UNI-T UT511 Insulation Resistance Megger Meter User Manual
- July 2, 2024
- UNI-T
Table of Contents
- UT511 Insulation Resistance Megger Meter
- Specifications
- Product Information
- Product Usage Instructions
- 1. Unpacking the Meter
- 2. Safety Information
- 3. International Electrical Symbols
- 4. Battery Saver (Sleep Mode)
- 5. Key Functions
- 6. Measurement Operation
- Q: How do I know if the battery needs replacement?
- Q: Can I use a power adaptor with the Meter?
UT511 Insulation Resistance Megger Meter
“`html
Specifications
-
Safety and Compliances: IEC61010 safety measurement
requirement -
Physical Specifications: Handheld
-
General Specifications: CAT. III 600V, CAT.II 1000V, double
insulation
Product Information
The Uni-Trend Model UT511 insulation resistance tester is
designed for resistance/insulation resistance measurement.
Product Usage Instructions
1. Unpacking the Meter
The Meter includes:
- English Operating Manual
- One plug test lead to one alligator
- Two plugs test lead to one alligator
- 1.5V Battery (R14 or LR14)
- Tool Box
- Power adaptor (optional, available at extra cost)
Check for missing or damaged items and contact your dealer if
needed.
2. Safety Information
The Meter complies with IEC61010 safety standards and has CAT.
III 600V, CAT.II 1000V ratings with double insulation. Follow the
safety instructions in the manual to avoid hazards and damage.
3. International Electrical Symbols
Refer to pages 4-5 of the Operating Manual for explanations of
the symbols used on the Meter.
4. Battery Saver (Sleep Mode)
The Meter features a battery saver mode to prolong battery life
when not in use. Refer to the manual for instructions on activating
and deactivating this mode.
5. Key Functions
Learn about the key functions of the Meter for accurate
measurements. Functions include measuring voltages, insulation
resistance, and low resistance.
6. Measurement Operation
Perform measurements using the Meter:
-
A. Measuring Voltages: Follow the steps
outlined in the manual for voltage measurements. -
B. Measuring Insulation Resistance:
- a) Continuous Measurement
- b) Timed Measurement
- c) Polarization Index (PI) Measurement
- d) Compare Function
-
C. Low Resistance Measurement: Utilize the
Meter for low resistance measurements as per the manual
instructions.
FAQs
Q: How do I know if the battery needs replacement?
A: The Meter will indicate when the battery is low. Refer to the
Battery Indication section in the manual for details on
interpreting battery status.
Q: Can I use a power adaptor with the Meter?
A: Yes, a power adaptor can be used with the Meter. Refer to the
section on The Use of Power Adaptor for instructions on using it
with the Meter.
“`
Model UT511 OPERATING MANUAL
Model UT511: OPERATING MANUAL
TITLE
Introduction Unpacking the Meter Safety Information International Electrical
Symbols Battery Saver (Sleep Mode) Battery Indication The Meter Structure
Display Key Functions Measurement Operation
A.Measuring Voltages B.Measuring Insulation Resistance
a) Continuous Measurement b) Timed Measurement c) Polarization Index (PI)
Measurement d) Compare Function C. Low Resistance Measurement
PAGE
5 5 5 7 8 8 9 10 12 15 15 16 17 18 18 19 20
1
Model UT511: OPERATING MANUAL
TITLE
The Use of Power Adaptor Maintenance
A. General Service B. Replacing the Battery Specifications Safety and
Compliances Physical Specifications General Specifications Feature Summary
Detailed Accuracy Specifications A. Voltage Measurement B. Insulation
Resistance Measurement C. Low Resistance Measurement
PAGE
21 22 22 22 24 24 24 25 25 26 26 26 27
2
Model UT511: OPERATING MANUAL
Table 1. 2. 3. 4. 5. 6. 7.
Title
Unpacking Inspection International Electrical Symbols Battery Indication Meter
Front Description Meter Side Description Display Description Key Description
Page
5 7 8 9 10 11 12
3
Figure
1. 2. 3. 4. 5. 6. 7. 8.
Model UT511: OPERATING MANUAL
Title
The Meter Front Structure The Meter Side Structure The Display Voltage
Measurement Insulation Resistance Measurement Low Resistance Measurement The
Use of Power Adaptor Battery Replacement
Page
9 10 10 15 16 20 21 23
4
Model UT511: OPERATING MANUAL
Introduction
Uni-Trend Model UT511 insulation resistance tester (hereafter, “the Meter”) is
a handheld instrument designed primarily to make resistance/ insulation
resistance measurement.
Unpacking the Meter The Meter includes the following items:
Table 1. Unpacking Inspection
Item 1 2 3
4 5 6
Description English Operating Manual One plug test lead to one alligator Two plugs test lead to one alligator 1.5V Battery (R14 or LR14) Tool Box Power adaptor (optionally, available at extra cost)
Qty 1 piece 2 pieces 1 piece
8 pieces 1 piece 1 piece
In the event you find any missing or damage, please contact your dealer immediately.
Safety Information
This Meter complies with the standards IEC61010 safety measurement
requirement: in pollution degree 2, overvoltage category (CAT. III 600V,
CAT.II 1000V) and double insulation.
CAT II: Local level, appliance, PORTABLE EQUIPMENT etc., with smaller
transient voltage overvoltages than CAT. III CAT III: Distribution level,
fixed installation, with smaller transient overvoltages than CAT. IV
Use the Meter only as specified in this operating manual, otherwise the
protection provided by the Meter may be impaired.
Danger identifies conditions and actions that pose hazard(s) to the user.
Warning identifies avoiding electric shock. Caution identifies conditions and
actions that may damage the Meter and carrying out accurate measurement.
5
Model UT511: OPERATING MANUAL
International electrical symbols used on the Meter and in this Operating
Manual are explained on page 4~5.
Danger
Use of instrument in a manual not specifed by the manufactuer may impair
safety features/ protection provided by the equipment. Read the following
safety information carefully before using or servicing the instrument.
l Do not apply more than 1000VDC or 750V AC. l Do not use the Meter around
explosive gas,
vapor or dust. l Do not use the Meter in a wet environment. l When using the
test leads, keep your figures
away from the lead contacts. Keep your figures behind the finger guards on the
leads. l Do not use the Meter with any parts or cover removed. l When carrying
out insulation measurement, do not contact the circuit under test.
6
Warning
l Do not use the Meter if it is damaged or metal part is exposed. Look for
cracks or missing plastic.
l Be careful when working above 30V rms, 42V ac rms and 60V DC. Such voltages
pose a shock hazard.
l Discharge all loading of circuit under test after measuring high voltage.
l Do not change battery when the Meter is in wet environment.
l Place test leads in proper input terminals. Make sure all the test leads are
firmly connected to the Meter’s input terminals. Make sure the Meter is turned
off when opening the battery compartment.
Caution
l When performing resistance tests, remove all power from the circuit to be
measured and discharge all the power.
Model UT511: OPERATING MANUAL
l When servicing the Meter, use only the same model number or identical
electrical specifications of test leads and power adaptor.
l Do not use the Meter if the battery indicator ( ) shows a battery empty
condition. Take the battery out from the Meter if it is not used for a long
time.
l Do not use or store the Meter in an environment of high temperature,
humidity, explosive, inflammable and strong magnetic field. The performance of
the Meter may deteriorate after dampened.
l Soft cloth and mild detergent should be used to clean the surface of the
Meter when servicing. No abrasive and solvent should be used to prevent the
surface of the Meter from corrosion, damage and accident. Dry the Meter before
storing if it is wet.
International Electrical Symbols International symbols on the Meter and in
this manual are explained in Table 2.
Table 2. International Electrical Symbols
Risk of electric shock Equipment protected by double or reinforced insulation.
DC Measurement AC Measurement Grounding See Manual Empty of Built-In Battery
Conforms to Standards of European Union
7
Model UT511: OPERATING MANUAL
Battery Saver (Sleep Mode)
The Meter enters the Sleep Mode and blanks the display if there is no button
press for 15 minutes. This is done to conserve battery power. The Meter comes
out of Sleep Mode when ON/OFF button is pressed two times.
The 15 minutes timer is disabled during any insulation resistance measurement.
The time period starts immediately following any measurement.
Battery Indication There is a battery indicator shows on the display upper
left hand corner. Below Table 3 is the explanation:
Table 3. Battery Indication
Battery Battery Voltage Indicator
8.5V or less. It means the battery is empty, don’t use the Meter as it cannot
guarantee accuracy. 8.6V~9.0V. It means the battery is nearly empty, replacing
battery is necessary. Accuracy will not be affected. 9.1V~10.2V 10.3V or more
8
Model UT511: OPERATING MANUAL The Meter Structure Below Figure 1 and Table 4
shows the Meter front structure and description
Figure 1. The Meter Front Structure
Table 4. Meter Front Description
1 LCD
12 Test Button
2
Scroll Button
13 Step Button
3 Emergency stop
14 Data Store Button.
4 Data Clear the
15 Data Recall Button
Display Backlight
Button,
5
Down Button
16 Scroll Button
6 On/Off Button
17 Up Button
7 Compare Button
18 LINE: Resistance
input terminal
8 Insulation Resistance 19 COM: Voltage input
Button
terminal
9 Voltages
20 EARTH: Resistance
measurement Button
input terminal
10 Timer Button.
21 V: Voltage input
terminal
11 Low Resistance
22 Testing leads
measurement Button
9
Model UT511: OPERATING MANUAL
Below Figure 2 and Table 5 shows the Meter side structure and description
Display Table 6 and Figure 3 describe the display.
Figure 2. The Meter Side Structure (Side View)
1 2
10
Table 5. Meter Side Description Safety Shutter Power adaptor Input Terminal
Figure 3. Display
Model UT511: OPERATING MANUAL
Number 1 2 3 4 5 6 7
8 9 10 11
Table 6. Display Description
Meaning Indicator for DC voltage Indicator for data store full Indicator for clearing Indicator for AC voltage Indicator for timer Step symbol Indicates selected pass/fail compare value Indicates for negative reading Timer 1 symbol Timer 2 symbol Data store is on
Number 12 13 14 15 16 17 18
19 20 21
Meaning Data recall is on Indicator for polarization index Unit symbols The
continuity buzzer is on Compare feature pass Analogue bar graph Risk of
electric shock
Compare feature fail Indicator for power adaptor Battery life indicator
11
Model UT511: OPERATING MANUAL
Key Functions
Table 7. Key Description
ON/OFF CLEAR/ SAVE
LOAD
Turn on or off the Meter. Press and hold the button for 1 second to turn the
Meter on. Press to clear the stored data,Push 1 SEC to turn on and off the
display backlight. Press to store the current measurement value. The maximum
number of stored reading is 18. When the stored readings memory is full, the
Meter shows FULL and stop storing. Press CLEAR to clear the stored value in
order to store the next measurement value. l Press once to recall the first
stored
value. l Press again to exit Load feature. l Load feature can only be used
when
there is no high voltage output.
l Under insulation resistance measurement mode: press to select one voltage
range up.
l Under load mode: press to recall the previous stored value.
l Under insulation resistance measurement mode: press to select one voltage
range down.
l Under load mode: press to recall the next stored value.
l When set the timer duration for the measurement of insulation resistance or
polarization index, press to decrement the time. The maximum length of time is
30 minutes, the Meter will automatically carry out measurement.
12
Model UT511: OPERATING MANUAL
Table 7. Key Description
l When compare feature measuring insulation resistance, press to decrement a
resistance comparing value.
l After polarization index measurement, press to display polarization index,
TIME 2 insulation resistance value and TIME 1 insulation resistance value in
sequence.
l When set the timer duration for the measurement of insulation resistance or
polarization index, press to increment the time. The maximum length of time is
30 minutes, the Meter will automatically carry out measurement.
l When use the compare feature measuring insulation resistance, press to
increment a resistance comparing value.
STEP
l After polarization index measurement, press to display polarization index,
TIME 2 insulation resistance value and TIME 1 insulation resistance value in
sequence.
