Quelfire QRS110-54 QRS Fire Sleeve and QRS Slim Fire Sleeve Instruction Manual

October 27, 2023
Quelfire

QRS Fire Sleeve & QRS Slim Fire Sleeve
Instruction ManualQuelfire QRS110-54 QRS Fire Sleeve and QRS Slim Fire
Sleeve -

INSTALLATION INSTRUCTIONS

This installation guide is intended for general information only and all details should be checked against relevant supporting test evidence and certification.

Quelfire QRS Fire Sleeves are lifesaving products designed to prevent the spread of fire where plastic vent ducts penetrate fire compartment walls. It is therefore essential that they are fitted in a responsible and workmanlike manner.
QRS Fire Sleeves are suitable for use in various wall constructions including solid concrete masonry/block walls and flexible fire rated plasterboard partitions with and without the QuelStop Fire Batt system. Fire ratings vary depending on the substrate and services so refer to the technical data and installation details for full details.
Apertures for the QRS should be cut or drilled as tight as practically possible to suit the external dimensions of the QRS Fire Sleeve. Suggested aperture sizes are provided in the table below and we would always recommend carrying out a trial on site:

Product Code| Duct Size (mm)| Approx. space needed around ductto fit QRS Fire Sleeve (mm)| Recommended approx. aperture (mm)
---|---|---|---
QRS110/54| 110 x 54| 13| 135 x 78
QRS205/60| 205 x 60| 13| 230 x 85
QRS220/90| 220 x 90| 22| 262 x 132
QRS75| 75 Ø semi-rigid| 8| 90 Ø
QRS90| 90 Ø semi-rigid| 13| 116 Ø
QRS110
| 100 Ø| 18| 135 Ø
QRS130*| 125 Ø| 23| 170 Ø
QRS110/54SS| 110 x 54| 8| 126 x 70
QRS204/60SS| 204 x 60| 8| 219 x 75
QRS220/90SS| 220 x 90| 12| 244 x 114

*QRS90, QRS130 and QRS110 are not currently CE Marked
Gaps around the installed QRS Fire Sleeve should not exceed 5mm and can therefore be sealed with QuelStop Intumescent Acrylic Sealant.
The QRS can be retrofitted but is dependent on being able to cut the right size aperture within the wall substrate which may be easier to achieve without the duct in position.
The normal and easier installation is to build the wall around the QRS Fire Sleeve and duct.

Installation principles of the Quelfire QRS Fire Sleeve

  1. Once the correct diameter hole or aperture has been achieved within the wall and the correct QRS Fire Sleeve has been identified, check the duct and penetration are clean of debris and there are no obstructions that would prevent the QRS being slid into position.
  2. Hinge open the QRS Fire Sleeve and wrap tight around the plastic vent duct.
  3. Secure the lid of the QRS shut with the self-adhesive tape fitted to the rectangular versions (or the self tapping screw supplied with circular versions).
  4. The QRS Fire Sleeve can then be slid along the duct into the substrate.
  5. Ensure that the QRS Fire Sleeve is centrally positioned within the wall and that the face of the QRS is either flush or
  6. protruding from the substrate in accordance with the specific installation detail – check both sides. Seal around the perimeter of the QRS where it meets the substrate with QuelStop Intumescent Acrylic Sealant.
  7. Where the duct is required to be insulated, this can now be butted up to the QRS Fire Sleeve and sealed in accordance with
    manufacturer’s recommendations.

Example Installation 1 – Direct to flexible or rigid walls

Drill or cut the hole in accordance with the details provided in the table above then install as described above ensuring the minimum required protrusion is achieved on both sides of the wall and finally seal both sides of the wall with QuelStop Intumescent Acrylic Sealant.Quelfire QRS110-54 QRS Fire Sleeve
and QRS Slim Fire Sleeve - Example Installation

Example Installation 2 – Multiple (stacked/side-by-side/cluster) ducts
Multiple ducts/QRS can be installed as a cluster and the QRS should be installed in accordance with the details given above.
Once finally positioned, the QRS should be touching, 0mm between each, and sealed around the perimeter. If the QRS are not touching then they need to be far enough apart so as to be able to practically and robustly install and seal the sleeve in the original wall construction or QuelStop Fire Batt. 50mm is usually regarded as an absolute minimum space, but 100mm is much more practical.

Quelfire QRS110-54 QRS Fire Sleeve and QRS Slim Fire Sleeve -
ducts

Example Installation 3 – In conjunction with QuelStop Fire Batt
In the case of oversized holes or formed letterboxes, depending on the services, it may be possible to use the QRS Fire Sleeve in conjunction with a single or double layer of QuelStop Fire Batt.
In these cases, the QRS should be installed first as described above and then during final positioning and before sealing in place, the QuelStop Fire Batt should be installed in accordance with separate supporting documentation.

Quelfire QRS110-54 QRS Fire Sleeve and QRS Slim Fire Sleeve - QuelStop Fire
BattQuelfire
QRS110-54 QRS Fire Sleeve and QRS Slim Fire Sleeve -
depending

Packaging & Storage:
Quelfire QRS Fire Sleeves are supplied individually to suit specific vent duct sizes and may be packaged in cardboard boxes for shipping purposes and should be stored in a cool, dry location.
Health & Safety:
QRS CE Marked Fire Sleeves consist of a pressed stainless steel shell containing graphite in a synthetic compound with the addition of filters and process oils.
The steel shells can have sharp edges, always wear gloves when handling.
For further information, please refer to the Material Safety Data Sheets, available on request or via the website.

Technical Support & Guidance:

Should you require any further information regarding this product, please do not hesitate to contact the technical department at Quelfire Ltd.
Tel: 0161 928 7308. Email: technical@quelfire.co.uk
Please be aware that this document is intended for general information only and all details should be checked against all relevant supporting test evidence, certification and installation guidelines Use of alternative components or deviations from the instructions in any way is likely to mean that the installation will not comply with the assessed rating.
Quelfire Ltd does not accept responsibility for the consequences of using Quelfire products in applications or for purposes not authorised by Quelfire Ltd. Expert advice should be sought where such applications are contemplated.
The policy of Quelfire Ltd is one of constant improvement. Installers should therefore ensure they are working from the latest published drawings and instructions. Whilst Quelfire will endeavour to keep its publications up to date, the accuracy of the information contained within this drawing may be affected by pertinent changes in the law or regulatory requirements and alterations or amendments to the specification of Quelfire products.
All information contained in this document is given in good faith and is provided for guidance only. Any drawings provided are for illustrative purposes only. As Quelfire Ltd has no control over the methods or competence of installation and of prevailing site conditions, no warranties, expressed or implied, is intended to be given as to the actual performance of the product mentioned or referred to herein and no liability whatsoever will be accepted for any loss, damage or injury arising from the use of the information given.