MICROSENS MS660102 Commissioning the Smart Lighting Controller User Guide

June 6, 2024
MICROSENS

MS660102 Commissioning the Smart Lighting Controller

Quick Start Guide Commissioning the Smart Lighting Controller
V0.0.7

Quick Start Guide Commissioning the Smart Lighting Controller

Aim of this Quick Start Guide

This quick start guide will help you with

  • the mechanical handling of the Smart Lighting Controller,
  • connecting the power supply via PoE+ and commissioning the device,
  • reset the device,
  • connecting the signal cables (inputs and outputs)
  • and setting up access to the network management.

For further information see the Web Manager of the managing MICROSENS switch or visit the MICROSENS  website.

Note: Make sure to connect all components (LED light, Smart Sensors) only to an unpowered Smart Light Controller!  Otherwise the components or the controller could be damaged due to uncontrolled voltage spikes!

2 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

1 Interfaces and Operating Elements

Figure 1: Interfaces

Smart Sensor portRJ-45, unshielded
proprietary

|

Reset button

|

10/100Base-TX uplink port
RJ-45, shielded, Cat 5e

---|---|---

LED light connector
Push-in-clamp
2x 0.2 – 4.0 mm²

|

Chassis ground and strain
relief lug for LED light connector cable

|

Mounting tabs
(chassis ground)

2 Mechanical Handling

The MICROSENS Smart Lighting Controller is ready to be attached via two different mountings:

  • A clamp for top hat rail mounting
  • and four mounting tabs for direct attachment to wall, ceiling or any other backing equipment.

2.1 Mounting Tabs

To attach the Smart Lighting Controller directly to a wall, ceiling or any other suitable backing equipment, use the  four mounting brackets (Figure 2, Pos. 1 to 4).

Note: Make sure to secure the attachment adequately when using less mounting tabs! It is not recommended to use  only one mounting tab or mounting tabs of only one side.

3 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

2.2 Top Hat Rail Mounting and Demounting

On its bottom side the Smart Lighting Controller housing (Figure 3, Pos. 1) is optionally equipped with a clamp for  mounting the device onto a standard top hat rail (Figure 3, Pos. 2).

Note: Assemble the clamp to the housing if not shipped with clamp already adapted. Be sure the clamp’s release lever  (Figure 3, Pos. 3) is pointing to the side with the Ethernet port (Figure 1, Pos. 3).

2.2.1 Mounting on Top Hat Rail

  1. Place the housing with the clamp’s stationary fixture over the top hat rail (Figure 3, Pos. 4).
  2. Gently press the housing (Figure 3, Pos. 5) until the clamp snaps into the top hat rail (Figure 3, Pos. 2) with an audible click.

2.2.2 Demounting from Top Hat Rail

1. Pull the release lever (Figure 4, Pos. 1) to unlock the clamp and lift the device (Figure 4, Pos. 2) to  remove it from the top hat rail.

4 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

3 Connecting the LED Light

Note: Connect the LED light only to an unpowered Smart Light Controller! Otherwise the LED light or the controller could  be damaged due to uncontrolled voltage spikes!

Connect the LED light cable to the push-in clamp (Figure 1, Pos. 4).

Make sure the connected LED light meets the following requirements of the interface:

  • Power output: max. 28 W
  • less power depending on the number of connected Smart Sensors
  • for the used sensor’s power consumption please refer to the respective data sheet
  • Power supply: 20 to 50 VDC
  • Current output: max. 1 A
  • Cable length: max. 3 m
  • Cable type: 2-wire cable, 0.2 to 4.0 mm² wire cross section

4 Connecting the Smart Sensor

Note: Make sure to use the Smart Sensor (i.e. CAN or MICROSENS) which matches the respective SLC. A wrong  combination of Smart Sensor and SLC may damage the Smart Sensor permanently! If in doubt, contact the  MICROSENS support.

Note: Connect the Smart Sensor only to an unpowered Smart Light Controller! Otherwise the sensor or the controller  could be damaged due to uncontrolled voltage spikes!

Connect the Smart Sensor cable to the Smart Sensor port (Figure 1, Pos. 1).

Depending on the Smart Sensor type and the type of SLC it is possible to connect multiple Smart Sensors to the  Smart Lighting Controller in series. In case of the wrong combination of SLC and Smart Sensor, the Smart Sensor  can be permanently damaged.

Note: Please refer to the technical documentation of the respective Smart Sensor regarding e.g. power consumption and  bus-termination demands.

5 Connecting the Power Supply

The MICROSENS Smart Lighting Controller is supplied by PoE+ (PD) via the Ethernet port (Figure 1, Pos. 3).

Note: Make sure to enable PoE/PoE+ PD on the powering device. For enabling PoE on MICROSENS devices please refer  to the respective documentation shipped with the device.

Note: The Smart Lighting Controller is powering a connected LED light via the PoE+ power supply with a maximum  power output of 28W. Make sure that the powering PoE+ device is able to deliver a power of at least 30 W and the connecting Cat 5e Ethernet cable does not exceed the recommended maximum length of 15 m.

5 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

5.1 Grounding with PoE Supply

For the installation of PoE components in corporate networks it is necessary to reference the DC supply voltage of  all devices to the same ground level. Normally this will be the positive polarity connected to ground level of  the building’s electrical system (i.e. “earth”).

Assuming, powering of the Smart Lighting Controller is done via a centralised far off PoE PSE device it is important  to connect the grounding lead of the controller’s chassis (Figure 1, Pos. 5 or 6) to the building’s ground potential  and thus to avoid “floating ground” problems. Besides safety issues, a floating ground of the network can cause  problems if only one component accidentally or on purpose is grounded (Figure 5).

6 Reset the Smart Lighting Controller

The Smart Lighting Controller is equipped with a reset button (Figure 1, Pos. 2);

  • < 2 s press: Reset the device
  • 2 s press: Switching to update mode.

If no update file is received within 20 s the device will start normally.

7 Operating the Smart Lighting Controller with MICROSENS Switches

Note: Using MICROSENS Smart Lighting Controller is possible with MICROSENS switches containing Firmware 10.7.7b and newer. IPv6 has to be enabled.

As soon as the Smart Lighting Controller is connected to the power supply (and therefore to the corporate  network) the controller is accessible via a MICROSENS switch containing the MICROSENS SmartDirector.

Note: Because of using IPv6 link local addresses it is possible to operate a remote Smart Lighting Controller with a  MICROSENS switch via the IPv6 corporate network as long as the connection is not routed.

7.1 Defining and Assigning a Function Template

The G6 switch contains configuration templates for specific controller types (in this case the Smart Lighting  Controller). The template’s parameter types correspond to the controller’s parameters accordingly.

To change the controller’s parameter from their default values, the following steps are recommended:

  1. Define the controller’s port functions via the G6 template in the Smart Office screen.
  2. Pair the controller to the G6 switch.
  3. Restart Smart Office on the G6 switch (disable and enable SmartOffice).

Now the controller receives the values, which remain stored permanently (even during a reset) until next change  via G6 template or e.g. MICROSENS Smart Config Tool.

Note: It is possible at all times to change the controller’s settings provided by the template by restarting SmartOffice  after the changes are entered.

6 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ Start the web browser and enter the IP address of the respective G6 device.
□ Log into the Web Manager with the administrator credentials.
□ Select the Controller screen and then select the tab SLC.
□ In the section Device.controller.smartlight_config add a new table entry for the Smart Lighting Controller (e.g. “SLC_1” as a unique name) and click on the button “+”.

□ The new controller entry is created with default values assigned to its template fields. Figure 7: Web Manager – Controller – SLC – Default Values

  • Name: The previously assigned device name.
  • Type: Select the specific type depending on the device model.

7 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ For adjusting the maximum source and panel power, select the SmartOffice screen, then select the  Device Configuration tab.

□ In the section Device.smartoffice.device_config scroll down to the respective SLC and in the field  additional parameter enter the values for “max_source_power=,max_panel_power=”  in mW.

□ Perform changes to the controller’s configuration as needed and click on the button apply to running  configuration to save the changes to the running configuration.

7.2 Pairing the Smart Lighting Controller and the MICROSENS Switch

The following steps describe how to pair a Smart Lighting Controller via the Web Manager of a MICROSENS switch.

Note: For this overview primarily the use of the Web Manager is shown. Using the CLI for pairing the devices is relatively  easy because the Web Manager uses the respective CLI commands as labels for fields and sections.

Using the Web Manager:

□ Start the web browser and enter the IP address of the respective G6 device.

□ Log into the Web Manager with the administrator credentials.

□ Select the SmartOffice screen and then select the tab Basic Configuration.

8 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ In the section Device. smartoffice. director_config click on the button scan light controllers.

  • The SmartDirector starts searching for connected Smart Controllers. As long as no controller is found  the section scanned Light Controllers stays empty.
  • After successfully scanning for available Smart Controllers the Web Manager lists all found controllers. Figure 10: Web Manager – SmartOffice – Basic Configuration – Available Controllers
  • As long as no device of the suitable product type is created previously the column Pairing Actions of  the respective Smart Lighting Controller is empty. Clicking on the button identify of the controller  entry causes the connected LED lights of this controller to blink several times. This ensures to use the  correct controller for the next steps.

□ Click on the button add to create the respective device entry.

  • This new device entry is named “scanned_” and assigned to the product type  “SMARTLIGHT_CONTROLLER”.

□ Select the tab Device Configuration and in the section Device.smartoffice.device_config scroll down  to the formerly created entry.

9 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ Change the device name to the name corresponding to the previously created controller (e.g.,  “SLC_1”).

□ Leave all other entries as is.

□ Click on the button apply to running configuration to save the changes to the running configuration.

□ Select the tab Basic Configuration and in the section Device.smartoffice.director_config click on  the button scan light controllers.

  • The SmartDirector again starts searching for connected Smart Controllers. As long as no controller is  found the section scanned Light Controllers stays empty.
  • After successfully scanning for available Smart Controllers the Web Manager lists all found controllers. Figure 12: Web Manager – SmartOffice – Basic Configuration – Available Controllers
  • In the column Pairing Actions the drop-down list offers the selection of the previously added and  modified device entry.

□ Select the fitting device from the drop-down list and click on the button pair as.

  • The Smart Lighting Controller is now properly paired to the SmartDirector of the MICROSENS G6  Switch.
  • Additionally the pairing process sets the previously empty device id to the correct value.

7.3 Calibration of LED Panel

The calibration of an LED panel ensures that the Smart Lighting Controller provides only the maximum current the  LED panel endures.

Note: It is important to calibrate the connected and paired LED panel before use in order to avoid damage to the panel! The calibration process depends on which LED panel is used:

  • 1-channel LED panel with anode and cathode
  • 2-channel LED panel with common electrodes (i.e. both channels share the same anode or cathode) 7.3.1 Calibration of a 1-Channel LEP Panel

To calibrate a 1-channel LED panel connected to a paired Smart Lighting Controller, proceed as follows: Using the Web Manager:

□ Start the web browser and enter the IP address of the G6 device containing the Smart Director. □ Log into the Web Manager with the administrator credentials.

□ Select the Smart Office screen and then select the tab Device Status.

10 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ In the section Device.smartoffice.device_information make sure that the respective Smart Lighting  Controller operates “normal”.

  • The Smart Lighting Controller’s MAC address must correspond to the hardware id of the device entry.
  • The operational state of the entry must indicate that the device is working “normal”.
  • Remember the name of the respective device.

□ Change to the tab Device Configuration.

11 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ In the section Device.smartoffice.device_config select the corresponding device entry and click on the  button calibrate. The calibration process starts.

  • The Smart Lighting Controller slowly increases the power output to the connected LED panel. ∙ The LED panel correspondingly becomes gradually brighter until it reaches its maximum.
  • The Smart Lighting Controller determines the 100% brightness to the measured maximum power  output.

□ The LED panel is ready for use.

7.3.2 Calibration of a 2-Channel LEP Panel with Common Electrodes

2-channel LED panels need a Smart Lighting Controller for each channel to control both channels independently  (e.g. light temperature settings for cold or warm light).

Usually, 2-channel LED panels share a common electrode (i.e. anode or cathode), connected to the respective  Smart Lighting Controller and provided with a cable bridge between both controllers power output ports (see  Figure 15).

Common Cathode Common AnodeFigure 15: 2-Channel LED Panels with Common Electrodes

Common cathode

|

Cathode 1

---|---

Anode 1

|

Cathode 2

Anode 2

|

Common Anode

Cable bridge between SLC A/B (cathodes)

|

Cable bridge between SLC C/D (anodes)

Note:

Please refer to the LED panels’s manual to detect the correct cable colors for cathodes and anodes.

It is important to physically isolate both Smart Lighting Controllers during the calibration process by using the  cable bridge only after the particular calibration process is successfully finished.

Note:

When using a 2-channel LED panel with separate electrodes (i.e. one anode and one cathode for each channel),  calibrate both applied Smart Lighting Controllers independently as described above.

12 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

To calibrate a 2-channel LED panel connected to two paired Smart Lighting Controllers, proceed as follows: Using the Web Manager:

□ Start the web browser and enter the IP address of the G6 device containing the Smart Director. □ Log into the Web Manager with the administrator credentials.

□ Select the Smart Office screen and then select the tab Device Status.

□ In the section Device.smartoffice.device_information make sure that the respective Smart Lighting  Controllers operate “normal”.

  • The Smart Lighting Controllers’ MAC addresses must correspond to the hardware id of the devices’ entries.
  • The operational state of the entries must indicate that the devices are working “normal”. ∙ Remember the name of the respective devices.

13 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ Connect the LED panel’s cathode (1 or 6) to the Smart Lighting Controllers negative port (B-, D-). □ Connect the LED panel’s anode (2 or 7) to the Smart Lighting Controllers positive port (B+, D+).

Common Cathode Common AnodeFigure 17: Calibration of a 2-Channel LED Panel – Step 1

□ Change to the tab Device Configuration.

Figure 18: Web Manager – SmartOffice – Device Configuration – Calibrate

14 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ In the section Device.smartoffice.device_config select the corresponding device entry (Smart Lighting  Controllers B or D) and click on the button calibrate. The calibration process starts.

  • The Smart Lighting Controller slowly increases the power output to the connected LED panel.
  • The LED panel correspondingly becomes gradually brighter until it reaches its maximum.
  • The Smart Lighting Controller determines the 100% brightness to the measured maximum power  output.

□ Connect the LED panel’s cathode (1 or 5) to the Smart Lighting Controllers negative port (A-, C-). □ Connect the LED panel’s anode (3 or 7) to the Smart Lighting Controllers positive port (A+, C+).

Common Cathode Common Anode Figure 19: Calibration of a 2-Channel LED Panel – Step 2

□ Repeat the calibration process described above with the Smart Lighting Controllers A or C.

□ Connect the negative ports of Smart Lighting Controllers A and B with a cable bridge (4). □ Connect the positive ports of Smart Lighting Controllers C and D with a cable bridge (8).

Common Cathode Common AnodeFigure 20: Calibration of a 2-Channel LED Panel – Step 3

□ The LED panel is ready for use.

15 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

7.4 Functional Test of the Paired Smart Lighting Controller

After pairing the Smart Lighting Controller the Smart Director automatically generates the corresponding entries  for the device and its enabled sensors and actors as well. The following steps describe how to test the correct pairing of a Smart Lighting Controller via the Web Manager of the paired MICROSENS switch.

Note:

For this overview primarily the use of the Web Manager is shown. Using the CLI for pairing the devices is relatively  easy because the Web Manager uses the respective CLI commands as labels for fields and sections.

Using the Web Manager:

□ Select the SmartOffice screen and then select the tab Device Status.

