Dwyer SAH Series SMART Air Hood Balancing Instrument SMART Air Hood App Software Instruction Manual
- June 4, 2024
- Dwyer
Table of Contents
- SAH Series SMART Air Hood Balancing Instrument SMART Air Hood App
- SETUP
- CONNECTING TO A WI-FI NETWORK
- SETTING UP A GOOGLE ACCOUNT
- UPDATING THE SMART AIR HOOD ® APPLICATION SOFTWARE
- APPLICATION PREFERENCES
- CONNECTING TO THE HOOD
- ZEROING THE HOOD **
- SELECTING THE DIFFUSER
- MANUAL K-FACTOR **
- HOOD INFORMATION **
- LOGGING **
- PREDICTIVE BALANCING
- BRANCHES **
- BRANCHES MENU
- ADD REGISTERS
- BALANCING PROCEDURE
- FCC/INDUSTRY CANADA NOTICE
- MAINTENANCE/REPAIR
- WARRANTY/RETURN
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Bulletin TE-SAH-SWV2
Series SAH SMART Air Hood ® Balancing Instrument SMART Air Hood ® App
Software
Specifications – Installation and Operating Instructions
SAH Series SMART Air Hood Balancing Instrument SMART Air Hood App
Software
The Series SAH SMART Air Hood ® Balancing Instrument is the most accurate and easy-to-operate air flow hood on the market. By using the included hood stand and wireless communications to the handheld, a single operator can balance a branch in less time than traditional balancing teams. Besides being lighter than most traditional capture hoods, the ergonomic design makes the Series SAH easy to maneuver, with less physical stress. The rugged polypropylene base hood features patented Quad Flow Design Technology for controlling air flow and minimizing back pressure, which yields superior measurement accuracy. The Wi-Fi direct communication gives reliable communication with a distance of up to 200 yards (183 m) between the hood and the handheld test instrument. The SMART Air Hood ® balancing instrument includes the SMART Air Hood ® application software which reduces the number of steps in the air flow balancing process using Predictive Balancing’s Express Balance mode. Predictive Balancing is a method of predicting the optimal flow set point for each register and the order in which they should be adjusted.
SETUP
To be able to update the SMART Air Hood ® application software, a Google account must be created so that the application can be updated from Google Play ™ store. To properly connect to Google Play ™ store a connection to a Wi- Fi network must be established.
CONNECTING TO A WI-FI NETWORK
First, press the application icon on the home screen (should look similar to
the below image).
Then find the settings icon and click on it.
Next, press Wi-Fi to enter into the Wi-Fi settings.
Next, choose a local Wi-Fi network to connect to.
Enter in the password to connect to the Wi-Fi access point.
The handheld will now be connected to the Wi-Fi network.
SETTING UP A GOOGLE ACCOUNT
First, go back to main Settings screen and choose the “Add account” option.
Select Google.
If you have a Google account select “Existing” and enter in your account
information to register your Google account to the device.
If you do not have a Google account follow the guide below to add one.
First, press “New” and follow the on-screen prompts.
When the account is created you might need to do an authentication check to
activate the account. The notice will be in the pull-down menu on the device.
Press the notification and follow the instructions to activate the account.
If the account was created correctly the following screen will show your new
account.
UPDATING THE SMART AIR HOOD ® APPLICATION SOFTWARE
Now that a Wi-Fi connection is established and a Google account is tied to the
handheld instrument, the Google Play ™ store can now be accessed. Open Google
Play ™ store from the applications.
Search for SMART Air Hood ® application software and press it. Once selected,
press the “UPDATE” button to update the application.
The SMART Air Hood ® app should now be up to date.
APPLICATION PREFERENCES
When the application is first opened, the following screen will be shown.
To access the application preferences, press the three lines at the top left
of the page and select “Preferences”. The following screen will appear.
After the initial startup, the app will automatically open to the home screen
shown below. The Preferences can also be accessed from the home screen by
pressing the three lines at the top left of the page and selecting
“Preferences”.
CONNECTING TO THE HOOD
Once the handheld instrument is on, open the SMART Air Hood ® application software. To begin searching for the air flow hood, the hood connection screen can be accessed by pressing the “HOOD SETTINGS & CONNECT BUTTON” on the welcome screen, or by selecting hood connection from the menu on the main screen..
As the app discovers hoods, they will be added to the list below the search
status bar.
Select the hood that is to be paired and confirm your selection by clicking
“YES” when prompted to do so.
Once connected, press the “X” in the top left corner to return to the home
screen. Note: Press the information button “ ” on the hood connection screen
to obtain general hood information such as calibration date, serial number,
etc.
