Z-D 15E Active Harmonic Filter with SiC Technology Instruction Manual

June 16, 2024
Z-D

15E Active Harmonic Filter with SiC Technology

Product Information

Specifications

  • Manufacturer: ZIEHL-ABEGG SE
  • Product: Active Harmonic Filter
  • Technology: SiC
  • Model Numbers: Z-D-15E-.., Z-D-35E-.., Z-D-55E-..

General

The active harmonic filter is a product of ZIEHL-ABEGG SE. The
manufacturer is referred to as ZIEHLABEGG in the remainder of these
operating instructions.

Compliance with the following instructions is mandatory to
ensure the functionality and safety of the product. If the
following instructions given especially but not limited for general
safety, transport, storage, mounting, operating conditions,
start-up, maintenance, repair, cleaning and disposal / recycling
are not observed, the product may not operate safely and may cause
a hazard to the life and limb of users and third parties.

Deviations from the following requirements may therefore lead
both to the loss of the statutory material defect liability rights
and to the liability of the buyer for the product that has become
unsafe due to the deviation from the specifications.

Meaning of the Instructions

These instructions instruct you on how to use the specified
product safely. They include safety instructions and information
that is necessary for fault-free operation.

Validity

This instruction applies to:

  • Active harmonic filter: Z-D-15E-..; Z-D-35E-.., Z-D-55E-..

The used active Harmonic Filter is recognizable from the type
designation (see rating plate). These operating instructions apply
only to a specific product and under no circumstances to the
complete system. The instructions contain information for your
guidance. No guarantee is provided with regard to the accuracy of
any information and no legal claims may be derived. Reproduction of
this information, or extracts thereof, is allowed only with written
approval.

Terms and Definitions

  • Filter module: For “Filter module Z-D-15/35/55E-..”, the term
    “Filter module” or “active harmonic filter” will be used.

  • Drive controller: For the non-linear loads which are used
    together with the power feedback unit, the term “Controller” is
    used.

  • Drive system: For a drive system with harmonic filter, power
    feedback units, controller, and other components of the drive
    system, the term “Drive system” is used.

Product Usage Instructions

Safety Instructions

Ensure that you read and understand all safety instructions
before operating the active harmonic filter:

  • Do not operate the product if it is damaged or if there are any
    visible signs of wear.

  • Only use the product for its intended purpose.

  • Do not modify or tamper with the product.

  • Ensure that the product is properly grounded.

  • Follow all local electrical regulations and codes.

Installation

Follow these steps to install the active harmonic filter:

  1. Choose a suitable location for the filter module.

  2. Ensure that there is enough space around the filter module for
    proper ventilation.

  3. Mount the filter module securely using the provided mounting
    brackets.

  4. Connect the input and output cables to the appropriate
    terminals on the filter module.

  5. Ensure that all connections are tight and secure.

Operation

To operate the active harmonic filter:

  1. Ensure that the power supply to the filter module is turned
    off.

  2. Turn on the power supply and monitor the indicator lights on
    the filter module.

  3. If the indicator lights are functioning properly, the filter
    module is ready for operation.

  4. Monitor the performance of the filter module and make any
    necessary adjustments as required.

Maintenance

Regular maintenance is required to ensure the optimal
performance of the active harmonic filter:

  • Inspect the filter module regularly for any signs of damage or
    wear.

  • Clean the filter module as necessary to remove any dust or
    debris.

  • Check all connections and tighten any loose terminals.

  • Refer to the manufacturer’s guidelines for any specific
    maintenance procedures.

FAQ

Error description and repair

8.1 What does this chapter contain?

This chapter provides information on error descriptions and
repair procedures for the active harmonic filter.

8.2 What are some typical errors and
repairs?

This section lists common errors that may occur with the active
harmonic filter and provides guidance on how to repair them.

Z-D-15/35/55E-..
Active Harmonic Filter with SiC Technology Operating Instructions
Index 002 Keep for reference!


L-BAL-E321-D 2021/11 Index 002

Operating Instructions Z-D-15/35/55E-..


Content
1 General ……………………………………………………………………………………………………………………………4 1.1 Manufacturer……………………………………………………………………………………………………………. 4 1.2 Meaning of the instructions………………………………………………………………………………………… 4 1.3 Validity ……………………………………………………………………………………………………………………. 4 1.4 Terms and definitions ……………………………………………………………………………………………….. 4 1.5 Intended use ……………………………………………………………………………………………………………. 5 1.6 Improper use……………………………………………………………………………………………………………. 5
2 Safety precautions …………………………………………………………………………………………………………..6 2.1 What this chapter contains ………………………………………………………………………………………… 6 2.2 Safety definitions and warning symbols ………………………………………………………………………. 6 2.3 General safety information ………………………………………………………………………………………… 8 2.4 Safety responsible persons ……………………………………………………………………………………… 10 2.5 Specification of wires and cables ……………………………………………………………………………… 10 2.6 Rest danger …………………………………………………………………………………………………………… 10
3 Fast start ……………………………………………………………………………………………………………………… 11 3.1 What this chapter contains ………………………………………………………………………………………. 11 3.2 First check when unpacking …………………………………………………………………………………….. 11 3.3 Suitability for the application …………………………………………………………………………………….. 11 3.4 Environment conditions …………………………………………………………………………………………… 11 3.5 Check of the installation ………………………………………………………………………………………….. 12 3.6 Simplified commissioning ………………………………………………………………………………………… 12
4 Product-Overview…………………………………………………………………………………………………………. 13 4.1 What this chapter contains ………………………………………………………………………………………. 13 4.2 Area of application / Notes on use: …………………………………………………………………………… 13 4.3 Function principle: ………………………………………………………………………………………………….. 13 4.4 Label code …………………………………………………………………………………………………………….. 13 4.5 Rating plate……………………………………………………………………………………………………………. 14 4.6 Storage …………………………………………………………………………………………………………………. 15 4.7 Transport and handling……………………………………………………………………………………………. 15
5 Installation instructions………………………………………………………………………………………………… 16 5.1 What this chapter contains ………………………………………………………………………………………. 16 5.2 Mechanical drawings ………………………………………………………………………………………………. 16 5.2.1 Active harmonic filter Z-D-15E-.. …………………………………………………………………………… 16 5.2.2 Active harmonic filter Z-D-35E-.. and Z-D-55E-.. …………………………………………………….. 17 5.2.3 Mechanical installation ………………………………………………………………………………………… 18


L-BAL-E321-GB 2021/11 Index 002

2/44

Operating Instructions Z-D-15/35/55E-..