  • In the section Device.smartoffice.device_information there should be listed an entry for the paired  Smart Lighting Controller with the device name previously assigned.

Figure 21: Web Manager – SmartOffice – Device Status – Smart Lighting Controller

16 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ Change to the tab Sensor Status.

  • In the section Device.smartoffice.sensor_list in the column device there should be listed the Smart  Lighting Controller with its assigned name.
  • In the column attribute there exists one row entry for every digital input port of the controller, named  by its assigned attribute. This corresponds to the attribute assignments “Din x attribute” defined in the  controller’s template configuration step (see above).
  • The column instance incrementally counts all input ports of the respective controller, beginning with  “1”. Depending on the prior attribute assignments the instance number can vary from the default  numbering order.

□ If any sensors are connected to the Smart Lighting Controller yet, both their last actual value and their  last response are shown in the status list. Scroll to the right to see those status table entries.

□ Change to the tab Actor Status.

17 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ With actors or sensors already connected to the Smart Lighting Controller it is possible to get or set  values from specific ports. Select the Controller screen and then select the tab SLC.

□ In the section Device.controller.smartlight_config scroll down to the rows read command and write  command.

E.g., to get the brightness value from a sensor connected to the input port enter the value “Brightness1” into the read command field and click on the button read command. After a short processing time the  Web Manager displays the received value. The number “1” in “Brightness1” is the instance indicator and  has to be entered.

E.g., to set the dim level of a connected LED panel to “100” enter the value “Dimlevel 100” into the write  command field and click on the button write command. After a short processing time the connected  LED panel lights up and the Web Manager displays a confirmation message.

7.5 Updating the Device’s Firmware

The Smart Lighting Controller has its own firmware that can be manually updated via the Web Manager of a  connected MICROSENS G6 switch. To update the firmware proceed as follows:

Using the Web Manager:

□ Start the web browser and enter the IP address of the respective G6 device.

□ Log into the Web Manager with the administrator credentials.

□ Select the Controller screen, then select the tab SLC and scroll down to the bottom of the dialogue.

18 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ In the section HTTP(s) upload via Web Manager open the browser’s file selection dialogue with a click  on the button “Browse”:

Figure 25: Web Manager – Controller – SLC – HTTP(s) Firmware Upload

□ In the file selection dialogue select the local firmware file and click the button Ok. □ Click on the button Start to begin the upload process to the G6 device.

∙ After successfully uploading the file it appears in the section available SLC firmware files on  device.

Note:

This list contains all available firmware files stored in the controller specific directory of the G6 device’s  memory. To remove this file click on the respective button remove.

19 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Using the Web Manager:

□ To update the controller’s firmware open the screen SmartOffice and change to the tab Device  Configuration.

Figure 26: Web Manager – SmartOffice – Device Configuration – Update Firmware

□ In the section Device.smartoffice.device_config scroll down to the respective controller.

□ In the field update firmware enter the name of the firmware file you want to load into the controller  and click on the button update firmware.

Note:

If the input field is left blank the latest firmware file is selected by default.

20 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

8 Configuring MQTT

The MICROSENS Smart Lighting Controller acts as MQTT client for sending and receiving MQTT messages from  and to an MQTT broker in the network, regarding the controller’s values. This is important if you want to use the  Smart Lighting Controller in automation projects with interaction between field devices.

8.1 Prerequisites

The controller always works with IPv6 Link Local Addresses. Therefore, the MQTT broker has to be enabled  working with IPv6 addresses. However, he can easily translate between IPv4 and IPv6 because of the architecture  of MQTT.

The MQTT protocol enables a very large range of different devices acting as broker, publisher and subscriber on  the OSI transport layer. The device communicates only via TCP port 1883 or – if adjusted – over Websockets on Port 9001 for external communications.

8.2 Using Smart Config Tool for MQTT Configuration

Note:

Use the MICROSENS Smart Config Tool for MQTT configuration of the Smart Lighting Controller. The application is  available for download via the MICROSENS web site (www.microsens.com). Therefore, navigate to the controller’s  product page, scroll down to the secure download area and login with your credentials. If you are not registered  yet, click on “Not registered?” to apply for login data.

To configure the MQTT settings as follows:

1. Start the Smart Config Tool.

Note:

This is a portable Microsoft® Windows® application that works without installation. For general  information about using the Smart Config Tool please refer to the application’s help function via the  button instructions on the upper right hand pane.

Note:

The Smart Config Tool version V0.5.0 or newer is required to manage a Smart Lighting Controller. 2. Hit the button Scan on the upper left hand pane.

Figure 27: Smart Config Tool – Start Page – Scan Result

21 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

A tree view list of all identified devices appears after the scan process is finished.

3. In the tree view select the device you want to configure and its configuration is shown automatically. If  the parameter should be updated, click on get for updating the values.

Note:

As the configuration of the device took place previously via the Web Manager GUI it is not necessary to  change parameters like device name or port names here. Should this be necessary anyway, bear in  mind to double-check those settings with the Smart Director settings (e.g. adapt scripts etc.).

Note:

Select the option load config from selected device from the drop-down list on the bottom left hand  pane to show all the device’s parameters immediately after selecting the device in the tree view.

4. Click on the button identify to cause the selected device’s port LEDs to blink, making sure this is the  device you want to configure within the following steps.

5. For configuring MQTT change to the tab MQTT.

Figure 28: Smart Config Tool – MQTT Parameters

The parameters have the following meaning:

  • Connection Status: Shows the connection status to the MQTT broker (read only).

o Disconnected: No active connection to an MQTT broker in the network.
o Accepted: The Smart Lighting Controller is connected to an MQTT broker.
o Timeout: The connection to the MQTT broker is closed due to a timeout.
o refused protocol: The MQTT broker refused the connection due to an invalid or unknown MQTT protocol  version.
o refused ID: The MQTT broker refused the connection due to an invalid client ID.
o refused server: The MQTT service is unavailable.
o refused authentication: The MQTT broker refused the connection due to invalid client credentials
o refused authorisation: The client does not have the appropriate access rights.
o unknown: The connection closed due to unknown reasons.
o connecting: The Smart Lighting Controller is connecting to the MQTT broker.
o paused: The connection is paused.

22 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

  • Client ID: The client ID that is built from a part of the MAC-Adress which is shown on the tab Device (read only).
  • Mode: Determines the MQTT mode (read/write).

o Disabled: MQTT disabled.
o QoS 0 (at most once):

– no guarantee for message delivery

– no acknowledgement of receiving the message by MQTT broker

– no storing or re-transmitting the message by MQTT publisher

– Packet ID automatically set to “0”

o QoS 1 (at least once):

– guarantee for delivering the message successfully at least one time to the broker

– storing and re-transmitting the message unless acknowledgement by the broker

– acknowledgement contains the unique packet ID only, so the publisher can assign message and  acknowledgement

o QoS 2 (exactly once):

– guarantee for delivering every message exactly one time to the broker

– publisher and broker using a four-part handshake for sending and acknowledgement

– acknowledgement messages between publisher and broker contain the packet ID only to assign  message and acknowledgements

∙ Broker: Sets the IPv6 address of the MQTT broker (read/write).

∙ Username: Username for MQTT broker access (read/write).

∙ Password: Password for MQTT broker access (write).

o As soon as valid parameters for broker IPv6 address, credentials and MQTT mode are set and the  broker is reachable, the MQTT broker connection status changes to “accepted”.

∙ Keepalive: Sets the interval in seconds within which the controller sends a message to its MQTT broker  (read/write) to announce itself as present. This prevents from being disconnected by the broker.

∙ Retain: This flag determines whether the broker will save this message as the last valid sample for this  specific topic. In case a new MQTT client subscribes for this topic the broker transmits this message to  the subscriber.

∙ Topic Prefix: The MQTT topics will always start with this string as identifier (read/write).

∙ Will Topic: This “last will topic” is sent to the MQTT broker on every first connection or on a parameter  change. The broker forwards it to subscribers in case the controller (as publisher) loses the connection to  the broker indicating the connection failure (read/write).

