victron energy BMV-700H Battery Monitor Owner’s Manual
- June 16, 2024
- victron energy
Table of Contents
Manual – BMV-700H
Battery monitor
Rev 12 – 05/2023
This manual is also available in HTML5.
Safety precautions
1.1. General safety precautions
Read this manual carefully. It contains important instructions that must be
followed during installation, operation and maintenance.
Save these instructions for future reference on operation and maintenance.
1.2. High voltage safety warnings
Voltages above 50Vdc up to 120Vdc (ELV) are dangerous and will cause serious
injury, death or equipment damage. Use appropriate personal protection
equipment. De-energize the system before maintenance and use appropriate
insulated tools. Voltages above 120Vdc (LV) are very dangerous and will cause
serious injury, death or equipment damage.
Use appropriate personal protection equipment. De-energize before maintenance
and use appropriate insulated tools.
1.3. Battery safety warnings
Working in the vicinity of a lead acid battery is dangerous. Batteries can
generate explosive gases during operation. Never smoke or allow a spark or
flame in the vicinity of a battery. Provide sufficient ventilation around the
battery.
Wear eye and clothing protection. Avoid touching eyes while working near
batteries. Wash your hands when done.
If battery acid contacts skin or clothing, wash them immediately with soap and
water. If acid enters an eye, immediately flood the eye with running cold
water for at least 15 minutes and get medical attention immediately.
Be careful when using metal tools in the vicinity of batteries. Dropping a
metal tool onto a battery might cause a short circuit and possibly an
explosion.
Remove personal metal items such as rings, bracelets, necklaces, and watches
when working with a battery.
A battery can produce a short circuit current high enough to melt objects such
as rings, causing severe burns.
1.4. Transport and storage
Store this product in a dry environment.
Store this product in temperatures between -40°C and +60°C.
Introduction
2.1. The battery monitor
The BMV-700H is a battery monitor. It measures battery voltage and current.
Based on these measurements, it calculates the battery’s state of charge and
the time to go. It also keeps track of historical data, such as deepest
discharge, average discharge and the number of charge and discharge cycles.
All monitored battery parameters can be read out, and settings can be changed
via the display and the four buttons.
A connection with the VictronConnect app is possible via Bluetooth or USB. The
VictronConnect app can be used to read out all monitored battery parameters or
to change settings. To connect via Bluetooth, an optional VE.Direct Bluetooth
Smart dongle is needed. To connect via USB, an optional VE.Direct to USB
interface is needed.
If the battery monitor is connected to a GX device, such as the Cerbo GX or
the ColorControl GX, the battery can be monitored locally with the GX device
or remotely via the VRM portal.
2.2. Why should I monitor my battery?
Batteries are used in a wide variety of applications, mostly to store energy
for later use. But how much energy is stored in the battery? No one can tell
by just looking at it. The service life of batteries depends on many factors.
Battery life may be shortened by under-charging, over-charging, excessively
deep discharges, excessive charge or discharge currents, and by high ambient
temperature. Monitoring the battery with a battery monitor will give important
feedback to the user so that remedial measures can be taken when necessary.
Doing this will extend battery life and the battery monitor will quickly pay
for itself.
2.3. Sizing
The battery monitor is available in one size; it has a 500A shunt. However, it
is possible to use the battery monitor with larger shunts all the way up to
9999A. Larger shunts are not included. For 1000A, 2000A or 6000A shunts see
the Shunt product page.
2.4. The VictronConnect app
The VictronConnect app can be used to monitor and configure the battery
monitor. Note that configuring the battery monitor using the VictronConnect
app is easier than configuring using the battery monitor head unit.
The VictronConnect app can connect to the battery monitor via:
-
Bluetooth, using the optional VE.Direct Bluetooth Smart dongle.
-
USB, using the optional VE.Direct to USB interface.
-
Remotely via a GX device and the VRM portal.
The VictronConnect app is available for the following platforms: -
Android.
-
Apple iOS (Note that USB is not supported, it is only possible to connect via Bluetooth).
-
macOs.
-
Windows (Note that Bluetooth is not supported, it is only possible to connect via USB).
The VictronConnect app can be downloaded from app stores or from the VictronConnect product page or scan the below QR code.
2.5. Accessories
These optional parts might be needed depending on your setup:
- GX Device, such as a Cerbo GX – for system and/or remote monitoring.
- VE.Direct cable – to connect the battery monitor to a GX device.
- VE.Direct to USB interface – to connect to the battery monitor via USB to a GX device or to the VictronConnect app.
- VE.Direct Bluetooth Smart dongle – to add Bluetooth functionality to the battery monitor.
- Wall mount enclosure for BMV or MPPT Control – use in case panel mounting of the battery monitor head unit is not possible.
- Wall mount enclosure for BMV and Color Control GX – use to wall mount the battery monitor head unit together with a Color Control GX in the same enclosure.
- RJ12 UTP cable – use in case the supplied 10m (32ft) RJ12 cable (the cable between the shunt and the head unit) is too long or too short. These cables are available in a variety of lengths of 30cm up to 30 meters (1ft up to 98ft).
Installation
3.1. What’s in the box?
BMV-700H head unit together with attachment sleeve.|
---|---
500A shunt in enclosure.|
10m (33ft) RJ12 UTP cable.|
Square face plate together with an attachment flange.|
Bag with 4 small screws.|
Spare serial number sticker.|
3.2. Mounting shunt enclosure
The shunt enclosure has four 3.5mm holes for mounting purposes, these are
located in the base of the shunt enclosure. The holes can be used to screw or
bolt the enclosure onto a hard surface (screws are not included).
For the exact location of the mounting holes see the dimension drawing in the
appendix of this manual.
3.3. Mounting the head unit
The head unit can be mounted in a variety of ways:
A. Panel mounting, the head unit is secured at the back of a panel.
B. Panel mounting, the head unit is secured at the front of the panel.
C. Wall mounting, using an optional wall mounting enclosure.
For the full wall mounting instructions, see the wall mounting installation manuals on the Wall mount enclosure for BMV or MPPT Control or Wall mount enclosure for BMV and Color Control GX product pages.
3.4. Connections overview
# | Name | Terminal type |
---|---|---|
A | Display | – |
B | Setup button | – |
C | Down button | – |
D | Up button | – |
E | Select button | – |
F | RJ12 connector | RJ2 terminal |
G | Buzzer | – |
H | Programmable relay connector | Push connector |
I | VE.Direct connector | VE.Direct terminal |
J | Negative battery connection | M10 bolt |
K | Positive battery connection | Push connector |
M | Negative load connection | M10 bolt |
N | Fuse holder with fuse | – |
3.5. Basic electrical connections
Connection procedure:
-
Remove the fuse.
-
Connect the negative battery terminal to the M10 bolt on the “BATTERY” side of the shunt. Tighten the shunt bolt with a maximum torque of 21Nm.
Note that there should be no other connections on this side of the shunt or on the negative battery terminal. Any loads or chargers connected here will be excluded from the battery state of charge calculation. -
Connect the negative of the electrical system to the M10 bolt on the “LOAD” side of the shunt. Tighten the shunt bolt with a maximum torque of 21Nm. Make sure that the negative of all DC loads, inverters, battery chargers, solar chargers and other charge sources are connected “after” the shunt.
-
Connect the M10 eye terminal of the red cable with the fuse to the positive terminal of the battery.
-
Connect the shunt to the head unit using the RJ12 cable. Plug one side of the RJ12 cable into the shunt RJ12 terminal and the other side of the cable into the RJ12 terminal on the rear of the head unit.
-
Replace the fuse.
The battery monitor is now powered up. The display is active,.
In order to be fully functional, the battery monitor needs to be configured; see the Configuration [10] chapter.
3.6. Programmable relay
The battery monitor is equipped with a programable relay. This relay can be
used as an alarm relay, to start a generator or for other applications. For
more information on the various relay modes and how to configure the relay,
see chapter Relay settings [26].
A usage example of the relay is to start a generator when the battery state of
charge has dropped too low, and then to stop the generator when the batteries
have been recharged.
By default, the relay is set to energise when the battery state of charge
falls below 50% and to de-energise when the battery state of charge has risen
to 90%. However, the relay can be configured to also trigger on other
conditions, like battery voltage.
The relay has 2 contacts: COM (common) and NO (normally open) and are located
on the back of the head unit.
When the relay contact is open, the coil is de-energised; there is no contact
between COM and NO. When the relay is energised, the relay closes, and contact
between COM and NO is made. The relay function can be inverted: de-energised
becomes energised and vice versa. See setting Invert relay [27].
The internal wiring diagram of the battery monitor with the relay in a de-energised state connected to an external alarm or generator start circuit.
