PRODUCT

Product Information

  • Specifications
    • Model: SIBER HRV/ERV
    • Double Flow Controlled Mechanical Ventilation Unit
    • Thermal Energy Recovery with up to 95% efficiency
    • Maximum ventilation capacity: 150 m3/h (SIBER EVO 1) / 200 m3/h (SIBER EVO 2)
    • Low energy consumption fans

Product Usage Instructions

  • Delivery
    • Before starting the installation, ensure that the delivery is complete and intact. The delivery contents should include:
    • MVHR unit with Thermal Energy Recovery (SIBER HRV EVO 1/2 or SIBER ERV EVO 1/2)
  • Installation Manual
    • Eco-design label
  • Installation guides
    • Bag with silent blocks and screws
  • Application
    • The SIBER EVO 1/2 is designed for controlled mechanical ventilation with thermal energy recovery. It offers high efficiency and maximum ventilation capacities of 150 m3/h for the SIBER EVO 1 and 200 m3/h for the SIBER EVO 2.
  • Model
    • The unit comes with technical specifications, characteristic curves, connections, dimensions, and an exploded view for reference.
  • Operation
    • The unit features descriptions of operation, bypass conditions, and anti-ice security measures.
  • Installation
    • General guidelines, unit positioning, and ceiling and wall mounting instructions are provided for proper installation.
  • Nozzle Orientation
    • Instructions on how to orient the nozzles for optimal performance.
  • Connection of the Condensate Drain
    • Guidance on connecting the condensate drain correctly.
  • Change of Filters
    • Steps to follow for changing the filters in the unit.
  • Electrical Connection
    • Details on mains connection for electrical supply.
  • Monitor Your Home – Probes / Wireless Controls
    • Information on monitoring your home using probes and wireless controls.
  • Smart Connectivity
    • Features related to Modbus RS485, KNX EVO Connect, and Ethernet bridge connectivity.
  • Maintenance
    • Maintenance instructions for filter maintenance and heat exchange maintenance.

FAQs

  • Q: Can children operate the unit?
    • A: The use of the unit is not authorized for persons, including minors, with reduced intellectual or physical capacities unless supervised by a responsible person.
  • Q: What accessories are available for the SIBER EVO?
    • A: Optional accessories include various filters, wireless controls, sensors, and communication gateways for smart monitoring.

DELIVERY

CONTENTS OF THE DELIVERY

Before starting the installation of the Dual Flow VMC Unit with Thermal Energy Recovery, you should check whether it has been delivered complete and intact.

The delivery content of the VMC SIBER EVO 1/2 unit consists of the following items:

  1. MVHR unit with Thermal Energy Recovery SIBER HRV EVO 1/2 or SIBER ERV EVO 1/2
  2. Installation Manual
  3. Eco-design label
  4. Installation guides
  5. Bag with silent-blocks and screwsSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(1\)

Unit supplied without regulating control

  • If the Unit has been delivered with any visible defects, such as dents or scratches, or if all the items and accessories listed above are not included, please contact your supplier.
  • The use of this Unit is not authorised for persons, including minors, with reduced intellectual capacities, limited physical capacities, or lack of experience and necessary knowledge, unless they are under the supervision of, or have been instructed by a person responsible for their safety, in the use of the Unit.
  • In any case, children should be monitored to ensure that they do not play with the Unit

OPTIONAL ACCESSORIES FOR SIBER EVO

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(2\)

APPLICATION

The SIBER EVO 1/2 is a Double Flow Controlled Mechanical Ventilation Unit with a Thermal Energy Recovery Unit with an efficiency of up to 95%, a maximum ventilation capacity of 150 m3/h for the SIBER EVO 1 and a maximum capacity of 200 m3/h for the SIBER EVO 2; with low energy consumption fans for both units.
Characteristics of the SIBER EVO 1/2 unit:

  • 600W preheater at the fresh air intake that raises the temperature up to 10ºC.
  • Continuous regulation of air flows by means of the control panel.
  • Presence of a filter status indicator on the Unit and the possibility of filter status indication on the position selector.
  • New smart anti-icing regulation ensures that the unit continues to operate optimally even at low temperatures. If necessary, switch on the pre-heating (included).
  • Low noise level.
  • Equipped as standard with a by-pass valve with automatic operation.
  • Constant flow regulation.
  • Energy saving.
  • High Performance.

The SIBER EVO 1/2 is available in 4 versions:

  • SIBER HRV EVO 1
  • SIBER HRV EVO 2
  • SIBER ERV EVO 1
  • SIBER ERV EVO 2

These installation instructions apply to both the SIBER HRV EVO 1/2 and the SIBER ERV EVO 1/2. The SIBER EVO 1/2 units can be wall or ceiling mounted, with the standard fixing brackets included. For the correct position of the duct connections and their dimensions.

Important! For the correct efficiency of the ventilation system, it is recommended not to disconnect the unit, except for maintenance

PREHEATER
The preheater protects the heat exchanger in the ventilation unit during the cold season.

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(3\)

MODEL

TECHNICAL SPECIFICATIONS

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(4\) Siber-EVO-1-2
-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(5\)

CHARACTERISTIC CURVES

SIBER® HRV EVO 1 & ERV EVOSiber-EVO-1-2-Passive-House-certified-Heat-
Recovery-Ventilation-unit-FIG-1 \(6\)

Working points AIRFLOW (m3/h) PRESSURE (Pa) POWER (W) SFP (W/l/s)
1 50 25 9.24 0.67
2 75 50 15.37 0.74
3 100 50 20.55 0.74
4 100 75 24.52 0.88
5 100 100 28.87 1.04
6 100 150 37.62 1.35
7 125 100 37.13 1.07
8 125 150 46.07 1.33
9 150 100 48.14 1.16
10 150 150 58.25 1.40

Sound level SIBER® HRV EVO 1 & ERV EVO 1

Ventilation flow rate (m3/h)| 50| 75| 100| 150
Sound level Lw (A)| Static pressure (Pa)| 25| 50| 50| 100| 100| 150
Box irradiation (dB(A))| 24| 34| 38| 44| 45| 49
Extraction duct (dB(A))| 28| 30| 39| 42| 46| 47
Insufflation duct (dB(A))| 42| 50| 53| 56| 61| 64

SIBER® HRV EVO 2 & ERV EVO

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(7\)

Working points AIRFLOW (m3/h) PRESSURE (Pa) POWER (W) SFP (W/l/s)
1 75 25 12.61 0.61
2 100 75 25.31 0.91
3 125 50 29.16 0.84
4 150 50 39.20 0.94
5 150 100 49.65 1.19
6 150 150 60.92 1.46
7 150 200 72.60 1.74
8 200 100 81.33 1.46
9 200 150 93.10 1.68
10 200 200 106.48 1.92

Sound level SIBER® HRV EVO 2 & ERV EVO 2

Ventilation flow rate (m3/h)| 75| 125| 150| 200

Sound level Lw (A)

| Static pressure (Pa)| 25| 50| 50| 100| 150| 200
Box irradiation (dB(A))| 33| 42| 44| 46| 51| 56
Extraction duct (dB(A))| 34| 43| 45| 48| 50| 57
Insufflation duct (dB(A))| 46| 51| 59| 62| 65| 66

SIBER EVO

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(8\)

LEGEND STANDARD VERSION

1 Exhaust air
2 Fresh air supply to the dwelling
3 Fresh air intake from outside
4 Extraction of stale air from inside the dwelling
5 Electrical connection
6 Condensate drain connection

EXPLODED VIEW OF THE UNIT SIBER EVO

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(9\)

LEGEND

1 High-performance filters
2 Energy-efficient engines
3 Temperature probes
4 High-performance heat exchanger
5 100% automatic bypass
6 Swivelling condensate drain
7 Electrical connections
8 Preheater

OPERATION

DESCRIPTION

  • The unit is delivered ready to be connected to the power supply and works fully automatically. The stale air extracted from the inside transfers the thermal energy (calories/B.T.U.s) to the fresh air coming from the outside.
  • This saves energy in air-conditioning, as the new, clean air is blown into the house at a conditioned temperature (cool in summer, warm in winter).
  • Depending on the type of control unit used, up to 5 ventilation positions are possible. The airflow rate is regulated by the regulating position. Constant volume control allows the air flow rate of the supply and extract fans to be obtained independently of the duct pressure.

BY-PASS CONDITIONS

  • The By-Pass fitted as standard allows fresh air to be blown in directly from outside without passing through the heat exchanger, so that the comfortable temperature outside at any given time can be used, for example on summer nights when fresh air should enter from outside to cool the inside of the house (free-cooling).
  • The by-pass valve is automatically activated when a certain number of conditions are met (see table below for by-pass values).

By-Pass gate conditions

By-pass valve open| •    The outside temperature is higher than 10ºC.

•    In summer, the outside temperature is 3ºC lower than the temperature of the air extracted from the home, and lower than the comfort temperature.

•    In winter, the outside temperature is 3ºC higher than the temperature of the air extracted from the home, and higher than the comfort temperature.

By-pass valve closed| •    • The outside temperature is below 10ºC.

•    • In summer, the outside temperature is higher than the temperature of the air extracted from the home, and higher than the comfort temperature.

•    • In winter, the outside temperature is lower than the temperature of the air extracted from the home, and lower than the comfort temperature.

The unit automatically detects the season (winter/ summer) and this will work according to the by-pass temperature selected.

ANTI-ICE SECURITY

  • To prevent the formation of ice in the heat exchanger at very low outdoor temperatures, the SIBER DF EVO 1/2 is equipped with anti- icing protection.
  • Thermostatic probes measure the temperatures in the heat exchanger and if necessary a progressive unbalance is set in the automatic equipment. Up to -16 degrees the Unit would stop and check every hour if the temperature is suitable for operation.

INSTALLATION

GENERALALITIES
The installation must be carried out in accordance with:

  • Ventilation quality requirements for rooms (CTE HS3 – RITE 2007).
  • Quality requirements for balanced ventilation of dwellings (CTE HS3).
  • Requirements for the ventilation of rooms and dwellings (CTE HS3).
  • Safety requirements for low voltage installations.
  • Requirements for the connection of drains to sewage systems in the rooms and dwellings.
  • Any additional requirements of local energy distribution companies.
  • Installation instructions for the SIBER EVO 1/2 unit.

POSITION OF THE UNIT
The SIBER EVO 1/2 can be fixed directly to the wall or ceiling thanks to the fixing brackets included for this purpose

Warning! Depending on the weight of the Unit, the installation of the Unit should always be carried out by 2 persons.

For a vibration-free result, a wall or ceiling with a minimum mass of 200 kg/m2 must be used as a suspension surface. It is not enough for the wall or ceiling to be made of concrete or metal structures. In these cases, additional measures will be necessary, such as double plate reinforcement or additional supports. The following points should be kept in mind:

  • The Unit must be set level, both in length and width.
  • The installation space should be chosen to allow for good condensate drainage, with a trap and a slope for condensate water.

Warning! Ensure that the condensate drain slope is not positive or parallel to the unit.
Warning! The unit is designed for wall or ceiling mounting only. Never install it directly on the

  • The installation space must be protected from the weather and frost.
  • Ensure that there is sufficient space around and underneath the Unit to ensure that changing or cleaning the filter as well as maintenance of the Unit can be carried out properly

CEILING MOUNTING

  1. Use the installation template, located on the back of the box
  2. Mark the area where the fixing brackets are to be installed with the help of the installation template.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(13\)
    • If the template is not used, the fixing brackets must be spaced 630 mm apart on the long sides (standard version) and 1,035 mm apart on the short sides.
    • By default, the unit comes with the Silentblock Hooks fitted on the long side. To switch to the short side, follow the steps below:
    • Unscrew the Silentblock Hooks
    • Replace the Silentblock Hooks to the short side, respecting theSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(15\)
    • Screw the Silentblock Hooks into the desired new position.
  3. Drill the marked surface and screw the fixing brackets through the oval holes.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(17\)
  4. Loosen the wing-nuts and leave 1 cm of space
  5. Place on top of the guide and slide until it engages with the threaded rod.
  6. Tighten the wing-nutsSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(20\)

WALL MOUNTING

  1. Use the installation template, located on the back of the box
    • Attention! When installed on the wall, the unit must be always installed in a vertical position to allow a proper water drain through the collection pipe
    • Attention! In the vertical installation, place the PCB connector at top position. The PCB must never be at the bottom position
  2. Mark the area where the fixing brackets are to be installed with the help of the installation template.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(24\)
    • If the template is not used, the fixing brackets must be spaced 630 mm apart on the long sides (standard version) and 1,035 mm apart on the short sides.
    • By default, the unit comes with the Silentblock Hooks fitted on the long side. To switch to the short side, follow the steps below:
    • Unscrew the Silentblock Hooks
    • Replace the Silentblock Hooks to the short side, respecting the same direction.
    • Screw the Silentblock Hooks into the desired new position.
  3. Drill the marked surface and screw the fixing brackets through the oval holes.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(28\)
  4. Loosen the wing-nuts and leave 1 cm of space
  5. Place on top of the guide and slide until it locks into place with the wing-nutsl.
  6. Tighten the wing-nuts

