Introduction
Your LAFM is a self-contained ceiling mounted electronic air cleaner. Model
HEPA LAFM uses a high efficiency non-electric media. They are designed for
installation in a standard T-Bar ceiling in the space occupied by a 2 x 4 drop
ceiling panel. Each unit is equipped to de-liver very high efficiency and
trouble free operation.
Providing Clean Fresh Air
Each day an individual breathes in at least 16,000 quarts of air. That air is
filled with particles of smoke, dust, pollen, microor-ganisms, and other
pollutants. With your new Electronic or HEPA air Cleaner, you and your
customers will breathe air which is relatively free of those pollutants. Today
the emphasis is on health and well being, and by using your LAFM you will see
a direct benefit to your busi-
Energy Consumption Is Lower
The exhausting of polluted air to the outside is the most common solution to
the removal of concentrations of polluted air. In doing so, however, you must
also bring supplies of fresh air to take the place of the air ex-hausted.
You must also heat or cool this air to make it comfortable for the occupants
of the space involved. This can be expensive, but with your LakeAir brand Air
Cleaner, you will drastically reduce the need for out-side air by
recirculating the indoor air and thereby reducing your heating and cooling
costs.
Recirculated Air for Comfort and Savings With continued use of your Air
Cleaner, you will find that bothersome smoke and other small particles which
settle out on walls, curtains, glasses, bottles, mir-rors, and other surfaces
will be substantially reduced or eliminated, thus saving you costly
maintenance and redecorating.
COMPONENTS OF THE LAFM AND HEPA LAFM
Hood Assembly
The LAFM is fitted with a corrosion resistant galvanized steel hood which
requires only 11.25” of space above the drop ceiling for installation.
Mounting System
The LAFM is equipped with a steel inner frame that has four drilled and tapped
1/4 x 20 holes for the provided eye bolts or for the use of threaded rod, to
mount the unit to the superstructure above for a safe and secure installation
HEPA LAFM units.
Intake Grille
A fixed position intake grille allows for even distribution of the incoming
air over the cleaning surface. The grille and the inner steel hinged frame
swing open for easy access to the filter.
Pre filter Screen
An aluminized pre-filter screen is provided to collect large particles such as
lint and hair. It is easily removed for cleaning with water and mild soap.
This filter helps keep your electronic filter cell or HEPA media cleaner for a
longer length of time.
Electronic Collection Cell
The Electronic Model LAFM uses one large collection cell positioned behind the
pre-filter screen which collects the majority of the airborne particles that
enter the system.
HEPA Pad Media and Carbon After-filter
A carbon after-filter is standard with all LAFM units, and is used to remove
odors from the air. It is integrated with the HEPA filter pad
Power Supply Module (Electronic Only)
The patented power supply has been used in thousands of electronic air
cleaners of all sizes. It is the only power supply in the industry which is
guaranteed for seven years. It delivers a constant regulated Voltage to the
collection cell.
vibration.
Blower Motor
Your LAFM is equipped with a powerful yet quiet motor-driven blower type fan
which is calibrated for two speeds of operation. The grommeted suspension
system eliminates chances for
Exhaust Grille
Large exhaust grille with vanes allows an airflow to be presented to the room.
Safety Interlock System Located in the channel behind the collecting cell, the
microswitch controlled interlock system will not allow operation of the LAFM
without having the intake panel locked into place.
Two-Speed Fan Switch
Your LAFM is equipped with a three-position switch that allows for High and
Low fan speed as well as a center off position. The electronic collection
system and the fans are designed to run simultaneously.
System Light
The LAFM is fitted with a system light which indicates when your air cleaner
is in operation. Located below the three-position switch, the light will be
lit when all system connections are activated.
Piggyback Fuse System
The unit is provided with a fused circuit that protects valuable components in
case of a power surge. An additional “piggyback” fuse is located in the fuse
holder for easy access if it is needed.
HOW YOUR MODEL LAFM WORKS
In business establishments or public buildings, millions of airborne particles
are continually being circulated in the air you breathe.
Your LAFM Self Contained Flush Mounted Electronic Air Cleaner removes the
smoke, dust, dirt, pollen, and other pollutants from the air with an
electrostatic process which works this way:
- The internal circulating blower mechanism draws the dirt laden air into the system where it first encounters the outer PREFILTER SCREEN.
- The PREFILTER SCREEN collects the larger particles from the air and holds them on its intermeshed surface.
- In electronic units, the air then passes into the ELECTRONIC FILTER CELL where it first meets the IONIZING SECTION with its many fine ion wires. These wires charge the airborne particles by exciting them with a high electrical charge. As the charged particles move along to the COLLECTING SECTION, they are trapped by the collector plates much like a magnet attracts and collects metal filings.
- In HEPA LAFM units, the air is drawn through a high efficiency, hospital grade media pad. The harmful particles are trapped and held by the closely spaced fibers.
- The ACTIVATED CARBON AFTER-FILTER, the final filter in the system, removes odors and freshens the air.
- The cleaned and purified air is then returned to the room environment.
INSTALLATION INSTRUCTIONS
IT IS IMPORTANT TO READ THE FOLLOWING INSTRUCTIONS CAREFULLY. DAMAGE TO THE
PRODUCT OR TO INSTALLER AND PROPERTY COULD RE-SULT IF INSTRUCTIONS ARE NOT
FOLLOWED.
Important Safety Precautions
- Do not connect the power source until after the unit is mounted. Shock and/or damage could result.
- Be sure to shut the unit off prior to any service work.
- Wear gloves to protect hands during installation as well as to keep the surface of air cleaner free from dirt and smudges.
Equipment Needed for Installation
- Regular and Phillips Screwdrivers
- Wire cutters
- Pliers
- Twelve gauge galvanized wire for hanging the wires from the true ceiling to the top of the unit (if threaded rod is to be used, it will replace the wire.).
- Enough twelve or fourteen gauge electrical wire and conduit to reach the nearest switched circuit. (see Electrical Instructions)
- Junction box fittings as required.
Items Supplied as Loose Parts
- Four (4) black 1/4 x 20 eyebolts
Unpacking
- Remove unit from carton and turn over so that grille surfaces are accessible.
- Remove pre filter and collection cell or HEPA pad from unit through intake side of cleaner. This is accomplished by turning the access screws and lifting the hinged opening. The electronic filter cell is attached by a black grid cap connector on the side of the cell.
- After removing the items in the previous step, close and lock the hinged intake panel.
Preparation for Mounting
- The LA-FM units are designed to fit into a T-bar drop ceiling. Remove as many of the 2 x 4 ceiling tiles as is necessary to safely and securely mount the air cleaner.
- The area between the true ceiling and the drop ceiling must be at least 11-inches. There must be no duct work, pipes, or other obstructions to the area where the unit is to fit.
- Make sure that the spot chosen will be oriented for good air circulation.
- These models are equipped with eyebolts on all 4 corners for easy hanging. Their relatively light weight allow them to be hung in most any structure. You should be able to hang them from the same supports that the drop ceiling is hung from.
Mounting
- Attach four (4) 12 gauge galvanized steel support wires to the true ceiling. Twist each wire at least four times to provide for safe support for the air cleaner. Make sure the free end of the wire extends far enough to adequately reach the eye bolts and
- Turn the air cleaner onto the grille portion so that the four holes are visible on the top portion of the unit. Attach the four eyebolts to the top by screwing them into the appropriate holes.
- Lift the air cleaner into place and rest on the T-Bar opening without putting weight upon the T-Bar grid work. The weight should be borne by the support wires with the T-Bar acting as holding receptacle for the unit facing. You should check the level of the unit to insure proper operation.
Installation of the Electrical Wiring
Caution: This procedure should only be attempted by persons qualified to
install electrical wiring.
All wiring must comply with applicable codes and ordinances.
- Locate a 120V AC, 60 Hz (alternative power sources would be used in the case of the LAFM 230V units) power circuit with a junction box near the air cleaner location.
- Check that the circuit breaker or fuse, for that circuit is rated at 15 amperes or 20 amperes. The required copper wire size will be: AWG #14 for 15 ampere circuits AWG #12 for 20 ampere circuits
- Caution: Turn off the building circuit at the fuse or circuit breaker before proceeding.
- Locate the connection box on the air cleaner and remove the outer plate which contains the knockout. You will note the presence of three wires on the inside of the box. One blue, one brown, and one green.
- Connect the blue and brown wires from the pigtails in the air cleaner, to the corresponding colors in the supply circuit. (See diagram on page 13.)
- Connect green wire from the grounded terminal in the air cleaner, to the grounded circuit of the building wiring system. If the building does not have conduit it will have a green or bare ground-ing conductor for connection to the air cleaner green wire. DO NOT CONNECT THE GROUNDING WIRE FROM THE AIR CLEANER TO THE WHITE WIRE OF THE BUILDING. The air cleaner frame must be electrically connected to the frame of the building or the electrical conduit system. Input electrical power should be run through flexible conduit as recommended by the National Electrical Code or your local authority.
Reassembly of the Unit
- With the unit now in place, loosen the 1/4 turn screws on the intake grille and allow the hinged portion to drop down.
- Replace the prefilter screen, electronic cell, and carbon afterfilter, making sure to connect the grid cap connector to the cell. REMOVE THE PLASTIC COVER FROM THE HEPA MEDIA BEFORE REINSTALLATION OF THE FILTER PAD.
- Close and lock the entire hinged panel into place.
Start-Up and Checkout of the Unit
To make sure the unit is operating correctly before leaving the installation,
please check the following:
- Check all electrical connections and make sure they are tight and properly connected.
- Electronic cell is in place and properly oriented so that the airflow arrow points in the direction of the airflow or the HEPA Media pad is properly oriented so that black carbon filter material is facing toward the ceiling.
- Turn the unit on and check to see that it runs properly at all speeds. In addition, make sure the light goes on when the unit is in operation.
- Open the intake grille section and check to see that the unit shuts off completely. Re-engage the panel and make sure unit turns on by watching light.
If for any reason the unit does not appear to work correctly, refer to the Troubleshooting Guide for assistance.
GENERAL INFORMATION:
Application
The LAFM should be mounted in the room or area where the air is to be
cleaned. Removal of such pollutants as tobacco smoke and pollen from the air
in areas like conference rooms, lounges, bingo halls, offices and the like is
the goal of the unit. The LAFM provides its own air circulation and as such
can be used for most applications requiring particulate removal.
Under no circumstances should the electronic Model LAFM, be used in an
atmosphere containing combustible gases or vapors. These applications are best
served by the model HEPA LAFM. Sizing
To size the air cleaner properly, one should know the volume of the room or
area to be cleaned. Also, consider the use of the area so that the number of
air changes per hour can be used in conjunction with the volume. Other
considerations to be made may include:
– Ceiling height
– Type of pollutant to be removed
– Outside air quality
– How fast is the level of contamination rising
– What kind of air speed is anticipated
ASHRAE Standard 62-81 recommends several different air change formulas
depending on the type of establishment to be ventilated.
Small offices, stores, homes | 4-5 Air Changes/Hour |
---|---|
Computer rooms, waiting rooms, large offices, conference rooms | 6-8 Air |
Changes/Hour
Beauty shops, cafeterias, bingo halls, bowling centers| 10-12 Air Changes/Hour
Bars, lounges, discos, hospitals, casinos| 12-15 Air Changes/Hour
To determine the number of LAFM units needed in a given room, use the method
below:
Volume of Room Air Changes/Hour (cu.ft.:LxWxH) x (use # from table above) =
Number of LAFM units 60,000
The LAFM is capable of 400-1000 cfm. This multiplied by 60 minutes per hour
yields the 60,000 figure above. It should be noted that this is an optimum
figure and the other considerations above should be made before a final
decision is reached. We can help you if necessary in making a good judgment.
MAINTENANCE
Washing the Electronic Cells and Prefilter
In order for your LAFM to maintain peak operating efficiency, the prefilter
screen and the electronic cells must be washed regularly. The frequency of
this cleaning will depend on the atmosphere in which the units are operating.
The best way to clean the cells is by soaking them in hot water with LA-99
cell cleaning detergent (other methods can be used if time is a restraint).
- Following the cell cleaner manufacture’s instructions, add LA-99 cell cleaning solution or other detergent to hot water in an appropriate container such as a stationary tub.
- Immerse the cell in the water and soak for 5 to 10 minutes. Then remove the cell and rinse with clean water, making sure to remove all residue from the cell surface.
- Check cells for broken ion wires or bent plates and repair or replace if necessary.
- Make sure the cell is completely dry before placing it back into the air cleaner.
- Remove lint and other dirt from the prefilter by vacuuming or washing it in a mild detergent solution.
CAUTION: Care should be taken when handling the LAFM cells and filters.
- Edges may be sharp on the collection plates as well as the area near the ionizing wires.
- Be sure to wear appropriate gloves and goggles when dealing with a cell chemical of any kind. Contact with the skin is not recommended.
- Electronic air cleaners and their components are susceptible to damage. Take care when working with them to avoid equipment damage.
Replacing the HEPA Media Pad
The HEPA Media pad cannot be cleaned and MUST BE REPLACED every 9-12
months. Failure to replace a heavily loaded filter can cause undue stress on
the blower motors due to the reduced airflow and will void warranty.
Service
Should your LAFM malfunction, there are several simple checks which you can
use to check the performance before a service person need be called.
- Check to see if the fuse on the unit is tripped which would indicate electrical interruption to the unit. Correct by replacing fuse. If the circuit breaker or service box fuse is blown, that too will need replacement.
- Be sure the electronic cell is in place and that the access door is locked down. Failure to have this done will cause the safety interlock to override the circuit.
- If the operating light is not lit after checking these things, a service person should be consulted. All electronic air cleaners undergo a process known as “arcing” from time to time. It is a snapping noise that comes from the electronic cell when very large particles enter into the col-lection cell or when the cells are wet or extremely dirty. If an unusual amount of arcing persists, check the collecting cells for broken wires, bent plates, or to see if they are very dirty. If arcing still occurs, check with your service person or dealer.
MODEL LAFM
TROUBLESHOOTING GUIDE AND CHART
WARNING!!! The following instructions are intended for qualified service
personnel only. Dangerous line voltage circuits are exposed during these
procedures. Disconnect power at fuse before servicing the unit. Trouble
shooting the LAFM can be accomplished with minimal tools and by following the
directions given below in the two sections of Troubleshooting Guide. The first
section deals with checks on determining the cause of a malfunction in your
LAFM, and the second section explains how to find a faulty component, or how
to determine that a specific com-ponent is functioning properly.
Diagnostic Checks
- Powering up the LAFM
a. Make sure the prefilter screen and electronic filter are clean, dry, and properly + installed in the air cleaner.
b. Turn on the LAFM and check to make sure all systems are in proper working order. In each case, the system light should be on and the fan should run.
-If the light does not come on, check the microswitch interlock for free movement as well at the power source for correct input.
-If the fan does not come on, check the fan motor, wiring to the motor, and the power source.
-If both the system light and the fan motor operate, go to step 2.
c. Test Technique
a. With the air cleaner turned on, use a long shank insulated screw driver to penetrate the pre filter screen and make contact with the electronic cell. A definite “snapping” sound and arcing should occur if the cell is properly energized.
b. If no arcing is heard, check for continuity through the collector cell, then check for failure of the cell due to broken wires, cracked insulators, bent plates; and following that, a possible failure in the voltage doubler or transformer.
d. Cell Check
a. To remove the electronic cell from the unit, loosen the two quarter turn fasteners and allow the hinged intake to drop into place. Remove the grid cap connector from the cell and take the cell and pre filter from the unit.
b. Close the hinged intake and check to see if the system light and the fan operate. If they do, check the cell for a short circuit.
c. Replace the cell. If the Test Technique still does not produce a “snap” or arcing, go to step 4.
e. Check Power Supply
a. Remove the power supply from the LAFM cabinet and check for continuity through the circuit.
b. Check continuity through the switch and go back through to the power source until the problem can be located.
c. Replace the power supply into the cabinet and check for correct line voltage by powering up the system and using a voltmeter to measure the input voltage at the transformer.
d. If voltage is correct (about 120V AC), then continue to check voltage at the secondary side of the transformer (2000V AC), and finally at the output (grid cap connector) which should yield about 6000V DC.
e. Any variation from these voltages could indicate a component failure where replacement may be required.
Component Checks
-
Check Fan Motor and Power Source
If the fan does not run when the switch is on either in the High or Low position, check the voltage supplied to the motor.
1. If the motor does not turn when the proper voltage is supplied to it, check to see that the shaft turns freely. Replace the motor if necessary.
2. If the correct line voltage is not measured, check back through the wiring to the power source, including the interlock system. -
Check the Electronic Cell
Visual Inspection — Carefully examine the electronic cell and look for the following:
– Bent plates
– Broken ionizing wires
– Dirt Accumulating on the cell plates
– Cracked or broken insulators -
Check for Short Circuits
Use an ohmmeter to check resistance through the cell. Resistance should show an open circuit. -
Check Transformer and Voltage Doubler (Electronic Units Only)
This check will locate a faulty component or connection in the power supply of your LAFM. CAUTION!!!’ EXPOSURE TO LINE VOLTAGE IN THIS PROCEDURE WARRANTS SPE-CIAL CARE. BE SURE THE POWER IS TURNED OFF BEFORE CONNECTING OR DIS- CONNECTING ANY COMPONENT.
1. Inspect power supply (transformer and doubler) for any physical signs of damage.
2. Turn the power off and connect voltage meter to the primary side of the high voltage transformer. Energize the system and check the line voltage.
3. Turn off the power, disconnect the primary side and reconnect to the secondary side of the transformer. A poor reading here will probably indicate a faulty transformer. Replacement is in order.
4. Turn off the power again, disconnect the transformer and connect to the output grid cap connector. Measure voltage (DC) at about 6000V open circuit. A poor measurement here should be traced back to the doubler in case of bad high voltage wire. If the reading is still poor at the doubler, it should be replaced.
TROUBLE SHOOTING FLOWCHART
Th e following trouble shooting procedure has been designed to speed th e serviceman ’s work and insure that any malfunction in th e electronic air cleaner is quickly and properly repaired. Refer first to flow ch art below for an outline of the procedure, and t hen refer to t he Tr oubleshooting Guide.
ELECTRICAL CONNECTIONS
ELECTRICAL SCHEMATIC MODEL LAF M , 120V, 230V
LAFM ELECTRONIC | 120V | 230V |
---|---|---|
SAFETY INTERLOCK MICRO SWITCH | 497576 | 497567 |
ON/OFF SWITCH | 497612 | 497612 |
MOTOR/BLOWER | 497602 | 497609 |
FUSE | 497547 | 497547 |
INDICATOR LAMP | 497570 | 497592 |
POWER SUPPLY | 10079 | 10179 |
MODEL LAF M PARTS SCHEMATIC
Part # | Description | Quantity Used |
---|---|---|
#1 | (contains 497606 Transformer & 497524 Voltage Quad) Complete Power | |
Complete Power Supply 120v (Electronic Only) | 1 | |
#10179 | Supply 230V (Electronic Only) (contains 497607 Transformer & 497524 | |
Voltage Quad) Complete | 1 | |
#10107 | Electronic Filter Cell (Electronic Only) | 1 |
#10130 | Ionizer Wire Kit (Electronic Only) – 6 each | 1 |
#30007 | LAFC Hood Assembly | 1 |
#495169 | Instrument Panel | 1 |
#40137 | Ceramic Stand-off Kit (Electronic Only) | 1 |
#480029 | Electrical Schematic Label | 1 |
#490128 | Prefilter Screen | 1 |
#497567 | Safety In terloc k Micro-switch | 1 |
#497602 | Motor/Blower 120V(2-HEPA) | 1 |
#497609 | Motor/Blower 230V | 1 |
#497612 | Off/On Rocker Switch | 1 |
#497547 | Fuses | 1 |
#499072 | Carbon Afterfilter (for us e with Electronic Filter Cell) | 1 |
#499081 | HEPA Media pad with integrated carbon filter | 1 |
LAFM COMMERCIAL AIR CLEANERS 7 YEAR LIMITED WARRANTY
The Complete Electronic or HEPA Air Cleaner is User’s Responsibility warranted
by LakeAir International, Inc. to the Please
Note: Your warranty is subject to original purchaser to be free from
defects in user responsibili ty. Some items and some material and workmanship
under nor- mal use and conditions resulting from causes other than service for
a period of one year from the date of manufacturing defects are the
responsibil- purchase. In addition, LakeAir International, Inc. ity of the
user of the LakeAir Electronic or warrants the Power supply mod- ule and HEPA
Air Cleaner and are not covered by transformer in the LakeAir Electronic Air
Cleaner the warranty. These are: for an additional six (6) years or a total of
seven (7) years from the date of purchase to the original
-
To operate and maintain according to purchaser. LakeAir’s liability is to be lim-ited to instructions. repairing or replacing such products during the
-
Periodic checking and cleaning of unit warranty period at its option, providing the product Failure to clean or replace filters within the is sent prepaid to LakeAir International, Inc. or an designated time spans will void warranty. Authorized Service Center and is deemed to the
-
Proper use of controls must be main- satisfaction of LakeAir International, Inc. to be tained ot warranty will be voided. defective in any part or portion.
-
Damage to unit from unsatisfactory wo operation because of blowing fuses, inade-
This warranty is in lieu of any other warranty quate electrical service or operation on expressed or implied and of all other obligations power supply other than that indicated on or liabilities in connection with the sale of the the rating plate, or incorrect electrical pro- described LakeAir Electronic or HEPA Model Air tection devices used Cleaners. In no case will any claim for consequen- -
Damage occurring during transportation tial damages or labor expenses be allowed. This or resulting from improper handling. warranty does not apply to a LakeAir Electronic
-
Damage due to accident or resulting
Air cleaner or any part thereof which has not been from alteration or tampering operated in accordance with the operating instruc- -