ectre MK3 Stacker Freestanding Wood Heater Installation Guide

June 28, 2024
ectre

ectre MK3 Stacker Freestanding Wood Heater

ectre-MK3-Stacker-Freestanding-Wood-Heater-PRODUCT

Product Information

Specifications

  • Product: NECTRE MK3
  • Manufacturer: Glen Dimplex Australia
  • Version: 1.0
  • Compliance Standards: AS/NZS 4012:2014, AS/NZS 4013:2014, AS/NZS 2918:2018

Installation Instructions

It is crucial to follow the specified Installation Standard AS/NZS 2918:2018 for wood heater installations in Australia. Ensure compliance with local building regulations before proceeding.

All Nectre wood heaters are tested to meet safety standard requirements if installation instructions are adhered to. Modifications to the appliance are not allowed without written permission from the manufacturer.

  • Determine whether standard installation or corner installation is suitable for your space.
  • Ensure a suitable floor protector is in place to prevent damage to the flooring.
  • Follow guidelines to reduce clearances to combustibles for safe operation.
  • Properly install the flue system following detailed instructions.
  • Place fire bricks correctly to ensure efficient heating.
  • Install baffle plates as per the provided instructions for optimal performance.
  • Follow steps to correctly install the ash plate for maintenance purposes.
  • Refer to technical drawings for additional installation insights.

FAQ

  • Q: Can I modify the Nectre wood heater without permission?
  • A: No, any modifications to the appliance must have written consent from the manufacturer to maintain compliance.
  • Q: Should I consult with the manufacturer before making changes to the flue system?
  • A: Yes, consulting with the manufacturer is advised to prevent hazardous conditions.

IMPORTANT INFORMATION

  • Most building regulatory Authorities in Australia require any wood heater installation to comply with Installation Standard AS/NZS 2918:2018. Different states and councils may have varying regulations. Check local building regulations before installing the appliance.

  • All Nectre wood heaters have been tested to ensure
    that they will meet the appropriate safety Standard requirements if the instructions in this manual are followed. As the safety and emissions performance can be affected by altering the appliance, no modifications are allowed without written permission from the manufacturer.

  • WE RECOMMEND THAT THE INSTALLATION OF YOUR NECTRE WOOD HEATER BE CARRIED OUT BY A QUALIFIED INSTALLER.

  • WARNING: THE APPLIANCE AND FLUE SYSTEM SHALL BE INSTALLED UNDER AS/NZS 2918:2018 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR CODES.

  • WARNING: APPLIANCES INSTALLED UNDER THIS STANDARD SHALL COMPLY WITH THE REQUIREMENTS OF AS/NZS 4012 & AS/NZS 4013 WHERE REQUIRED BY THE REGULATORY AUTHORITY, I.E. THE APPLIANCE

  • SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH THE MARKING ‘TESTED TO AS/NZS 4012 & AS/NZS 4013’.

  • ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE TESTING AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR COMPLIANCE WITH AS/NZS 4012 & AS/NZS 4013.

  • CAUTION: MIXING APPLIANCE OR FLUE-SYSTEM COMPONENTS FROM DIFFERENT SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER SHOULD BE CONSULTED IN THE FIRST INSTANCE.

  • CAUTION: CRACKED AND BROKEN COMPONENTS, EG. GLASS PANELS OR CERAMIC TILES MAY RENDER THE INSTALLATION UNSAFE.

WARNING: KEEP BATTERIES OUT OF REACH OF CHILDREN

  • Swallowing may lead to serious injury in as little as 2 hours or death, due to chemical burns and potential perforation of the esophagus.
  • If you suspect your child has swallowed or inserted a button battery immediately call the 24-hour Poisons Information Centre on 13 11 26 (in Australia) or 0800 764 766 (in New Zealand) for fast, expert advice.
  • Examine devices and make sure the battery compartment is correctly secured, e.g. that the screw or other mechanical fastener is tightened. Do not use if the compartment is not secure.
  • Dispose of used button batteries immediately and safely. Flat batteries can still be dangerous.

INSTALLING THE HEATER

POSITIONING THE HEATER

  • First review the necessary clearances specified on the following page before considering where to position the heater.
  • The heater can be installed with a choice of three different flue configurations. Clearances specific to each are listed in the associated tables. Also, check the practicability of installing the flue system concerning any obstructing roof beams before positioning the heater.
  • These clearance distances can only be reduced if the surrounding walls are made of non-combustible material, eg. Stone, brick, or concrete. If non-combustible material, the distance can be reduced to 100 mm. Alternatively, shielding of the wall(s) can reduce clearances (refer to next section for more detail).

STANDARD INSTALLATION

CORNER INSTALLATIONectre-MK3-Stacker-Freestanding-Wood-Heater-
FIG-4

FLOOR PROTECTOR (HEARTH)
Unless the heater will be standing on a heat-resistant floor such as a concrete slab with slate or tiles, it will be necessary to provide a floor protector (hearth).
The dimensions given on the previous page (“2.1. Positioning the Heater”) are the minimum required for
the floor protector to extend beyond the firebox door opening. It must extend no less than 300 mm in front of the door opening, no less than 200mm on both sides of the door opening, and extend under the heater.

MEASUREMENT WIDTH

  • Door opening width 500mm
  • Minimum floor protector width 900mm

Minimum dimensions for floor protectors are 900mm wide by 900mm deep.