NOZZLE ORIENTATION

To change the default direction of the nozzles, follow the steps below:

  1. Remove the filter covers
  2. Unscrew the outer cover
  3. Remove the outer cover and the front polypropylene of the Unit, leaving the interior exposed
  4. Unscrew the nozzle from the back side
  5. Raise the nozzle
  6. Turn the nozzle
  7. Screw the nozzle back on again from the back.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(36\)
  8. Fit the outer and inner covers of the Unit
  9. Screw on the outer coverSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(37\)
  10. Replace the filter

CONNECTION

CONNECTION OF THE CONDENSATE DRAIN

  • The SIBER HRV EVO 1/2 must always be fitted with a condensate drain. Condensation water must be drained off.
  • The 1/2″ male threaded condensate drain connection fitting (not included with the Unit) must be screwed by the installer into the condensate tank of the Unit.
  • Important! Always use a detachable condensate drain connection between the trap and the unit for proper maintenance.
  • The condensate drain pipe can be fitted underneath. The installer can adjust the condensate drain into the desired position. The drain must end at the trap water level.
  • Use a 32 mm diameter condensate drain pipe.
  • In the case of a ceiling installation, make sure that the condensate drainage is below the level of the SIBER HRV EVO 1/2.
  • Note: Only one condensate drain is connected, the other drain must remain closed with the plug. In the case of the Siber ERV EVO 1/2 (Enthalpic) ,the two drains must be closed with two plugs, it is not necessary to connect to the condensate drain.
  • Note: In the case of ceiling installation: Install the condensate trap in the drain on the side of the ducts leading to the outside. The other drain should be covered with the plug. In the case of a wall installation: Install the condensate trap in the bottom drain of the device. The other drain should be covered with the plug.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(40\)
  • Attention! For the equipment warranty to remain valid, it is necessary to install a dry siphon (Dry Ball Siphon or Dry Flexible Siphon).
  • If the evacuation of condensates is executed in another way and there is any unforeseen event in the After-sales related to the evacuation of condensates, Siber is excluded from any responsibility, and it will be the responsibility of the installation company that has carried out the installation to solve any problem and the costs derived from this problem.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(41\)
  • IMPORTANT! A removable connection is required for the mounting.

CHANGE OF FILTERS

  1. Remove the filter cover.
  2. Pull the filter outwards.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(42\)
  3. Place the new filter in the slot and push it in.
  4. Replace the filter coversSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(43\)

ELECTRICAL CONNECTION

MAINS CONNECTION
The electrical installation must correctly comply with the relevant standards.

Warning! The fans and the control circuit shall operate at 230 V. If handling or maintenance work is carried out, the unit must be disconnected from the mains.

HOSE IDENTIFICATION COLOURS

BROWN| Line
BLUE| Neutral
GREEN / YELLOW| Earth

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(44\)

NUMBERING AND DESCRIPTION OF PIN CONNECTORS

CONNECTOR| DESCRIPTION| PLATE| CONN| ECTOR| DESCRIPTION|  | PLATE
PIN| 1| Home automation input 10 v| X-26| PIN| 11| Not used|
PIN| 2| Home automation input 0V| X-26| PIN| 12| Common selector 3V V1 230V| X-9
PIN| 3| Home automation dry contact input| X-25| PIN| 13| Selector 3V| V2| X-9
PIN| 4| Home automation dry contact input| X-25| PIN| 14| Selector 3V| V3| X-9
PIN| 5| Forecast probe external Canadian well| Forecast| PIN| 15| Post-heating output 230 V| X-17
PIN| 6| Forecast probe external Canadian well| Forecast| PIN| 16| Post heating output| Ground| X-17
PIN| 7| Not used| X-16| PIN| 17| Post heating output| Neutral| X-17
PIN| 8| Not used| X-16| PIN| 18| Output 230 V Close| Canadian Well Actuator| X-28
PIN| 9| Not used| X-32| PIN| 19| Output 230 V Open| Canadian Well Actuator| X-28
PIN| 10| Not used| X-32| PIN| 20| Neutral Output| Canadian Well Actuator| X-28

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(45\)Siber-EVO-1-2
-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(46\)

MONITOR YOUR HOME – PROBES / WIRELESS CONTROLS

Take care of your health and that of your loved ones by monitoring the Air Quality in your home! The Siber EVO unit can be equipped with various (optional) wireless accessories:

  • Wireless CO2 probe
  • Wireless Humidity sensor (RH)
  • Wireless smart Multicontrol
  • Wireless 4-position push-button control

Siber EVO Probes/Control Command (optional)

Wireless multicontrol| DFEVOCTRL
Wireless 4-position push-button control| DFPULS4B
Wireless CO2 probe| DFEVOCO2
Wireless Humidity sensor (RH)| DFEVOHR

  • The Siber Smart Wireless Multicontrol communicates via RF (radio frequency) with the ventilation unit and can choose from 5 different flow rate positions linked to the unit. It is a user and installation interface for monitoring and configuring the connected heat recovery unit. It has multiple functions connected to the Unit.
  • The Siber 4-Position Wireless Push Button Control communicates via RF (radio frequency) with the ventilation unit and can choose between 4 different positions linked to the unit. It has a dirty filter indicator.
  • The wireless Siber CO2 probe monitors the CO2 level of the air inside the house. It measures the CO2 in the rooms of the house and sends its measurements via RF (radio frequency) to the Siber EVO Unit. The unit will be able to react and vary the appropriate ventilation flow rate to ensure indoor air quality according to the information from the probe.
  • The wireless Siber HR (Relative Humidity) Probe controls the relative humidity of the indoor air in the house. It measures the indoor humidity in damp rooms and sends its measurements via RF (radio frequency) to the Siber EVO Unit. The unit will be able to react and vary the ventilation flow rate suitable for indoor air quality according to the information from the probe.

SMART CONNECTIVITY

You can turn the dwelling into a smart home (optional) using various available gateways, as well as to connect the unit to your mobile device with the Siber EVO APP.

  • MODBUS – RS485
  • KNX – Evo Connect
  • Ethernet bridge (specifies Siber EVO APP connection)

MODBUS – RS485

  • The Siber RS485 device (DFEVORFRS485) connects to the building management system (BMS) via cable, in Modbus language for both reading and writing data.
  • Collects information from Siber EVO units and compatible wireless probes and controllers(DFPULS4B, DFEVOCTRL, DFEVOCO2 and DFEVOHR) that are linked to this ventilation unit.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(51\)

KNX – EVO CONNECT

  • The EVO CONNECT device (DFEVOCONNECT) is a modbus / knx converter. It needs to be connected by cable to the gateway (Modbus
  • RS485) to translate the information collected by the gateway (Modbus – RS485) and send it by cable to the BMS.
  • Collects information from Siber EVO units and compatible wireless probes and controllers(DFPULS4B, DFEVOCTRL, DFEVOCO2 and DFEVOHR) that are linked to this ventilation unit.
  • The Evo Connect requires a 24 V power supply for its proper operation.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(52\)

BRIDGE ETHERNET – SIBER EVO APP

Thanks to the smart control system, online monitoring of the most important elements is achieved, making it possible to control and monitor the indoor air quality of the home through the Siber EVO APP.

  • Control and regulation of the unit’s speeds.
  • Monitoring of CO2 and relative humidity in the home.
    • The Siber EVO unit collects information from the various compatible wireless probes and controllers(DFPULS4B, DFEVOCTRL, DFEVOCO2 and DFEVOHR) via radio frequency.
    • The information is sent to the Ethernet gateway (Ethernet Bridge – DFEVORFETH – DFEVORFETH) DFEVORFETH), whose device must be connected by cable to the home’s internet connection modem, transferring the collected data to the “cloud” to provide access and monitoring of the data via the Siber EVO APP.Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(53\)

MAINTENANCE

FILTER MAINTENANCE (FOR THE USER)

Filters should be checked every three months. Filters should be cleaned every six months and replaced at least once a year.