5.3 Electrical wiring………………………………………………………………………………………………………. 19 5.3.1 EMC directive …………………………………………………………………………………………………….. 20 5.3.2 Voltage supply ……………………………………………………………………………………………………. 20 5.3.3 LED status display ………………………………………………………………………………………………. 21 5.3.4 Current transformer wiring ……………………………………………………………………………………. 22 5.3.5 Active harmonic filter in parallel wiring …………………………………………………………………… 23 5.3.6 Selection of CT (current transformers) …………………………………………………………………… 24 5.3.7 Wiring when using current transformers with high ratio ……………………………………………. 24 5.3.8 EPO and Z-D-15/35/55E-.. ID……………………………………………………………………………….. 25 5.3.9 Input and output interface …………………………………………………………………………………….. 26
6 Supervision- and control software ………………………………………………………………………………… 27 6.1 What this chapter contains ………………………………………………………………………………………. 27 6.2 Introduction in the system………………………………………………………………………………………… 27 6.2.1 Log In ………………………………………………………………………………………………………………… 27 6.2.2 Home ………………………………………………………………………………………………………………… 28 6.2.3 Initialize communication ………………………………………………………………………………………. 29 6.2.4 System configuration …………………………………………………………………………………………… 30 6.2.5 Data ………………………………………………………………………………………………………………….. 36 6.2.6 Procedure to power on ………………………………………………………………………………………… 36
7 Maintenance and check of hardware …………………………………………………………………………….. 37 7.1 What this chapter contains ………………………………………………………………………………………. 37 7.2 Periodicity of maintenance ………………………………………………………………………………………. 37 7.3 Disposal/Recycling …………………………………………………………………………………………………. 38
8 Error description and repair………………………………………………………………………………………….. 39 8.1 What this chapter contains ………………………………………………………………………………………. 39 8.2 Typical errors and repairs ………………………………………………………………………………………… 39
9 Enclosure …………………………………………………………………………………………………………………….. 40 9.1 Technical Data……………………………………………………………………………………………………….. 40 9.1.1 Technical Data Active harmonic filter Z-D-15E-.. ……………………………………………………. 41 9.1.2 Technical Data Active harmonic filter Z-D-35E-.. ……………………………………………………. 42 9.1.3 Technical Data Active harmonic filter Z-D-55E-.. ……………………………………………………. 43 9.2 Service information …………………………………………………………………………………………………. 44


L-BAL-E321-GB 2021/11 Index 002

3/44

Operating Instructions Z-D-15/35/55E-..

General


1 General

1.1 Manufacturer
The active harmonic filter is a product of ZIEHL-ABEGG SE. The manufacturer is referred to as ZIEHLABEGG in the remainder of these operating instructions.
ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau phone: +49 (0) 7940 16-0 [email protected] http://www.ziehl-abegg.com
Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the following instructions given especially but not limited for general safety, transport, storage, mounting, operating conditions, start-up, maintenance, repair, cleaning and disposal / recycling are not observed, the product may not operate safely and may cause a hazard to the life and limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specifications.
1.2 Meaning of the instructions
These instructions instruct you on how to use the specified product safely. They include safety instructions and information that is necessary for fault- free operation.
· Store the instructions safely on the product for further use. They must be passed on to every subsequent owner, user or end customer.
· Ensure that all persons performing activities on the product can easily view the instructions at any time.

1.3 Validity
This instruction applies to:
Active harmonic filter: Z-D-15E-..; Z-D-35E-.., Z-D-55E-..
The used active Harmonic Filter is recognizable from the type designation (see rating plate). These operating instructions apply only to a specific product and under no circumstances to the complete system. The instructions contain information for your guidance. No guarantee is provided with regard to the accuracy of any information and no legal claims may be derived. Reproduction of this information, or extracts thereof, is allowed only with written approval.

1.4 Terms and definitions
Filter module For ,,Filter module Z-D-15/35/55E-..” the term ,,Filter module” or active harmonic filter will be used. Drive controller For the non-linear loads which are used together with the power feedback unit in the following the term ,,Controller” is used Drive system For a drive system with harmonic filter, power feedback units, controller and other components of the drive system in the following the term ,,Drive system” is used.


L-BAL-E321-GB 2021/11 Index 002

4/44

Operating Instructions Z-D-15/35/55E-..

General


1.5 Intended use

Active harmonic filter are used for reduction of harmonics from for example 6-puls rectifier, frequency converter or uninterruptible power sources (UPS). Filter are used with further equipment and are implemented within an electrical system. Active harmonic filter are intended to be installed in an electrical panel or similar electrical room. Active harmonic filter are not household appliances and may be considered for commercial use only. Any other use in not allowed.

The manufacturer shall not be liable for any damage resulting from improper use. The user bears the sole risk.

The intended use also includes:
· Compliance with technical data, application and performance limits according to the data sheet, order confirmation and other specifications
· Compliance with the prescribed intervals for all inspection work · Persons performing work completely reading and understanding this documentation and
especially the safety instructions chapter
1.6 Improper use
Any use that is not described in the intended use is improper and therefore impermissible.
The following foreseeable types of misuse are also improper:
· Unauthorized changes to the active harmonic filter · Operating error · Improper work on and with the harmonic filter · Reversing the current direction of the current transformers
Use:
– as a safety component or for performance of safety related functions as defined in EN ISO 13849- 1
– as an independent household appliance – in low voltage systems with special fire risks in compliance with IEC 60364-4-42 – in explosive atmosphere – proximity to flammable substances or objects – in open operating rooms
Operation:
– use outside the operating data approved in the data sheet, the order confirmation and in other provided specifications
– in a way that personal injury or material damage may occur in the event of malfunction or failure
– with a load that leads to higher power consumption and current values than specified on the rating plate
– with vibrations


L-BAL-E321-GB 2021/11 Index 002

5/44

Operating Instructions Z-D-15/35/55E-..

Safety precautions


2 Safety precautions

2.1 What this chapter contains
Please read this manual carefully and follow all safety precautions before moving, installing, operating and servicing the active harmonic filter, if ignored, physical injury or death may occur, or damage may occur to the devices.
If any physical injury, death, or damage to the devices occurs for ignoring to the safety precautions in the manual, our company will not be responsible for any damages and we are not legally bound in any manner.

2.2 Safety definitions and warning symbols
All Safety definitions have a uniform layout:
– The pictogram shows the kind of danger – The signal word characterizes the severeness of danger – The note describes the danger and suggest how to avoid the danger.
Signal Word
Note

Warning of personal injury

Used Pictogram Imminent danger by Danger! electricity

Warning of an

Warning

imminent danger

Instruction Warns of an immediate imminent danger. In case of disrespect, death or severe injury may happen.
Warns of a possible, very dangerous situation. In case of disrespect, death or severe injury may happen.

Dangerous situation

Caution!

Warns of a possible, dangerous situation. In case of disrespect, minor injury may happen.

Warning of hot surface

Warning of property damages
Usefull information and and hints for using

STOP

Harmful situation

Information

Warning! Warns of touching of a hot surface. In case of disrespect, burnings may happen

Stop!

Warns of possible property damage. In
case of disrespect, the system and it’s environment may be damaged

Note!

Marks a general, useful hint. If it is observed, usage of the system will be easier


L-BAL-E321-GB 2021/11 Index 002

6/44

Operating Instructions Z-D-15/35/55E-..

Safety precautions


Safety and application notes for drive systems
(following Low Voltage Directive 2006/95/EG)

1. General During operation, filter modules may have, according to their type of protection, live, bare, in some cases also movable or rotating parts as well as hot surfaces. Non ­authorized removal of required cover, inappropriate use, incorrect installation or operation, creates the risk of severe injury to persons or damage to material assets.
Further information can be obtained from the documentation. All operations concerning transport, installation and commissioning as well as maintenance must be carried out by qualified, skilled personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC-Report 664 or DIN VDE 0110 and national regulations for the preventions of accidents must be observed). According to this basic safety information qualified skilled personnel are persons who are familiar with the erection, assembly, commissioning and operation of the product and who have the qualifications necessary for their occupation.
2. Application as directed Filter modules are components which are designed for installation in electrical systems or machinery.
When installing in machines, commissioning of the filter module (i.e. the starting of operation as directed) is prohibited until it is proven, that the machine corresponds to the regulations of the EC Directive (2006/42/EG) (Machinery Directive); EN 60204 must be observed. Commissioning (i.e. starting operation as directed) is only allowed when there is compliance with the EMCDirective (2004/108/EG). The filter modules meet the requirements of the Low-Voltage Directive (2006/95/EEC). The harmonized standards of the prEN 50178/DIN VDE 0160 series together with EN 60439-1/DIN VDE 0660 part 500 and EN 60146/DIN VDE 0558 are applicable for the power feedback unit. The technical data and information on the connection conditions must be obtained from the nameplate and the documentation and must be observed in all cases.
3. Transport, storage Notes on transport, storage and appropriate handling must be observed. At non-observance any warranty expires. The filter module unit has to be protected from inadmissible stress. The transport is only valid in original packaging and in the thereon by pictograms marked transport position. In particular during transport and handling no components are allowed to be bent and / or isolating distances may not be altered. The modules are equipped with electrostatic sensitive devices, which may be damaged by improper handling. Therefore, it has to be avoided to get in contact with electronic components. If electronic components are damaged mechanically the module must not be put into operation, as it cannot be ensured, that all relevant standards.
This safety information must be kept!

4. Erection The modules must be erected and cooled according to the regulations of the corresponding documentation. The filter modules must be protected from inappropriate loads. Particularly during transport and handling, components must not be bent and / or isolating distances must not be changed. Touching of electronic components and contacts must be avoided. Filter modules contain electro-statically sensitive components which can easily be damaged by inappropriate handling. Electrical components must not be damaged or destroyed mechanically (health risk are possible!).
5. Electrical Connection When working on live filter modules, the valid national regulations for the prevention of accidents (e.g. VBG 4) must be observed. Before any installation or connection works, the plant has to be switched off and to be secured properly. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross- sections, fuses, PEconnection). More detailed information is included in the documentation. When using the filter module with controllers without safe separation from the supply line (to VDE 0100) all control wiring has to be include in further protective measures (e.g. double insulated or shielded, grounded and insulated) . Notes concerning the installation in compliance with EMC ­ such as screening, grounding, arrangement of filters and laying of cables ­ are included in the chapter installation of this documentation. These notes must be also observed in all cases for filter modules with the CE-mark. The compliance with the required limit values demanded by the EMC legislation is the responsibility of the manufacturer of the system or machine.
6. Operation Systems where filter modules are installed, if applicable, have to be equipped with additional monitoring and protective devices according to the valid safety regulations e.g. law on technical tools, regulations for the prevention of accidents, etc.. After disconnecting the filter module the supply voltage, live parts of the filter module and power connections must not be touched immediately, because of possibly charged capacitors. For this, observe the corresponding labels on the drive controllers.
During operation, all covers and doors must be closed
7. Maintenance and service The manufacturer’s documentation must be observed.
The product-specific safety and application notes in these Operating Instructions must also be observed!!


L-BAL-E321-GB 2021/11 Index 002

7/44

Operating Instructions Z-D-15/35/55E-..

Safety precautions


2.3 General safety information

· These safety regulations are not entitled to completeness. In case of questions please contact

our technicians.

· When commissioning the filter module is compliant with the state of the art. The filter module

generally allows safe operation.

· The statements of this manual describe the attributes of the products without guaranteeing

them.

· The filter module unit may expose persons, the power feedback units itself and other material

to danger, if

– non-qualified personal works at and with the filter module

– the filter module is used in opposite to its purpose.

· Filter modules have to be projected in a way, that they fulfil their function and don’t expose

persons to danger, if they are mounted correctly and are used in accordance with their purpose.

This applies also for the interplay with the whole plant.

· The units, operational data and circuit details described in this manual have to be understood

analogously and have to be checked for transferability to each application.

· Use the drive system only in flawless condition.

· Modifications of the filter modules without consultation of a ZIEHL-ABEGG- technician are not

allowed generally

.

· The warranty given by us expires, if the unit is modified or (even partially) dismantled or if it is

used in contradiction to our instructions.

· The constructor of the plant, who has to know the technical guidelines, bears the responsibility

for the correct selection and arrangement of the electrical components.

· Putting into operation of the power feedback unit is only admissible at VDE- conform nets of

electrical power supply. Non observance may damage the device!

· In accordance with the corresponding standards and guidelines the operation on even for a

short time over-compensated networks (cos1) respectively on un-choked compensation-units

is not admissible. If this is done nevertheless, overvoltage will occur (caused by oscillating

currents), which may damage all connected components, especially electronic units like

controllers and filter modules.


L-BAL-E321-GB 2021/11 Index 002

8/44

Operating Instructions Z-D-15/35/55E-..

Safety precautions


STOP

Stop!
Undisturbed and safe operation of the filter module is possible only if the hints of this instruction are
observed.

If they are not observed, in some cases malfunctions and damages may occur:
– Observe specified mains voltage. – Power and control cables must be installed with distance (> 15cm) – Use screened / twisted control wires. Connect screen to PE at both ends! – Ensure good grounding of drive, motor and filter module. Connect the screen of power cables
to ground extensive at both ends.(remove lacquer)! – Observe star layout for grounding of cabinets and systems (AVOID ground loops!) – The filter module is designed for fixed mounting and electrical connection.
The ground wire must have a minimum cross section of 2,5mm² (depending of filter module size).


L-BAL-E321-GB 2021/11 Index 002

9/44

Operating Instructions Z-D-15/35/55E-..

Safety precautions


2.4 Safety responsible persons

Operator
– The operator is any natural or legal person who is using the system or let someone use the system.
– The operator and / or the safety responsible person must take care for: – all relevant rules , guidelines and laws must be observed – only qualified personnel will work with and on the system – the manual will be available for the personnel during working at the system. – unqualified personnel will be forbidden to work on the system.

STOP

Qualified personal Stop!
Qualified technical personnel are persons, who – have appropriate training, knowledge and experience – are informed about relevant specifications, standards and accident prevention regulations – are trained in the installation and operation of relevant systems – are able to recognize and avoid possible dangers (Definition for qualified personnel in accordance to IEC 364)

2.5 Specification of wires and cables
The used wires and cables must comply the relevant standards at place of installation and operation. Rules regarding minimum PE crass section must be observed in any case!
2.6 Rest danger
Danger! After switching off the mains supply all terminals may stay life for up to ten minutes!


L-BAL-E321-GB 2021/11 Index 002

10/44

Operating Instructions Z-D-15/35/55E-..

Fast start


3 Fast start

3.1 What this chapter contains
This chapter describes the basic guidelines for installation and commissioning of the active harmonic filter, which should be observed for fast and easy usage.

3.2 First check when unpacking

Please check the goods during and immediately after receipt on the following characteristics:

1

Please check the packaging for intactness and dryness. If this is not the case, immediately get in contact with the sender.

2

Please check if the type-code on the packaging matches the ordered product. If this is not the case, immediately get in contact with the sender.

3

Please check for any kind of moisture inside the packaging and for any kind of damages at the product. If this is not the case, immediately get in contact with the sender.

4

Please check if the type code on the packaging matches the data on the rating plate. If this is not the case, immediately get in contact with the sender.

5

Please check if the packaging contains all accessories including manual. If this is not the case, immediately get in contact with the sender.

3.3 Suitability for the application
Please check if all current transformers and the the adjusted parameters asre suitable for the application before you start up the active harmonic filter for the first time.

3.4 Environment conditions

Please check and consider the following environment conditions before starting the installation:

Check for the ambient temperature to be below 40 °C. If it is higher, consider derating of

1

3%/K. This would mean that a Z-D-55E-.. with rated current 55 A at 45 °C must be loaded with not more than 46,75 A. Operation above 50 °C is not acceptable.

Check for the ambient temperature to be above -10 °C. If it is lower, a heater must be

2

installed. Hint: Ambient temperature means the temperature inside the cabinet with the Z-D-15/35/55E-

Check for the installation height to be below 1000m above sea level. If it is higher, consider 3. derating of 1%/100m. This would mean that a Z-D-35E-..with rated current 35 A at 2000mC
must be loaded with not more than 31,5 A. Operation above 4000 m is not acceptable.

Check for ambient moisture to be below 90%. If the moisture is higher, measures for 4 reduction of moisture must be taken.

Check for no direct sunlight exposition of the Z-D-15/35/55E-.. and for no dust impact. If that 5 could happen, countermeasures must be taken.


L-BAL-E321-GB 2021/11 Index 002

11/44

Operating Instructions Z-D-15/35/55E-..

Fast start


3.5 Check of the installation

Perform this check AFTER installation but BEFORE first powering up:

Check the correct mounting and wiring of the current transformer (CT). The wired used must 1 comply with the requirements of components (CT, Z-D-15/35/55E-..) and of place of installation.

Check that power and controls wires are installed separately and that EMC guidelines are observed.

4

Check the grounding of the system and components for compliance with guidelines and requirements of the drives.

5

Check if the clearance between the components comply with the requirements of these instructions.

6

Check if the installation meets the requirements of these instructions. The active harmonic filter must be mounted in an upright position.

3.6 Simplified commissioning
The active harmonic filter Z-D-15/35/55E-.. is a largely automated product for reduction of harmonics. Complete the simplified commissioning as described below BEFORE first usage:
1 Check all parameters of the monitoring system on your computer 2 Check the correct wiring of the current transformers 3 If several products are used in parallel, check for compliant adjustment of the parameters.
Hint: If the result of harmonic compensation is not satisfying, please check the parameters once again first, wiring (especially polarity) of the current transformers second. If everything is o.k., modify the phase angel of the system to achieve even better results.


L-BAL-E321-GB 2021/11 Index 002

12/44

Operating Instructions Z-D-15/35/55E-..

Product-Overview


4 Product-Overview

4.1 What this chapter contains
This chapter describes the function principle, the characteristics of the product and dimensions.
4.2 Area of application / Notes on use:
The active harmonic filter is intended to reduce harmonics of certain B6 rectifiers or frequency converters in electrical power supply networks. Its intended to be used for installation in a machine or for assembly with other components to build a machine. Active harmonic filters are electrical equipment for installation in control cabinets or similar closed operating rooms. Active harmonic filters are not household appliances, but are designed as components exclusively for commercial use.
Possible application examples: – Reduction of harmonics in public and non- public networks – Reduction of harmonics in industry and business networks

4.3 Function principle:
The following drawings show the principle, simplified setup for active harmonic filters.

Topology of Z-D-15/35/55E-..

4.4 Label code

The type code is part of the rating plate and contains important information about the active harmonic filter.

Examples for a type code designation with explanation

Z –

Nr.

D – 15

Detaillierte Bezeichnung

E – 060

Designation for product category accessoriesr

Designation for 3 phase alternate current

Rated current of active harmonic filter = 15 A

Designation for assembly device (Protection rating IP20)


L-BAL-E321-GB 2021/11 Index 002

13/44

Operating Instructions Z-D-15/35/55E-..

Product-Overview


Rated current of current transformer = 60 A

4.5 Rating plate
The rating plate carries the technical data valid for the delivered product. Example for rating plate active harmonic filter

6

7

8

9

1 2

3

11

4 12

13 5

10

Nr. Designation

Nr. Designation

ZIEHL-ABEGG related data

UL related data

1 Part number ZIEHL-ABEGG SE

11 Motor identification UL

2 Series number

12 Rated voltage, Rated frequency, Rated current,

3 Rated voltage, Rated frequency, Rated current,

13 Max. ambient temperature authorisation at rated power

4 Max. ambient temperature at rated current Protection rating

5 Components of part number Type of active filter Rated currrent of CT Series number of coresponding CT

6 Date of manufacture

7 Type designation of active harmonic filter including the coresponding CT

8 Weight

9 Barcode part number

10 European mark of conformity


L-BAL-E321-GB 2021/11 Index 002

14/44

Operating Instructions Z-D-15/35/55E-..

Product-Overview


4.6 Storage

Store correctly:

· Store the product in the original packaging in a dry and weatherproof location and protect it from dirt and weather until final installation.
· Make sure the environment is dry, vibration-free and condensation-free. Prevent formation of condensation inside the product and packaging.
· Avoid extreme stresses due to heat, cold or moisture (see technical data for the temperature range for storage and transport). Recommended values: Temperature 0 °C to 40 °C, max. relative humidity 60 %.

4.7 Transport and handling
Improper transport can cause damage to the product and its accessories, which shortens the product service life and/or impair its function.
Transport correctly:
· Transport active harmonic filter in the original packaging. · Only transport if protected against weather; unprotected transport is not allowed. Moisture
penetration into the packaging is not allowed. · Avoid impacts and bumps during transport and observe the limit values from ISTA 3E and ISTA
3B. · When transporting a device with an installed active harmonic filter, do not exceed the limit values
stipulated in EN 60721-3-2, Category 2M1 for vibrations and impacts.


L-BAL-E321-GB 2021/11 Index 002

15/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5 Installation instructions

5.1 What this chapter contains
This chapter describes mechanical and electrical installation.

5.2 Mechanical drawings

5.2.1 Active harmonic filter Z-D-15E-..


L-BAL-E321-GB 2021/11 Index 002

16/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.2.2 Active harmonic filter Z-D-35E-.. and Z-D-55E-..


L-BAL-E321-GB 2021/11 Index 002

17/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.2.3 Mechanical installation

For safe and undisturbed operation, it is mandatory to follow those instructions for mechanical installation:

1. Clearance between active harmonic filter and other components like chokes, cabinet walls, drives: – 100 mm in horizontal direction (left/right) and – 100 mm in vertical direction (bottom)
2. Clearance between several active harmonic filter: – 100 mm in horizontaldirection (left/right) – 100 mm in vertical direction (bottom)
3. Min. clearance in vertical direction (top): – Z-D-15E-..: 130 mm – Z-D-35E-..: 180 mm – Z-D-55E-..: 180 mm
4. Use screws with min. diameters – Z-D-15E-..: 6 mm – Z-D-35E-..: 6 mm – Z-D-55E-..: 6 mm


L-BAL-E321-GB 2021/11 Index 002

18/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3 Electrical wiring

Active harmonic filters may only be installed, commissioned and serviced by certified electrician.

Connect the active harmonic filter according to the attached connection diagram. The labeling is in the immediate vicinity of the connection terminals.

3 Wire 3 Phase

Note: For part numbers 349110, 349111, 349112, the conductor of the load current must be passed through the converter two times (loop once) to achieve the correct current transformer rating. It is essential (as with simple implementation) that the direction of energy flow in the conductor and the direction of the arrow on the converter match.

Exemplary illustration:

One times passage of the conductor

Two times passage of the conductor

Part number: 349114, 349115, 349116, 349117, 349118, 349119, 349120, 349121

Part number: 349110, 349111, 349112


L-BAL-E321-GB 2021/11 Index 002

19/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.1 EMC directive

Compliance with the EMC directive is only given if the active harmonic filter is connected directly to the main power supply.

If the active harmonic filter is built into a system or combined with other products, the manufacturer of the system / operator of the device is responsible for compliance with the EMC directive according to the locally applicable standards.

5.3.2 Voltage supply The voltage supply must match the information on the rating plate (see technical data). The voltage supply must comply with the EN 50160 quality characteristics and the defined standard voltages of IEC 60038!

Remarks for connection of CT (current transformer):

Routing of wires: The wires between the active harmonic filter and current transformers must be twisted pair cables. A correct function is only possible if the wiring matches exact the diagram below. If wires are interchanged, the harmonics will not be reduced but amplified. To avoid interchanging of wires it is strongly recommended not to use any wire colour twice.

Wire cross section: The cross section of the wires has a significant influence on the quality of the control. Is the cross section to small in relation to the length of the wire, the resulting measurement within the active harmonic filter will be too small to achieve a good control quality and good reduction of harmonics.

=

2××ײ×

The following values needed to be known:

– S = Power of the current transformer (30 A – 80 A typical 1.5 VA, 100 A typical 2.5 VA )

– d = Distance (length of cableway) between active harmonic filter and current transformer

– v = Twisting factor (typical 1,5)

– I = secondary current of the current transformer ( typical 5 A)

=

Rho

=

specific

resistance

of

copper

(

0,01786

²

)

Example:

=

2×2

×1,5×52×0,01786 2,5 ײ

×

=

1,07

²

Wiring type: At 3W3P (installation of two current transformers) the neutral must not be connected to the active harmonic filter. It is mandatory that the physical installation must match the adjusted method in the software of the active harmonic filter. If this is not observed, the reduction of harmonics is not optimal.


L-BAL-E321-GB 2021/11 Index 002

20/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.3 LED status display

LED Green: Red: Flashing:

Operation Error Standby


L-BAL-E321-GB 2021/11 Index 002

21/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.4 Current transformer wiring

PE GND CT_C GND CT_B GND CT_A

Terminal label

Function / Terminal

CT_A

CT S1 in Phase AL1

GND

CT S2 in Phase A (L1.1)

CT_C

CT S1 in Phase CL3

GND

CT S2 in Phase C (L3.1)

PE

Protective wire / screening

Remark: To achieve best performance of Z-D-15/35/55E-.. the pairs CT_A+GND and CT_C+GND should be twisted.

Exemplary illustraiton of current transformer: Connection of S1 and S2:

One times passage:

Two times passage


L-BAL-E321-GB 2021/11 Index 002

22/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.5 Active harmonic filter in parallel wiring

Z-D-15/35/55E-.. may be connected in parallel without limitation to achieve higher power ratings. It is necessary to adjust the related parameters in the software and do adopt the wiring of the current transformers.

Phase A (L1) is used for reference for the other phases.

Example Case 1: Parallel wiring of two Z-D-15/35/55E-..:

Hint: Like the polarity of S1 and S2, the polarity of P1 and P2 is very important for the correct function. P1 must face to mains supply and P2 (on opposite side of current transformer) must face to the load.
Example Case 2: Parallel wiring of more than two Z-D-15/35/55E-..:

Hint: Like the polarity of S1 and S2, the polarity of P1 and P2 is very important for the correct function. P1 must face to mains supply and P2 (on opposite side of current transformer) must face to the load.


L-BAL-E321-GB 2021/11 Index 002

23/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.6 Selection of CT (current transformers)

Selection of current transformers depends on the load current of the application. Applicable are current transformers in the range of 30:5 to 250:5. The transfer ratio must be adjusted in the correlated parameter of the software. For optimal performance, the nominal current of the current transformer must not be much higher than the load current of the application (e.g. load current 95A => current transformer 100A)

Following CT´s are provided for corresponding nominal current

Nominal current of CT (current transformer)1 in A

Filter

Nominal current of filter2 in A

Order code3 Filter + CT

30

Z-D-15E-030

15

349110

40

Z-D-15E-040

15

349111

50

Z-D-15E-050

15

349112

60

Z-D-15E-060

15

349114

60

Z-D-35E-060

35

349115

80

Z-D-35E-080

35

349116

100

Z-D-35E-100

35

349117

150

Z-D-35E-150

35

349118

150

Z-D-55E-150

55

349119

200

Z-D-55E-200

55

349120

250

Z-D-55E-250

55

349121

1Current transformers should be selected based on the maximum load current to be filtered and the THDi target to be achieved

2Relates to the maximum possible compensation current

3Each part number consists of a filter and 2 current transformers

5.3.7 Wiring when using current transformers with high ratio
For part numbers 349110, 349111 and 349112 the conductor of the load current must be passed through the converter two times (loop once) to achieve the correct current transformer rating. It is essential (as with simple implementation) that the direction of energy flow in the conductor and the direction of the arrow on the converter match. A 100A bushing current transformer is used as an example for part number 349112, here the conductor must be passed through twice instead of once. See capture 5.3. Such an adaptation is not possible with converters without a feed through.
If you have any questions, please contact our technical support for control systems – ventilation technology.


L-BAL-E321-GB 2021/11 Index 002

24/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.8 EPO and Z-D-15/35/55E-.. ID

EPO

GND

ID_DS

Terminal label EPO GND
ID_DS

Function
EPO connection for usage as part of EMERGENCY OFF line. If the contact to be wired here is closed, the EMERGENCY OFF function
is active.
Adjustment of the ID of the active harmonic filter. This is required for correct software function if several modules are connected to the same interface of one computer


L-BAL-E321-GB 2021/11 Index 002

25/44

Operating Instructions Z-D-15/35/55E-..

Installation instructions


5.3.9 Input and output interface

Terminal label
1N1
1N2
GND_O NO1 COM NO2 485+ 485-
+7,5V GND_O CANH CANL

Function IN1+ for DC +, recommended input voltage range: 10 ~ 24V DC IN2+ for DC +, recommended input voltage range: 10 ~ 24V DC Common ground for DC input Relay 1, Normal Open, DC, capacity: 8A/250VAC Common ground for relay output Relay 2, Normal Open, DC, capacity: 8A/250VAC 485 Interface for remote control by a computer. A standard-485communikation interface requires screened or twisted wires. If the wire length exceeds 1m, GND must be connected. Common ground for communication 485 and CAN
CAN communication

Wiring example RS 485:

USB=>RS485

Z-D-15/35/55E-


L-BAL-E321-GB 2021/11 Index 002

26/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6 Supervision- and control software

6.1 What this chapter contains
This chapter contains guidelines for using the supervision and control software. There are hints how to check the parameters before commissioning and how to optimize them during operation.

6.2 Introduction in the system
Naming of the software: Software-Version High frequency RHF-Active SiC V3.2.3

Suitable for RHF-Active 15, 35,55 A

6.2.1 Log In After start, the following dialog screen is shown:

To log in use following data: ID: 001 Password: 010101


L-BAL-E321-GB 2021/11 Index 002

27/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.2 Home

The home screen will be shown:

Home: Information concerning grid and load are shown. The three buttons at the bottom are used to start, stop and reset the active harmonic filter.
User Set: All parameters can be read and modified.
DATA: Displays grid voltage and current (each RMS, frequency and THD of all active wires), load current (each RMS, frequency and THD of all active wires), power (each apparent, active, reactive and power factor), load current of the inverter (RMS, load rate, choke current) and the temperatures of the transistors
Record: Historical values of recorded data and warnings

Help: Shows easy hints.

Note! The colour of the line beside the blue ribbon at the left shows connect status between PC and active

harmonic filter:

Red

=> no connect

Green

=> connect,


L-BAL-E321-GB 2021/11 Index 002

28/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.3 Initialize communication

When computer and Z-D-15/35/55E-.. are connected the first time, it is necessary to set the communication parameters. Thereto click on ,,User Set”, then ,,Comm” and start ,,PortCheck”:

The drop down list offers the available ports. Choose one of them. Adjust the transmission speed in accordance to the list below:

Software-Version

Suitable for

Baud Rate

SiCAHF-3.2.1

Z-D-15/35/55E-..

19200

Initialize the connection by clicking on ,,Connect”. If succesful, the software will show this:


L-BAL-E321-GB 2021/11 Index 002

29/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.4 System configuration

Overall there are seven pages for adjustment of parameters.

Page

Content (Adjustment of…)

1

Module

2

Phase angle

3

Odd harmonics

4

Even harmonics

5

Sensor-calibration

6

Trouble shooting

7

communication

The description of page 7 ,,Communication” is part of in chapter 6.2.3. All others can be found in the following:

6.2.4.1 Device

This page shows the following adjustments:

Nr. Name

Description

1 Compensate Mode of compensation:

priority

H: only Harmonic compensation

HR: compensation of harmonics and reactive power, whereas harmonic compensation has priority.

HRU: compensation of harmonics, reactive power and phase unbalance, whereas harmonic compensation has priority.

2 Grid Frequency

Adjustment to grid frequency: 50hz or 60hz

3 CT Location Placing of current transformers. Load side (preferred) or grid side.


L-BAL-E321-GB 2021/11 Index 002

30/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


4 CT Variable Ratio of current transformers, (typical XX: 5). XX must be written in here. Ratio

5 Power Factor Set value for power factor if HR or HRU have been selected

6 Harmonic

Harmonic compensation algorithm:

Detect Mode 1. Manual: The compensation rate must be adjusted manually.

2. Auto: The compensation rate is adjusted automatically.

3. Completely: the compensation rate is set to 1. Compensation includes reactive power.

The default setting is ,,Manual

7 Compensate Compensation rate: It is possible to adjust between 0.1-1.0 to reduce the

Ratio

compensation current. 1.0 means full compensation current

8 Parallel current

If several active harmonic filter operate in parallel (at one set of current transformers), this cell expects the total current of all active harmonic filter

9 Topology

If three phases and three wires (L1, L2, L3) with two current transformers are used, select 3P3W

If three phases and four wires (L1, L2, L3;N) with three current transformers are used, select 3P4W.

10 Power On mode

Power on status at voltage recovery. Auto: At voltage recovery module will start automatically

Manuel: At voltage recovery the start of the module must be initiated manually

The default setting is ,,Manual

11 Grid Voltage

Grid voltage. The default setting is 380 V (fits also for 400 V). Alternatively 480 V can be chosen.

12 CT Line Mode Connection type of current transformers. Possible are series and parallel connection

13 Damp

Damping of the control. Admissible values are between 10 and 30. At symmetrical three phase load (3W3P) : 30. At single phase or unsymmetrical load (4W3P) : 10.


L-BAL-E321-GB 2021/11 Index 002

31/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.4.2 Angle_Coeff

The angle coefficient of can compensate deviation of current transformers.

No. Name

Description

1

Fundamental Angle Set value range -99.99 to 99.99

2

Phase A Angle

Set value range -99.99 to 99.99

3

Phase B Angle

Set value range -99.99 to 99.99

4

Phase C Angle

5

3rd Angle

Set value range -99.99 to 99.99 Set value range -99.99 to 99.99

6

5th Angle

7

7th Angle

8

9th Angle

9

11th Angle

10

13rd Angle

11

15th Angle

12

17th Angle

13

19th Angle

14

21th Angle

15

23th Angle

16

25th Angle

Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99 Set value range -99.99 to 99.99

Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results are achieved with these.


L-BAL-E321-GB 2021/11 Index 002

32/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.4.3 Odd_Coeff

The odd coefficient can compensate characteristics of the grid on site:

No.

Name

Description

1-31

Compensation rate1st ­ 59th

Set value range 0.01 to 1.0

Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results

are achieved with these.

6.2.4.4 Even_Coeff

The even coefficient can compensate characteristics of the grid on site::

No.

Name

Description

1-30

Compensation rate 2nd ­ 60th

Set value range 0.01 to 1.0

Optimized parameters for ECblue are already stored at the factory. Normally, the best possible results

are achieved with these.


L-BAL-E321-GB 2021/11 Index 002

33/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.4.5 Calibration

This page defines the calibration of external and internal sensors (current and voltage transformers). This adjustment is done in factory and must not be changed without manufacturer’s acknowledgment.


L-BAL-E321-GB 2021/11 Index 002

34/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.4.6 Debug

This page defines the internal variables of the active harmonic filter (among other purposes for trouble shooting). This adjustment is done in factory and must not be changed without manufacturer’s acknowledgment.
Refer to chapter 6.2.3.


L-BAL-E321-GB 2021/11 Index 002

35/44

Operating Instructions Z-D-15/35/55E-..

Supervision- and control software


6.2.5 Data

The “Data” pages show electrical values of the system. Based on the data from the “Home” page, also Voltage vs time and current vs. time are displayed.

6.2.6 Procedure to power on
1. Connect the Z-D-15/35/55E-.. with the PC
2. Adjust current transformer ratio, compensation rate, grid voltage, grid frequency etc. on pages ,,User Set” 3. Check that on page ,,Record” no errors or alarms are displayed. If there are, first clear the messages on page ,,Home” by using ,,Clear Fault” button. 4. Click at ,,Power on” on page ,,Home”.


L-BAL-E321-GB 2021/11 Index 002

36/44

Operating Instructions Z-D-15/35/55E-..

Maintenance and check of hardware


7 Maintenance and check of hardware

7.1 What this chapter contains This chapter contains instructions for predictive maintenance of the active harmonic filter.
7.2 Periodicity of maintenance When installed in an appropriate environment the active harmonic filter from ZIEHL-ABEGG required minimal maintenance. The recommended maintenance is listed below.

Check

Task

Method

Check of ambient temperature, humidity, vibrations and for absence of dust, gas, oil mist and water drops

Optical check and measurment of the parameters

Environment conditions

Ensure that no tools or other potentially dangerous components have been placed nearby

Optical check

Measurement with multimeter Measure voltage in power and control circuits

Voltage

Supply lines

Check of system and cabinet
Check for abnormal sound emission or vibrations Check for loosen screws Check of absence of dark colour due to overheating or aging
Check for debris in the cooling system

Check for loosen screws
Check of absence of sparks, damages, dark colour due to overheating or aging of isolation Ensure that no dust or dirt is present
Optical check or estimation of operation time based on maintenance files
Fix screws Optical check or estimation of operation time based on maintenance files
Optical check

Fan

Cooling system

Air duct


L-BAL-E321-GB 2021/11 Index 002

37/44

Operating Instructions Z-D-15/35/55E-..

Maintenance and check of hardware


7.3 Disposal/Recycling

Disposal must be carried out professionally and in an environmentally friendly way in accordance with the respective national legal stipulations.

– Demountontaminate the product before starting work if it was previously used in a contaminated environment.
– Separate the materials by type and in an environmentally friendly way. – If necessary,commission a specialist company with the waste disposal.


L-BAL-E321-GB 2021/11 Index 002

38/44

Operating Instructions Z-D-15/35/55E-..

Error description and repair


8 Error description and repair

8.1 What this chapter contains This chapter describes known issues and their solving.

8.2 Typical errors and repairs

Error

cause

Z-D-15/35/55E-.. wrong compensation (THDi rises)

Current transformer System settings

Phase angle

Z-D-15/35/55E-.. insufficient compensation (THDI decreases but is higher than expected)

Low impedance

Error signal (red LED)
No communication

System settings Software settings

repair
Check wiring and polarity
Check transformer ratio
Setting the phase angle compensation with patience and carefully step by step, Trial and error iteration
Low impedance of the connection result in very harmonic levels before compensation. It is highly recommended to install impedance as first counter measurement against harmonics (for Drives basically DC or AC chokes).
Check for first error than for second
Improve baud rate and/or interface selection


L-BAL-E321-GB 2021/11 Index 002

39/44

Operating Instructions Z-D-15/35/55E-..

Enclosure


9 Enclosure

9.1 Technical Data


L-BAL-E321-GB 2021/11 Index 002

40/44

Operating Instructions Z-D-15/35/55E-..

Enclosure


9.1.1 Technical Data Active harmonic filter Z-D-15E-..

Electrical data

Network type

3 phase with/ without neutral 3P4W/3P3W

Rated voltage

380-480 V (+10 % / -15 %)

Rated current

15 A

Mains frequency

50 Hz / 60 Hz (5 Hz)

Harmonic compensation

1.-60. Harmonic

Response time

20 µs

Full response time

5 ms

Filter performance

96 %

Switching frequency

40 kHz-60 kHz, typical 50 kHz

Technology

Advanced SIC

System topology

Two Level Topology

Function

Harmonic compensation, power factor correction, three phase balancing

Efficiency

99,4% at nominal load

Power losses

207 W at 30 kW nominal power

User-Interface & Remote monitoring

HMI

Not present / extern

Communication protocol

RS485

PC-Software

V3.2.3

Installation / Configuration

Noise

<60db

Current transformer ratio

30/5~60/5

Cooling

Forced air cooling

Air flow requirement

105m³/h

Mounting

Wall mount

Parallel configuration

Unlimited

Extensions

Modules in parallel

Protection level

IP20

Cable entering

bottom

EMC regarding IEC60038

class A (EN61000-6-4*, EN 61000-6-1)

Environmental

Ambient temperature

-10~40

Temperature-Derating

Derating above 40 (3%/K)

Maximum temperature

50

Permissible temperature range for transport

-25 °C~+70 °C (regarding EN 50178)

Permissible temperature range for storage

-25 °C~+55 °C (regarding EN 50178)

Relative Humidity

5%~95% Class F without condensation

Altitude

below 1000m

Altitude Derating

above 1000m (5%/1000m to 4000m)

Weight, Dimensions, Certifications

Weight

10 kg

Dimensions WHD[mm]

89417260

Certifications

CE

*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate protection of radio reception in such environments.


L-BAL-E321-GB 2021/11 Index 002

41/44

Operating Instructions Z-D-15/35/55E-..

Enclosure


9.1.2 Technical Data Active harmonic filter Z-D-35E-..

Electrical data

Network type

3 phase with/ without neutral 3P4W/3P3W

Rated voltage

380-480 V (+10 % / -15 %)

Rated current

35 A

Mains frequency

50 Hz / 60 Hz (5 Hz)

Harmonic compensation

1.-60. Harmonic

Response time

20 µs

Full response time

5 ms

Filter performance

96 %

Switching frequency

40 kHz-60 kHz, typical 50 kHz

Technology

Advanced SIC

System topology

Two Level Topology

Function

Harmonic compensation, power factor correction, three phase balancing

Efficiency

99,3% at nominal load

Power losses

415 W at 55 kW nominal power

User-Interface & Remote monitoring

HMI

Not present / extern

Communication protocol

RS485

PC-Software

V3.2.3

Installation / Configuration

Noise

<60db

Current transformer ratio

60/5~150/5

Cooling

Forced air cooling

Air flow requirement

105m³/h

Mounting

Wall mount

Parallel configuration

Unlimited

Extensions

Modules in parallel

Protection level

IP20

Cable entering

bottom

EMC regarding IEC60038

class A (EN61000-6-4*, EN 61000-6-1)

Environmental

Ambient temperature

-10~40

Temperature-Derating

Derating above 40 (3%/K)

Maximum temperature

50

Permissible temperature range for transport

-25 °C~+70 °C (regarding EN 50178)

Permissible temperature range for storage

-25 °C~+55 °C (regarding EN 50178)

Relative Humidity

5%~95% Class F without condensation

Altitude

below 1000m

Altitude Derating

above 1000m (5%/1000m to 4000m)

Weight, Dimensions, Certifications

Weight

17 kg

Dimensions WHD[mm]

105548360

Certifications

CE

*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate protection of radio reception in such environments.


L-BAL-E321-GB 2021/11 Index 002

42/44

Operating Instructions Z-D-15/35/55E-..

Enclosure


9.1.3 Technical Data Active harmonic filter Z-D-55E-..

Electrical data

Network type

3 phase with/ without neutral 3P4W/3P3W

Rated voltage

380-480 V (+10 % / -15 %)

Rated current

55 A

Mains frequency

50 Hz / 60 Hz (5 Hz)

Harmonic compensation

1.-60. Harmonic

Response time

20 µs

Full response time

5 ms

Filter performance

96 %

Switching frequency

40 kHz-60 kHz, typical 50 kHz

Technology

Advanced SIC

System topology

Two Level Topology

Function

Harmonic compensation, power factor correction, three phase balancing

Efficiency

99,3% at nominal load

Power losses

721 W at 90 kW nominal power

User-Interface & Remote monitoring

HMI

Not present / extern

Communication protocol

RS485

PC-Software

V3.2.3

Installation / Configuration

Noise

<60db

Current transformer ratio

150/5~250/5

Cooling

Forced air cooling

Air flow requirement

105m³/h

Mounting

Wall mount

Parallel configuration

Unlimited

Extensions

Modules in parallel

Protection level

IP20

Cable entering

bottom

EMC regarding IEC60038

class A (EN61000-6-4*, EN 61000-6-1)

Environmental

Ambient temperature

-10~40

Temperature-Derating

Derating above 40 (3%/K)

Maximum temperature

50

Permissible temperature range for transport

-25 °C~+70 °C (regarding EN 50178)

Permissible temperature range for storage

-25 °C~+55 °C (regarding EN 50178)

Relative Humidity

5%~95% Class F without condensation

Altitude

below 1000m

Altitude Derating

above 1000m (5%/1000m to 4000m)

Weight, Dimensions, Certifications

Weight

19 kg

Dimensions WHD[mm]

105548360

Certifications

CE

*Warning note: This device is not intended to be used in residential areas and cannot ensure adequate protection of radio reception in such environments.


L-BAL-E321-GB 2021/11 Index 002

43/44

Operating Instructions Z-D-15/35/55E-..

Enclosure


9.2 Service information

Service information Our products are manufactured in accordance with the relevant international regulations. If you have
any questions concerning the use of our products or plan special uses, please contact:

If you have any technical questions while commissioning or regarding malfunctions, please contact

phone: +49 (0) 7940 16-800 Email: [email protected]

Our worldwide contacts are available in our subsidiaries for deliveries outside of Germany, see www.ziehl-abegg.com. Our products are manufactured in compliance with the applicable international regulations. If you have any questions about the use of our products or if you are planning special applications, please contact us. We would be pleased to help


L-BAL-E321-GB 2021/11 Index 002

44/44