To disconnect from the current hood, press the hood name on hood connection
screen. The disconnect dialog comes up, which allows for the hood to be
disconnected. If “No” is selected, the dialog will be closed without any other
action being taken. If “Yes” is selected, the hood will be disconnected, but
still paired.
ZEROING THE HOOD **
**
In order for the hood to be zeroed, place it in the desired orientation in
which is going to be utilized. Make sure that the hood is blocked so that no
air is flowing through it.
In order to zero the hood, press the three bars at the top of the screen or
slide from the left or press the menu button. Press the “Zero” button at the
top of the home screen. After the correct hood position is verified, select
“Zero The Hood” to begin the zeroing process.
When the zeroing process is complete, it will show the following screen and
the reading will be 0. Note: If there is too much air flow, the zero button
will be disabled.
SELECTING THE DIFFUSER
To select a diffuser, press the diffuser tab above the “Log This Reading”
button.
Select the “Standard” accuracy level to take readings at the industry standard
accuracy level.
Select the “High” accuracy tab to take high accuracy readings. The neck size and diffuser type must be considered for high accuracy readings which results in a larger diffuser selection list.
If the desired diffuser is not available in the diffuser library, the K-factor can be entered under the “Manual” tab.
MANUAL K-FACTOR **
**
In the case that diffuser being used is not in the downloadable library, but the K-factor of the diffuser is known, the K-factor can be manually entered into the application. While on the application home screen, tap on the diffuser to open the Diffuser list.
Select “Manual” under the accuracy level selection. Define it as a Register for supply flow or Return for return flow and press on the K-Factor field to enter the K-factor of the diffuser. Once completed, select “SAVE” in the top right corner to exit to the main menu.
HOOD INFORMATION **
**
As mentioned in the hood connection menu, general hood information can be
obtained by selecting the “ ” next to the desired hood.
Once the “ ” button is selected, the information below will appear.
To return to the main menu, select the “X” in the top left corner of the
“About the hood” screen and again in the “Hood Connection” screen.
LOGGING **
**
Log files can be generated from the main home screen. To begin logging, press
the “LOG THIS READING” towards the bottom of the screen.
Once the reading has been logged, the reading will be indicated in the bottom
right corner.
To view the logged readings, press the log button in the bottom right corner.
In the reading log screen, the individual logs can be named by clicking below the “Register name” heading. To delete individual logs, select the “X” corresponding to the log that is to be deleted.
Logs can be exported by selecting the “EXPORT” button in the bottom left corner. To delete all logs, select the “CLEAR ALL” button in the top right corner and confirm the action by selecting “YES” on the pop-up.
PREDICTIVE BALANCING
Predictive balancing is available on Android applications only
To enter predictive balancing, press the menu button in the top left corner of
the home screen (three horizontal bars) and select “PREDICTIVE BALANCING”.
BRANCHES **
**
Once Predictive Balancing is opened, you will be prompted to create a new branch or to import an existing branch if there is not currently any branches set up.
To create a new branch, select “CREATE NEW BRANCH” and enter the name and location of the branch when prompted to do so. Once the branch has been named, registers can either be imported or added manually.
To manually add registers, select “ADD REGISTERS”. From the register screen,
the name, target CFM, and diffuser type can be entered.
Once all of the necessary registers have been entered or imported, the branch
will be added to the “Current Branches” list.
Next, click on the desired branch name. This will bring up a dialog with the
available actions for that branch. If the branch has been previously started,
then the following menu will be shown.
“Edit” will bring up the “Add Edit Branch” screen. Note: “Restart” will appear instead of “Edit” if balancing has already begun. “Restart” will clear any balancing data for that branch and allow you to restart balancing from the beginning.
“Delete” will bring up a dialog asking to confirm the deletion.
“Export Branch” will bring up a file dialog.
Click on the “File Name” field to enter the file name associated with this
branch. This field can’t be blank or an error message will appear. The folder
icon with the arrow will navigate up a folder. Folder names do not have
extensions and file names will have extensions.
BRANCHES MENU
Clicking the 3 horizontal lines at the top of the page will open the Branches
Menu.
Pressing “Sort Branches” will bring up a dialog that contains the options to
sort branches by different methods.
Clicking the “+” symbol in the bottom right corner will allow you to add a new
branch.
“Import” will allow you to select a file to choose which branch to load.
Clicking the branch name loads that branch and adds it to the list of
branches. Once complete, the app will be return to the Branches main page
with the new branch added to the list.
“New Branch” will allow you to set up an additional branch by manually
entering in the registers.
ADD REGISTERS
If “New Branch” was selected, registers will have to be added.
“Import Registers” will open the file manager and allow a .csv file to be
chosen. Note that some of the files might not be a register file, which
displays an error if selected.
“Add Register” will bring up the Add Edit Register screen with nothing filled
in except for the default diffuser. As in Meter Mode, if the desired diffuser
is not shown, select the manual diffuser to create a diffuser with a known
K-Factor.
Clicking either the Name or Target field will bring up a keyboard allowing
values to be entered. Note that the register name must be unique. If a
registered name is entered that is already in the list, the following dialog
will be shown.
Both the name and the target fields must be filled in to create a register.
For more options on the Add/Edit Resisters screen, press the three horizontal
bars in the top left corner to open the menu.
“Clear Registers” will erase all the registers in the list for the selected
branch.
“Export Registers” will allow the registers to be saved to the handheld
instrument. Note that the same dialog will come up asking to overwrite the
file if a name is chosen that is already in use.
“Set Keys” will bring up a dialog that allows the selection of which registers
are candidates to be the key (checked registers can be the key and unchecked
cannot be the key). At least one register must be selected.
BALANCING PROCEDURE
Once the desired branches have been created, the balancing can be started by
selecting “Begin Balancing”.
After confirming all dampers are opened, the first step of the balancing
procedure is to take an initial sweep of all registers within the selected
branch.
Red indicates that a reading still needs to be taken from the register. After
selecting the register to measure it’s button will turn from red to white,
indicating that it is the active register.
Click register button again to store the reading, at which point it will
change from white to green, indicating that a value has been stored for that
register.
Repeat this procedure until all of the registers have been measured. Clicking
on a register again allows for a retaking of that register if needed.
If the slide-out menu is opened, the following choices will be shown.
If the slide-out menu is opened, the following choices will be shown.
“Pause Balancing” will pause the balancing project and return to the home
screen.
“Enter Manual Data” allows data to be entered manually for a register that
cannot be measured. To manually enter data, select a register (changing the
button from red to white) and then select “Enter Manual Data” to enter the
flow value.
Once all of the registers have been measured, press and hold the continue
button at the bottom until the predictive balancing screen appears.
As shown below, the app will direct you to the register to measure:
Press and hold the OK button to bring up the dialog box asking to confirm that
the hood is correctly placed.
If the “Yes” button on the hood placement confirmation dialog was pressed the
app will bring up the Adjust to Target screen.
“Manual Data” will bring up the Manual Data screen similar to the initial
sweep manual entry dialog. After the manual data is entered, another dialog
will appear. This manual entry dialog asks for the flow of the register after
adjusting (if it can be adjusted). The dialog includes the target flow that
the register needs to reach to balance the system.
If the CANCEL button is pressed, a Pause Balancing screen will be brought up.
Pressing the PAUSE button in the pause dialog will store the current location
and data within the selected balancing method and return back to the Branches
screen.
While in this screen, the damper needs to be adjusted to match the target.
Press and hold the NEXT button to bring up the next screen which will guide
you to the next register to measure and adjust. Once all registers except the
key register are adjusted the app will require a post-reading from all the
registers. The app will guide you through the post-reading process.
The last register measured will be the key register after which the adjust
system will come up requesting to adjust the branch’s flow source to the given
target.
After adjusting all the registers, the Final Reading screen can be accessed.
This screen is to gather the final readings to calculate the error ratio of
the balancing process which is displayed on the next screen.
Once all of the registers are measured, Press and hold the NEXT button, to
bring up the Final Results screen. This screen displays how accurate the
balancing method was.
Sliding a finger from the left edge of the screen towards the right, clicking
the menu button, or clicking the 3 lines at the top of the page will open the
Final Results Menu.
“Retake Readings” will return to the Final Readings screen so that one or more
of the register readings can be retaken.
When back in the “Branches” screen the menu when the branch will now have the
option “ View Results” instead of “Resume Balancing” or “Start Balancing”.
“View Results” will bring you back to the “Final Results” screen with the
previous balancing process’s final results.
FCC/INDUSTRY CANADA NOTICE
This device complies with Part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between equipment and receiver
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
- This device may not cause harmful interference;
- This device must accept any interference received, including interference that may cause undesired operation of the device.
Pursuant to FCC 15.21 of the FCC rules, changes or modifications not expressly approved by Dwyer Instruments, Inc. may void the user’s authority to operate the equipment.
RF NOTICE
This product complies with FCC OED Bulletin 65 and Industry Canada’s RSS-102
radiation exposure limits set forth for an uncontrolled environment.
This Class B digital apparatus complies with Canadian ICES-003.
The antenna used for this transmitter must maintain a separation of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
MAINTENANCE/REPAIR
Upon final installation of the Series SAH, no routine maintenance is required. The Series SAH is not field serviceable and is not possible to repair the unit. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
©Copyright 2022 Dwyer Instruments, Inc.
Printed in U.S.A. 2/22
FR# 444357-50 Rev. 1
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone:219-879-8000
Fax:219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com