MELTEM M-WRG-II DVU-E Decentral ventilation with heat recovery Installation Guide

June 5, 2024
MELTEM

M-WRG-II DVU-E Decentral ventilation with heat recovery
Installation Guide
744100, 06/2022 

Installation Manual for Universal Design Valves

M-WRG-II DVU-E-…, M-WRG-II DVU-R-… Fitting the valve body

  • Before installing the design valve, pull the glass front plate (item 1 in Fig. 4) away from the valve body (item 2 in Fig. 4).

The design valve can be used as a supply air or exhaust air valve and may be used directly in a DN 100 ventilation pipe.

  • To do this, press the valve body (item 1 in Fig. 1) into the ventilation pipe (item 2 in Fig. 1), turning it clockwise slightly at the same time.

Removing the valve body

  • Pull the valve body (item 1 in Fig. 2) out of the ventilation pipe (item 2 in Fig. 2), turning it clockwise slightly at the same time.

Fitting and removing the glass front plate
We recommend that you measure the air volume flow rate with the glass front plate fitted.

  • To do this, unscrew the wing nut (item 1 in Fig. 3) slightly.
  • Now press the glass front plate (item 1 in Fig. 4) with the springs into the valve cone (item 4 in Fig. 4) until you hear it click into place.
  • To remove, simply pull the glass front plate away from the valve cone (see Fig. 4).

Regulating the air flow

  • Turn the glass front plate (item 1 in Fig. 4) anti-clockwise to increase the air volume flow rate.
  • Turn the glass front plate (item 1 in Fig. 4) clockwise to reduce the volume flow rate.

We recommend that you use a suitable measuring device (capture hood) to measure the air volume flow rate.

  • After adjusting precisely, remove the glass front plate and fix the valve cone in this position using the wing nut (item 1 in Fig. 3).
  • Then refit the glass front plate by pressing it back into the valve cone (see Fig. 4).

Minimum distance between design valves and the wall and ceiling
— Minimum distance (A) for design valve with square front plate: 150 mm (see Fig. 5)
— Minimum distance (A) for design valve with round front plate: 130 mm (see Fig. 6)
NOTE
Increase these distances if possible if the design valve is to be used as a supply air valve (acoustics).
All information in these instructions is supplied without guarantee. Subject to technical modifications and misprints.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals