AQUA FLO GEN5-8R12 Rack Mount Systems Owner’s Manual
- June 17, 2024
- AQUA FLO
Table of Contents
- AQUA FLO GEN5-8R12 Rack Mount Systems
- AQUA FLO – Rack-Mount Systems
- Before You Begin
- Assembly
- System Sizing
- Installation
- System Preparation
- Cleaning the UV Sensor
- Filter housing drain plug
- Operation
- Optional Modules Check
- System Troubleshooting
- AQUA FLO Rack-Mount UV System Specifications
- LIMITATIONS OF WARRANTY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AQUA FLO GEN5-8R12 Rack Mount Systems
AQUA FLO – Rack-Mount Systems
AQUA FLO – Rack-Mount Systems
SYSTEM| GEN4-8R1 GEN5-8R1| GEN4-8R12 GEN5- 8R12|
GENH4-13R2 GENH5-13R2| GENH4-13R22 GENH5- 13R22|
GENH4-13R122 GENH5- 13R122| GENH4-13R222 GENH5-
13R222
Rated Flow| 8.0 GPM| 15.0 GPM
1st Filter| Sediment 10”| Sediment 10”| Sediment 20”| Sediment 20”| Mesh
strainer 10”| Sediment 20”
2nd Filter| N/A| Carbon 20”| N/A| Carbon 20”| Sediment 20”| Scale reduction
20”
3rd Filter| N/A| N/A| N/A| N/A| Carbon 20”| Carbon 20”
Safety Considerations
It is important that care is taken when operating and/or maintaining your
system.
Please read the instructions
- The appliance is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
- Children should be supervised so that they do not to play with the appliance.
- WARNING: Do not operate the UV-C emitter when it is removed from the appliance enclosure.
- The appliance is to be supplied through a residual current device (RCD) having a rated residual operating current not exceeding 30 mA.
- This appliance contains a UV-C emitter.
- Unintended use of the appliance or damage to the housing may result in the escape of dangerous UV-C radiation. UV-C radiation may, even in little doses, cause harm to the eyes and skin.
- The appliance must be disconnected from the supply before replacing the UV-C emitter.
- The appliance is intended to be permanently connected to the water mains and not connected by a hose-set.
- Maximum working voltage of built-in UV driver U-OUT=240V
- If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
- Before servicing this equipment, disconnect the power cord from the electrical outlet.
- Energy given off by the UV lamp is harmful to your eyes and skin. NEVER look directly at an illuminated UV lamp without adequate eye protection and always protect your skin from direct exposure to the UV light.
- For complete disinfection**, use ONLY genuine replacement parts.
- Do not operate the unit if it has any damaged or missing components.
- To avoid possible electrical shock, use only with a properly grounded electrical outlet.
- Never perform any maintenance to the system unless you are comfortable in doing so.
- Contact the manufacturer for service instructions if required.
- Do not use this system for any purpose other than what it was intended for. Misuse of this system could potentially cause harm to the user or others.
- Your system is intended to be installed indoors and away from leaking plumbing. DO NOT plug the unit in if the system or any of the components are wet.
- The system should be directly installed into a ground fault circuit interrupter (GFCI). If use of an extension cord is required, the cord must be manufactured with a minimum of 16 gauge wire and care should be taken to avoid potential tripping hazards.
- We recommend that a licensed plumber or certified technician install the system.
Before You Begin
The following will be needed for installing the UV system:
- Tools Pipe cutter, hacksaw or other specialized tools required to cut into your existing plumbing (e.g. if you have PEX piping) • Soldering tools (torch, flux, emery cloth and solder) • Wrench (for tightening fittings) Other Materials
- Inlet/outlet connections Teflon™ tape Water Quality Parameters UV disinfection is only effective if the UV light can pass through the water it needs to treat.
- This means that the quality of your water is very important in order to ensure complete disinfection.
- Treated water should be tested for at the least the parameters listed below.
- If the water exceeds the listed parameters AQUA FLO strongly recommends that appropriate pretreatment equipment be installed (equipment required will depend on parameters being treated): Hardness: <7 gpg (120 mg/L) – if hardness level is 7 gpg or slightly below the quartz sleeve must be cleaned periodically in order to ensure efficient UV penetration; if above the water must be softened.
- Iron (Fe): <0.3 ppm (0.3 mg/L) Manganese (Mn): <0.05 ppm (0.05 mg/L) Turbidity: < 1 NTU Tannins (organics): <0.1 ppm (0.1 mg/L) UVT (transmittance): >85%
- (Please contact AQUA FLO if water has a UVT that is less than 80% for pre-treatment recommendations) You can have your water tested at a private analytical laboratory or by your local dealer. It is always recommended to install pre-filtration of at least 5 microns prior to a AQUA FLO UV disinfection system.
Assembly
Unpack the system and ensure all the components are included with the system. Your system is shipped with the following components: AQUA FLO (Standard/High output lamp systems
System Sizing
The AQUA FLO rack-mount UV system is designed as a do-it-yourself (DIY) system with a single inlet and outlet port. This system comes fully assembled with the exception of a single stainless steel hose connection that comes unattached, yet fully taped for easy installation. PLEASE NOTE that increasing the flow above this rating or disinfecting water that does not meet the quality parameters will decrease the dose and therefore compromise the efficacy of the system. To determine the flow rate, follow these simple steps:
- Be sure no water is being used in the home.
- Open a faucet or tap nearest the pressure system and run until the well pump starts.
- Close the faucet and using a second hand watch, record the length of time in seconds until the pump stops. This is known as the cycle time.
- Then using a container of known volume, preferably in US Gallons, open the faucet or tap nearest the pressure system and measure the amount of water drawn off until the pump starts again. Depending on the size of the container used, it is acceptable to turn the faucet on and off to empty the container. This measurement is known as the draw down.
To calculate the pressure system flow rate divide the draw down by the cycle
time and multiply that by 60.
Draw Down__÷ Cycle Time____ x 60=__Pumping Rate in
USGPM
AQUA FLO (Standard/High output lamp systems)
Location
Choose a location where the main cold water line is accessible. The system
must be installed after other water treatment equipment (i.e. softener), but
before any branches (See Figure 1).
PLEASE NOTE: All AQUA FLO UV disinfection systems are intended for indoor
use only as they should not be exposed to the elements. A ground fault circuit
interrupter (GFCI or GFI) outlet is required.
Orientation
This system has the ambidextrous capability of being able to have the main
water inlet enter from either the left hand side or right hand side of the
unit. The units comes pre plumbed from the factory for a left hand water
inlet. To change to a right hand water inlet follow these simple steps (See
Figure 2):
Step 1 : Remove the blue filter sump housings (either one or two housings
depending on the model purchased) from the filter head and set aside.
Step 2: Remove the filter head screws from the top mounting plate (4
screws for a single filter model and 8 screws for a double filter model).
Step 3: Carefully lower the filter head (or heads) from the rack assembly
and rotate 180 degrees. Reassemble onto the rack assembly and take note of the
arrows located on the top of the filter heads indicating water flow (which now
should be indicating a flow direction of right-to left).
Step 4: Remove the stainless steel UV reactor from the two plastic clamps located on the top of the rack. Carefully remove the top straps securing the reactor with the aid of a standard (slot) screwdriver). Rotate the reactor 180 degrees (with the inlet now facing to the left and the lamp connections located towards the right) and place back into the cell clamps and re affix the two top straps. In either the left or right configurations, to facilitate lamp removal, ensure there is enough space at the lamp connector end to safely remove the UV lamp and/or quartz sleeve (See Figure 3).
Installation
Step 1: Once both the orientation and location have been selected, securely fasten the rack to a suitable backing. As the rack system is extremely heavy when filled with water, it is imperative that the rack be mounted with suitable fasteners for the particular installation. Mounting to a drywall backing is not suitable, unless the rack is fastened directly to the wall studs.
Step 2: The use of a bypass assembly is recommended as it will allow you
to isolate the UV system This will allow for easier access in case maintenance
is required.
Step 3: For water supplies where the maximum flow rate is unknown, a flow
restrictor is recommended so that the rated flow of your particular AQUA FLO
system is not exceeded. The flow restrictor should be installed on the inlet
port of the reactor.
Step 4: It is recommended to have a licensed plumber connect the UV
reactor to the water supply and may be a requirement depending on where you
are located.
Step 5: Wrap the MNPT side of the flex hose with an appropriate amount of
teflon tape. Install the flex hose by first tightening the MNPT side of the
hose into the outlet of the filter housing. Be careful not to over tighten and
crack the housing. After the MNPT side is tightened, connect the FNPT side of
the hose to the stainless chamber. The gasket should compress and seal on the
chamber.
Step 6: Connect both the inlet and outlet to the rack system with the
applicable connections based on your particular plumbing requirements. The
inlet port of the filters is a 1” FNPT connection and the outlet port of the
UV reactor is a 1” MNPT connection.
Step 7: Once the system has been plumbed in, gently remove the quartz
sleeve from its packaging being careful not to touch the length with your
hands. The use of cotton gloves is recommended for this procedure as oils from
the hands can leave residue on the sleeve and lamp which can ultimately block
the UV light from getting to the water. Carefully slide the sleeve into the
reactor until you can feel it hit the opposite end of the reactor. Align the
sleeve so it centered along the length of the reactor, then gently push it in
to lock it into the internal centering springs in the far side of the reactor.
CAUTION: Pushing too hard when the sleeve is not aligned can damage the
centering springs. Slide the o-ring onto the sleeve until it is butted up
against the reactor (See Figure 4). Figure 4. Quartz Sleeve Installation
Step 8 : Hand tighten the provided gland nut over the quartz sleeve onto
the threaded end of the reactor. It has a positive stop to prevent over-
tightening. A firm force may be required to fully tighten the gland nut, but
DO NOT USE TOOLS for this step. Insert the provided stainless steel
compression spring into the quartz sleeve. The spring works with the lamp and
lamp connector to create the proper lamp alignment. PLEASE NOTE: DO NOT
install a UV lamp inside the quartz sleeve without the sleeve spring in place
Step 9: Install the filter cartridges in their appropriate housings. For
the AQUA FLO branded products, please refer to the chart located on page 12 of
this manual.
PLEASE NOTE: This chart indicates the correct cartridge position for the
default “left-hand” orientation with the water inlet located on the left side
of the rack system. If the orientation was switched, the cartridge placement
must also be switched. Once the cartridges are in place, use the supplied
filter wrench to “snug” the filter housing onto the filter head (See Figure
5).
Step 10: Install the optional UV sensor (purchased separately). Align the
flat portion so it faces the gland nut end and matches up with the half metal
lip on the sensor port (see Figure 6). Insert the sensor so it is fully seated
and hand tighten the sensor nut. Insert the sensor connector into the IEP port
located on the right side of the controller (Figure 7). For the sensor to be
recognized by the controller, the controller power must be plugged in last. Do
not plug the controller power cord in before the last step.
Step 11: The system is now ready for water flow. WARNING: Sudden filling of an empty reactor could potentially break the protective quartz sleeves. It is strongly recommended to gradually fill the empty reactor. Damage because of sudden filling is not covered under warranty.
Step 12: Always hold UV lamps by their ceramic ends, not by the lamp quartz. Remove the lamp from its packaging. Again, the use of cotton gloves is recommended. Remove the lamp key from the lamp’s connector and set it aside for the next step. Be careful to not touch the key’s exposed contacts. Insert the UV lamp into the reactor, being careful not to drop it.
When all plumbing connections have been completed, slowly turn on the water supply and check for leaks. Make sure the bypass valves are functioning properly and that the water is flowing through the reactor. The most common leak is from the o-ring not making a proper seal on the reactor. For new installations, review steps 6 and 7.
For older systems drain the reactor, remove the o-ring, dry it and reapply silicon grease. Reinstall the o-ring ensuring that it is properly sealed against the reactor and check again for leaks. To help vent the pressure from the system while the system is filling up with water, it is a good idea to physically depress the red pressure relief button located on the top of the filter head. Simply depress the button down, venting the air, until water appears at the button. If the system has two filters, perform this function on the housing closest to the water inlet first and then on the next filter in sequence.
WATER-HAMMER WARNING
Quartz sleeves can break inside the reactor if water-hammer occurs. Water
hammer is caused by sudden closing of valves elsewhere in the piping system.
It is strongly recommended to ensure that the piping and valve system is
designed to prevent water-hammer. Damage due to water-hammer is not covered by
warranty. Step 12: Always hold UV lamps by their ceramic ends, not by the lamp
quartz. Remove the lamp from its packaging. Again, the use of cotton gloves is
recommended. Remove the lamp key from the lamp’s connector and set it aside
for the next step. Be careful to not touch the key’s exposed contacts. Insert
the UV lamp into the reactor, being careful not to drop it.
Step 13: Install the lamp key into the controller (GEN5, GEN6 systems
only). The key always comes packaged with the lamp and sits on the connector.
With the key removed from the lamp, orient it so the label is upright and
facing you. The key will plug into the lamp key port on the right side of the
controller (Figure 9).
Step 14: Plug the lamp connector into the lamp. Note the keying for
proper alignment (see Figure 8a, 8b). Insert the lamp connector into the gland
nut and turn the connector approximately ¼ turn to lock the connector to the
gland nut as in Figure 9.
Step 15: Tighten the captive ground screw to the ground lug on the UV reactor to ensure proper grounding.
Step 16: Ensure all connections are sealed prior to pressurizing system,
including factory connections.
Step 17: Your system is now ready to be plugged into the appropriate GFCI
protected outlet. Refer to the following section before any water is allowed
to flow through the system.
Note : Installation of your AQUA FLO disinfection systems shall comply with applicable provincial/state & local regulations.
System Preparation
With a new installation, or any time the UV system is shut down for service,
without power, or is inoperative for any other reason, the lines in the home
or facility could be contaminated. Use the following steps to prepare the
lines throughout the entire home or facility.
Step 1: Check for and remove any “dead ends” in the lines throughout the
home as these can harbor dirt and debris. Plug in the UV system and wait until
it is ready for operation.
Step 2: Remove the filter cartridge from the last sump and fill it with
1-2 cups of household bleach (most are 5.25% chlorine). Replace the sump and
slowly turn on the water supply.
Step 3: At a water outlet, run the water until bleach can be smelled.
Repeat this for all faucets, toilets, shower heads, refrigerators, outdoor
taps, the washing machine, dishwasher, etc. at the home or facility. Once
finished, wait a minimum of 30 minutes before continuing.
Step 4: Reinstall the filter cartridge into the sump and flush the
chlorine solution by opening all faucets until chlorine can no longer be
detected. Your AQUA FLO system is ready to use.
Cleaning the Quartz Sleeve
Depending on the water quality, the quartz sleeve may require periodic
cleaning. At a minimum, the quartz sleeve should be cleaned on an annual
basis. The following steps outline a basic cleaning procedure.
Step 1: If a bypass assembly is installed, shut the inlet valve off to
prevent water flow through the system. Otherwise, turn off main water inlet
valve (and/or turn off the water pump).
Step 2: Disconnect power cord of UV system from electrical outlet.
Step 3: Release water pressure by opening a downstream faucet and then
close the outlet shut-off valve (if any). If there is no outlet shut-off
valve, expect water to drain from the system as the head pressure in the
system will cause the water to flow back down.
Step 4: Remove the captive ground screw from the ground lug on the UV
reactor.
Step 5: Remove the lamp connector from the reactor (gland nut) by pushing
the lamp connector in and turning it ¼ turn counter-clockwise. Disconnect the
lamp connector from the lamp.
CAUTION: the lamp may be hot!
Step 6: Being careful to touch only the ceramic ends, remove the lamp out
of the reactor.
Step 7: Unscrew the gland nut from the reactor exposing the end of the
quartz sleeve.
Step 8: Remove the quartz sleeve and o-ring by gently twisting and
pulling the quartz sleeve.
Step 9: Using a soft, lint-free cloth or towel wipe the sleeve down using
a commercial scale cleaner (i.e. CLR® or LIME-A-WAY®). This removes scaling or
iron deposits that may be on the outside of the quartz sleeve. Be careful not
to get any moisture or liquids inside of the sleeve.
Step 10: Dry the sleeve with separate cloth.
Step 11: Replace the o-ring and slide the sleeve back into the reactor
following steps 7 and 8 from the installation section of the manual.
Cleaning the UV Sensor
Depending on the water quality, the UV sensor may require periodic cleaning.
At a minimum, the UV sensor should be cleaning on an annual basis. The
following steps outline a basic cleaning procedure.
Step 1: If a bypass assembly is installed, shut the inlet valve off to
prevent water flow through the system. Otherwise, turn off main water inlet
valve (and/or turn off the water pump).
Step 2: Disconnect power cord of UV system from electrical outlet.
Step 3: Release water pressure by opening a downstream faucet and then
close the outlet shut-off valve (if any). If there is no outlet shut-off
valve, expect water to drain from the system as the head pressure in the
system will cause the water to flow back down.
Step 4: Place something under the reactor to catch any water that may
come out of the reactor during the removal of the UV sensor.
Step 5: Unscrew (counterclockwise) sensor nut from the reactor and pull
the sensor slowly out of the sensor port.
Step 6: Holding the sensor in your hand wipe the flat portion (sensor
face) of the sensor with isopropyl alcohol using a clean lint-free cloth.
Step 7: Replace sensor following step 9 from the installation section of
the manual.
Cleaning Mesh Strainer (GENH5-13R122 models only)
This system contains a washable mesh filter that is designed to prolong the
life of your subsequent filters. Actual water quality will impact required
cleaning frequency. The filter is designed to be cleaned in place without
turning off the water supply or depressurizing the system.
Step 1: Ensure that an appropriate drain line or bucket is below the system. The drain line should be no more than 2m (6ft) in length.
Step 2: Open the drain valve for 15-20 seconds. This generates a
pressure-drop in the filter that pushes the cartridge downward, automatically
reversing water flow from the inside (countercurrent) out of the cartridge.
This water flow in counter-current carries particles and substances deposited
on the cartridge to drain.
Step 3: Close the valve. After a couple of seconds, the internal spring
will return the cartridge to its service position.
If contamination is significant, the previous steps may not be sufficient to
fully clean the filter cartridge. In this case:
Step 1: Shut off water flow upstream and downstream of the system.
Step 2: Open the drain valve and vent(s) to drain the water from the
system.
Step 3: Open the filter by unscrewing the sump from the head using the
supplied wrench.
Step 4: Remove the cartridge, being careful not to lose the spring.
Step 5: Clean the cartridge under a jet of cold water and use a soft
brush to remove impurities.
Step 6: Insert the clean cartridge back in the sump.
Step 7: Screw the sump to the head.
Step 8: Close the vent(s) and drain ports.
Step 9: Slowly open the inlet valve into the system, then open the outlet
valve once the system is pressurized. If any damage is observed on the filter,
it should be replaced.
Filter Housing Drain Plug
In order to remove all water from the filter housing, unscrew the drain plug
from the underside of the housing.
Filter housing drain plug
Operation
AQUA FLO systems come with a feature laden controller that incorporates both the lamp driver (ballast) and control features in one water-tight case. Four main controllers are available for the AQUA FLO systems (depending on your model). All four models feature a power factor corrected, constant current lamp driver with a universal power input.
Please Note: While the LED or display screen is red and the buzzer is sounding the water from the system should NOT be consumed. If any water does pass through the system during this period, please follow the disinfection procedure as outlined in this manual before the water is consumed. For GEN4 and GEN5 systems, even though they have a visual and audible warning built into the controller, a green LED or status screen does not necessarily indicate that the water coming from this system is in fact potable (safe to drink). These systems do not measure the level of disinfection; they simply measure the “on-off” status of the lamp. Please have your waterchecked for microbiological contaminants on a regular basis.
Simplistic in operation, these systems feature a tri-colour LED that indicating system status and a 4-digit display to indicate lamp life remaining. Pressing the button will change the display to indicate total running time. When the UV lamp is on and within its operating age, the LED will be green. When the UV lamp is not on or the lamp life has expired, the LED will be illuminated red and an audible buzzer will be sounding. To remedy this condition, the UV lamp must be replaced with a new genuine AQUA FLO UV lamp.
A full colour LCD screen provides the user with a detailed description of the system’s performance in addition to providing any applicable fault messages and system diagnostics. The controllers used in both the GEN5 and GEN6 are identical. The difference is that the GEN6 series of products includes a UV intensity monitor. All GEN5 and GEN6 controllers include an “infinite expandability port” located on the right side of the controller. Simply plug in an optional UV sensor module into the expandability port of a GEN5 controller and the system will now monitor the UV intensity of the system!
GEN5 & GEN6 Power-up Sequence
On start up, the controller will run through a diagnostic start-up and the
sequence will be displayed as follows on the colour LCD: Next, the controller
checks for and initializes any optional modules that may be attached to the
system.
Optional Modules Check
A final module screen is displayed showing which specific modules were initialized. The controller then displays the lamp optimization screen for 60 seconds to allow the lamp to reach its optimum output. Finally, a final “start-up complete” screen is displayed. The system will now be ready to disinfect water flow.
GEN5 Operational Screens
On systems without the UV monitor, the default screen shows the AQUA FLO Home
Screen. At any point during operation the user is able to scroll through the
AQUA FLO Home Screen, Lamp life remaining, QR Code, Contact Info and
Maintenance Parts screens by pressing the button located on the front of the
controller.
GEN6 Operational Screens
On systems with the UV monitor, the system will display the same screens as on
the GEN5 except the UV Intensity replaces the home screen. The UV Intensity
screen displays the level of UV light detected by the sensor. UV intensity can
be affected by poor water quality, scaling on the quartz sleeve and/or sensor,
lamp failure or lamp expiring. The following screens show the UV Intensity
dropping.
Below 56%, the numbers and warning sign turn red and an audible chirp is given by the ballast every 15 seconds. Below 51%, the screen is solid red and a constant audible alarm is given. This alternates with a screen indicating “water may be unsafe for consumption”. With the solenoid module, the controller de-activates the solenoid valve, shutting off all water flow.
