Functinal Devices RIBTWLB-7-BC Enclosed BACnet MS/TP Network Relay Device Instructions

June 5, 2024
Functinal Devices

Functinal Devices RIBTWLB-7-BC Enclosed BACnet MS/TP Network Relay Device

Functinal Devices RIBTWLB-7-BC Encl-

UL 864 Fan-Safety-Circuit Mode (Factory Default)

  • Operates as AND function. When binary inputs BI 1 – BI 6 are closed, Binary output relay BO 1 will close. Opening any of the 6 binary inputs (as in the case of an alarm condition) will open BO 1 again.
  •  Binary output relay BO 2 is bound to binary input BI 7 for applications involving a Fan Current Status contact. When BI 7 is closed, BO 2 will activate. BO 2 indicator will illuminate when BO 2 is active and BI 7 indicator will illuminate when BI 7 is closed.

Two Binary Outputs (2 SPDT relays + Override)

  •  Relay Rating, BO 1-1:
    3 Amp Max @ 24 Vac/dc

  •  Relay Rating, BO 1-2:
    10 Amp Resistive @ 30 Vdc
    10 Amp General Use @ 277 Vac
    1/2 HP @ 120/240 Vac

  •  Relay Rating, BO 2:
    20 Amp Resistive @ 277 Vac
    5 Amp @ 480 Vac
    20 Amp Ballast @ 277 Vac
    16 Amp Electronic Ballast @ 277 Vac 1 HP @ 120 Vac
    2 HP @ 277 Vac

Functinal Devices RIBTWLB-7-BC Encl- fig 1

  • Relay Override is selected via DIP switches.
  • Red LED is on when corresponding Relay is on.
  •  The BO1 and BO2 DIP switch override status can read by way of Proprietary Properties DIP_SWBO1 and DIP SW_BO2 (No. 277005) in BO1 and BO2.
  •  The Priority level of the DIP switch function can be set by way of Proprietary Properties DIP_SW_Priority_BO1 and DIP_SW_Priority_BO2 (No. 277004) in BO1 and BO2.

Seven Binary Inputs (Dry Contact, Class 2)

Functinal Devices RIBTWLB-7-BC Encl- fig 4 Binary inputs can be N/C (default) or N/O depending on the Polarity setting in the respective BI object.

Open is alarm condition for N/C.

Binary Input Override

  •  Binary inputs can be overridden with BI Override DIP switches on board.
  •  Overriding binary inputs for Fan-Safety-Circuit mode only.

Binary Input Latch

  • Binary inputs can be latched with Latch-Select DIP switches on board.
  •  Latched binary inputs will stay in alarm condition once triggered until input is reset.
  •  Latch can be reset by local pushbutton, power cycle, or by setting Present_Value True (1) in Binary Value BV1 (automatically returns to 0 in preparation for future resets.)
  •  Present Latch-Select DIP switch settings for specific binary inputs can be read by way of Proprietary Property Latch_Enabled (No. 277008) in respective BI object.
  • Latched status (if input is presently latched or not) of specific binary inputs can be read by way of Proprietary Property Input_Latched (No. 277009) in respective BI object.
  • Latching Binary Inputs for Fan-Safety-Circuit mode only.

24 Vac/dc Power Input

  •  Connect to terminal pair 24Vac/dc Input
  •  When connecting 24Vac to both the RIB(s) and a halfwave device, damage to device can occur.

Option 1: Use seperate transformer for each device, or an isolated 24Vdc power supply.

Option 2: Add diode between devices, see diagram.

Functinal Devices RIBTWLB-7-BC Encl- fig 5

BACnet® MS/TP Network

  • Optional End of Line Resistor (EOL) Included.
  •  Basic Data
    • Network Media: Twisted Pair 22-24AWG, shielded recommended
    • Terminations: Functional Devices product installed at both ends of the MS/TP network – Use 120 Ω end of line resistors. All other cases – Follow instructions from the device installed at the end of the MS/TP network.
    • Polarity: Network is polarity sensitive
    • Baud Rate: 9600, 19200, 38400, 57600, 76800, 115200 (DIP Switch Selectable)

Functinal Devices RIBTWLB-7-BC Encl- fig 6

  •  MS/TP Addressing, Baud Rate, and ID
    • MS/TP Address & Baud Rate must be set prior to power up via DIP switches.
    • Device ID will default to 277XXX where XXX is the MS/TP Address.
    • Examples: MS/TP Address – 004 Device ID – 277004 MS/TP Address – 121 Device ID – 277121
    • Device ID can be changed via network command. Once changed, it will no longer default to 277XXX. (Each MS/TP Address & Device ID must be unique.)
    • Device Instance is changed via Object-Identifier Property of the Device Object

  • 0 = Open ; 1 = Closed
    All other combinations = 9600 Baud

Address selected via DIP Sw 1 – 7 , see Bulletin B2028

Additional Features

  • BI 7 and BO 2 Binding Settings
    • Binary input BI 7 can be unbound from binary out relay BO 2 by way of Proprietary Property Bind_BI7 ( No. 277006) in BO2.
    • Priority level of the Bind function can be set by way of Proprietary Property Bind_BI7_Priority (No. 277007) in BO 2.

  • I/O Board Mode
    • I/O Board mode can be enabled temporarily for troubleshooting purposes by way of Proprietary Property AND_Function_Enable (No. 277001).
    • Operates as a logic board with 7 binary inputs and 2 binary output relays. Allows user to test individual inputs and outputs.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals