Grid-Tied PV Inverter GW5000-MS-US30 Series Grid Tied Inverter Single Phase Installation Guide

June 1, 2024
Grid-Tied PV Inverter

Grid-Tied-PV-Inverter-LOGO

Grid-Tied PV Inverter GW5000-MS-US30 Series Grid Tied Inverter Single

Phase

Quick Installation Guide
Grid-Tied PV Inverter
MS Series
(GW5000-MS-US30 | GW6000-MS-US30 | GW7600-MS-US30 |GW7700-MS-US30| GW9600-MS- US30 | GW11K4-MS-US30)
V1.4-2023-11-30

Safety Precautions

General Disclaimer

  • The information in this quick installation guide is subject to change due to product updates or other reasons. This guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All descriptions here are for guidance only.
  • Before installations, read through the quick installation guide. For additional information, please see the user manual.
  • All operations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations.
  • Check the deliverables for correct model, complete contents, and intact appearance. Contact the manufacturer if any damage is found or any component is missing.
  • Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear anti-static gloves, clothes, and wrist strip when touching electronic components to protect the inverter from damage. The manufacturer shall not be liable for any damage caused by static electricity.
  • Strictly follow the installation, operation, and configuration instructions in this guide and user manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://en.goodwe.com/warranty.

Safety Disclaimer

Warning

DC Side:

  1. Ensure the component frames and the bracket system are securely grounded.
  2. Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for equipment damage if other connectors are used.
  3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may cause poor contacts or high impedances, and damage the inverter.
  4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and extremely high voltage.
  5. The PV modules used with the inverter must have an IEC61730 class A rating.

AC Side:

  1. The voltage and frequency at the connecting point should meet the on-grid requirements.
  2. Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the maximum AC output current.
  3. Make sure that all the groundings are tightly connected. When there are multiple inverters,make sure that all the grounding points on the enclosures are equipotential bonding.
  4. You are recommended to use copper cables as AC output cables. If you prefer aluminum cables, remember to use copper to aluminum adapter terminals.

Product:

  1. Do not apply mechanical load to the terminals, otherwise the terminals can be damaged.
  2. All labels and warning marks should be visible after the installation. Do not scrawl, damage, or cover any label on the device.
  3. Unauthorized dismantling or modification may damage the equipment, the damage is not covered under the warranty.
  4. Install the inverter away from high magnetic field to avoid electromagnetic interference. If there is any radio or wireless communication equipment below 30MHz near the inverter, you have to:
    • Install the inverter at least 30m(98.43ft) far away from the wireless equipment.
    • Add a low pass EMI filter or a multi winding ferrite core to the DC input cable or AC output cable of the inverter.
  5. Warning labels on the inverter are as follows.

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(1\)

Check before Power-on

No. Check Item
1 The product is firmly installed at a clean place that is well-ventilated

and easy-to-

operate.

2| The PE, DC input, AC output, and communication cables are connected correctly and

securely.

3| Cable ties are intact, routed properly and evenly.
4| Unused ports and terminals are sealed.
5| The voltage and frequency at the connection point meet the inverter grid connection requirements.

LED Indicators

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(2\)

Product Introductions

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(3\)

  1. DC Switch
  2. Button For Ezlink Reset[1]
  3. Wiring Conduit Hole
  4. WiFi Module Port[1]
  5. WiFi / BT Antenna Terminal[1]
  6. 4G Antenna Terminal[1]
  7. LED
  8. Mounting Bracket
  9. Heat Sink
  10. Mounting Plate [1]: Optional.

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(4\)

Dimensions

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(5\)

Inverter Installation

Packing List

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(6\)

Space Requirements

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(7\)

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(8\)

Angle Requirements

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(9\)

Installing the Inverter

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(10\)

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(11\)

Electrical Connection

Removing the Cover

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(12\)

Cable Specifications

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(13\)

No.| Terminal/Port| Silkscreen| Recommended Cable Specifications
---|---|---|---

1

|

PV input terminal

Dry conta t

| PV1+ PV1-

PV2+ PV2-

|

90℃(194°F) copper cables, 12AWG.

PGVW37+70P0V-3M- S(O-UnSly30fo, r
GW1610K04–MS–US30)
2| cteormmminual ication| DRY-OUT CT2| –
3| CT communication

terminal

| CT1| –

Outdoors communication cables that meet

4| Remote Shutdown communication terminal| DRM0| UreLq2u9i1re9m, CeMn/tCs,M2G4-(1N6EACWtGyp. e), or CMH(CSA type)
5| Power supply terminal for RSD module| RSD-12V| OUr Lu2td9o19o,rsCcMo/mCs,MmGu(nNiEcaCttioynpec)a, bolreCsMthHa(tCmSAeetyt pe)

Oequirement 24-16AWG. cables that meet

utdoors communication

6| Meter

communication

terminal

| METER| UreLq2u9i1re9m, CeMn/tCs,M2G4-(1N6EACWtGyp. e), or CMH(CSA type)
7| Communication terminal for multi inverter parallel connection| 485-12| OUr Lu2td9o19o,rsCcMo/mCs,MmGu(nNiEcaCttioynpec)a, bolreCsMthHa(tCmSAeetyt pe) equirement 24-16AWG.
8| USB port| USB

GRID-L1

| –
9| AC cable terminal| GRLD-N| 90℃(194°F) copper cables, 6AWG.
GRID-L2

10| Grouding busbar| –| 90℃(194°F) copper cables, 10-6AWG.

DC Cable

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(14\)

AC Cable

PE terminals need to be provided by customer, and the reference specifications are as follows:

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(15\)

Communication Connection

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(16\)

PIN Function Definition
1

Remote shutdown

| COM/DRM0
2| REFGEN
3|

power supply for RSD module

| 12V-AC_SPS
4| RSD-12V
5|

Meter

| Meter+
6| Meter-
7| 12V+
8| GND
9|

parallel connection

| RS485-A
10| RS485-B
11| RS485-A
12| RS485-B

WARNING

  • The communication terminal connected to the power supply port of the RSD switch is equipped with a resistor. When using the RSD function, the resistor needs to be removed and properly stored.
  • Do not remove the resistor when the RSD function is not required. Otherwise, the inverter may fail to connect to the power grid.

The cables for remote shutdown, smart meter, parallel connection, and power supply for RSD module are connected in the same way. The following illustration shows an example of connecting smart meter communication cable.

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(17\)

Antenna(Optional)

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(18\)

Power On and Off

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(19\)

Commissioning

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(20\)For more detailed instructions, scan the QR codes below.

Grid-Tied-PV-Inverter-GW5000-MS-US30-Series-Grid-Tied-Inverter-Single-Phase-
FIG- \(21\)

GoodWe Technologies Co., Ltd.

No. 90 Zijin Rd., New District, Suzhou, 215011, China
www.goodwe.com
[email protected]