Press to display S1 S2 S3 in sequence. l When the Meter is under timed
measurement or polarization index measurement:
S1 means increment of 1, then each press of increase 1 or decrease 1. S2 means
increment of 10, then each press of increase 10 or decrease 10. S3 means
increment of 30, then each press of increase 30 or decrease 30.
13
Model UT511: OPERATING MANUAL
Table 7. Key Description
STEP
COMP TIME TEST Ho
l When the Meter is under compare mode: S1 means increment of 1, then each
press of increase 1 or decrease 1. S2 means increment of 10, then each press
of increase 10 or decrease 10. S3 means increment of 100, then each press of
increase 100 or decrease 100.
Set a pass / fail limit for insulation tests. The default value is 100M Pres
to step through continuous measurement, timed measurement and polarization
index measurement in sequence. Press to stop or start an insulation resistance
test Press to initiate insulation resistance measurement
Lo
DVC /ACV
Press to initiate low resistance measurement Pres to initiate voltages measurement
E-STOP Emergency stop button. Press this button when the Meter is hang and cannot turn off the power.
14
Model UT511: OPERATING MANUAL
Measurement Operation Below section explains how to make measurements. A.
Measuring Voltages
Black
Red
Figure 4. Voltages Measurement
Caution
l Special care should be taken when measuring high voltage.
Warning
l To avoid harms to you or damages to the Meter, please do not attempt to
measure voltages higher than 1000V DC or 750V AC, although readings may be
obtained.
To measure voltages, set up the Meter as Figure 4 and do the following:
1. Press DCV or ACV button to select DC voltage or AC voltage measurement
2. Insert the red test lead into the V terminal and the black test lead into
the COM terminal.
3. Connect the red and black alligator clip to the circuit to be measured.
4. During measurement, when the red test lead is negative voltage, then “-”
shows on the display.
15
Model UT511: OPERATING MANUAL
Note
l When voltage measurement has been completed, disconnect the connection
between the testing leads and the circuit under test and remove testing leads
away from the input terminals of the Meter.
B. Measuring Insulation Resistance
Red
Black
Figure 5. Insulation Resistance Measurement
16
Model UT511: OPERATING MANUAL
Caution
l When performing insulation resistance tests, remove all power from the
circuit to be measured and discharge all the power.
l Do not short circuit two test leads under high voltage status.
l Do not measure insulation resistance after high voltage output.
l Do not measure over 10 seconds when: 100V measure resistance lower than 500k
250V measure resistance lower than 1M 500V measure resistance lower than 2M
1000V measure resistance lower than 5M
l When the measurement is completed, don’t touch the circuit as the circuit
has already stored capacitance which may cause electric shock.
l Don’t touch the test leads even after it has been removed from the circuit
until voltages are all released.
To measure insulation resistance, set up the Meter as Figure 5 and do the
following:
1. Press HO button to select insulation resistance measurement.
2. Press and button to select voltages of 100V, 250V, 500V or 1000V.
3. Insert the red test lead into the LINE terminal and the black test lead
into EARTH terminal.
4. Connect the red and black alligator clip to the circuit to be measured,
positive voltage output from LINE terminal.
5. Choose below insulation resistance measurement mode.
l Press TIME button to select continuous measurement mode, there is no timer
icon on the LCD.
l Press and hold TEST button for 1 second to carry out continuous measurement.
Output insulation resistance testing voltage, TEST button light up, blinks on
every 0.5 seconds.
17
Model UT511: OPERATING MANUAL
Press TEST button to close the insulation resistance measurement voltage when
measurement is completed. TEST button lights off , disappears. The LCD shows
the current insulation resistance measurement value.
l Press TIME button to select timed measurement mode, the LCD displays TIME 1
and symbols.
l Press , and STEP buttons to set the time (00:05~29:30).
l Then press and hold TEST button for 1 second to carry out timed measurement.
TIME 1 and are displayed and blinked on the LCD on every 0.5 seconds.
l When the set time is reached, the insulation resistance measurement voltage
will be closed and the measurement will be automatically stopped. The LCD
displays the insulation resistance reading.
18
l Press TIME button to select timed measurement mode, the LCD displays TIME 1
and symbols.
l Press , and STEP buttons to set the time (00:05~29:30).
l Press TIME button again. TIME 2, PI and symbols appear on the LCD.
l Press , and STEP buttons to set the time (00:10~30:00).
l Then press and hold TEST button for 1 second to carry out timed measurement.
l TIME 1 and are displayed and blinked on the LCD on every 0.5 seconds before
TIME 1 set time is reached.
l TIME 2 and are displayed and blinked on the LCD on every 0.5 seconds before
TIME 2 set time is reached.
l When the two set time are reached, the insulation resistance measurement
voltage will be closed and the measurement will be automatically stopped. The
LCD displays the polarization index reading.
Model UT511: OPERATING MANUAL
l Press , to set through the polarization index, TIME 2 insulation resistance
reading and TIME 2 insulation resistance reading.
Information: PI = 3 minutes ~10 minutes reading / 30 second ~1 minutes reading
PI
4 or more 4~2 2.0~1.0 1.0 or less
Standard The best Good Warning Bad
l Press COMP button to select compare feature. COMP symbol displays on the
LCD.
l Press , and STEP buttons to set the compare value. The minimum value is 1M
The maximum value is the maximum tested voltage allowable measurement value.
l Press and hold TEST button for 1 second to carry out the measurement.
l The NG symbol will display if the insulation resistance value is smaller
than resistance value. Otherwise GOOD symbol will be displayed.
19
C. Low Resistance Measurement
Red
Black
Figure 6. Low Resistance Measurement
20
Model UT511: OPERATING MANUAL
Caution
l When performing insulation resistance tests, remove all power from the
circuit to be measured and discharge all the power.
To measure low resistance, set up the Meter as Figure 6 and do the following:
1. Press LO button to select low resistance measurement..
2. Insert the red test lead into the LINE terminal and the black test lead
into EARTH terminal.
3. Connect the red and black alligator clip to the circuit to be measured.
When the resistance is less than 30 the buzzer sounds.
4. This range can test LED diode. Connect the anode LED diode to the red test
lead, the LED diode will light up if it is good. If the LED diode does not
light up, it means it is damaged.
Model UT511: OPERATING MANUAL The Use of Power Adaptor The use of power
adaptor, see figure 7
Figure 7. The Use of Power Adaptor
1. Open the side safey shutter, then you will see there is a power adaptor
input terminal.
2. Make sure the Meter is power off and Insert the UT511 power adaptor to the
input terminal.
3. It is highly recommed to take out all the batteries when you are using the
power adaptor.
4. Make sure the Meter is power off when you disconnect the UT511 power
adaptor from the Meter. (Input voltage 230VAC, Frequency 50/60Hz, Input
current 50mA, Output voltage DC 15V, MAX current 600mA)
Caution
If you want to choose power adaptor for power supply, please use special power
adaptor SA48-150060EU which supported by our company, otherwise it will be
dangerous.
21
Model UT511: OPERATING MANUAL
Maintenance
This section provides basic maintenance information including battery
replacement instruction.
Warning Do not attempt to repair or service your Meter unless you are
qualified to do so and have the relevant calibration, performance test, and
service information.
A. General Service l Periodically wipe the case with a damp cloth and
mild detergent. Do not use abrasives or solvents. l To clean the terminals
with cotton bar with detergent,
as dirt or moisture in the terminals can affect readings. l Turn the Meter to
OFF when it is not in use. l Take out the battery when it is not using for a
long
time. l Do not use or store the Meter in a place of humidity,
high temperature, explosive, inflammable and strong magnetic field. l If the
Meter is wet, dry it before use.
22
B. Replacing the Battery
Warning To avoid electric shock, remove all the test leads from the Meter when
replacing the batteries.
Caution l Don’t mix to use old and new batteries. l Be careful the polarity is
correct when installing
batteries. l Do not use the Meter if the battery indicator
( ) shows a battery empty condition.
Model UT511: OPERATING MANUAL Figure 8. Battery Replacement
Follow Figure 8 and proceed as follows to replace the battery: l Turn the
Meter to OFF and remove all connections
from the terminals. l Remove the screw from the battery compartment,
and separate the battery compartment from the case bottom. l There are 8pcs of
1.5V (R14) carbon battteries in the meter, except this, it can support 1.5V
(LR14) alkalescence batteries and the special power apapter which our company
provided. l Rejoin the case bottom and battery compartment, and reinstall the
screw.
23
Model UT511: OPERATING MANUAL
Specifications
Safety and Compliances
Certification Compliances IEC 61010 CAT.II 1000V, CAT.III 600V overvoltage and
double insulation standard
Physical Specifications Display (LCD) Operating Temperature Storage
Temperature Relative Humidity
Battery Type
Dimensions (HxW xL) Weight
Digital: 9999 counts Analog bar graph. -10 ~40 (14 ~104 ) -20 ~60 (-4 ~140 )
85% @ -10 ~40 below; 90% @ -20 ~60 : 8pcs of 1.5V (R14 or LR14) batteries or
DC15V power adaptor. DC15V power adaptor is optionally at extra cost. 202 x
155 x 94 mm Approx. 2kg (including battery)
24
Model UT511: OPERATING MANUAL
General Specifications
Range Overloading Battery Indicator Icon Display Current Consumption
Feature Summary
Display Backlight Autorange Warning Voltage COMP Measurement
PI Measurement
Auto Display OL on insulation resistance range Display Equips with function
and battery indicator icons. Maximum: around 90mA Average: around 20mA
Bright backlight for clear readings in poorly lighted areas. The Meter
automatically selects best range
and red light will on. Auto release voltage Use the Compare function to set a
pass/fail compare level for the insulation measurements. Polarization Index is
the ratio of insulation resistance. You can pre-set two point of times and
automatically carry out the measurement.
25
Model UT511: OPERATING MANUAL
Detailed Accuracy Specifications Accuracy: ([% of reading] + [number of least
significant digits), guarantee for 1 year. Operating temperature: 18 ~28
Relative humidity: 45~75%RH
A. Voltage Measurement
Measurement Range Resolution Accuracy
DC Voltage 30 ~ 1000V
1V (2%+3)
AC Voltage 30V~750V (50/60Hz)
30~100V (2%+5) 100~750V (2%+3)
B. Insulation Resistance Measurement
Output Voltage Display Range
100V 0.1M ~99.9M 100~500M
Open Circuit Voltage DC100V + 20%,-0%
Test Current
1mA~1.2mA@100k
Short Circuit
Accuracy
100k
250V 0.5M ~99.9M 100~999M 1.00~1.99G DC250V + 20%, -0% 1mA~1.2mA@250k
500V
1000V
1M ~99.9M
2M ~99.9M
100~999M
100~999M
1.00~3.99G
1.00~10.00G
DC 500V + 20%, -0% DC1000V + 20%, -0%
1mA~1.2mA@500k 1mA~1.2mA@1M
Around 2.0mA to 100M : (3%+5) 100M above: (5%+5)
26
Model UT511: OPERATING MANUAL
Caution At any output voltage, when the tested resistance is les than 5M, the
testing time cannot exceed 10 seconds.
C. Low Resistance Measurement
Function Measurement Range Resolution Accuracy Maximum open circuit voltage Buzzer Overload Protection
Resistance 0.1~999.9 0.1
(1%+3) Around 2.8V Open at less than 30 220V rms/10 seconds
27
Model UT511: OPERATING MANUAL
END
This operating manual is subject to change without notice. 28
Model UT511: OPERATING MANUAL
Copyright 2006 Uni-Trend Group Limited. All rights reserved.
Manufacturer: Uni-Trend Technology (Dongguan) Limited Dong Fang Da Dao Bei
Shan Dong Fang Industrial Development District Hu Men Town, Dongguan City
Guang Dong Province China Postal Code: 523 925
Headquarters: Uni-Trend Group Limited Rm901, 9/F, Nanyang Plaza 57 Hung To
Road Kwun Tong Kowloon, Hong Kong Tel: (852) 2950 9168 Fax: (852) 2950 9303
Email: info@uni-trend.com http://www.uni-trend.com
29