  • It may be desirable, e.g. for aesthetic reasons, for the floor protector to be larger than these minimum dimensions.
  • The floor protector shall be constructed from noncombustible material no less than 15mm thick and with a thermal conductivity not greater than 0.33W/m ºK, eg. a compressed-fiber cement sheet.
  • The floor protector may be laid directly on the combustible floor.
  • For more details and variations on floor protectors refer to AS/NZS 2918 Clause 2.2, 3.3.1, & 3.3.2

REDUCING CLEARANCES TO COMBUSTIBLES

  • If it is necessary to install a heater closer to a combustible surface than the stated requirements in Section 2 of this Installation Guide, it must be done in accordance with Australian Standard AS/NZS 2918 Section 3, Tables 3.1 & 3.2.
  • Shield Construction: The shield shall be constructed from a heat-resistant material. The shield must be fixed to the surface that requires protection and NOT the heater.
  • The Standard allows three options to reduce stated clearances.

A single layer of continuous material with Minimum Air
Gap of 12mm—Clearance Factor = 0.40
A single layer of continuous material with Minimum Air
Gap of 25mm—Clearance Factor = 0.30
Two-spaced layers of continuous material with Minimum
Air Gaps of 12mm + 12mm—Clearance Factor = 0.20

The shielding must be open at the top and bottom (vented) to allow a continuous airflow. It is this airflow that keeps the surface requiring protection cool. Fixings should not impede this airflow.
The shielding needs to go far enough along and up the wall so that the original side and rear required clearances are not compromised. As the flue is now closer to the wall the shielding should also protect the wall from the flue pipe.
For example

  • Side wall clearance for the Mk3 is 400mm.
  • A 12mm gapped shield on the wall with a factor of 0.40.
  • Calculate: 400mm x 0.40 = 160mm. This is the new side wall minimum clearance.
  • The shielding needs to be large enough so that none of the original clearances of 400mm are compromised.

INSTALLING THE FLUE

The flue system used when installing the heater MUST comply with the current installation standard AS/NZS 2918.
Full instructions on the installation of the flue will be supplied with the flue kit. These MUST be adhered to, including the minimum exit height from the top of the floor protector being not less than 4.6m, and the minimum exit height above the roof line of roof ridge as detailed in the instructions.
The MK3 uses a 6”/150mm active flue and must be fitted with one of the following:

Rear Flue Shield

  • 900 mm long, minimum 160° arc, stainless steel unpainted rear flue shield with 25mm gap between it and the active flue.

Decromesh / Solid Flue Shield
Note – must be installed with an internal heat shield/ reflector AND ventilated locating ring at the base of flue shielding.

  • A full-length, half-radius perforated flue shield extending from the heater through into the drop box penetrating the ceiling with the perforated surface facing the front, OR equivalent in solid outer flue shield casing (7.75” diameter)
  • The first length of casing must have an inner shield extending the full length and positioned so that the inner shield is between the active flue and the rear wall.
  • The manufacturer’s ‘locating ring’ must be used to support the flue shielding up off the heater top. It is important that air can be drawn into the base and rear of the flue shielding.
  • Place the locating ring around the flue spigot (resting on the heater top) and then place the first length of active flue into the spigot. Slide the shielding over the active flue. Locate the bottom of the decromesh or solid outer shield inside the locating ring.ectre-MK3-Stacker-Freestanding-Wood-Heater-FIG-5
  • Depending on the supplier, the flue shielding can be one of three sizes – 200 mm, 7 ¾ inch, or 8 inch diameter. The locating ring will fit the two smaller diameters but not the 8-inch. In this scenario, snip through the outer ring with tin snips as shown in the drawing below. Bend the two “arms” in a little so they end don’t project out when fitted to the decromesh. Ensure that the snipped section is at the rear of the flue, out of sight.

If the draft is insufficient or periodic down drafting occurs and the heater smokes or only burns slowly, extending the flue or fitting a specialized cowl will usually resolve the issue.ectre-MK3-Stacker-Freestanding-Wood-Heater-
FIG-7

FITTING FLUE SEAL
Any gaps between the inside of the flue spigot and the active flue should be sealed. This can be done by wrapping the bottom of the flue with a length of fiberglass tape. Alternatively, high-temperature stove cement can also be used.

INSTALLING THE FIRE BRICKS

  • The Nectre Mk3 comes with 11 full-size bricks (230(h) x 115(w) x 38(d)mm).
  • Raise the brick retainer (supplied inside the firebox) and start standing the bricks up against the rear and sides of the firebox as shown in the diagram below.
  • Once the bricks are in, fit the retainer over the top to hold them in place.

INSTALLING THE BAFFLE PLATES

  • The Nectre Mk3 is supplied with two baffle plates:

Upper baffle plate – 400(w) x 160(d) x 5(h) mm

  1. Fit the upper baffle plate first.
  2. With the plate in a horizontal position, slide it up and over the shorter of the two sets of support hooks welded to the top of the firebox.
  3. Slide the plate back so that it rests on the upper support rod on the rear wall of the firebox.
  4. The upper baffle plate should be in a horizontal orientation.

Lower baffle plate – 500(w) x 300(d) x 12(h) mm

  1. Slide the lower baffle plate up and over the lower set of support hooks welded to the top of the firebox.
  2. Slide the plate back so that it rests on the lower support rod on the rear wall of the firebox.
  3. Unlike the upper baffle plate, the lower baffle plate rests on a slight angle sloping down and back to the rear of the firebox.

INSTALLING ASH PLATE

  • The ash plate acts to protect the front of the firebox below the door opening from the hot coal bed and fire.
  • When positioning the ash plate, ensure that the front top edge is flush against the inside edge of the firebox beneath the door opening.ectre-MK3-Stacker-Freestanding-Wood-Heater-FIG-10

TECHNICAL DRAWINGS

ectre-MK3-Stacker-Freestanding-Wood-Heater-FIG-11

CONTACT

Glen Dimplex Australia Pty Ltd

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals