Chiltrix CXRC1 Radiant Cooling Controller
Radiant cooling is the most efficient and comfortable method of cooling
available for users is a dry or moderate climate and be highly beneficial even
in humid climates. However, if a radiant surface is operated below the dew
point, unwanted condensation will be produced. A fast acting radiant cooling
controller designed to prevent this, such as CXRC1, is required. The CXRC1 is
designed to be added to any existing radiant heating controller to enable the
additional function of radiant cooling. The existing radiant controller will
need to have thermostat(s) that are capable of calling for cooling. These can
be added to nearly any controller.
Below is a logical topology of the CXRC1 radiant cooling
controller:
Theory of Operation
The CXRC1 monitors the indoor dew point and compares it to the water
temperature entering the supply manifold. There is a cross-connect between the
supply and return lines, and a motorized 3-way mixing valve that can mix water
returning from the radiant system back into the supply, before entering the
supply manifold, to quickly raise the temperature as needed to adjust the
water temperature so that it will be above the dew point or above a pre-set
delta to the dew point. This helps ensure that water entering the radiant
system is at a temperature that will not produce condensation.
Application Notes:
The CXRC1 is not a radiant controller, it is an add-on to most any Brand or
model standard radiant controller, to allow you to operate a radiant heating
system In a cooling mode without condensation issues.
BEFORE ORDERING OR INSTALLING THE CXRC1, PLEASE CONSULT WITH CHILTRIX
TECHNICAL SUPPORT DEPT. TO VERIFY THAT YOUR RADIANT CONTROLLER IS COMPATIBLE.
YOU WILL NEED TO PROVIDE THE MAKE AND MODEL, AND A PDF MANUAL OR A LINK TO THE
MANUAL ONLINE FOR YOUR RADIANT CONTROLLER.
- The radiant controller will need to have one or more thermostats that have the capability of cooling function. You may need to replace or add to your current thermostats.
- This radiant cooling controller is designed to monitor indoor dew points and adjust the temperature of the water (or water/glycol) entering the radiant system such that the radiant surfaces do not drop below the dew point. This can prevent condensation (accidental dehumidification) which could cause water damage or inconvenience.
- The system is ordered as follows: CXRC1-4 has 4x RJ45 Ethernet ports, can connect to one to four dew point sensors. CXRC1-8 has 8x RJ45 Ethernet ports, can connect to one to eight dew point sensors. DPX1 Dew Point Sensors are ordered separately.
- All dew point sensors connect to the CXRC1 via CAT6 cable (supplied by installer). Up to 150 ft. cabling distance is allowed per sensor.
- ASHRAE requires an indoor humidity </= 60% RH to prevent EMC, corrosion, or mold. In some climates, you will need a dehumidifier to ensure this. A radiant cooling system cannot and will not dehumidify.
Installation Overview
- READ THIS MANUAL IN IT’S ENTIRETY BEFORE PROCEEDING.
- Verify the thermostats used with the existing radiant heating controller are capable of a cooling setting. If not, augment or replace the thermostats. Consult with the radiant cooling controller manual to see how to connect any new or additional thermostat or call Chiltrix technical support for assistance. Radiant cooling control can be configured to work with nearly all radiant controllers.
- Install sensor well and PT100 sensor fitting.
- Install the controller CXRC1.
- Install supply-return cross-connect and proportional mixing valve.
- Install dew point sensors, run cabling, and connect CAT6 cables to all dew point sensors to the controller according to this manual.
- Connect all wiring according to this manual.
- Determine and install optional customer-provided alarm output device.
- Configure the controller according to the Chiltrix radiant calculators particularly using the “Surface temperature” tab.
- Test system operation.
Installation of fittings
When installing any fittings, make sure that you use some type of sealant on all threads. Regular Teflon tape will work fine for sealant. The included sensor fitting is 1 ¼ “ FNPT, you can adapt to this as needed for your PEX or copper fittings. The fittings on the included 3 way valve are 1” FNPT. Above is an image of the sensor fitting, a Tee-adapter from 1 ¼” to the ½”. This size fitting is used to create a near-0 pressure drop sensor fitting for the PT100 sensor.
A properly installed PT100 sensor assembly
Three-way mixing valve
Installation of Mixing Valve
When installing the 3 way valve please use Teflon tape on the fitting ports
to prevent any water leakage. The 3 way valve must be installed with the white
actuator on top as shown below. Secure the valve to a mounting board if it is
directly connected to PEX tubing on all ends. The orientation of the position
of the valve (0 to 1) at time of install does not matter, it will be addressed
later in the manual.