Lamp Countdown Sequence
The system counts down the number of days until a lamp change is required. At
thirty days remaining, the LED or display screen will change to a yellow
caution indicator. At seven days remaining, the system will additionally
repeat an audible chirp. Past the zero day threshold, the LED or display
screen changes to solid red with a continuous buzzer.
At any point during this sequence, the audible chirp or alarm can be deferred for seven days by holding the controller button down for a period of five seconds. The number of deferrals used will be displayed as below. Once the deferral expires, the alarm will sound once again. The deferral can be repeated up to three times. PLEASE NOTE: At any point after lamp expiration, the water may be unsafe for consumption and should not be consumed without another form of disinfection.
System Service Suggested
GEN5 and GEN6 controllers will display the System Service Suggested Screen
every 6 months to remind consumers to maintain both their UV and other
prefiltration. This will serve as a prompt only and will not put the system
into alarm. To clear this condition simply press the button located below the
screen.
Lamp Replacement (GEN4 systems)
After the lamp is expired, it must be replaced with the same part number as
indicated by the label on the reactor. Begin replacing the lamp by unplugging
the power for the controller, then refer to Installation, starting with step
11 (page 11) for instructions on installing the new lamp. To reset the timer
in the controller, firmly hold down the button on the controller for 10
seconds. The controller will read “rSt3”, “rSt2”, “rSt1” and then beep. The
button can now be released, the lamp countdown timer has been reset.
Lamp Replacement (GEN5 & GEN6 systems)
After the lamp is expired, it must be replaced with the same part number as
indicated on the Maintenance Parts screen or on the label on the reactor. With
the system powered down, remove and discard the lamp key from the controller.
The replacement lamp is packaged with a lamp key on the connector at the end
of the lamp. Remove the key from the lamp and place it in the controller.
Refer to Installation, starting with step 11 (page 11) for instructions on
installing the new lamp.
QR Codes
A QR code (Quick Response code) is a matrix barcode first designed for the
automotive industry. AQUA FLO uses the QR code to store a link to a specific
page on our website. Users with a camera phone equipped with the correct
reader application can scan the image of the QR code and over a wireless
network connect to a AQUA FLO web page in the phone’s browser. AQUA FLO’s QR
webpage has information on how to purchase replacement components as well as a
helpful video directory on system servicing (i.e. How to change a UV lamp or
quartz sleeve). To access the QR code on the AQUA FLO controller, press the
control button until the QR code screen appears.
System Troubleshooting
Hard Alarms
The following give a constant audible alarm. If present, the solenoid valve
is closed, and the 4-20, remote alarm and WiFi modules transmit the alarm.
Soft Alarms
The following remaining errors give a 15 second audible chirp only
Warning: After any hard alarm, the home or facility should be disinfected. Follow the steps under the “System Disinfection” heading. Boil Water Advisory: If any failure occurs on an AQUA FLO UV system, the water must not be used for human consumption until the system is returned to a safe operational mode. If the water is used for human consumption during this period, the water must be boiled (minimum 20 minutes at a full boil) prior to consumption.
Temperature Management Devices
Your AQUA FLO AQUA FLO system is designed to run continuously to ensure
optimal disinfection. However, during periods when no water is drawn through
the system, the energy from the disinfection process can cause the temperature
of the water inside the chamber to rise. In extreme situations elevated water
temperature or the fluctuation in temperature can lower the output of the UV
lamp. In these cases, or if the elevated water temperature is a nuisance, AQUA
FLO recommends one of the following forms of temperature management devices.
Cooling Fan
Designed for use on the AQUA FLO-HO systems, the fan runs continuously to cool
the water by forced convection. The long-life fan is powered independently
using a compact modular power adapter that operates from 90-265V (47-63Hz).
Order PN 40040009 (only fits GENH4/GENH5 systems).
Temperature Relief Valve (TRV)
On reaching a higher temperature, the TRV is designed to drain a small amount
of water to allow fresh, cooler water to enter the system. The TRV works
without power and comes complete with 10’ of drain line. Order PN 40040100 for
1” ports.
Expansion Modules
AQUA FLO controllers incorporate an “Infinite Expandability Port” (IEP) which
allows for expansion to the UV sensor and all other modules. Each module
(including the sensor) comes with both a male and female connection. Connect
any device to the controller and all subsequent devices are then connected
into the female end of last device added in a “daisy chain” configuration. The
following optional expansion modules are available for use on AQUA FLO UV
controllers. Contact your authorized distributor for purchasing information.
REMOTE ALARM CONNECTION MODULE
Allows for a connection to a remote device such as a buzzer, light, alarm
system, PLC, etc., via a pair of contacts. In normal operation the OK and COM
contacts will be connected, and in a fault condition (Low UV, Lamp fail, Power
Fail), the Fault and COM contacts will be connected. Maximum Contact Rating is
1A-120V AC/DC (use 16-22 AWG). Order PN 40040008.
SOLENOID CONNECTION MODULE: Connects a NORMALLY CLOSED line voltage solenoid valve to the system. On a non-monitored system, the solenoid will only close on a lamp failure error. On a monitored system, the solenoid is closed when the UV level drops below 50%. Also note that in cases where emergency use of untreated water is required, the controller can be placed into a manual override mode allowing for the flow of water in an alarm condition. Order PN 40040006. 4-20 mA MODULE: Outputs a 4-20mA signal of the UV output to a remote device such as a data logger or computer. Order PN 40040007.
The WiFi module and accompanying IoT application allows you to connect your UV system to a smart phone, tablet, computer or other connected platform. View system status, receive SMS or email messages of alarm conditions and monitor the health of your UV from anywhere via this connected platform. Connect the device via the APP found on Google Play or the APP Store. Connect your UV device to your router, download the software for your connected device and have peace of mind that your UV system is fully operational
AQUA FLO Rack-Mount UV System Specifications
AQUA FLO EQUIPMENT SPECIFICATIONS | |
---|---|
MODEL
| GEN4-8R1 (40030061N)
GEN5-8R1 (40030050N)
| GEN4-8R12 (40030062N)
GEN5-8R12 (40030051N)
| GENH4-13R2 (40030063N)
GENH5-13R2 (40030052N)
| GENH4-13R22 (40030064N)
GENH5-13R22 (40030053N)
| ****
GENH4-13R122 GENH5- 13R122
| ****
GENH4-13R222 GENH5- 13R222
Flow Rate (@30mJ/cm2)
| 8.0 gpm| 15.0 gpm
30.3 lpm| 56.8 lpm
1.82 m3/hr| 3.4 m3/hr
Flow Rate (@40mJ/cm2)
| 5.6 gpm| 12 gpm
21.2 lpm| 45.4 lpm
1.3 m3/hr| 2.7 m3/hr
Filter Housing – 1| 5 micron sediment| 5 micron sediment| 5 micron sediment| 5
micron sediment| 90 micron mesh strainer| 5 micron sediment
Filter Housing – 2
| ****
N/A
| high capacity carbon| ****
N/A
| high capacity carbon| 5 micron sediment 36287| ****
scale reduction
Filter Housing – 3| N/A| N/A| N/A| N/A| high capacity carbon| high capacity
carbon
Port Size| 1”FNPT (filter side) / 1” MNPT (UV side)
Electrical| 90-265V/50-60Hz.
Plug Type| American: NEMA 5-15P
Lamp Power (Watts)| 20 (standard-output lamp)| 45 (high-output lamp)
Power (Watts)| 23 (21 @ 230V.)| 57 (48 @ 230V.)
Replacement Lamp| 40040096| 40040020
Replacement Sleeve| 40040042
Reactor Dimensions| 8.9 x 50.8 cm (3.5 x 20”)
Chamber Material| Polished 316L Stainless Steel, A249 Pressure Rated Tubing
(to ASME specs)
Controller Dimensions| 17.2 x 9.2 x 7.6 cm (6.8 x 3.6 x 3”)| 21.8 x 10.7 x 8.9
cm
(8.6 x 4.2 x 3.5”)
Operating Pressure| 0.7-6.9 bar (10-100 psi)
Operating Water Temperature| 2-40° C (36-104° F)
UV Monitor| OPTIONAL (optional UV module (40040002) for GEN5, (40040003) for
GENH5 sold separately)
Solenoid Output| YES (optional solenoid module (40040006) sold separately)
Dry Contacts| YES (remote alarm module (40040008) sold separately)
4-20mA Output| YES (4-20mA module (40040007) sold separately)
Lamp Change Reminder| YES (audible & visual)
Lamp Out Indicator| YES (audible & visual)
Shipping Weight| 11.3 kg (24.8 lbs)| 19.0 kg (41.8 lbs)| 16.4 kg (36.2 lbs)|
20.3 kg (44.8 lbs)| 23.13 kg (51 lbs)| 27.21 kg (60 lbs)
Limited Warranty Statement
Products manufactured by AQUA FLO are warranted to the original user only to
be free of defects in material and workmanship for a period as specified
below. This warranty only applies to the original purchaser and is not
transferable.
UV SYSTEMS
Ten (10) year Limited Warranty on the stainless steel reactors, from the date
of original purchase, or installation (proper documentation required for
verification).
ELECTRONICS
Three (3) year Limited Warranty on the ballasts and controllers, from the date
of original purchase, or installation (proper documentation required for
verification).
UV LAMPS, UV SENSORS & QUARTZ SLEEVES
One (1) year Limited Warranty on all AQUA FLO ultraviolet lamps, UV sensors
and quartz sleeves from the date of original purchase, or installation (proper
documentation required for verification). AQUA FLO warrants that it will
repair, replace or refund, at AQUA FLO’s sole option, any ultraviolet system
or component that is defective in materials or workmanship for the period as
outlined above, subject to the “Limitations of Warranty” as outlined below.
AQUA FLO’s liability under this warranty shall be limited to repairing or
replacing at AQUA FLO’s option, without charge, F.O.B. AQUA FLO’s factory or
authorized service depot, any product that AQUA FLO manufactures.
AQUA FLO will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by AQUA FLO are subject to the warranty provided by the manufacturer of said products and not by AQUA FLO’s warranty. AQUA FLO will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with AQUA FLO’s printed installation and operating instructions.
LIMITATIONS OF WARRANTY
This warranty does not apply to any of the following:
- Water Quality Parameters lie outside of the following ranges
- Hardness > 120 mg/L (7 gpg)
- Iron > 0.3 mg/L (ppm)
- Manganese > 0.05 mg/L (ppm)
- Tannins > 0.1 mg/L (ppm)
- Turbidity > 1 NTU
- Transmittance (UVT) < 75%
- A product that has been incorrectly installed according to the technical installation manual.
- A product that has been modified in any manner, unless approved by the manufacturer.
- A product where the serial number has been altered defaced or removed.
- Damage caused by the use of parts that are not compatible, suitable and/or authorized by AQUA FLO for use with the product (e.g. non-original lamps or sleeves).
- Damage caused during shipment of the product.
- Water damage is found inside ballast housing or controllers.
- Product is installed outdoors in direct contact with the environment (rain).
- Product is installed in freezing temperatures.
- Product is used in conditions that exceed AQUA FLO’s specifications.
TO GET WARRANTY SERVICE
Please contact the Dealer or Distributor where the product was originally
purchased to obtain
service under this warranty. Your Dealer / Distributor will obtain a Warranty
Return Authorization and will then need to return the product to Canature,
together with proof of purchase and
installation date, failure date, and supporting installation data. Any
defective product to be returned must be sent freight prepaid.
CANATURE WATERGROUP INC. WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY MADE BY CANATURE WITH RESPECT TO THIS ULTRAVIOLET DISINFECTION PRODUCT, AND IS GIVEN IN LIEU OF ANY OTHER WARRANTY. TO THE EXTENT ALLOWED BY APPLICABLE LAW, ANY AND ALL EXPRESS OR IMPLIED WARRANTIES NOT SET FORTH HEREIN ARE WAIVED AND DISCLAIMED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE.
CANATURE’S LIABILITY
UNDER THIS LIMITED WARRANTY IS LIMITED SOLELY TO THOSE LIABILITIES SET FORTH
ABOVE. IN THE EVENT THAT ANY PROVISION OF THIS LIMITED WARRANTY SHOULD BE
FOUND TO BE OR BECOME INVALID OR UNENFORCEABLE UNDER APPLICABLE LAW, THE
REMAINING TERMS AND CONDITIONS HEREOF SHALL REMAIN IN FULL FORCE AND EFFECT
AND SUCH INVALID OR UNENFORCEABLE PROVISION SHALL BE CONSTRUED IN SUCH A
MANNER AS TO BE VALID AND ENFORCEABLE.
Warranty Registration
It is imperative that you complete the warranty registration process. This not
only registers your UV disinfection system for the provided manufacturer’s
warranty, but also allows the factory to provide you with any important
product updates or technical bulletins concerning your product. The
registration process is a simple process and can ONLY be done online at www
.uv-warranty.com. Please ensure that ALL
information is filled in, including a valid e-mail address.
PLEASE NOTE: This information is for the sole purpose of technical
support for your disinfection system and will not be used, or sold, to any
other organization for any other purpose.
Canature WaterGroup Canada Inc. Canature WaterGroup U.S.A. Inc.
855 Park St. Unit 1 9760 Mayflower Park Drive
Regina, SK, S4N 6M1 Suite 110
CANADA Carmel, IN 46032 USA
Toll Free: 877-288-9888 Toll Free:
877-288-9888
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>