3.7. Use of alternative shunts
The battery monitor is supplied with a 500A, 50mV shunt. This shunt is
suitable for most applications. However, a larger shunt will be required if
system currents above 500A are expected.
The battery monitor can be configured to work with a wide range of different
shunts. Shunts of up to 9999A and up to 75mV can be used. For a selection of
larger shunts, i.e. 1000A, 2000A or 6000A, see our shunt product page.
When using a shunt other than the one supplied with the battery monitor,
please proceed as follows:
-
Unscrew the circuit board from the shunt.
-
Mount the circuit board on the new shunt, and ensure that there is good electrical contact between the circuit board and the shunt.
-
Connect the new shunt to the electrical system and battery monitor head unit as shown in chapter Basic electrical connections [7]. Pay special attention to the orientation of the shunt circuit board in relation to the battery and load
connections. -
Follow the setup wizard; see the Setup wizard [10] chapter.
-
After completing the setup wizard, set the proper shunt current and shunt voltage according to the Shunt current [32] and the Shunt voltage [32] settings.
-
If the battery monitor reads a non-zero current, even when there is no load, and the battery is not being charged, calibrate the zero current reading using the Zero current calibration [26] setting.
3.8. GX device connection
If the system contains a GX device such as a Cerbo GX, the battery monitor can
be connected to the GX device using a VE.Direct cable or a VE.Direct to USB
interface.
Once connected, the GX device can be used to read out all monitored battery
parameters. For more information see chapter Connecting to a GX device and the
VRM portal [21].
The battery monitor is connected to a Cerbo GX and a GX Touch screen.
Configuration
Once the electrical connections have been made, and the battery monitor has
been powered up, it needs to be configured to be suitable for the system it is
used in.
This can be done with the buttons on the battery monitor head unit or even
easier via the VictronConnect app. Note that a VE.Direct Bluetooth Smart
dongle or VE.Direct to USB interface is required.
This chapter describes how to configure the battery monitor by making the
basic settings. See the All features and settings [23] chapter for all
settings and features.
4.1. Setup wizard
The battery monitor will automatically start the setup wizard on the first
power-up or after a factory reset. The setup wizard must be completed before
any other settings are made.
-
The display shows the scrolling text “battery capacity” .
-
Press any button to enter the setup wizard. The scrolling text will stop, and the factory default battery capacity value (200 Ah) will be shown with the first digit blinking.
-
Use the + and – buttons to set the first digit of the battery capacity value. Preferably use the 20-hour (C20) battery capacity rating. For more information on battery capacity, see the Battery capacity and Peukert exponent [34] chapter.
-
Press SELECT to set the next digit in the same manner. Repeat this step until the required battery capacity is displayed.
-
Press SELECT to store the value. A short beep confirms this.
Should a correction need to be made, press SELECT again and repeat the previous steps. -
Press the SETUP, + or – button to end the setup wizard and switch to the normal operating mode.
Immediately after the completion of the setup wizard, the battery monitor will
automatically detect the nominal voltage of the battery system. For details
and limitations of automatic voltage detection, see the next chapter ???.
The battery monitor is now ready for use. It is now set up for an average
system with GEL, AGM or flooded lead-acid batteries.
Further battery monitor configurations are required if your system contains a
battery with different chemistry, like lithium, or if other specific system
settings are needed. See the All features and settings [23] chapter.
If the setup wizard is not showing, i.e. there is no scrolling text, it can be
re-activated by performing a battery monitor reset. To do this: simultaneously
press the SETUP and the SELECT button for 3 seconds. This resets the battery
monitor to its factory settings.
Note that factory settings can only be restored if the Lock setup [31] setting
has been set to OFF.
4.2. How to change settings
4.2.1. Settings via the head unit
Use the display buttons to enter and navigate through the settings menu. Each
setting has a number and a name. For example: “01 – Battery capacity”. The
full list of all battery settings and their corresponding number can be found
in the All features and settings [23] chapter.
It is also possible (and easier) to make the battery monitor settings via the VictronConnect app. See the The VictronConnect app [11] chapter on how to do this.
To access the settings menu and change settings:
1| Start in the main menu.|
---|---|---
2| Press SETUP for two seconds to enter the settings menu.|
3| The first setting item 01-Battery capacity will be shown.|
4| Use the + and – buttons to go to the desired setting item.|
5| Press SELECT to access the setting item.|
6| Use SELECT and the + and – buttons to customize the setting.|
7| Press SETUP to return to the setting menu.|
8| Go to the next setting using the + or – buttons.|
9| After all settings have been made, press SETUP to return from the settings
menu to normal mode.|
4.2.2. The VictronConnect app
The VictronConnect app can be used to change all settings and to update the
firmware.
Ways to connect to the battery monitor:
- Locally via USB using the VE.Direct to USB interface connected to the VE.Direct port.
- Locally via Bluetooth using the VE.Direct Bluetooth Smart dongle connected to the VE.Direct port.
- Remotely via a GX device, using VictronConnect “Remote” feature. For more information, see the VictronConnect-Remote chapter in the VictronConnect app manual.
How to connect with the VictronConnect app to the battery monitor:
- Open the VictronConnect app.
- Ensure that the battery monitor is powered.
- Look for the battery monitor to appear in the device list in the “Local” or the “VRM” tab.
- Click on the battery monitor.
- In case of a connection via Bluetooth; enter the default PIN code: 000000. After entering the default PIN code, the VictronConnect app will ask you to change the PIN code. This is to prevent unauthorized connections in the future. It is recommended that you change the PIN code on the first installation.
To view and/or change battery monitor settings, navigate to the settings page by clicking on the cog icon at the top right of the home screen.
Note that this manual only covers the items that are specific to the battery monitor. For more general information about the VictronConnect app, like how to use it and where to download it, or how to connect, see the VictronConnect app product page and manual.
4.3. Update firmware
On a new install, it is recommended to update the firmware of the battery
monitor. If there is a newer firmware version available, the VictronConnect
app will notify you of this as soon as a connection with the battery monitor
is made.
Note that the firmware can only be updated via the VictronConnect app. The app needs to be up to date to be able to access the latest firmware.
To check if the firmware is up to date or to manually update firmware, connect to the battery monitor using the VictronConnect app and follow the below steps:
- Navigate to the product settings by clicking the “cog” symbol in the top right-hand corner of the product status screen.
- Click on the “3 dots” symbol in the top right-hand corner of the settings screen.
- Select “Product info” from the pop-up menu.
- The firmware version will be displayed. It is mentioned if this is the latest firmware version (or not). If a newer firmware version is available, an “UPDATE” button will be displayed.
- To update the firmware, press the “UPDATE” button.
4.4. Make essential settings
The default settings of the battery monitor are tailored for lead acid
batteries, like AGM, GEL, OPzV or OPzS batteries.
Most settings can stay at their factory default. But there are a few settings
that need to be changed. These are:
- Battery capacity.
- Charged voltage.
- State of charge or start synchronised.
If lithium batteries (or batteries with a different chemistry) are used, some
additional settings will have to be changed.
First, make the essential settings as described in this paragraph and then
refer to the next paragraph for the special lithium settings.
For more information about these and any of the other settings, see chapter
All features and settings [23].
4.4.1. Set the battery capacity value
In the VictronConnect app, see: Settings > Battery.
Via the head unit, see: Setup menu > Setting 01 – Battery capacity.
The battery monitor is by default set to 200Ah. Change this value to match
your battery capacity. For lead-acid batteries, we recommend entering the
20-hour (C20) rate.
4.4.2. Set charged voltage value
In the VictronConnect app, see: Settings > Battery > Charged voltage.
Via the head unit, see: Setup menu > Setting 02 – Charged voltage.
These are the recommended “Charged voltage” values for lead acid batteries:
Use multiples of the 12V charge voltage, i.e. 13.2V, or consult the battery
documentation.
For more information, also see the Charged voltage [24] chapter.
4.4.3. Set state of charge
In the VictronConnect app, see: Settings > Battery > Battery start
synchronized.
Via the head unit, see: Setup menu > Setting 70 – Start synchronised.
When set to ON, the battery monitor will consider itself synchronized when
powered up, resulting in a state of charge of 100%.
If set to OFF, the battery monitor will consider itself un-synchronized when
powered up, resulting in a state of charge that is unknown until the first
actual synchronization.
For VictronConnect only: The initial state of charge value can also be
manually set, by default, this is 100%, and can be set to a different value if
so desired. See: Settings > Battery > State-of-charge.
4.5. Make Lithium settings (if needed)
LiFePO4 (Lithium Iron Phosphate or LFP) is the most used Li-ion battery chemistry. The factory defaults are in general also applicable to LFP batteries with exception of these settings:
- Tail current.
- Peukert exponent.
- Charge efficiency.
- Discharge floor.
Tail current
In VictronConnect see: Settings > Battery > Tail current.
Via the head unit, see: Setup menu > Setting 03 – Tail current.
Some lithium battery chargers stop charging when the current drops below a set
threshold. The tail current must be set higher in this case.
Peukert exponent
In VictronConnect see: Settings > Battery > Peukert exponent.
Via the head unit, see: Setup menu > Setting 05 – Peukert exponent.
When subjected to high discharge rates, lithium batteries perform much better
than lead-acid batteries. Set the Peukert exponent at 1.05, unless the battery
supplier advises otherwise.
Charge efficiency
In VictronConnect see: Settings > Battery > Charge efficiency factor.
Via the head unit, see: Setup menu > Setting 06 – Charge efficiency factor.
The charge efficiency of lithium batteries is much higher than that of lead-
acid batteries. We recommend setting the charge efficiency at 99%.
Discharge floor
In VictronConnect see: Setting > Battery > Discharge floor Via the head unit,
see: Setup menu > Setting 16 – SoC relay.
This setting is used in “the time to go” calculation and is set at 50% by
default for lead-acid batteries. However, lithium batteries usually can be
discharged significantly deeper than 50%. The discharge floor can be set to a
value between 10 and 20%, unless the battery supplier advises otherwise.
Important warning
Lithium batteries are expensive and can be irreparably damaged due to very
deep discharge or overcharge.
Damage due to deep discharge can occur if small loads slowly discharge the
battery when the system is not in use. Some examples of these loads are alarm
systems, standby currents of DC loads and back current drain of battery
chargers or charge regulators.
A residual discharge current is especially dangerous if the system has been
discharged all the way until a low cell voltage shutdown has occurred. At this
moment the state of charge can be as low as 1%. The lithium battery will get
damaged if any remaining current is drawn from the battery. This damage can be
irreversible.
A residual current of 1mA for example can damage a 100Ah battery if the
battery has been left in a discharged state for more than 40 days (1mA x 24h x
40 days = 0.96Ah).
The battery monitor draws <48mW from the battery. The positive supply must
therefore be interrupted if a system with Li-ion batteries is left unattended
during a period long enough for the battery monitor power consumption to
completely discharge the battery.
In case of any doubt about the possible residual current draw, isolate the
battery by opening the battery switch, by pulling the battery fuse(s) or by
disconnecting the battery positive when the system is not in use.
Operation
5.1. How does the battery monitor work?
The main function of the battery monitor is to follow and indicate the state
of charge of a battery, to be able to know how much charge the battery
contains and to prevent an unexpected total discharge.
The battery monitor continuously measures the current flow in and out of the
battery. Integration of this current over time, if it was a fixed current,
boils down to multiplying current and time and gives the net amount of Ah
added or removed.
For example, a discharge current of 10A for 2 hours will take 10 x 2 = 20Ah
from the battery.
To complicate matters, the effective capacity of a battery depends on the rate
of discharge, the Peukert efficiency, and, to a lesser extent, the
temperature. And to make things even more complicated: when charging a battery
more energy (Ah) has to be ‘pumped’ into the battery than can be retrieved
during the next discharge. In other words: the charge efficiency is less than
100%.
The battery monitor takes all these factors into consideration when
calculating the state of charge.
5.2. Readout overview
The head unit display or the VictronConnect app battery monitor status screen,
displays an overview of the most important
parameters. These are:
- State of charge
- Battery voltage
- Battery current
- Power
State of charge
This is the actual state of charge of the battery in a percentage and is
compensated for both the Peukert efficiency and charge efficiency. The state
of charge is the best way to monitor the battery.
A fully charged battery will be indicated by a value of 100.0%. A fully
discharged battery will be indicated by a value of 0.0%.
Please note that if the state of charge indicates three dashes: “—” this means
that the battery monitor is in an unsynchronised state. This mainly occurs
when the battery monitor has just been installed or after the battery monitor
has been left unpowered and is powered up again. For more information, see the
Synchronising the battery monitor [19] chapter.
Voltage
This is the terminal voltage of the battery.
Current
This is the actual current flowing in or out of the battery. A negative
current indicates that current is taken from the battery. This is the current
needed for DC loads. A positive current means that current is going into the
battery. This is current coming from charge sources. Keep in mind that the
battery monitor will always indicate the total battery current, being the
current traveling into the battery minus the current traveling out of the
battery.
Power The power drawn from or received by the battery.
Consumed Ah
The battery monitor keeps track of the Amp-hours removed from the battery
compensated for the efficiency.
Example: If a current of 12A is drawn from a fully charged battery for a
period of 3 hours, the readout will show -36.0Ah (-12 x 3 = -36).
Please note that if the “Consumed Ah” reading indicates three dashes: “—” this
means that the battery monitor is in an unsynchronised state. This mainly
occurs when the battery monitor has just been installed or after the battery
monitor has been left unpowered and is powered up again. For more information,
see the Synchronising the battery monitor [19] chapter.
Time remaining
The battery monitor estimates how long the battery can support the present
load. This is the “time-to-go” readout and is the actual time left until the
battery is discharged to the set “discharge floor”. The discharge floor is by
default set at 50%. For the discharge floor setting see the Discharge floor
[24] chapter. If the load is fluctuating heavily, it is best not to rely on
this reading too much, as it is a momentary readout and should be used as a
guideline only. We recommend the use of the state of charge readout for
accurate battery monitoring.
If the “Time remaining” indicates three dashes: “—” this means that the battery monitor is in an unsynchronised state. This occurs when the battery monitor has just been installed or after it has been left unpowered and is powered up again. For more information, see see the Synchronising the battery monitor [19] chapter.
5.3. Using the head unit menus
Alternatively, use the VictronConnect app to access the battery monitor settings. See the chapter The VictronConnect app [11] on how to do this.
When the battery monitor is powered up for the first time or when the factory
settings have been restored, the battery monitor will start the quick setup
wizard; see chapter: Setup wizard [10]. After that, the battery monitor will
operate in normal mode, and the battery menu can be accessed as described in
this chapter.
The battery monitor is controlled by the four buttons on the head unit. The
function of the buttons depends on which mode the battery monitor is in. This
is indicated in the below table.
If the backlight is off, press any button to restore the backlight.
Button| Function when in normal mode| Function when in setup
mode
---|---|---
SETUP
| Press and hold for two seconds to switch to setup mode. The display will scroll the number and description of the selected parameter.| Press SETUP any time to return to the scrolling text, and press again to return to normal mode. When pressing SETUP while a parameter is out of range, the display blinks five times, and the nearest valid value is displayed.
SELECT
|
Press to switch to the history menu. Press to stop scrolling and show the value. Press again to switch back to normal mode.
| • Press to stop scrolling after entering the setup mode with the SETUP
button.
• After editing the last digit, press to end editing. The value is stored
automatically. A short beep indicates confirmation.
• If required, press again to restart editing.
SETUP and SELECT
simultaneously
| Press and hold both SETUP and SELECT buttons simultaneously for three
seconds to restore factory settings (disabled when setting 64, lock setup, is
on, see Lock setup [31]).| n/a
+| Move upwards.| When not editing, press to move up to the previous
parameter.
When editing, this button will increment the value of the selected digit.
–| Move downwards.| When not editing, press to move down to the next
parameter.
When editing, this button will decrement the value of the selected digit.
+ and – simultaneously| Press and hold both buttons simultaneously for three
seconds to manually synchronise the BMV.| n/a
5.4. Trends
The VictronConnect app provides battery monitor data logging, but only while
the VictronConnect app is connected and communicating with the battery
monitor. It will simultaneously log two of the following parameters:
- Voltage (V).
- Current (A).
- Power (W).
- Consumed Amp Hours (Ah).
- State of charge (%).
5.5. History
The battery monitor stores historic events. These can be used at a later date
to evaluate usage patterns and battery health.
The history data is stored in a non-volatile memory and will not be lost when
the power supply to the battery monitor has been interrupted or when the
battery monitor has been reset to its defaults.
5.5.1. Accessing historical data via the VictronConnect app
The battery monitor’s historical data can be accessed in the “History” tab in
the VictronConnect app.
The VictronConnect app battery monitor history screen.
5.5.2. Accessing historical data via the head unit
To view the battery monitor history menu press SELECT when in normal mode:
- Press + or – to browse the various parameters.
- Press + or – to browse the various values.
- Press SELECT again to stop scrolling and show the value.
- Press SELECT again to leave the historical menu and to go back to the normal operation mode.
The below table gives an overview of the history parameters and how they are displayed in the menu. For the meaning of each parameter see the next chapter.
5.5.3. History data
Discharge information in Ah
- Deepest discharge: The battery monitor remembers the deepest discharge and each time the battery is discharged deeper the old value will be overwritten.
- Last discharge: The battery monitor keeps track of the discharge during the current cycle and displays the largest value recorded for Ah consumed since the last synchronisation.
- Average discharge: The cumulative Ah drawn divided by the total number of cycles.
- Cumulative Ah drawn: The cumulative number of Amp hours drawn from the battery over the lifetime of the battery monitor.
Energy in kWh
- Discharged energy: This is the total amount of energy drawn from the battery in kWh.
- Charged energy: The total amount of energy absorbed by the battery in kWh.
Charge
- Total charge cycles: The number of charge cycles over the lifetime of the battery monitor. A charge cycle is counted every time the state of charge drops below 65% and then rises above 90%.
- Time since last full charge: The number of days since the last full charge.
- Synchronisations: The number of automatic synchronisations. A synchronisation is counted every time the state of charge drops below 90% before a synchronisation occurs.
- Number of full discharges: The number of full discharges. A full discharge is counted when the state of charge reaches 0%.
Battery voltage
-
Min battery voltage: The lowest battery voltage.
-
Max battery voltage: The highest battery voltage.
Voltage alarms -
Low voltage alarms: The number of low voltage alarms.
-
High voltage alarms: The number of high voltage alarms.
5.6. Alarms
The battery monitor can raise an alarm in the following situations:
- Low battery state of charge (SOC).
- Low battery voltage.
- High battery voltage.
The alarm will activate when the value reaches a set threshold and will
deactivate when the value clears this threshold. The thresholds are
configurable. For more information, see the Alarm settings [28] chapter.
The alarm will be displayed on the head unit, a buzzer will sound, the display
backlight will flash, and the alarm icon will be visible on the display. An
alarm is acknowledged when a button is pressed. However, the alarm icon is
displayed as long as the alarm condition remains. The programmable relay can
be triggered depending on the configuration of the alarm settings.
The alarm is also a software alarm.
When connecting with the VictronConnect app, while an alarm is active, the
alarm will show in the app. Alternatively, when the battery monitor is
connected to a GX device, the alarm will show on the GX device display or the
VRM portal.
In the case of the VictronConnect app, an alarm is acknowledged when a button
is pressed. And in the case of a GX device, an alarm is acknowledged when
viewed in notifications. The alarm icon is displayed as long as the alarm
condition remains.
Left: alarm displayed on the VictronConnect app. Right: alarm displayed on a GX device.
5.7. Synchronising the battery monitor
For a reliable readout, the state of charge, as displayed by the battery
monitor, must self-synchronise regularly with the true state of charge of the
battery. This is to prevent drift of the “State of charge” value over time. A
synchronisation will reset the state of charge of the battery to 100%.
5.7.1. Automatic synchronisation
Synchronisation is an automatic process and will occur when the battery has
been fully charged. The battery monitor will look at a few parameters to
ascertain that the battery has been fully charged. It will consider the
battery to be fully charged when the voltage has reached a certain value and
the current has dropped below a certain value for a certain amount of time.
These parameters are called:
- Charged voltage – the float voltage of the battery charger.
- Tail current – a percentage of the battery capacity.
- Charged detection time – the time in minutes.
As soon as these 3 parameters have been met, the battery monitor will set the state of charge value to 100%, thus synchronising the state of charge.
Example:
In the case of a 12V battery, the battery monitor will reset the battery’s
state of charge to 100% when all these parameters have been met:
- The voltage exceeds 13.2V,
- the charge current is less than 4.0% of the total battery capacity (e.g. 8A for a 200Ah battery) and,
- 3 minutes have passed while both the voltage and current conditions are met.
If the battery monitor does not perform a regular synchronisation, the state of charge value will start to drift over time. This is due to the small inaccuracies of the battery monitor and because of the estimation of the Peukert exponent [34]. Once a battery has been fully charged, and the charger has gone to the float stage, the battery is full and the battery monitor will automatically synchronise by setting the state of charge value to 100%.
5.7.2. Manual synchronisation
The battery monitor can be synchronised manually if required. This can be done
by pressing the “Synchronise” button in the VictronConnect app. Navigate to
“settings” and then to “battery settings”.
Alternatively, the battery monitor can be synchronised when in normal
operating mode by simultaneously pressing and holding the + and – buttons for
3 seconds.
A manual synchronisation can be needed in situations when the battery monitor
does not synchronise automatically. This is for example needed during the
first installation or after the voltage supply to the battery monitor has been
interrupted.
A manual synchronisation can also be needed when the battery has not been
fully charged, or if the battery monitor has not detected that the battery has
been fully charged because the charged voltage, current or time has been set
incorrectly. In this case, review the settings and make sure the battery
regularly receives a full charge.
Interfacing
The battery monitor can be connected to other equipment, this chapter describes how this can be done.
6.1. VictronConnect app via USB
The VictronConnect app can not only connect via Bluetooth but it can also
connect via USB. A USB connection is essential when connecting to the Windows
version of the VictronConnect app and is optional when the MacOS or Android
version is used. Please note that in case of connecting to an Android phone or
tablet a “USB on the Go” cable might be needed.
To connect via USB, you will need a VE.Direct to USB interface. Use this
interface to connect the computer to the battery monitor.
for more information see the VE.Direct to USB interface product page.
For more information also see the VictronConnect app manual.
Example of a VE.Direct to USB interface connection between the battery monitor and a computer.
# | Description |
---|---|
A | VE.Direct to USB interface. |
B | Computer or laptop. |
6.2. Connecting to a GX device and the VRM portal
A GX device, such as the Cerbo GX, is a Victron Energy device that provides
control and monitoring for all Victron equipment that is connected to it.
Control and monitoring of the GX device and it’s connected equipment can be
done locally or remotely via our free Victron Remote Monitoring portal, the
VRM portal.
The battery monitor can be connected to a GX device with a VE.Direct cable.
The VE.Direct cables are available in lengths ranging from 0.3 to 10 meters
and are available with straight or right-angle connectors. Alternatively, the
battery monitor can also connect to a GX device using a VE.Direct to USB
interface.
Once connected, the GX device can be used to read out all monitored battery
parameters.
Example of a battery monitor connecting to a GX device.
6.3. Custom integration
Please note that this is an advanced feature and requires programming
knowledge.
The VE.Direct communications port can be used to read data and change
settings. The VE.Direct protocol is extremely simple to implement.
Transmitting data to the battery monitor is not necessary for simple
applications: the battery monitor automatically sends all readings every
second.
All the details are explained in the Data communication with Victron Energy
products document.
All features and settings
This chapter explains all battery monitor settings. In addition to this we
also have a video available explaining these settings and how the interact
with each other to achieve accurate battery monitoring for both lead acid and
lithium batteries.
Link to the video: https://www.youtube.com/embed/mEN15Z_S4kE
7.1. How to change settings
Settings can be changed by using the battery monitor’s head unit or by using
the VictronConnect app.
7.1.1. Accessing settings via the head unit
To access and change setting parameters use the buttons on the head unit in
the following way:
- Press SETUP for two seconds to access these functions and use the+ and – buttons to browse them.
- Press SELECT to access the desired parameter.
- Use SELECT and the + and – buttons to customize. A short beep confirms the setting.
- Press SETUP at any time to return to the scrolling text, and press again to return to normal mode.
7.1.2. Accessing settings via the VictronConnect app
To access and change setting parameters do the following:
- Click on the settings symbol to go to the battery settings menu.
- To navigate from the general settings menu to the product settings menu, click on the menu symbol .
For information on how to connect with the VictronConnect app to the battery monitor, see the The VictronConnect app [11] chapter.
7.1.3. Saving, loading and sharing settings in VictronConnect
In the settings menu you can find the following 3 symbols:
Save settings to file – This will save settings for reference or for later
use.
Load settings from file – This will load earlier saved settings.
Share settings file – This allows you to share the settings file via email,
message, airdrop and so on. The available sharing options depend on the
platform used.
For more information on these features, see the VictronConnect manual.
7.2. Battery settings
The battery settings can be used to fine-tune the battery monitor. Please be
careful when you change these settings, as a change might affect the battery
monitor’s state of charge calculations.
7.2.1. Battery capacity
This parameter is used to tell the battery monitor how big the battery is.
This setting should already have been done during the initial installation.
The setting is the battery capacity in Amp-hours (Ah).
For more information on the battery capacity and the related Peukert exponent
see the Battery capacity and Peukert exponent [34] chapter.
Setting | Default | Range | Step size |
---|---|---|---|
Battery capacity (setting 01) | 200Ah | 1 – 9999Ah | 1Ah |
7.2.2. Charged voltage
The battery voltage must be above this voltage level to consider the battery
as fully charged. As soon as the battery monitor detects that the voltage of
the battery has reached this “charged voltage” parameter and the current has
dropped below the “tail current [24]” parameter for a certain amount of time,
the battery monitor will set the state of charge to 100%.
Setting | Default | Range | Step size |
---|---|---|---|
Charged voltage (setting 02) | 158.4V (144V nominal) | 0 – 384V | 0.1V |
The “charged voltage” parameter should be set to 0.2V or 0.3V below the float
voltage of the charger.
7.2.3. Discharge floor
The “Discharge floor” parameter is used in the “time remaining” calculation.
The battery monitor calculates the time it takes until the set “discharge
floor [24]” has been reached. It is also used to set the state of charge alarm
defaults.
For lead-acid batteries set this to 50% and for lithium set it lower.
Note that this setting only appears when accessing the battery monitor via the
VictronConnect app. In case the battery monitor is accessed via the head unit,
see the Low State of Charge (SoC) relay [27] setting instead.
Setting | Default setting | Range | Step size |
---|---|---|---|
Discharge floor | 50% | 0 – 99% | 1% |
7.2.4. Tail current
The battery is considered as fully charged once the charge current has dropped
to less than this “Tail current” parameter. The “Tail current” parameter is
expressed as a percentage of the battery capacity.
Note that some battery chargers stop charging when the current drops below a
set threshold. In these cases, the tail current must be set higher than this
threshold.
As soon as the battery monitor detects that the voltage of the battery has
reached the set “Charged voltage [24]” parameter and the current has dropped
below this “Tail current” parameter for a certain amount of time, the battery
monitor will set the state of charge to 100%.
Setting | Default | Range | Step size |
---|---|---|---|
Tail current (setting 03) | 4.00% | 0.50 – 10.00% | 0.1% |
7.2.5. Charged detection time
This is the time the “Charged voltage [24]” parameter and the “Tail current
[24]” parameter must be met in order to consider the battery fully charged.
Setting | Default setting | Range | Step size |
---|---|---|---|
Charged detection time (setting 04) | 3 minutes | 0 – 100 minutes | 1 |
minute
7.2.6. Peukert exponent
Set the Peukert exponent parameter according to the battery specification
sheet. If the Peukert exponent is unknown, set it at 1.25 for lead-acid
batteries and set it at 1.05 for lithium batteries. A value of 1.00 disables
the Peukert compensation. The Peukert value for lead-acid batteries can be
calculated. For more information on the Peukert calculation, the Peukert
exponent and how this relates to the battery capacity, see the Battery
capacity and Peukert exponent [34] chapter.
Setting | Default | Range | Step size |
---|---|---|---|
Peukert exponent (setting 05) | 1.25 | 1.00 – 1.50 | 0.01 |
7.2.7. Charge efficiency factor
The “Charge Efficiency Factor” compensates for the capacity (Ah) losses during
charging. A setting of 100% means that there are no losses.
A charge efficiency of 95% means that 10Ah must be transferred to the battery
to get 9.5Ah actually stored in the battery. The charge efficiency of a
battery depends on battery type, age and usage. The battery monitor takes this
phenomenon into account with the charge efficiency factor.
The charge efficiency of a lead acid battery is almost 100% as long as no gas
generation takes place. Gassing means that part of the charge current is not
transformed into chemical energy, which is stored in the plates of the
battery, but is used to decompose water into oxygen and hydrogen gas (highly
explosive!). The energy stored in the plates can be retrieved during the next
discharge, whereas the energy used to decompose water is lost. Gassing can
easily be observed in flooded batteries.
Please note that the ‘oxygen only’ end of the charge phase of sealed (VRLA)
gel and AGM batteries also results in a reduced charge efficiency.
Setting | Default setting | Range | Step size |
---|---|---|---|
Charge efficiency factor (setting 06) | 95% | 50 – 100% | 1% |
7.2.8. Current threshold
When the current measured falls below the “Current threshold” parameter it
will be considered zero. The “Current threshold” is used to cancel out very
small currents that can negatively affect the long-term state of charge
readout in noisy environments. For example, if the actual long-term current is
0.0A and, due to injected noise or small offsets, the battery monitor measures
0.05A the battery monitor might, in the long term, incorrectly indicate that
the battery is empty or will need to be recharged. When the current threshold
in this example is set to 0.1A, the battery monitor calculates with 0.0A so
that errors are eliminated.
A value of 0.0A disables this function.
Setting | Default | Range | Step size |
---|---|---|---|
Current threshold (setting 07) | 0.10A | 0.00 – 2.00A | 0.01A |
7.2.9. Time-to-go averaging period
The time-to-go averaging period specifies the time window (in minutes) that
the moving averaging filter works. A value of 0 (zero) disables the filter and
gives an instantaneous (real-time) readout. However, the displayed “Time
remaining” value may fluctuate heavily. Selecting the longest time, 12
minutes, will ensure that only long-term load fluctuations are included in the
“Time remaining” calculations.
Setting | Default | Range | Step size |
---|---|---|---|
Time-to-go averaging period (setting 08) | 3 minutes | 0 – 12 minutes | 1 |
minute
7.2.10. Battery starts synchronised
Note that if the battery monitor settings are accessed via the head unit, this
setting will be part of the miscellaneous setting, and if accessed via
VictronConnect it will be part of the battery settings.
The battery state of charge will become 100% after the battery monitor is
powered up. When set to ON, the battery monitor will consider itself
synchronised when powered up, resulting in a state of charge of 100%. If set
to OFF, the battery monitor will consider it unsynchronised when powered up,
resulting in a state of charge that is unknown until the first actual
synchronisation.
Please be aware that situations can occur where special consideration is
needed when setting this feature to ON. One of these situations occurs in
systems where the battery is often disconnected from the battery monitor, for
example on a boat. If you leave the boat and disconnect the DC system via the
main DC breaker and at that moment the batteries were, for example, 75%
charged. On return to the boat, the DC system is reconnected and the battery
monitor will now indicate 100%. This will give a false impression that the
batteries are full, while in reality they are partially discharged.
There are two ways of solving this, one is to not disconnect the battery
monitor when the batteries are partially discharged or alternatively turn the
“Battery starts synchronised” feature off. Now when the battery monitor is
reconnected the state of charge will display “—” and will not show 100% until
the batteries have been fully charged. Please note that leaving a lead acid
battery in a partially discharged state for a length of time will cause
battery damage.
Setting | Default | Modes |
---|---|---|
Start synchronized (setting 70) | ON | ON/OFF |
7.2.11. State of charge
With this setting, you can manually set the state of charge value. This
setting is only active after the battery monitor has, at least once, been
synchronised. Either automatically or manually.
This setting is only available when accessing the battery monitor via the
VictronConnect app.
Setting | Default | Range | Step size |
---|---|---|---|
State of charge | — % | 0.0 – 100% | 0.1% |
7.2.12. Synchronise SoC to 100%
Setting 10
This option can be used to manually synchronise the battery monitor.
When navigating to this setting on the head unit , press the SELECT button to
synchronize the battery monitor to 100%.
In the VictronConnect app press the ”Synchronise” button to synchronise the
battery monitor to 100%.
See the Manual synchronisation [20] paragraph for more information on this
setting.
7.2.13. Zero current calibration
Setting 09
This option can be used to calibrate the zero reading if the battery monitor
reads a non-zero current even when there is no load and the battery is not
being charged.
A zero current calibration is (almost) never needed. Only perform this
procedure in case the battery monitor shows a current while you are absolutely
sure that there is no actual current flowing. The only way to be sure is to
physically disconnect all wires and cables connected to the LOAD side of the
shunt. Do this by unscrewing the shunt bolt and removing all cables and wires
from that side of the shunt. The alternative, switching loads or chargers off,
is NOT accurate enough as this does not eliminate small standby currents.
Ensure that there really is no current flowing into or out of the battery
(disconnect the cable between the load and the shunt), then press SELECT in
the head unit menu or press CALIBRATE in the VictronConnect app.
7.3. Relay settings
The battery monitor is equipped with a programmable relay. These settings are
used to program the function of the relay.
The relay settings are disabled by default (except the State of Charge (SoC)
relay setting). To enable, a relay setting do the following:
- In the VictronConnect app, enable the relay setting by sliding the slider button to the right.
- Via the head unit, enable the relay setting by changing the set and clear value to any value above zero.
7.3.1. Relay mode
This setting has the following relay modes, namely:
Setting | Default mode | Modes | Description |
---|---|---|---|
Relay mode (setting 11) | DFLT | DFLT | |
Default mode. | The relay settings 16 up to 31 can be used to control the |
relay.
| | CHRG
Charger mode.| The relay will close when the state of charge falls below
setting 16 (discharge floor) or when the battery voltage falls below setting
18 (low voltage relay). The relay will be open when the state of charge is
higher than setting 17 (clear state of charge relay) and the battery voltage
is higher than setting 19 (clear low voltage relay).
An application example is to start and stop control of a generator, together
with settings 14 and 15.
---|---|---|---
REM
Remote mode.| The relay can be controlled via the VE.Direct interface. Relay
settings 12 and 14 up to 31 are ignored as the relay is under the full control
of the device connected via the VE.Direct interface.
7.3.2. Invert relay
This function enables selection between a normally de-energised (contact open)
or a normally energised (contact closed) relay.
When inverted, the open and closed conditions as described in all the relay
settings are inverted (with the exception of the Relay state [27]).
Note that the “normally energised” setting will slightly increase the power
consumption of the battery monitor.
Setting | Default mode | Modes | Range |
---|---|---|---|
Invert relay (setting 12) | OFF | OFF | Normally de-energised |
ON | Normally energised |
7.3.3. Relay state
This is a read-only parameter and it displays whether the relay is open or
closed (de-energised or energised).
Setting | Value | Description |
---|
Relay state (setting 13)
| OPEN| The relay is open (de-energised)
CLSD| The relay is closed (energised)
7.3.4. Relay minimum closed time
Sets the minimum time the “closed” condition will remain present after the
relay has been energised.
Note that this changes to “open” and de-energised if the relay function has
been inverted (Invert relay [27] setting).
An application example is to set a minimum generator run time when the relay
is set to “charger” mode (Relay mode [26] setting).
Setting | Default | Range | Step size |
---|---|---|---|
Relay minimum closed time (setting 14) | 0 minutes | 0 – 8 hours | 1 minute |
7.3.5. Relay off delay
Sets the amount of time the “de-energise relay” condition must be present
before the relay opens.
An application example is to keep a generator running for a while to charge
the battery better when the relay is set to “charger” mode (Relay mode [26]
setting).
Setting | Default | Range | Step size |
---|---|---|---|
Relay off delay (setting 15) | 0 minutes | 0 – 500 minutes | 1 minute |
7.3.6. Low State of Charge (SoC) relay
When the state of charge percentage has fallen below the “set relay” value,
the relay will close.
When the state of charge percentage has risen above the “clear relay” value,
the relay will open (after a delay, depending on the Relay minimum closed time
[27] and/or the Relay off delay [27] settings).
The “clear relay” value needs to be greater than the “set relay” value.
Setting | Default | Range | Step size |
---|---|---|---|
Set relay value (setting 16) | 50% | 0 – 99% | 1% |
Clear relay value (setting 17) | 90% | 0 – 99% | 1% |
When the “set relay” and “clear relay” values are equal, the state of charge
condition will be unable to drive the relay.
Note that this setting is also known as the discharge floor. The time-to-go
reading displayed by the battery monitor relates to this setting. The time to
go is the time left until this setting (the discharge floor) has been reached.
7.3.7. Low voltage relay
When the battery voltage falls below the “set relay” value for more than 10
seconds the relay will close.
When the battery voltage rises above the “clear relay” value, the relay will
open (after a delay, depending on the Relay minimum closed time [27] and/or
the Relay off delay [27] settings).
The “clear relay” value needs to be greater than the “set relay” value.
Setting | Default | Range | Step size |
---|---|---|---|
Set relay value (setting 18) | 0V | 0 – 384V | 0.1V |
Clear relay value (setting 19) | 0V | 0 – 384V | 0.1V |
7.3.8. High voltage relay
When the battery voltage rises above the “set relay” value for more than 10
seconds the relay will close.
When the battery voltage falls below the “clear relay” value, the relay will
open (after a delay, depending on the Relay minimum closed time [27] and/or
the Relay off delay [27] settings).
The “clear relay” value needs to be greater than the “set relay” value.
Setting | Default | Range | Step size |
---|---|---|---|
Set relay value (setting 20) | 0V | 0 – 384V | 0.1V |
Clear relay value (setting 21) | 0V | 0 – 384V | 0.1V |
7.4. Alarm settings
The BMV battery monitor is equipped with an alarm relay and a buzzer. Alarms
are also visible on the VictronConnect app while connected to the battery
monitor or are used to send an alarm signal to a GX device.
Alarms are disabled by default. To enable do the following:
- In the VictronConnect app, enable the alarm by sliding the slider button to the right.
- Via the head unit, enable the alarm by changing the “set” and “clear” value in the alarm settings to any value above zero.
7.4.1. Alarm buzzer
When enabled (set to ON), the buzzer will sound an alarm as soon as an alarm
condition occurs. After a button is pressed, the buzzer will stop sounding.
When disabled (set to OFF) the buzzer will not sound an alarm.
Setting | Default | Modes |
---|---|---|
Alarm buzzer (setting 32) | ON | ON |
OFF
7.4.2. Low SoC alarm settings
When enabled, the alarm will activate when the state of charge (SoC) falls
below the set value for more than 10 seconds. The alarm will deactivate when
the state of charge rises above the clear value
Setting | Default | Range | Steps |
---|---|---|---|
Set alarm value (setting 33) | 1% | 0 – 100% | 1% |
Clear alarm value (setting 34) | 1% | 0 – 100% | 1% |
7.4.3. Low voltage alarm
When enabled, the alarm will activate when the battery voltage falls below the
set value for more than 10 seconds. The alarm will deactivate when the battery
voltage rises above the clear value.
Setting | Default | Range | Steps |
---|---|---|---|
Set alarm value (setting 35) | 1.1V | 0 – 95.0V | 0.1V |
Set alarm value (setting 35) | 0V | 0 – 384V | 0.1V |
Clear alarm value (setting 36) | 1.0V | 0 – 95.0V | 0.1V |
Clear alarm value (setting 36) | 0V | 0 – 384V | 0.1V |
7.4.4. High voltage alarm
When enabled, the alarm will activate when the battery voltage rises above the
set value for more than 10 seconds. The alarm will deactivate when the battery
voltage drops below the clear value.
Setting | Default | Range | Steps |
---|---|---|---|
Set alarm value (setting 37) | 1.1V | 0 – 95.0V | 0.1V |
Set alarm value (setting 37) | 0V | 0 – 384V | 0.1V |
Clear alarm value (setting 38) | 1.0V | 0 – 95.0V | 0.1V |
Clear alarm value (setting 38) | 0V | 0 – 384V | 0.1V |
7.5. Display settings
7.5.1. Backlight intensity
The intensity of the backlight This setting ranges from 0 (always off) to 9
(maximum intensity).
Setting | Default | Range | Step size |
---|---|---|---|
Backlight intensity (setting 49) | 5 | 0 – 9 | 1 |
7.5.2. Backlight always on
When set the backlight will not automatically turn off after 60 seconds of
inactivity.
Setting | Default | Modes |
---|
Backlight always on (setting 50)
|
OFF
| ON
OFF
7.5.3. Scroll speed
The scroll speed of the display. This setting ranges from 1 (very slow) to 5
(very fast).
Setting | Default | Range | Step size |
---|---|---|---|
Scroll speed (setting 51) | 2 | 1 – 5 | 1 |
7.5.4. Main voltage display
Must be set to ON to display the voltage of the main battery in the monitoring
menu.
Setting | Default | Modes |
---|---|---|
Main voltage display (setting 52) | ON | ON |
OFF
7.5.5. Current display
Must be set to ON to display the current in the monitoring menu.
Setting | Default | Modes |
---|---|---|
Current display (setting 53) | ON | ON |
OFF
7.5.6. Power display
Must be set to ON to display the power measurement in the monitoring menu.
Setting | Default | Modes |
---|---|---|
Power display (setting 54) | ON | ON |
OFF
7.5.7. Consumed Ah display
Must be set to ON to display the consumed Ah in the monitoring menu.
Setting | Default | Modes |
---|---|---|
Consumed Ah display (setting 55) | ON | ON |
OFF
7.5.8. State of charge display
Must be set to ON to display the battery state of charge in the monitoring
menu.
Setting | Default | Range | Step size |
---|---|---|---|
State of charge display (setting 56) | 5 | 1 – 5 | 1 |
7.5.9. Time-to-go display
Must be set to ON to display the state of charge in the monitoring menu.
Setting | Default | Modes |
---|---|---|
Time-to-go display (setting 57) | ON | ON |
OFF
7.6. Miscellaneous settings
7.6.1. Software version
Setting 61
This is a read-only setting. it displays the firmware version of the battery
monitor.
The software version as displayed on the head unit is the same as the firmware
version as displayed in the VictronConnect app product settings. In addition
to this, the VictronConnect app also allows updating of the firmware. For more
information see the Firmware [32] setting.
Setting | Default | Mode |
---|---|---|
Software version (setting 61) | Displays the battery monitor firmware | |
version. | Read-only |
7.6.2. Restore defaults
Setting 62
This head unit setting resets all settings to factory default.
The defaults can also be restored via the VictronConnect app. For more
information on how to do this see the Reset to defaults [33] chapter.
To restore defaults do the following:
- Navigate to setting 62: the text “restore defaults” is displayed
- Press SELECT on the head unit: the blinking text “reset” is displayed.
- Press SELECT again: a beep is heard, and all settings have gone back to factory default.
- Should the reset function have been entered accidentally and the text “reset” is blinking, press SETUP to leave and go back to the regular settings menu.
Note that restoring the defaults does not clear the history settings. To clear
the history see the Clear history [31] setting.
When in normal operating mode, the factory settings can also be restored by
pressing SETUP and SELECT simultaneously for 3 seconds on the head unit. Note
that this is only possible if the Lock setup [31] setting is off.
7.6.3. Clear history
Setting 63
This setting resets all settings to factory default. To clear the history do
the following:
- Navigate to setting 63: the text “clear history” is displayed
- Press SELECT on the head unit: the blinking text “clear” is displayed.
- Press SELECT again: a beep is heard and all settings have gone back to factory default.
- Should the reset function have been entered accidentally and the text “clear” is blinking, press SETUP to leave and go back to the regular settings menu.
The history can also be cleared via the VictronConnect app, for more
information on how to do this see the Reset history [32] chapter.
Please be aware that history data is an important tool to keep track of
battery performance and is also needed to diagnose possible battery problems.
Do not clear the history unless the battery bank is replaced.
7.6.4. Lock setup
When on, all settings (except this one) are locked (read-only) and cannot be
altered via the head unit. Note that they still can be altered via the
VictronConnect app.
Setting | Default | Modes |
---|---|---|
Lock setup (setting 64) | OFF | ON/OFF |
7.6.5. Shunt current
When a shunt other than the one supplied with the battery monitor is used, use
this setting to set the rated current of the shunt.
Setting | Default | Range | Step size |
---|---|---|---|
Shunt current (setting 65) | 500A | 1 – 9999A | 1A |
7.6.6. Shunt voltage
When a shunt other than the one supplied with the battery monitor is used, use
this setting to change the rated voltage of the shunt.
Setting | Default | Range | Step size |
---|---|---|---|
Shunt voltage (setting 66) | 50mV | 1 – 75mV | 1mV |
7.6.7. Battery starts synchronised
Note that if the battery monitor settings are accessed via the head unit, this
setting will be part of the miscellaneous setting, and if accessed via
VictronConnect it will be part of the battery settings.
For full information about this setting see the Battery starts synchronised
[25] chapter.
Setting | Default | Modes |
---|---|---|
Start synchronized (setting 70) | ON | ON/OFF |
7.7. Additional settings
These VictronConnect settings are not located in the VictronConnect settings
menu but are located elsewhere in the VictronConnect app.
7.7.1. Reset history
This setting can be found at the bottom of the history tab.
This setting can also be made via the head unit. For more information see the
Clear history [31]chapter.
Please be aware that history data is an important tool to keep track of
battery performance and is also needed to diagnose possible battery problems.
Do not clear the history unless the battery bank is replaced.
7.7.2. Reset PIN code
Note that the PIN code is only applicable when connecting to the battery
monitor via Bluetooth.
This setting can be found in the settings of the VictronConnect app itself.
Leave the battery monitor by clicking on the ← arrow.
This will bring you back to the device list of the VictronConnect app. Now,
click on the menu symbol next to the battery monitor listing.
A new window will open which allows you to reset the PIN code back to its
default: 000000. To be able to reset the PIN code you will need the enter the
battery monitor unique PUK code. The PUK code is printed on the product
information sticker on the Battery monitor.
7.7.3. Serial number
The serial number can be found in the battery monitor product info section of
the VictronConnect app or on the product information sticker rear of the
battery monitor head unit.
7.7.4. Custom name
In the battery monitor product information screen, you can change the name of
the battery monitor. By default, it is called by its product name. But a more
applicable name might be needed, especially if you are using multiple battery
monitors in close proximity of each other it might become confusing with which
battery monitor you are communicating. You can, for example, add
identification numbers to their name, like: Battery Monitor A, Battery Monitor
B and so on.
7.7.5. Firmware
The battery monitor runs on firmware.
Occasionally a newer firmware version is available. New firmware is released
to either add features or to fix a bug. The product overview in the
VictronConnect app displays the battery monitor firmware version. It also
indicates whether the firmware is the latest version, and there is a button
you can press to update the firmware.
On the first installation, it is always recommended to update to the most
recent firmware (if available). Whenever you connect to the battery monitor
with an up-to-date version of the VictronConnect app, it will check the
firmware, and if there is a newer version available, it will ask you to update
the firmware. The VictronConnect app contains the actual firmware files, so an
internet connection is not needed to update to the most recent firmware as
long as you are using the most up-to-date version of the VictronConnect app.
A firmware update is not mandatory. If you choose not to update the firmware,
you can only read out the battery monitor, but you cannot change settings.
Settings can only be changed if the battery monitor runs on the most recent
firmware.
For more information on firmware updates also see the VictronConnect app
manual Firmware update chapter.
This setting is also available via the head unit Software version [31]
setting. But note that this is a read-only setting. The firmware cannot be
updated via the head unit.
7.7.6. Reset to defaults
To set all settings back to default select “Reset to defaults”. Please note
that this only resets all settings to their default values, the history is not
reset.
This setting is also available via the head unit. For more information see the
Restore defaults [31] chapter.
Battery capacity and Peukert exponent
Battery capacity is expressed in Amp hour (Ah) and indicates how much current
a battery can supply over time. For example, if a 100Ah battery is being
discharged with a constant current of 5A, the battery will be totally
discharged in 20 hours.
The rate at which a battery is being discharged is expressed as the C rating.
The C rating indicates how many hours a battery with a given capacity will
last. 1C is the 1h rate and means that the discharge current will discharge
the entire battery in 1 hour.
For a battery with a capacity of 100Ah, this equates to a discharge current of
100A. A 5C rate for this battery would be 500A for 12 minutes (1/5 hours), and
a C5 rate would be 20A for 5 hours.
There are two ways of expressing the C rating of a battery. Either with a
number before the C or with a number after the C.
For example:
- 5C is the same as C0.2
- 1C is the same as C1
- 0.2C is the same as C5
The capacity of a battery depends on the rate of discharge. The faster the
rate of discharge, the less capacity will be available.
The relation between slow or fast discharge can be calculated by Peukert’s law
and is expressed by the Peukert exponent. Some battery chemistries suffer more
from this phenomenon than others. Lead acid are more affected by this than
lithium batteries are.
The battery monitor takes this phenomenon into account with Peukert exponent.
Discharge rate example
A lead acid battery is rated at 100Ah at C20, this means that this battery can
deliver a total current of 100A over 20 hours at a rate of 5A per hour. C20 =
100Ah (5 x 20 = 100).
When the same 100Ah battery is discharged completely in two hours, its
capacity is greatly reduced. Because of the higher rate of discharge, it may
only give C2 = 56Ah.
Peukert’s formula
The value which can be adjusted in Peukert’s formula is the exponent n: see
the formula below.
In the battery monitor the Peukert exponent can be adjusted from 1.00 to 1.50.
The higher the Peukert exponent the faster the effective capacity ‘shrinks’
with increasing discharge rate. An ideal (theoretical) battery has a Peukert
exponent of 1.00 and has a fixed capacity regardless of the size of the
discharge current. The default setting in the battery monitor for the Peukert
exponent is 1.25. This is an acceptable average value for most lead acid
batteries.
Peukert’s equation is stated below:
Where Peukert’s exponent n is:
To calculate the Peukert exponent you will need two rated battery capacities. This is usually the 20h discharge rate and the 5h rate, but can also be the 10h and 5h, or the 20h and the 10h rate. Ideally use a low discharge rating together with a substantially higher rating. Battery capacity ratings can be found in the battery datasheet. If in doubt contact your battery supplier.
Calculation example using the 5h and the 20h rating
The C5 rating is 75Ah. The t1 rating is 5h and I1 is calculated:
A Peukert calculator is available at http://www.victronenergy.com/support- and-downloads/software#peukert-calculator.
Please note that the Peukert exponent is no more than a rough approximation of reality. In case of very high currents, the battery will give even less capacity than predicted by a fixed exponent. We do not recommend changing the default value in the battery monitor, except in the case of lithium batteries.
Troubleshooting
9.1. Functionality issues
9.1.1. Unit is dead
On first connection the display of the head unit should be active.
If this is not the case check the fuse in the BATTERY + cable and also check
the cable itself and its terminals.
9.1.2. Unable to change VictronConnect settings
Settings can only be changed if the battery monitor is running on the most up
to date firmware. Update to the latest firmware with the VictronConnect app.
9.2. Connection issues
9.2.1. Cannot connect via Bluetooth
It is highly unlikely that the Bluetooth interface is faulty. Some pointers to
try before seeking support:
-
Is the battery monitor connected to a VE.Direct Bluetooth Smart dongle? The battery monitor does not have built-in Bluetooth.
The VE.Direct Bluetooth Smart dongle needs to be connected to the VE.Direct terminal of the head unit to equip the battery monitor with Bluetooth. -
Is the battery monitor powered up? The display on the head unit should be active. If not see the Unit is dead [36] chapter.
-
Is another phone or tablet already connected to the battery monitor? Only one phone or tablet can be connected to the battery monitor at any given time. Make sure no other devices are connected and try again.
-
Is the VictronConnect app up to date?
-
Are you close enough to the battery monitor? In an open space, the maximum distance is about 20 meters.
-
Are you using the Windows version of the VictronConnect app? This version is unable to connect via Bluetooth. Use Android, iOS or macOS instead (or use the USB – VE.Direct interface).
-
Has Bluetooth been turned off in the settings? See the ??? chapter.
For connection issues, see the troubleshooting section of the VictronConnect manual: https://www.victronenergy.com/live/victronconnect:start.
9.2.2. PIN code lost
Note that the PIN code is only applicable when connecting to the battery
monitor via Bluetooth.
If you have lost the PIN code you will need to reset the PIN code to its
default PIN code, see the Reset PIN code [32] chapter.
More information and specific instructions can be found in the VictronConnect
manual: https://www.victronenergy.com/live/victronconnect:start.
9.3. Incorrect readings
9.3.1. Charge and discharge current are inverted
The charge current should be shown as a positive value. For example: 1.45A.
The discharge current should be shown as a negative value. For example:
-1.45A.
If the charge and discharge currents are reversed, the negative power cables
on the battery monitor must be swapped.
9.3.2. Incomplete current reading
The negatives of all the loads and the charge sources in the system must be
connected to the system minus side of the shunt.
If the negative of a load or a charge source is connected directly to the
negative battery terminal or the “battery minus” side on the shunt, their
current will not flow through the battery monitor and will be excluded from
the overall current reading and the state of charge reading.
The battery monitor will display a higher state of charge than the actual
state of charge of the battery.
9.3.3. There is a current reading while no current flows
If there is a current reading while no current is flowing through the battery
monitor, perform a zero current calibration [26] while all loads are turned
off or set the current threshold [25].
9.3.4. Incorrect state of charge reading
An incorrect state of charge can be caused by a variety of reasons.
Incorrect battery settings
The following parameter(s) will have an effect on the state of charge
calculations if they have been set up incorrectly:
- Battery capacity.
- Peukert exponent.
- Charge efficiency factor.
Incorrect state of charge due to a synchronisation issue:
The state of charge is a calculated value and will need to be reset
(synchronised) every now and then.
The synchronisation process is automatic and is performed each time the
battery is fully charged. The battery monitor determines that the battery is
fully charged when all 3 “charged” conditions have been met. The “charged”
conditions are:
- Charged voltage (Voltage).
- Tail current (% of battery capacity).
- Charge detection time (minutes).
A practical example of the conditions that need to be met before a synchronisation will take place:
- The battery voltage has to be above 13.8V.
- The charge current has to be less than 0.04 x battery capacity (Ah). For a 200Ah battery, this is 0.04 x 200 = 8A.
- Both above conditions have to be stable for 3 minutes.
If the battery is not fully charged or if the automatic synchronisation does
not happen, the state of charge value will start to drift and will eventually
not represent the actual state of charge of the battery.
The following parameter(s) will have an effect on automatic synchronisation if
they have been set incorrectly:
- Charged voltage.
- Tail current.
- Charged detection time.
- Not occasionally fully charging the battery.
For more information on these parameters see the chapter: “Battery settings”.
Incorrect state of charge due to incorrect current reading:
The state of charge is calculated by looking at how much current flows in and
out of the battery. If the current reading is incorrect, the state of charge
will also be incorrect. See paragraph Incomplete current reading [37].
9.3.5. State of charge is missing
This means that the battery monitor is in an unsynchronised state. This can
occur when the battery monitor has just been installed or after it has been
unpowered for some time and is being powered up again.
To fix this, fully charge the battery. Once the battery is close to a full
charge, the battery monitor should synchronise automatically.
If that doesn’t work, review the synchronisation settings.
If you know the battery is fully charged but don’t want to wait until the
battery synchronises, then perform a manual synchronisation, see paragraph
Synchronise SoC to 100% [25].
9.3.6. State of charge does not reach 100%
The battery monitor will automatically synchronise and reset the state of
charge to 100% as soon as the battery has been fully charged. In case the
battery monitor does not reach a 100% sate of charge, do the following:
- Fully charge the battery and check if the battery monitor correctly detects if the battery is fully charged.
- If the battery monitor does not detect that the battery has been fully charged you will need to check or adjust the charged voltage, tail current and/or charged time settings. For more information see Automatic synchronisation [19].
9.3.7. State of charge always shows 100%
One reason could be that the negative cables going in and out of the battery
monitor have been wired the wrong way around, see Charge and discharge current
are inverted [36].
9.3.8. State of charge does not increase fast enough or too fast when
charging
This can happen when the battery monitor thinks the battery is bigger or
smaller than in reality. Check if the battery capacity [13] has been set
correctly.
9.3.9. Incorrect battery voltage reading
Check if there is an issue with the BATTERY + cable. Perhaps the fuse, the
cable itself or one of the terminals is faulty or there is a loose connection.
Check for incorrect wiring: the BATTERY + cable has to be connected to the
positive of the battery bank, not midway of the battery bank.
9.3.10. Synchronisation issues
If the battery monitor does not synchronise automatically, one possibility
could be that the battery never reaches a fully charged state. Fully charge
the battery and see if the state of charge eventually indicates 100%.
Another possibility is that the charged voltage setting [24] should be lowered
and/or the tail current setting [24] should be increased.
It is also possible that the battery monitor synchronises too early. This can
happen in solar systems or in systems that have fluctuating charge currents.
If this is the case change the following settings:
- Increase the “charged voltage [24]” to slightly below the absorption charge voltage. For example: 14.2V in case of 14.4V absorption voltage (for a 12V battery).
- Increase the “charged detection time [24]” and/or decrease the “tail current [24]” to prevent an early reset due to passing clouds.
Technical data
10.1. Technical data
Battery monitor | BMV-700H |
---|---|
Supply voltage range | 60 – 385 Vdc |
Current draw (backlight off) | < 4mA |
Battery capacity (Ah) | 1 – 9999Ah |
Operating temperature range | -40 +50°C (-40 – 120°F) |
VE.Direct communication port | Yes |
Relay | 60V / 1A normally open (function can be inverted) |
RESOLUTION & ACCURACY (with a 500A shunt)
Current| ± 0.01A
Voltage| ± 0.01V
Amp hours| ± 0.1Ah
State of charge (0 – 100%)| ± 0.1%
Time-to-go| ± 1 min
Accuracy of current measurement| ± 0.4%
Accuracy of voltage measurement| ± 0.3%
INSTALLATION & DIMENSIONS
Installation| Flush mount
Head unit front diameter| 63mm (2.5 inch)
Head unit front bezel| 69 x 69mm (2.7 x 2.7 inch)
Head unit body diameter and depth| 52mm (2.0 inch) and 31mm (1.2 inch)
Shunt connection bolts| M10 (0.3937 inch)
Head unit protection category| IP55 (not intended for outdoor use)
STANDARDS
Safety| EN 60335-1
Emission / Immunity| EN 55014-1 / EN 55014-2
Automotive| ECE R10-4 / EN 50498
ACCESSORIES
Shunt (included)| 500A / 50mV
**** Cables (included)| 10 meter 6 core UTP with RJ12 connectors.
1 cable with 1A slow blow fuse for the battery positive connection.
Temperature sensor| Optional (ASS000100000)
Appendix
11.1. Dimensions BMV head unit
11.2. Dimensions BMV H shunt enclosure
References
- victronconnect:start [Victron Energy]
- Manual - BMV-700H
- 9. Firmware updates
- 10. VictronConnect-Remote (VC-R) – Configuration and monitoring via VRM
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>