Above, valve supported by copper pipe on 2 sides
IMPORTANT NOTE
The mixing valve, cross-connect piping, and PT100, MUST all be on the manifold
supply line and MUST be “upstream” of the pump(s) as shown in the various
diagrams of this manual.
Example Piping Diagram
Mounting of the Controller and Dew Point Sensors
Mount the controller in an interior location near the mixing valve and PT100
temperature sensor fitting, and away from any exposure to water or dirt.
Mounting tabs are located on the control box on each side. This location may
be near the buffer tank, or near the manifolds.
NOTE: neither the controller or dew point sensors are waterproof. It’s
also recommended to consider access to a wall outlet (110-120vac). The
controller is powered by a 110-120 wall outlet plug.
Sensors
Mount each sensor in each area where you wish to monitor the dew point. The
sensors have mounting tabs on each side just like the control box. The wire
connector can go in two different ways. First method is to drill a hole in the
wall and slide the connector through the back of the sensor box, it is an
oval-shaped hole. The short end of the housing “vents” can also be pushed out
with your fingers to run the sensor wire through if you wanted to mount the
sensor on the celling or alongside a wall. Note these vents are designed to
“break away” so they are relatively fragile. Be careful and don’t break them
by accident.
Dew Point Sensors CAT6 Sensor Cabling
Sensor cabling is an installer-provided item. After determining the sensor
locations you will need to measure the length you need and then order or make
cable of the correct length with RJ45 connectors in order to connect the
sensors to the controller. You can have up to 4/8 sensors connected to the
controller according to which model was ordered, you can use as few as one
sensor according to your needs.
USE CAT6 CABLE
Location, Location, location – where to put the dew point sensors? So here we
may hear a lot about classical physics and the ideal gas laws, in particular,
Avogadro’s Law and Fick’s Laws of Diffusion. Without going deeper into this,
these laws tell us that 1) humidity seeks equilibrium and does not need the
actual movement of in order to equalize across an area, and 2) that, as
counterintuitive as it may seem, a volume of air is lighter when it has higher
humidity and therefore rises. Don’t worry about which law wins. In a cooler
part of an enclosed space, RH will be higher because the air can hold less
moisture, in a warmer area the air can hold more water, so the RH is lower.
Neither have anything to do with the dew point unless the actual (absolute)
humidity changes. Don’t worry about it or let the experts confuse you. Just
locate the dew point sensors in the area served by the radiant cooling
surface, and generally as near as practical to the surface that you are
protecting from a dew point issue. We are only concerned about the dew point
and not RH in this regard.
For most users, one or two dew point sensors, more or less central to the
area, based on common sense, per floor, is all that’s needed. If you use
radiant from the ceiling you can put the sensors higher on the wall, for floor
radiant it really does not matter. One note –if you have a persistent source
of new absolute humidity, like a leaky pipe, fix it. Another note – if you
have a high cathedral-type ceiling, this is a good location to pull in air for
your dehumidifier, Location, Location, location – where to put the dew point
sensors? So here we may hear a lot about classical physics and the ideal gas
laws, in particular, Avogadro’s Law and Fick’s Laws of Diffusion. Without
going deeper into this, these laws tell us that 1) humidity seeks equilibrium
and does not need the actual movement of in order to equalize across an area,
and 2) that, as counterintuitive as it may seem, a volume of air is lighter
when it has a higher humidity and therefore rises. Don’t worry about which law
wins. In a cooler part of an enclosed space, RH will be higher because the air
can hold less moisture, in a warmer area the air can hold more water, so the
RH is lower. Neither have anything to do with the dew point unless the actual
(absolute) humidity changes.
Don’t worry about it or let the experts confuse you. Just locate the dew point
sensors in the area served by the radiant cooling surface, and generally as
near as practical to the surface that you are protecting from a dew point
issue. We are only concerned about the dew point and not RH in this regard.
For most users, one or two dew point sensors, more or less central to the
area, based on common sense, per floor, is all that’s needed. If you use
radiant from the ceiling you can put the sensors higher on the wall, for floor
radiant it really does not matter. One note –if you have a persistent source
of new absolute humidity, like a leaky pipe, fix it. Another note – if you
have a high cathedral-type ceiling, this is a good location to pull in air for
your dehumidifier,The controller has firmware to read the sensors and control
the valve position, the end-user will need to set a temperature dew point
offset. This temperature may the set by the user to automatically track the
dew point, or may be set to operate at some delta above or below the dew
point.
Note: In many cases the water temperature can be safely set below the dew
point. See the section on temperature selection. Ex: If you set the controller
at “+2F” the controller will operate with a target temperature to the supply
manifold as “dew point plus 2 degrees Fahrenheit”. The controller will cycle
between two different menus as shown below.
CXRC1 Controller Operation Cont’d
In order to change any settings on the controller you will need to hold down
the menu button for about 5-10 seconds in order to enter into the main menu.
Once in the main menu, you can select “Dew Pt Offset”, this setting is the
offset to which the controller will target the output water temp based on the
highest dew point read (the highest reading of any individual
sensor).
The dew point offset is a target in relationship to the dew point. Example: if the offset is +4F and the highest dew point read from the sensors is 54F then the controller will target an output temp of 58F. If the setting is -4F and the sensors are reporting a dew point of 54F then the target would be 50F. The Dew Pt Offset is configurable to target an output water temp below the dew point in cases where you have a sealed system and a known R value between the surface of the water and the surface that is in contact with the rooms air temperature. See temperature selection section.
Condensation Safety Precautions:
It is recommended that the CXRC1 be powered from the same circuit as the
pump(s) such that any power or circuit breaker problem that stops power to the
CXRC also disables the circulator pump(s).
Alarm Output
The CXRC1 has a low-amp (.2a) 5v alarm output that can be used signal an error
or loss of communication with dew point sensors. It is recommended that this
be connected to a small solid state relay that can be set up to trigger a
warning signal such as a bell or other alarm to let you know of any failed
sensor. If the mixing valve fails to receive communications from the
controller but still has power, the mixing valve will move to full-
recirculation as a safety precaution.
Testing & Troubleshooting
Testing:
Run the system and pay close attention to the radiant surface temperatures and
dew point (see next page diagram) where unwanted condensation may occur and
look for any condensation. There should be no wetness at all. Temperatures
should agree with your projections within 1-2 degrees F, adjust as needed.
Monitor this closely at various temperatures and conditions after initial
startup, until you are sure your settings are sufficient.
Problem: Valve does not operate upon start up
Solution: Make sure your power wires are plugged in, if the controller LCD is
not lit up then the valve does not have power. Upon start up the valve will
start at full recirculation and then it will begin to modulate.
Problem: Valve is moving too much, too fast, too far, etc. Solution: This is
not exactly as it appears. This valve uses a gear reduction motor so the valve
manual positioner that you can see may appear to move a very large amount,
note that even an apparent full turn of the valve is only a small change to
the actual amount of in mixing/non-mixing adjustment applied.
Problem: I am getting unexpected condensation
Solution: Check your calculations for error, or there may be an error in your
R-value assumptions. If this cannot be corrected with adjustments on your own,
please contact Chiltrix technical support (advanced support dept.).In any case
where there is uninsulated or exposed piping at any point where condensation
would be a problem, we suggest a setting of dew point +2F. Likewise, if the
thermal sandwich is not vapor tight and properly insulated, use dew point +2.
We suggest to properly insulate and use vapor tight taping or barrier to allow
a lower offset to dew point and therefore higher capacity. If all piping is
insulated, and the back side of the “thermal sandwich” is also insulated well
and vapor tight, a target below the dew point can be used to gain more cooling
capacity. The “thermal sandwich” refers to the radiant surface, and to what is
behind it. An example below shows a typical thermal sandwich on a ceiling. The
same logic is to be applied for floor or wall use.
In the above example, assuming the piping and all insulation is vapor tight
and has an R-value of at least as high as the sandwich section marked “drywall
or wood”, the only surface where condensation risk is presented is the drywall
or wood surface (the “radiant surface”. The temperature target offset of the
CXRC1 will be based on this surface and therefore the water temperature target
can be lower than the dew point. You can use our surface temperature
calculator to estimate a safe offset. See the calculators page. Any questions
or uncertainty can be resolved by contacting Chiltrix Advanced Support
(Engineering Department).Please continue reading for an explanation of how to
use the calculators. About these calculators – in spite of the fact that most
radiant systems are designed and configured based on rule-of-thumb or
experience, there are laws of physics that can and should be used for proper
design and configuration of any radiant system, for heating or cooling. Beyond
just physics in fact, in is mostly related to quantum mechanics. To spare our
partners and customers the burden of learning how to use Plancks constant,
Kirchhoff’s laws, Wien’s law, the Stefan-Boltzmann Law, Newtons Law of
Cooling, Fourier’s law, and others, we have created some basic calculators.
On the calculator page you will see there are four tabs across the top as
follows: Radiant, Surface Temp, Convert K to R, and Dew Point.
The Radiant Tab:
This calculator allows you to see the net radiant heating or cooling that can
be obtained from a square meter or square foot of a radiant surface based on
its temperature and the temperature of its local environment (i.e. the
temperature of the “things” in the room to be conditioned – walls, furniture,
floor, ceiling, people, etc. You will note there are two sections, in the top
section you will input the following:
- Radiant Cooling (and Heating) Calculators (cont’d)Find The Best Temperature Offset For Maximum Capacity
- The next input of the Radiant calculator is the temperature. Note this is not the water temperature, rather it refers to the temperature of the radiant surface which we will get to in a moment.
- The next input is the area, please leave this as-is at 1 M^2 (the output will be converted for BTU per Ft.^2 automatically later on)
- In the next section, you can also input the average emissivity for a collection of normal things found in a room – wood, stone, plastic, fabrics, painted surfaces, etc. This can be left at the default value of .91 unless you have reason to change it.
- And in this section, you can input the average temperate of these “things” in the conditioned space. Generally for a radiant heating calculation you would use 65-68F. For cooling, we suggest 76-78F. Note that when using radiant, many users find that an indoor winter air temperature of around 64-65F is quite comfortable, due to the nature of radiant heating. Likewise with radiant cooling, user are often comfortable at 80F and report that it feels more like 75F.
- At the bottom, you will find the net output. So how to define the radiant panel temperature? It will not be the same as the operating water temperature. Go to the Surface Temp tab.
The Surface Temp Tab:
This is a handy way to estimate the surface temperature when you know the
water temperature, and the R-value of what is between the water (PEX tube) and
the radiant surface, and the air temperature of the room.
For “radiant temp” input a water temperature. You can play with some worst
case scenarios, maybe from 45-65F. For air temp, you can also play with some
worst case scenarios, maybe 70-90F. For entering an R-value, this is where
things get tricky. So in the thermal sandwich there may be multiple different
types of materials. And many materials do not have a published R-value. But
don’t worry, there is a solution on the next page. Once you have the R values
(see next page for info on K to R conversion) along with the water temp and
the air temp, you will be able to calculate the estimated surface
temperature.
Radiant Cooling (and Heating) Calculators (cont’d) Find The Best Temperature Offset For Maximum Capacity
The Convert K to R Tab:
As mentioned, many materials will not have a published R-value that is easy to find. But nearly every material will have a published K value if you look for it. K value is essentially the inverse of an R value measured in W/m^2/K. Don’t worry about what all of that means. Just find your K values online, here is a good example of where to find many material K values: https://www.engineeringtoolbox.com/thermal-conductivity-d_429.htmlOr here https://www.researchgate.net/publication/336875733_DESIGNING_A_GUID ELINE_FOR_GREEN_ROOF_SYSTEM_IN_MALAYSIA There are many online resources that list nearly every possible material, use a search engine if needed. Note, sometimes you may find K-values expressed as mW/cm^2/K. If so, convert the values to W/m^2/K before using the calculator.
The Dew Point Calculator Tab This one seems self- explanatory.
If you are in a higher humidity climate, you may not be a good candidate for
100% radiant cooling. But even then, radiant cooling can be used along with a
properly sized dehumidifier to provide up to 100% of your cooling, or, for
augmentation. Radiant cooling is excellent for the augmentation of a normal
air conditioning system to increase indoor air quality, allow for higher
volumes of outside ventilation air, be more comfortable, save energy costs, or
cool a stubborn area. In the case of augmentation, you may for example be able
to do half of your cooling at an efficiency rate 3x higher than your
conventional cooling system. That comes out to a 17% net energy savings.
Radiant Augmentation can allow expanded design and architectural flexibility.
For example, if you will have a room with a lot of south facing glass, the
floor itself can become a source of radiant heat that will seemingly defeat a
conventional air conditioning system. The thermostat says the temperature is
OK, but it still feels hot? That’s one of the usually desirable effects of
radiant heat, that in this case, when it interferes with cooling, it is not
desirable. One option for this case is to use radiant floor cooling in that
area, to zero-out the radiant heating effects of the floor that result from
sun and window glass.
Contact us with any questions.