BASGE-EN868 EnOcean BACnet Gateway Installation Guide

June 27, 2024
enocean

BASGE-EN868 EnOcean BACnet Gateway

Specifications

  • Product Name: EnOcean to BACnet Gateway
  • Model Number: BASGE-EN868
  • Frequency: 868 MHz (European Version)
  • Electrical:
    • DC: 24 V, 3 W
    • AC: 24 V, 6 VA, 47-63 Hz
  • Operating Temperature: N/A
  • Storage Temperature: N/A
  • Relative Humidity: N/A
  • Ethernet: 10BASE-T, 100BASE-TX
  • EnOcean: 868 MHz
  • Cable Length Limit: 100 m
  • EnOcean Distance: 30 m typically inside buildings
  • Ethernet LED: Flashing = activity at 10Mbps or 100Mbps

Product Usage Instructions

1. Installation
Follow the Installation Guide provided in the manual. Ensure electrical connections are made for DC 24 V and AC 24 V as specified.

2. Physical Layer
The unit can be DIN-rail or panel mounted using M6 pan head screws. Antennas available for purchase separately are BASGE-ANT868 and BASGE-ANT-2M.

3. Web Page Configuration
The EnOcean to BACnet Gateway has an interactive web server accessible from any Internet-compatible PC on the local network.A defaultt IP address is 192.168.92.68 with User Name: admin and Password: admin.

4. Reset IP
To reset the IP, remove the top cover, locate the reset IP switch, and press for 10 seconds while the unit is powered. Wait for the unit to reboot and complete its booting process.

EnOcean to BACnet Gateway
The EnOcean to BACnet Gateway provides the systems integrator with a flexible building block when integrating EnOcean wireless devices to BACnet/IP networks or expanding the number of EnOcean points in an existing building automation system. Thanks to virtual routing technology, our gateway seamlessly discovers and connects to EnOcean devices and makes them appear as individual BACnet- compliant devices. The gateway creates a set of BACnet objects, specific for each EEP, and decodes the received EnOcean data into standard BACnet objects, such as analog inputs for temperatures, humidity, light levels, etc, and multistate objects for EnOcean values that represent multiple states, for easy integration into the BACnet system – saving the head-end from decoding the transmitted EnOcean data.

Bidirectional Gateway functionality between EnOcean Wireless and BACnet/IP

  • EnOcean device discovery
  • Remote commissioning of link tables and configuration settings
  • Each EnOcean device appears as a  virtual BACnet device to aid in the  integration
  • Received EnOcean data is decoded into standard BACnet objects
  • No external tools are  required for the  configuration

InstallationGuided
Electrical (Class 2 Circuits Only)

INPUT                             DC              AC

Voltage (±10%):               24 V             24 V

Power:                             3 W              6 VA

Frequency:                      N/A             47-63 Hz

Environmental

Operating temperature:     0°C to 60°C Storage temperature:     –40°C to +85°C

Relative humidity:            10–95%, non-condensing

Functional __ Physical Layer

Ethernet:                          10BASE-T, 100BASE-TX

EnOcean:                         868 MHz

Cable length limit:             100 m

EnOcean distance:           30 m typically inside buildings

Ethernet LED:                  flashing = activity at 10Mbps or 100Mbps

Antenna (sold separately)

BASGE-ANT868:           EN868 stick antenna: 50ohmsm, gain -0.1 dBi, efficiency 40%
BASGE-ANT-2M:    EnOcean antenna w/ 2 m cable: 50 ohm, gain 0.73 dBi (868 MHz) efficiency 60%

Installation

Power Connection

  • The EnOcean to BACnet Gateway requires 24 VAC or 24 VDC while drawing no more than 6 VA of power. The recommended conductor size is 16–18 AWG. COM is directly connected to zero volts and the chassis is DC isolated from zero volts. Input connections are reverse-polarity protected. See figure for power options. The
  • SMA connector supports a stick antenna (as shown in the product image) or an antenna witha  2 m cable for mounting the antenna outside the control cabinet.
  • The unit can be DIN-rail orpanel-mountedd. It uses M6 pan head screws in both the body of the gateway and the DIN-rail clip.

BASGE-EN868-EnOcean-BACnet-Gateway-FIG-1

WARNING
Internally, this device utilizes a half-wave rectifier and therefore can only share the same AC power source with other half-wave rectified devices. Sharing a common DC power source is also possible. Sharing AC power with full-wave rectified devices is NOT recommended. Devices powered from a common AC source could be damaged if a mix of half-wave and full-wave rectified devices exists.

Web Page Configuration

  • The EnOcean to BACnet Gateway contains an interactive web server accessible from any Internet-compatible PC on the local network with recent versions of most standard web browsers such as Microsoft Edge, Mozilla Firefox, or Google Chrome installed.
  • To configure the gateway initially, connect it to your Windows PC using an Ethernet cable and set the PC’s IP and subnet mask in Local Area Connection –> Properties. In the Internet Protocol Version 4 (TCP/IPv4) settings of your Windows PC, specify an IP address and a Subnet mask in the same subnet as the gateway (e.g. 192.168.92.5 /24).
  • EnOcean to BACnet Gateway’s factory-programmed: Default IP address is 192.168.92.68 and a Class C subnet mask of 255.255.255.0 (/24)
  • User Name is: admin and thee  Password is: admin

Reset IP
Remove the top cover, locate the reset IP switch (see picture,) and while the unit is powered press for 10 seconds. The unit will reboot, and you can access it via the IP address and user name/password defaults shown above. Please wait 30 seconds for the gateway to complete its booting process

Contemporary Control Systems, Inc. reserves the right to make changes in the specifications of the product described within this manual at any time without notice and without obligation of Contemporary Control Systems, Inc. to notify any person of such revision or change.

FAQ:

1. Can I use the EnOcean to BACnet Gateway with full-wave rectified devices?
No, it is not recommended to share AC power with full-wave rectified devices as it may cause damage to connected devices.

2. How can I access the web server for configuration?
You can access the interactive web server from any Internet-compatible PC on the local network using a web browser such as Microsoft Edge, Mozilla Firefox, or Google Chrome.

3. Whatares the default IP address and login credentials?
The default IP address is 192.168.92.68 with User Name: admin and Password: admin.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

enocean User Manuals

Related Manuals