004
35
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M To forsyningskilder
Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPSsystem
3. Tilslut UPS-indgangskablerne/UPS-bypasskablerne fra UPS 1. 4. Tilslut UPS-
indgangskablerne/UPS-bypasskablerne fra UPS 2. 5. Tilslut UPS-udgangskablerne
fra UPS 1. 6. Tilslut UPS-udgangskablerne fra UPS 2. 7. Tilslut lastkablerne.
8. Fastgør kablerne til kabelaflastningen med kabelbindere (medfølger) som
vist.
36
990-91216D-004
Tilslut strømkablerne på GVSBPAR40K50H til et 3:3 UPSsystem
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR40K50H til et 3:3 UPS-system
1. Slut PE-kablerne til PE-busbaren.
2. Tilslut indgangskablerne/bypasskablerne fra hovedforsyningen.
990-91216D-004
3. Tilslut UPS-indgangskablerne/UPS-bypasskablerne fra UPS 1. 4. Tilslut UPS-
indgangskablerne/UPS-bypasskablerne fra UPS 2. 5. Tilslut UPS-udgangskablerne
fra UPS 1. 6. Tilslut UPS-udgangskablerne fra UPS 2. 7. Tilslut lastkablerne.
8. Fastgør kablerne til kabelaflastningen med kabelbindere (medfølger) som
vist.
37
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR60K120H til et 3:1 UPSsystem
Tilslut strømkablerne på GVSBPAR60K120H til et 3:1 UPS-system
1. Slut PE-kablerne til PE-busbaren.
38
990-91216D-004
Tilslut strømkablerne på GVSBPAR60K120H til et 3:1 UPSsystem
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
2. Tilslut indgangskablerne/bypasskablerne fra hovedforsyningen.
Én forsyningskilde
990-91216D-004
39
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR60K120H til et 3:1 UPSsystem
To forsyningskilder
3. Tilslut UPS-indgangskablerne/UPS-bypasskablerne fra UPS 1. 4. Tilslut UPS-
indgangskablerne/UPS-bypasskablerne fra UPS 2. 5. Tilslut UPS-udgangskablerne
fra UPS 1. 6. Tilslut UPS-udgangskablerne fra UPS 2. 7. Tilslut lastkablerne.
8. Fastgør kablerne til kabelaflastningen med kabelbindere (medfølger) som
vist.
40
990-91216D-004
Tilslut strømkablerne på GVSBPAR60K120H til et 3:3 UPSsystem
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR60K120H til et 3:3 UPS-system
1. Slut PE-kablerne til PE-busbaren.
2. Tilslut indgangskablerne/bypasskablerne fra hovedforsyningen.
990-91216D-004
3. Tilslut UPS-indgangskablerne/UPS-bypasskablerne fra UPS 1. 4. Tilslut UPS-
indgangskablerne/UPS-bypasskablerne fra UPS 2. 5. Tilslut UPS-udgangskablerne
fra UPS 1. 6. Tilslut UPS-udgangskablerne fra UPS 2. 7. Tilslut lastkablerne.
41
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilslut strømkablerne på GVSBPAR60K120H til et 3:3 UPSsystem
8. Fastgør kablerne til kabelaflastningen med kabelbindere (medfølger) som vist.
42
990-91216D-004
Slut signalkablerne til Galaxy VS UPS-enheder
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Slut signalkablerne til Galaxy VS UPS-enheder
BEMÆRK: Fremfør signalkablerne adskilt fra strømkablerne, og fremfør Class 2
/SELV-kablerne adskilt fra non-Class 2/non-SELV-kablerne.
1. Slut Class 2/SELV-signalkablerne til afbryderindikatorerne fra
kontrolklemrækken i det parallelle vedligeholdelsesbypasspanel til UPS 1 og
UPS 2.
BEMÆRK: Afbryderindikatorkredsløbet betragtes som Class 2/SELV. Class 2/SELV-
kredsløb skal være isoleret fra det primære kredsløb. Slut ikke et kredsløb
til afbryderindikatorterminalerne, medmindre det kan bekræftes, at kredsløbet
er Class 2/SELV.
2. Slut non-Class 2/non-SELV-signalkablerne fra kontrolklemrækken i det
parallelle vedligeholdelsesbypasspanel til UPS 1 og UPS 2.
990-91216D-004
43
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Slut signalkablerne til Galaxy VS UPS-enheder
3. Stram signalkablerne, og fastgør dem til kabelaflastningerne.
44
990-91216D-004
Slut signalkablerne til Easy UPS 3S og Easy UPS 3M
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Slut signalkablerne til Easy UPS 3S og Easy UPS 3M
BEMÆRK: Fremfør signalkablerne adskilt fra strømkablerne, og fremfør Class 2
/SELV-kablerne adskilt fra non-Class 2/non-SELV-kablerne.
1. Fjern de tre afbryderindikatorlamper og tilhørende indikatoretiketter fra
vedligeholdelsesbypasspanelet. Afbryderindikatorlamperne understøttes ikke for
Easy UPS 3S og Easy UPS 3M.
2. Monter tre runde blindpropper (medfølger ikke) i hullerne i den indre dør.
3. Fjern de interne forbindelser til afbryderindikatorlamperne (ben 1-6) på
kontrolklemrækkerne.
990-91216D-004
4. På kontrolklemrækken ændres den interne forbindelse til MBB
meldekontakterne (ben 11-14) fra normalt lukket (NC) til normalt åben (NO).
45
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Slut signalkablerne til Easy UPS 3S og Easy UPS 3M
5. Slut non-Class 2/non-SELV-signalkablerne fra kontrolklemrækken i det
parallelle vedligeholdelsesbypasspanel til UPS 1 og UPS 2. Følg en af
nedenstående procedurer:
For Easy UPS 3S: Slut til J5 i UPS-enhederne ELLER til J6 og J7 i
UPSenhederne.
For Easy UPS 3M: Slut til J8 i UPS-enhederne.
46
990-91216D-004
Slut signalkablerne til Easy UPS 3S og Easy UPS 3M Easy UPS 3S
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M Easy UPS 3S
Easy UPS 3M
990-91216D-004
47
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Slut signalkablerne til Easy UPS 3S og Easy UPS 3M
6. Stram signalkablerne, og fastgør dem til kabelaflastningerne.
48
990-91216D-004
Tilføj oversatte sikkerhedslabels på produktet
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tilføj oversatte sikkerhedslabels på produktet
Sikkerhedslabelerne på produktet er på engelsk og fransk. Der følger ark med
oversatte sikkerhedslabels med produktet.
1. Se de ark med oversatte sikkerhedslabels, som følger med produktet.
2. Tjek, hvilke 885-XXX numre, der er på arket med oversatte
sikkerhedslabels.
3. Find de sikkerhedslabels på dit produkt, som svarer til de oversatte
sikkerhedslabels på arket kig efter 885-XXX numrene.
4. Sæt udskiftningssikkerhedslabelen på dit foretrukne sprog på produktet
oven på den eksisterende franske sikkerhedslabel.
990-91216D-004
49
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til en ny placering
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til en ny placering
1. Luk UPS’en helt ned følg instruktionerne i UPS’ens betjeningsvejledning.
2. Sæt afbryderne på afbrydertavlen til OFF (åben position).
3. Lås/markér alle batteriafbrydere på afbrydertavlen/i batteriløsningen i
positionen OFF (åben).
4. Kontrollér, at alle afbrydere før indgangen på UPS’en står i positionen
OFF (åben position).
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Kontrollér, at alle afbrydere før indgangen på UPS’en står i positionen OFF
(åben position).
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
5. Åbn fordøren til det parallelle vedligeholdelsesbypasspanel.
6. Lockout/Tagout UIB1, UIB2, UOB1, UOB2 og MBB i det parallelle
vedligeholdelsesbypasspanel i positionen OFF (åben).
7. Fjern skruerne, og åbn den indre dør i det parallelle
vedligeholdelsesbypasspanel.
50
990-91216D-004
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til en ny placering
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
8. Mål og bekræft FRAVÆR af spænding på hver indgang/bypass-busbar,
UPSindgang/UPS-bypass-busbar, UPS-udgangs-busbar og last-busbar, før du
fortsætter.
FARE
FARE FOR ELEKTRISK STØD, EKSPLOSION ELLER LYSBUER
Mål og bekræft FRAVÆR af spænding på hver indgang/bypass-busbar, UPS-indgang
/UPS-bypass-busbar, UPS-udgangs-busbar og last-busbar, før du fortsætter.
Personer vil komme i livsfare eller alvorligt til skade, hvis disse instrukser
ikke overholdes.
GVSBPAR10K30H
990-91216D-004
51
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M GVSBPAR40K50H
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til en ny placering
52
990-91216D-004
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til
en ny placering
GVSBPAR60K120H
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
990-91216D-004
9. Frakobl og fjern alle strømkabler fra det parallelle
vedligeholdelsesbypasspanel. Se flere oplysninger i Tilslut strømkablerne på
GVSBPAR10K30H, side 33, Tilslut strømkablerne på GVSBPAR40K50H til et 3:1 UPS-
system, side 34, Tilslut strømkablerne på GVSBPAR40K50H til et 3:3 UPS-system,
side 37, Tilslut strømkablerne på GVSBPAR60K120H til et 3:1 UPS-system, side
38, eller Tilslut strømkablerne på GVSBPAR60K120H til et 3:3 UPS-system, side
41.
10. Frakobl, og fjern alle signalkabler fra det parallelle
vedligeholdelsesbypasspanel. Se flere oplysninger i Slut signalkablerne til
Galaxy VS UPS-enheder, side 43, eller Slut signalkablerne til Easy UPS 3S og
Easy UPS 3M, side 45.
11. Fjern de fire-skruer fra væggen, og afmonter det parallelle
vedligeholdelsesbypasspanel fra væggen.
FORSIGTIG
TUNG LAST
GVSBPAR10K30H vejer 35 kg, GVSBPAR40K50H vejer 86 kg, og GVSBPAR60K120H vejer
110 kg. Brug passende hjælpemidler, når det parallelle
vedligeholdelsesbypasspanel skal løftes.
Personer kan komme til skade, eller udstyr kan blive beskadiget, hvis disse
instrukser ikke overholdes.
12. Luk den indre dør, og fastgør den med skruerne.
13. Luk og lås det parallelle vedligeholdelsesbypasspanels fordør.
53
Til Galaxy VS, Easy UPS 3S og Easy UPS 3M
Tag det parallelle vedligeholdelsesbypasspanel ud af drift eller flyt det til en ny placering
14. Transport:
ADVARSEL
FARE FOR AT VÆLTE UDSTYRET
Sørg for følgende, når det parallelle vedligeholdelsesbypasspanel skal
transporteres: · det personale, der udfører transporten, har de nødvendige
færdigheder
og har modtaget tilstrækkelig træning · Brug passende hjælpemidler til at
løfte og transportere produktet. · produktet beskyttes mod skader ved at bruge
passende beskyttelse
(såsom indpakning eller emballage). Personer kan komme i livsfare eller
alvorligt til skade, eller udstyr kan blive beskadiget, hvis disse instrukser
ikke overholdes.
Krav til transport:
· Monter det parallelle vedligeholdelsesbypasspanel i vandret position midt på
en egnet palle med følgende minimumsmål: 1000 mm x 1200 mm. Pallen skal være
stærk nok til at kunne bære vægten af det parallelle
vedligeholdelsesbypasspanel (35-110 kg).
· Fastgør det parallelle vedligeholdelsesbypasspanel på pallen med passende
fastgørelsesmidler, der kan modstå vibrationer og stød under læsning,
transport og aflæsning.
· Den originale fragtpalle kan genbruges i kombination med de originale
transportbeslag, hvis de er i ubeskadiget stand.
ADVARSEL
UVENTEDE UDSTYRSREAKTION
Løft ikke det parallelle vedligeholdelsesbypasspanel direkte på rammen med en
gaffeltruck/palleløfter, da det kan bøje eller beskadige udstyret.
Personer kan komme i livsfare eller alvorligt til skade, eller udstyr kan
blive beskadiget, hvis disse instrukser ikke overholdes.
15. Gør et af følgende:
Tag det parallelle vedligeholdelsesbypasspanel ud af drift, ELLER
Flyt det parallelle vedligeholdelsesbypasspanel til et nyt sted for at
installere det.
16. Kun til installation af det parallelle vedligeholdelsesbypasspanel på et
nyt sted: Installer det parallelle vedligeholdelsesbypasspanel på den nye
placering ved at følge installationsvejledningen. Se Installationsprocedure
for Galaxy VS, side 25 eller Installationsprocedure for Easy UPS 3S og Easy
UPS 3M, side 26 for installationsoversigt. En ny installation og opstart må
kun udføres af kvalificeret personale.
54
990-91216D-004
Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison Frankrig + 33
(0) 1 41 29 70 00
990-91216D-004
Da standarder, specifikationer og design ændres fra tid til anden, bør du bede
om bekræftelse af oplysningerne i denne publikation.
© 2019 2023 Schneider Electric. Alle rettigheder forbeholdes 990-91216D-004
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>