Note: The equipment must never be operated without filters

  1. Remove the filter cover.
  2. Pull the filter outwards.
  3. Vacuum the filter to remove theSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(54\)
  4. Place the new filter in the slot and push it in.
  5. Replace the filter coversSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(55\)

MAINTENANCE OF THE HEAT EXCHANGE (FOR THE INSTALLER)

  1. Remove the filter cover.
  2. Pull the filter outwards.
  3. Unscrew the outer coverSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(56\)
  4. Remove the outer cover and the front polypropylene of the Unit, leaving the interior exposed
  5. Unscrew and remove the left support bracketSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(57\)
  6. Separate the retaining tabs to remove the heat exchanger
  7. Remove the heat exchanger
  8. Clean the heat exchanger with waterSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(58\)
    • Note: Carefully remove the heat exchanger; a small amount of condensation water may still remain in the heat exchanger.
  9. Put the heat exchanger back in place
  10. Insert the support bracket and screw it back onSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(60\)
  11. Fit the outer and inner cover of the Unit.
  12. Screw on the outer coverSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(61\)
  13. Replace the filters
  14. Replace the filter coversSiber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1 \(62\)

EXPLODED VIEW AND DESCRIPTION

No,                                                             Article description SIBER EVO 1/2

1| Orientable nozzles 160 Ø| 4 units
2| Front cover| 1 piece
3| Front Polypropylene| 1 piece
4| By-Pass Valve| 1 piece
5| By-Pass valve motor| 1 piece
6| Energy-saving fan| 2 units
7| High-performance heat exchanger| 1 piece
8| Fastening tabs| 2 units
9| Swivelling condensate drain| 2 units
10| High performance filter| 2 units
11| Filter Cover| 2 units
12| Temperature probe| 4 units
13| Connection plate| 1 piece
14| Silentblock| 4 units
15| Electronic connection board| 1 piece
16| Preheater 600W| 1 piece

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(63\)

CERTIFICATE OF GUARANTEE

All Siber products are carefully tested and are covered by a warranty for a period of 36 months from the date of purchase, in accordance with current legislation. These rights, as provided for in the above-mentioned legislation, may only be asserted with respect to the seller himself. Within this period, Siberzone S.L.U .will repair and/or replace, at its own account and expense, any components which, in its unquestionable judgement, are recognised to be malfunctioning.
The following cases are excluded from the guarantee and invalidate its validity:

  • Installation of the appliance by non-professionally trained personnel (applies only to appliances not equipped with the manufacturer’s plug);
  • Non-compliance with the suggestions for use, installation, and maintenance indicated in the corresponding instruction manual;
  • Breakage due to misuse and neglect;
  • Breakage caused by transport;
  • Wrong connection to the power supply.
  • Power supply at a voltage different fromthat indicated on the device.
  • Repairs or manipulations carried out by unauthorised personnel;
  • Interventions due to defects or falsified verifications.
  • Missing guarantee certificate and/or guarantee certificate not filled in;
  • Removal or alteration of the label and stamp proving the date of manufacture.

In any case, the product returned for repair or replacement must be returned to the place where it was purchased, together with this certificate duly completed and with the corresponding tax document proving the date of installation. This warranty never extends to the obligation to repair damages of any kind or nature suffered by persons and/or things.

  CERTIFICATE Central VMC DF Siber:

Siber Zone, SLU. Apdo. de Correos nº 9 – C/Can Macia nº 2 08520 Las Franquesas del Vallés (Barcelona) Tel: 902 02 72 14 Fax: 902 02 72 16
E-mail siber@siberzone.es| Address of the work: __

__ _Apartment/Dwelling: Municipality:

 | Province: __

Siber-EVO-1-2-Passive-House-certified-Heat-Recovery-Ventilation-unit-FIG-1
\(64\)

CONTACT

  • Tel: 902 02 72 14 / Int. 00 34 938 813 1
  • Fax: 902 02 72 16 / Int. 00 34 938 813 0
  • siber@siberzone.
  • www.siberzone.

Sustainable ventilation and air handling systems

  • Tel. 902 02 72 14
  • Int. 00 34 938 616 261
  • Fax. 902 02 72 16
  • Int. 00 34 937 814 108
  • siber@siberzone.es.
  • www.siberzone.es.
  • Siber Zone, S.L.U.
  • HEADQUARTERS
  • Central Offices
  • Logistics Centre –
  • ShowroomFactory – Training
  • Centre
  • Apdo. de Correos
  • 9 C/ Can Macia n. 2
  • 08520 Les Franqueses del
  • No part of the contents of this publication may be reproduced in any form without the express permission of the owner.
  • Siber Zone, S.L.U. reserves the right to make any technical modification to the equipment and elements without prior notice.
  • v.21.0623