∙ Will Message: Sets the message for the last will topic in case of loss of connection (read/write). ∙ Will QoS: Sets the MQTT mode for the last will topic (read/write).

o Settings correspond to the MQTT mode settings above. It is recommended to use a higher QoS level  for last will topics.

∙ Will Retain: If set the broker saves the last will message to inform new subscribers about the controller  has lost its connection previously (read/write).

∙ Publish uptime: Sets the interval in seconds within which the controller sends its uptime to the broker  using the topic “/uptime” (read/write).

o Setting this parameter to “0” disables this function.

8.3 Using MQTT Topics with MICROSENS Switches

A topic can be understood as the category of a message. Topics are structured hierarchically (with a forward slash  as delimiter between levels), comparable to a file system structure (e.g. “Building/Floor1/Room1/CeilingLight”).

Topics are defined by the user, where a user friendly self-descriptive naming convention mirrors the Smart  Building infrastructure.

Topic names are case sensitive (“…/CeilingLight” differs from “…/ceilinglight”) and must contain at least one  character.

23 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide Commissioning the Smart Lighting Controller

Note:

It is possible to use every UTF-8 character (besides “$” since this character is used by the broker for internal  statistics).

The use of the following wildcards is possible:

∙ +: This character replaces a single level in a topic.

Example: “Building/Floor1/+/Temperature”

This topic addresses the “Temperature” related messages for all rooms on “Floor1”.

∙ #: This character replaces multiple levels in a topic.

Example: “Building/Floor1/#”

This topic addresses all occurring messages on “Floor1”.

Note:

The use of wildcards is allowed when using microScript to register topics.

It is not allowed using the MQTT mapping table and matching multiple topics to only one component is not  appropriate (e.g. matching a sensor to a topic containing multiple rooms).

For setting up topics or IDs more easily it is possible to use specific variables. The following variables with their  respective value are available:

  • {SMO}: fixed text “SmartOffice”
  • {MFG}: fixed manufacturer’s name (i.e. “MICROSENS”)
  • {MAC}: MAC address of the device (Device.factory.device_mac, e.g. “00:60:A7:09:37:4E”)
  • {IP4}: IPv4 address of this device (Device.ip.v4_status.dynamic_device_ip, e.g. “10.100.89.187”)
  • {IP6}: IPv6 address of this device (if enabled, Device.ip.v6_status.ip, e.g. “fe80::260:a7ff:fe09:374e/64”)
  • {DMN}: Domain name of the Smart Office network (Device.smartoffice.director_config.domain_name, e.g. “domain1”)
  • {ART}: article number of this device (Device.factory.article_number, e.g. “MS652119PM”)
  • {SER}: serial number of this device (Device.factory.serial_number, e.g. “00345860”)
  • {LOC}: SNMP SysLocation (Management.snmp.device_info.sys_location, e.g. “Office”)
  • {NAM}: SNMP SysName (Management.snmp.device_info.sys_name, e.g. “MICROSENS G6 Micro Switch”)

The variables can be combined e.g. in topics like “{SMO}/{MFG}_{MAC}/”.

Note:

These variables are limited to the use with MICROSENS G6 switches (e.g., for microScripts). They cannot be used  i.e. with MQTT topics of a Smart Lighting Controller.

24 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Quick Start Guide

Commissioning the

Smart Lighting Controller

Disclaimer

All information in this document is provided ‘as is’ and subject to change without notice.

MICROSENS GmbH & Co. KG disclaims any liability for the correctness, completeness or quality of the  information provided, fitness for a particular purpose or consecutive damage.

Any product names mentioned herein may be trademarks and/or registered trademarks of their respective  owners.

©2021 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany.

All rights reserved. This document in whole or in part may not be duplicated, reproduced, stored or  retransmitted without prior written permission of MICROSENS GmbH & Co. KG.

Document ID: QSG-EN-20013


25 MICROSENS GmbH & Co. KG, Kueferstr. 16, 59067 Hamm, Germany

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals