Safety Instructions

Please read the safety instructions below before using the EV Charging Station to avoid risks of fire, electric shocks, personal injuries or equipment damage.
Installation and adjustments must be made by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so.
For electrical work, follow the local national wiring standard, regulation and these installation instructions. Connection to the mains supply must be in accordance with the national regulations for electrical installations.
This product is designed and tested in accordance with international standards. The equipment should be used for its designated application only and in accordance with the specified operating parameters.
Warnings and cautions:

  • Never install near fire sources, explosive materials, combustibles or other flammable sources. Never use it at places where gas or other chemical explosions could occur.
  • It must be connected all the times to the ground, otherwise it will not allow charging.
  • Turn off the EV Charging Station power before installing or performing operations to it.
  • Make sure children are supervised if using the equipment.
  • Do not put fingers or insert objects or sharp metallic objects into the terminals. Do not insert objects into any other parts of the EV Charging Station.
  • Do not use the device if the power cord or EV cable is broken, shows any signs of damage or does not function properly.
  • Do not use the EV Charging Station if it is broken, defective, cracked, damaged or does not function properly.
  • Do not apply strong force on the equipment, to prevent crashes and deterioration.
  • Do not use any sharp objects to damage the product.
  • Do not service the equipment by yourself, do not open, disassemble or make any modifications to it. Contact your Victron Energy Distributor.
  • Do not touch any live electrical parts.
  • Do not place the EV cables connected to the charging station in water.
  • Make sure ground connection is properly done to prevent equipment damage.
  • Transport the device with care in its original package to avoid damage to it and its components.
  • Store in a dry environment, at temperatures between –20 °C to 60 °C.
  • Do not operate at temperatures outside the operating range of -25 ˚C to 50 ˚C.
  • As the EV Charging Station can affect the functioning of certain medical electronic implants, check any potential side effects with your electronic device manufacturer before using the device.c

Description and features

2.1. Description
The EV Charging Station with its three-phase and single-phase charging capabilities integrates seamlessly into the Victron environment with its GX device connection via WiFi and enables easy operation and control via Bluetooth and the VictronConnect App. It delivers a maximum of 22kW AC in three-phase or 7.3kW in single-phase mode. A built-in 4.3-inch LCD touch screen enables easy monitoring and control.
Not only does this EV charging station fully integrate with a Victron Energy GX device and VRM, if you have solar, it can also be set up to allow excess energy from the sun to directly charge your vehicle once your house batteries are full and feed-in is active.
The tough plastic enclosure is designed to withstand harsh weather and can be mounted inside or outside.
A programmable RGB light ring around the charging port (type 2 EV charging plug) allows for quick determination of the device state and can be programmed from the integrated web interface to display different light effects based on the current state (disconnected, charging, charged etc.).
2.2. Features
Three operation modes:

  1. Automatic mode to ensure maximum PV system efficiency
    Thanks to the seamless integration of the EV Charging Station with the rest of the Victron installation, it detects when surplus power is available and uses only this power to charge the vehicle. Note that this mode requires a GX device in your system and communication with the EVCS.
    Instead of loosing surplus energy when the batteries are full if feeding back into the grid at a lower price, the energy is stored into the EV battery.
    • Seamless integration into the Victron installation
    • Detects when excess power is available and uses only that to charge the vehicle before exporting it to the grid
    • Ensures maximum PV efficiency

  2. Manual mode to configure output current
    Manual mode allows configurable output current between 6-32A.
    The charging power is controlled in several ways:
    • By using the slider on the LCD touch screen
    • By using the web interface via a web browser
    • From a GX device touch screen like the GX Touch 50 & GX Touch 70
    • From the Remote Console
    • By using the Controls on the Dashboard of our VRM Portal (requires a GX device)
    • Via Bluetooth and the VictronConnect App
    It allows charging to be started or stopped manually when an EV is connected to the charging station, regardless of PV production.

  3. Scheduled mode to allow automatic charging at custom time intervals
    The Scheduler allows charging at different time intervals, for example at certain times during the night when grid energy is cheaper.
    In addition to the start and end time, various parameters such as charging current and interval can be defined.
    WiFi Communication WiFi 802.11 b/g/n for configuration, control and monitoring The internal WiFi module can be configured in Access Point mode or Station mode, for first setup, control and monitoring.

Bluetooth communication via VictronConnect
Integrated Bluetooth capability enables easy monitoring and control of the EV Charging Station via VictronConnect from any mobile device such as an iPhone, iPad or Android phone.
For more details see the VictronConnect setup, configuration and operation [20] chapter.
Integration with GX devices
Control and monitor the EV Charging Station from a GX device such as the Cerbo GX and the Remote Console.
For more details see the GX device setup, configuration and operation [18] chapter.
Integration with VRM
Several options are available in the VRM Portal:

  • Real time reports
  • Custom reports for configurable time periods
  • Advanced functions such as remote firmware updates
  • Change mode and charge current via Dashboard Controls on the VRM Portal and start/stop charging Control and monitoring is also possible via VRM App (download from App Store or Google Play) and VRM App Widgets directly from the home screen of a mobile device.

victron energy 22kW EV Charging Station - Integration with GX
devices

For detailed information, see the VRM Portal documentation.
LCD Touch Screen
Built-in 4.3″ LCD touch screen for monitoring and control directly from the charging station.
Light Ring for fast viewing the device state
It also has a fully programmable RGB light ring around the charging port, which can be used to quickly determine the status of the device even from a distance. It can be programmed via the web interface to display different light effects depending on the current
state (disconnected, charged, loaded, etc.).
2.3. What’s in the box?
The following items are in the box:

  • EV Charging Station with supplied 28mm nylon cable gland for power cables up to 19mm in diameter

Installation

This product may only be installed by qualified personnel (licensed electrician).
It is suitable for wall mounting or pole mounting (vertical surface). In all cases, the surface should be solid and flat.
Precautionary measures

  • Ensure that the AC input is protected by a fuse or magnetic circuit breaker rated at 40A or less. The cable cross-section must be sized accordingly. If the AC input supply is rated at a lower value, the fuse or magnetic circuit breaker should be sized accordingly.

  • For charging at 22kW we recommended a 40 amp RCD type B protected supply.

  • Recommended cable cross-section is 6mm² / AWG 10.

  • Inside the device is a sticker with the model, serial number, WiFi password and, depending on the date of manufacture, the unique Bluetooth pairing code.
    Note the password and pairing code on the internal label for future reference. This initial password can be used for both logging in on the web page but also for WiFi connection.

  • The tightening force of the screws on the backing plate should be 1-1.2 Nm.

  • The mounting surface should be solid and flat.

  • Make sure you always have the latest version of this manual, which is updated regularly and available on the EV Charging Station website.

Installation steps:

  1. Remove the black backing plate by unscrewing the 8 screws.
  2. Mark the wall where it should be mounted using the removed backing plate as a template.
  3. Drill 4 holes with wall plugs ready for installation.
  4. Measure a suitable location and drill through the wall for the cable (when main supply cable comes from inside the building).
  5. Label each individual cable and pass it through the wall, the nylon gland, the grommet and into the charging station.
  6. Terminate the cable ends with ferrules and connect to the relevant points.
  7. If this is a single-phase installation, use L1, neutral and earth connections.
  8. Tighten the nylon gland around the cable.
  9. Reattach the black plate to the charging station and tighten the 8 screws.
  10. Mount the station on the wall.
    Watch this video for an installation example:

victron energy 22kW EV Charging Station - screws

System example

victron energy 22kW EV Charging Station - System
example

This system displays all available options, specifically:

  • All solar types: AC PV on AC input, AC PV on AC output and DC PV
  • EV Charging Station on AC input or AC output of the inverter/charger
  • Single-phase or three-phase
Key Description
A Grid-feed PV Inverter connected to the AC input of the inverter/charger
B Grid-feed PV Inverter connected to the AC output of the inverter/charger
C Setup, control and monitoring via WiFi or Bluetooth and VictronConnect, web

interface or VRM portal (setup only via WiFi or Bluetooth)
D| EV Charging Station: Connected to the AC input of the inverter/charger
E| For single-phase systems: a single inverter/charger or inverters/chargers connected in parallel
For three-phase systems: three inverter/chargers connected in 3-phase or multiple strings of paralleled units connected in 3-phase
F| EV Charging Station: Connected to the AC output of the inverter/charger
G| Lynx Distributor: On the battery side and on the system side, containing a positive and negative bus bar and all DC fuses
H| Lynx Smart BMS: Monitors and controls (with built-in battery monitor and contactor) the Victron Smart Lithium batteries and Lynx Distributor fuses
I| Cerbo GX: Serves as a control and communication center and enables remote control and monitoring via the VRM portal and/or the VRM App Widgets, accessible directly from a mobile device
J| Victron Lithium Battery Smart: Available in 12.8V & 25.6V and different capacities. A maximum energy storage capacity of 102kWh can be achieved by combining batteries in both series and parallel configurations
K| Solar Charge Controller: A variety of MPPT solar charge controllers are available with voltage ranges from 75V to 450V, allowing for topping up of energy storage and storage of surplus energy in the vehicle’s battery
L| Dedicated RCD type B (40A for charging at 22kW) on the EV charger input

Setup

5.1. First setup
5.1.1. First setup via WiFi access point
The charging station broadcasts its own WiFi access point as soon as the charging station is powered for the first time. The following steps describe the first setup to prepare the charging station for operation.

  1. Connect to the WiFi access point:
    I. Scan the QR Code on the internal label.
    II. Or go to the WiFi menu of your mobile device or laptop and manually add the access point that broadcasts automatically its SSID. SSID and WiFi key are noted on a sticker inside the case.
    III. Or scan the QR code shown on the display during the first setup phase. Note that after the first setup, another QR code will appear on the display, linking to the Victron website. Once connected to the access point, enter the default IP address 192.168.0.1 into a web browser. The First setup process will then start:

  2. WiFi setup: Configure the WiFi network by choosing the WiFi mode
    I. Access point: The unit creates its own WiFi access point. This is either for setting up the unit or in the absence of a separate WiFi network including a GX device. Set SSID, IP address and Netmask according to your needs.
    1. Set SSID, IP address and Netmask according to your needs. II. Station: Connects the device to a local WiFi network that includes other Victron devices like a GX device or VRM.
    1. Change the WiFi mode from AP to Station. 2. Click the Scan button (the scan period and RSSI threshold applies) to search for other WiFi networks or add manually a known AP by clicking the Add button. Note the WiFi standards: 802.11 b/g/n (2.4Ghz only).
    3. Tick the network you wish to connect to and then click Apply. 4. In the Password box, enter the external WiFi password and click Next.
    In case you need a static IP rather then DHCP, change the IP mode button to Manual and fill in the static IP address, Mask, Gateway and DNS.

  3. Access setup:
    I. Click into the Username field and type in your own username. The default username is ‘admin’.
    II. Click into the Password field and change the password to a new one with at least 8 characters, containing lower, upper and special characters. The default password is printed on the sticker inside the unit.
    III. Confirm your new password.
    IV. Click Next.

  4. Charging current setup:
    I. Set the maximum charging current (10 – 32A). II. Click Save to apply all settings. The system restarts and the login page of the web interface is displayed. III. Log in with your credentials that you entered under 3. IV. The main page is then displayed and the EV Charging Station is ready for use.

5.1.2. First setup via VictronConnect
Note that operation via VictronConnect requires Bluetooth to be enabled. Bluetooth is disabled on devices shipped with firmware version 1.23 or earlier. In order to enable Bluetooth for these devices, it is mandatory to first go through the First setup via Wifi access point [6] procedure and then activate it via the Networks menu [17]. Devices shipped with firmware version 1.24 and higher have Bluetooth enabled by default.
The first setup is even easier via VictronConnect.

  1. Open VictronConnect and find the entry for your EVCS (EVCS-HQXXXXXXXXX).
  2. Tap on EVCS. This will start the pairing dialogue. Enter the pairing code which is either 000000 or a uniqe number on a sticker inside the housing.
  3. If pairing was successful, the status page will appear; ignore the page for now (using the EVCS is not yet possible) and tap the cog wheel icon in the upper right to open the Settings page.
  4. Go to the Network settings and tap on it.
  5. One of the following parameters must be changed to complete the first setup and start using the EV:
    I. Selected network mode: Access Point
    The unit creates its own WiFi access point. This is either for setting up the unit or in the absence of a separate WiFi network including a GX device.
    If sticking with AP mode, then change at least the Access Point SSID, the Access Point passphrase or the Access Point IP address in the Wireless Access Point settings. II. Selected network mode: Connect to local WiFi
    Connects the device to a WiFi network that includes other Victron devices like a GX device or VRM.
    1. Change the network mode to Connect to local WiFi, hit OK but do not store the settings yet. Leave the Settings changed popup untouched. 2. Tap on SCAN FOR NETWORKS and make sure you have the password for your local network ready.
  6. Once the scan is complete, a list of available networks will be displayed. Tap ADD for the network of your choice. 4. Enter the passphrase for this network in the popup and press OK.
    5. Change the IP configuration if needed: Automatic (DHCP) or Manual for static IP (requires valid IP address, Netmask, Gateway and DNS from your system administrator). 6. Scroll up and tap on STORE SETTINGS to apply the new settings and confirm with YES. The EVCS will automatically connect to the local network.victron energy 22kW EV Charging Station -
STORE6. The first setup is now finished and the EV Charging Station is ready for use. For more details on how to operate the charging station via VictronConnect, see the VictronConnect setup, configuration and operation [20] chapter

5.2. EV Charging Station setup
After initial setup, set up the EVCS according to your needs. To do this, connect to the web interface and click on the Settings tab for further setting options. The main page options are explained in The main page [16] chapter.
Six subtabs will appear:

  1. Networks tab: See the Networks menu [17] chapter.

  2. General tab: Provides setting options for the charger, GX device communication, display, time zone and device name.
    a. Charger: Charger related settings.
    i. EV charger position: Select where the EVCS is positioned in the system. Examples:
    1. If the charging station is on the output of an inverter as one of the main’s AC outsources, select Inverter AC out.
    2. If connected to the grid and the EVCS is positioned at the AC input of the grid before the inverter, select Inverter AC in.
    ii. EV charger autostart: If enabled, the EVCS will automatically start charging when the vehicle is connected.
    iii. Contactor active when charged: Keeps the contactor closed after charging. For example, when an air conditioner is active in the vehicle, it is powered by AC power rather than the car battery.
    iv. Maximum charging current: 10 – 32A
    v. Minimum charging current: From 6A up to 1A below max. value. Example: A Renault Zoe needs at least 10A.
    vi. Min SoC to allow charging if no grid available (%): If you are off-grid and have no grid connection, you can set the minimum system state of charge (SoC) percentage to retain some power to use in the property.
    vii. Energy price per kWh (€): Enter the cost per kWh in EUR (later firmware versions will allow changing the currency icon) to calculate the session cost saved.
    viii. CP line calibration procedure: If the vehicle is not detected or if the vehicle is fully charged and the EVCS contactor opens/closes, the calibration should be performed.
    ix. Power calibration(0.6 – 1.4): If the displayed power value is not correct, a maximum correction factor of +/- 40% can be applied.
    x. Actual power (kW): Displays the current power value with which the EV is charged.
    b. GX device: The EV Charging Station can be used:
    i. As a stand alone device.
    ii. As part of a larger Victron Energy system. When enabling GX device communication, the GX IP address is that of the GX device. Modbus TCP must be enabled in the GX device (see Modbus TCP activation [18] section) itself to enable communication.
    Note that if GX communication is enabled and the IP address is not correct, the charging station will report the error “low SoC” as it cannot get the SoC from the GX device. Make sure the GX IP address setting matches that of the GX device.
    A. Enable communication: Tick the box to enable communication with a GX device.
    B. GX IP address: The IP address of your GX device.
    C. Discover: Click the Discover button to search for the GX device. Select the GX device from the list that will pop up; the GX IP address will then be entered automatically.
    c. ModbusTCP Server:
    EVCS ModbusTCP server. The address is the same as that of the GX device.
    i. IP address whitelist state: Enable or disable the whitelist state.
    Note that when the IP address whitelist state is enabled, only the devices from the IP address whitelist table below can communicate with the EVCS.
    ii. IP address whitelist table: Add IP addresses that are allowed to communicate with the EVCS.
    d. Display:
    i. Active backlight (%): The brightness of the displays when active.
    ii. Idle backlight (%): The brightness of the displays when idle.
    iii. Active timeout (s): The time after which the active display goes back to idle.
    iv. Lock charger display: Enable/disable control on the display.
    v. Hide WiFi credentials: WiFi credentials are hidden.
    e. Others:
    i. Time zone: Choose the time zone.
    ii. Device name: Change the name of the EV Charging Station, which will then also be updated in the GX device,
    VictronConnect and the VRM portal.

  3. Scheduler tab: The schedule required for the scheduled mode is created in this menu.
    You can schedule scenes to activate automatically under certain conditions. These conditions include:
    a. Start time: Start time of the schedule in hh:mm (24h time format applies)
    b. End time: End time of the schedule in hh:mm (24h time format applies)
    c. Current[6-32A]: Maximum charging current while the schedule is active
    d. Repeat: The time interval at which the schedule is automatically executed again. Possible options:
    i. Daily: Repeats daily
    ii. Mon-Fri: Repeated from Monday to Friday
    iii. Weekends: Repeats every weekend
    iv. Custom: Choose the days of the week you want the scene to repeat
    e. State: State of the scene. If disabled, the schedule for the scene will not run.
    Once a scene has been created, press the Accept button and then the Save button. Note that the scenes are only active when the charging station is in scheduled mode. A currently active scene is highlighted in green in the scheduler and marked active. Scenes can be edited at any time. The same rules apply as described above.
    Use the import and export buttons to import/export scenes in .json format.

  4. Light Ring tab: Customises the ring of lights on the front of the station, around the vehicle socket. A variety of modes to choose from, how long the mode is displayed, the brightness of the lights and their colour.
    The coloured ring is to indicate at a glance what the EV Charging Station is doing: for example, when the vehicle is fully charged, when there is a low state of charge.
    Click the Save button at the bottom of the screen after any change or import/export the Light Ring settings in .json format.

  5. Access tab: Change the username and password.

  6. Backup & FW tab: Export or import saved settings, reset the charging station back to factory defaults and update firmware manually.
    a. FW Update: The EVCS firmware can be updated manually via the web interface or remotely via VRM: Remote firmware update.
    i. Select firmware file (*.evcsup): Press the Open button and browse to the location where the provided firmware file is stored, then click Update. This will start the update process. After a successful update, the charging station restarts and the main page is then displayed again. Note that all settings are retained.
    b. Backup: Backup and restore all system settings from/to a .json format file.
    c. Reset to factory defaults: Resetting the device to default values can be done in 2 ways:
    i. From the webpage by selecting the Backup & FW menu and then press “Reset to factory defaults” or
    ii. From inside the unit, by pressing the DEF button for more than 15 seconds. See image below. Note that if the DEF button is pressed less than 15 seconds but more than 5 seconds, it will reset the password only.

The DEF button procedure should only be performed by qualified personnel as this process requires the EV Charging Station to be powered. Working under high voltage is very dangerous and can be fatal if used incorrectly. Be sure to avoid touching parts in the area marked in red.

5.3. The main page
The main page of the web interface provides control and monitoring elements for the EV Charging Station. These are from top to bottom:

  • Charging mode switch: Change the charging mode to manual, auto or scheduled.
  • Charging current slider: Adjust the charging current.
  • Start/Stop button: Start or stop charging when in manual mode.
  • Session statistics and an animated graphical overview to see the charging progress at a glance.

victron energy 22kW EV Charging Station - main page

5.3.1. Charging mode switch in detail
The Charging mode switch is located on the main screen and provides three different operation modes:

  • Manual mode: Enables the user to turn the vehicle charging ON and OFF manually, using the START STOP button. The amount of current the station provides, can be changed using the Charging current slider.
  • Automatic mode: The system will determine all the settings for the user. Similar to a GX device, the screen shows how the current is flowing. In case a GX device (Cerbo GX or Color Control GX) is included in the system on the same network as the EV Charging Station, there are a variety of settings that can be changed directly from the GX device related to either manual or automatic mode. One can see the device, its summary as well as more advanced power graphs on the main dashboard of the VRM Portal.
  • Scheduled mode: Charge the EV at certain time intervals, for example during the night hours when grid energy is cheaper.
    Note that it is only possible to switch to scheduled mode from VictronConnect or the web interface.
    The manual and automatic modes ensure the best use of the charging station.
    The charging mode can be changed via:
    • The charger screen
    • The web interface
    • A GX device
    • The VRM Portal
    • Bluetooth and VictronConnect
    The manual mode gives flexibility in choice and charges the car independently of PV production. By manually determining how much power goes into a vehicle charge, you can make allowances for other loads in your home.
    The automatic mode ensures maximum efficiency of the PV system and charges excess PV power to the EV before it is fed into the grid.
    When the EV Charging Station is connected to a Victron system and is in automatic mode, the surplus solar power can be used to charge the vehicle instead of feeding it into the grid at a lower price.

5.4. Networks menu
WiFi options and Bluetooth are configured via the network menu of the web interface. Available options are:

  1. WiFi
    a. WiFi mode: Toggles between access point and station mode.
    i. Access point mode: The unit creates its own WiFi access point. This is either for setting up the unit or in the absence of a separate WiFi network including a GX device. SSID, password, IP address and Netmask are configurable.
    ii. Station mode : Connects the device to a WiFi network that includes other Victron devices like a GX device or VRM.
    To do this:
    A. Change the WiFi mode from AP to Station.
    B. Click the Scan button to manually search for other WiFi networks or manually add a known AP by clicking the Add button. Note the WiFi standards: 802.11 b/g/n (2.4Ghz only).
    C. Tick the network you wish to connect to and then click Apply.
    D. In the Password box enter the external WiFi password and click Next.
    E. In case you need a static IP rather then DHCP, change the IP mode button to Manual and fill in the static IP address, Mask, Gateway and DNS.
    F. Click Save. Note that when Station mode is enabled, a WiFi strength indicator appears at the top of the web page. iii. Scan period: If there is only one network to connect to (e.g. a router), the scan period can be set to 0 to avoid unnecessary scanning during an existing connection. If the EVCS connects to more than one network, it is recommended to leave it at the default (60). Note that this is about background network scanning. This parameter has no effect on the manual scan button.
    iv. RSSI threshold: An RSSI threshold can be applied to background scanning.

  2. Bluetooth
    Bluetooth establishes a direct wireless connection between a mobile device and the EV Charging Station to control and monitor the EVCS via VictronConnect. The distance is usually a few meters indoors.
    Note that Bluetooth is disabled on devices with firmware version 1.23 or earlier and must be manually enabled before VictronConnect can be used. The default pairing code for this is 000000. Devices shipped with firmware version 1.24 and higher have Bluetooth enabled by default. The pairing code for this is located inside the housing and is unique.
    The pairing code can be changed via VictronConnect. A factory reset resets the pairing code to factory defaults.
    To enable, disable or unpair Bluetooth via the network menu, the following options are available:
    a. State: Enables or disables Bluetooth functionality. A change requires pressing the Save button to apply the new status.
    b. Unpair all devices: Click to unpair the EVCS from your mobile device(s). Note that this will also restart the charging station and you will still need to remove the pairing from your mobile device’s Bluetooth menu.

GX device setup, configuration and operation

6.1. Modbus TCP activation
The EV Charging Station communicates with the GX device via Modbus TCP. This must first be activated in the GX device and is a mandatory step.

  • In the GX device go to Settings → Services → Modbus TCP and enable Modbus TCP.victron energy 22kW EV Charging Station - Modbus

6.2. Setup menu and options
As soon as Modbus TCP has been activated, the EVCS appears in the device list and displays the current mode and charging state.

victron energy 22kW EV Charging Station - Setup

Highlight the EVCS then press spacebar or cursor right to enter the next menu and at the setup menu item press spacebar again to enter the setup menu. See the EV Charging Station setup [13] and the Description [2] chapter for the meaning of the available options.

victron energy 22kW EV Charging Station - VRM instance

6.3. Overview and device menu
The overview menu provides a button to activate (start) charging in manual mode and the following status information:

  • Actual charging current: The charging current in A
  • Total power: Total power of all phases
  • L1..L3: Power of each individual phase
  • Charging time: The charging time per session
  • Charged energy: Charged energy per session
    If you scroll further down the menu, you will see the Setup and Device menu. See the Setup menu and options [18] chapter for details.
    The last menu item is the Device menu, which provides additional device information such as the connection type, product ID, VRM instance, firmware version and serial number. It is also possible to assign a custom name to the EVCS.

victron energy 22kW EV Charging Station - VRM instance

VictronConnect setup, configuration and operation

7.1. Setup
The following steps are necessary to successfully connect to the EV Charging Station via Bluetooth and VictronConnect:

  1. Make sure Bluetooth is enabled in your EVCS. See the Networks menu [17] chapter for details.
  2. Download and install the VictronConnect app from the App Store or Google Play.
  3. Open VictronConnect and scroll through the list of devices for the EVCS.
  4. Tap on it to launch the pairing dialog. Enter the pairing code which is either 000000 or a unique number on the sticker inside the housing.
  5. If the pairing was successful, the EVCS overview page is displayed.

7.2. Overview
The overview page provides information about the charging state, controls to start/stop charging or changing the charging mode and charging current. Furthermore, the actual charging values and session statistics can be monitored.

victron energy 22kW EV Charging Station - Overview

Controls:

  • Start/Stop: Start or stop charging when in manual mode.

  • Charging mode: Change the charging mode to manual, auto or scheduled.

  • Charging current: Adjust the charging current.
    Actual charging values:

  • Current: The charging current

  • Power: Charging power (of all phases)
    Session statistics:

  • Session time: The time of the actual charging session

  • Session energy: Total energy charged in this session

  • Session cost: The session cost (when charged from grid) depending on the energy price per kWh set in the EVCS settings, see the EV Charging Station setup [13] chapter.

  • Session saved cost: Saved cost based on energy charged from PV and depending on the energy price per kWh set in the
    EVCS settings.

  • Total Energy: The total energy charged since initial installation.

7.3. Settings
The Settings menu offers the possibility to change the network settings, adjust the minimum and maximum charge current, recalibrate the CP line or restart the EVCS.
To get to the Settings menu, tap the cog wheel icon from the Overview menu in the top right.

victron energy 22kW EV Charging Station - Settings

The settings are similar to those explained in the Networks menu [17] and EV Charging Station setup [13] chapter, with the exception that it is possible to trigger a system reboot if required.
7.4. Product info
The Product info page provides options to change the PIN code for Bluetooth pairing or assign a custom name to the EV Charging Station. It also contains the serial number and the firmware version number.
To get to the Product info page, tap the 3 vertical dots icon from the Settings page.
7.5. Reset to defaults
It is possible to factory reset the EV Charging Station via VictronConnect. Note that this process will reset all settings to their default values and require the first setup (see the Setup [6] chapter for details) to be performed again.
For devices shipped with firmware 1.23 or earlier, this will also disable Bluetooth. In order to enable Bluetooth for these devices, it is mandatory to first go through the First setup via Wifi access point [6] procedure and then activate it via the Networks menu [17].
To get to the Reset to defaults option, tap the 3 vertical dots icon from the Settings page and tap on Reset to defaults.

Reset to factory defaults and password recovery

In case the password is lost, the initial password can be recovered in different ways:
Reset to factory defaults from the web interface:

  1. Click on the Settings button.
  2. Click on the Backup & FW button.
  3. Click on Reset to factory defaults.

Reset to factory defaults via VictronConnect:

  1. Open VictronConnect and tap on the EVCS from the My devices list.
  2. On the Status screen, tap on the cog wheel icon in the top right.
  3. On the Settings page, tap on the three vertical dots icon and choose Reset to defaults.
  4. A warning will appear that all settings will be reset to factory defaults. Tap YES to reset to factory defaults.

Reset to factory defaults will reset all system settings to default values. The First setup [6] must be performed again.
Reset the password using the DEF button inside the device:
The procedure described below should only be performed by qualified personnel as this process requires the EV Charging Station to be powered. Working under high voltage is very dangerous and can be fatal if used incorrectly.

  1. Open the unit by removing the backing plate. Be careful not to touch the high power parts inside the unit. Only the area around the DEF button is safe.
  2. Press the DEF button (see the image in chapter 4.3. [13] for its location) for more than 5 seconds but less than 15 seconds. This will reset only the password, all other settings are retained.
  3. Mount the backing plate onto the device and tighten the screws.

Maintenance

The EV Charging Station does not require specific maintenance.
9.1. CP line calibration What is CP?
CP is fidici pilot signal {line) inside? the other connector of the Type2 charger. It is a two-way communication line that facilitates communication between charging station and electric car. Among other things, the charging station informs the EV about the maximum available charging current.

  • EV Zerovert informs the charger the station about its status, for example whether the EV is connected or whether the right ones have been charged.
  • Prof, is it necessary to calibrate the CP line?
  • Due to differences in the length of the cable and the manufacturer, as well as the catch in the nominal values ​​of the mide sign sl CP electronic components, there may be deviations.
  • CP calibration takes into account the deviation of the signal and adjusts the values ​​of the signal to the required ranges.
  • When is it necessary to calibrate the CP line?
  • There are several divods for calibrating the CP line. The most popular are:
  • The EV is connected to the EVCS pies charging cable, but still in a disconnected state When the EV is charged, the EVCS will alternate between the “charged” and “charged” states. EVCS does not start charging after connecting the vehicle, because it cannot detect the correct state after connecting How to calibrate the CP line?
  • You can calibrate the CP through the web interface (Settings General Charge Calibration CP or through VictronConnect (Settings page).

The procedure is following:

  1. Press the calibration button
  2. Pin EV to EVCS and then tap Daldi in VictronConnect
  3. Confirm that the vehicle is actually connected to the EVCS by pressing the “Vehicle is connected” button (or click Dali in VictronConnect)
  4. Sweat until the EVCS sweats completely As soon as the calibration is complete, a message will be displayed stating, Calibration has been completed

victron energy 22kW EV Charging Station - Settings 1 9.2. Frequently asked questions
9.2.1. Q1: How do I prevent unauthorized persons from using the charging station?
Make sure auto-start EV charger is disabled in general settings. This will prevent the charging station it started charging automatically as soon as it is connected to the EV. What is CP? How is CP line calibration done? Also, make sure that the Lock charger display setting is enabled on the main tab of the web interface or in the remote console of the GX device. CP is the control pilot signal (line) inside each Type2 charger connector. It is a two-way communication line that enables communication between charging station and electric car. Among other things, the charging station informs the EV about the maximum available charging current. The EV also informs the charger station about its status, such as whether the EV is connected or charging. CP calibration can be performed via the web interface (Settings General Charger CP Calibration or via VictronConnect (Settings page). The procedure is following: Charging can then only be started or stopped via the web interface, VRM App widget, VRM controls and VictronConne 9.2.3. Q3: The light ring bothers my neighbors at night, how can I disable the light ring?
You can disable the light ring completely in the light ring menu and change the brightness to 0 or below Grover if you want.
9.2.4. Q4: Why is my car not recognized when I connect the charging cable?
Try to calibrate the CP line (from the general section in the web interface or in the VictronConnect settings). This is sometimes necessary because the supply the cables can be slightly compressed. Ground impedance is also divisible4, so all measurements are referenced to ground (GND).
9.2.5. Question 5: Why does my EV Charging Station show up on multiple GX devices?
If there are more than one GX installed on the same local network, activate the whitelist of IP addresses in the General section of the web interface, and then whitelist add only the IP address of the GX device, by which the EVCS should be authenticated. Then remove the EVCS from the last GX devices.
9.2.6. Q6: How much PV energy do I need at least to charge the EV in automatic mode?
The minimum current for EV charging is GA@230V. So you need no more than 1.3 kW. You don’t have to pay that much under certain circumstances, e.g. if the current stele are powered by AC power. Charging will only take place in the event of a sufficient surplus of soldering energy, which will occur as follows: Solar energy consumption = Total PV production – AC 2dté2e (without car consumption) = 1380W (230V¥ x 6A) Be sure that there are electric cars that require even higher minimum charging current, e.g. Renault Zoe; 10A, the code further increases the minimum submitted PV execution
9.2.7. Q7: Is it possible to operate multiple EV charging stations in one system?
Yes, it is mine. The available power is then shared between them.
9.2.8. Question 8: The EV is fully charged, but the EVCS keeps stuttering between charging start and charging stop, why?
The most likely scenario is that the EVCS has not been properly charged. To fix the problem perform the calibration of the CP line [24] .
9.2.9. Q9: I keep getting GX device communication error! Minimum SoC cannot be checked. what’s the reason for that?
Pte te oa oe vr – – ll This error indicates that EVCS cannot print the SoC from the GX device because there is a communication problem, although the communication with zafizenim GX enabled in the EVCS web interface. If you want to fix the problem, make sure that the IP address specified in both settings of the web interface corresponds to the GX load address. Help the Discover function allows the EVCS to derive the correct IP address from the VRM Portal ID – for more details, see the EV Charging Station Settings chapter (14).Also make sure ModbusTCP is enabled [19] in the GX device itself.
9.2.10. Q10: Is the GX device absolutely necessary in the system?
This depends on the operating mode. Try calibrating the CP line (general tab in the web interface or VictronConnect settings). This is sometimes necessary because the charger cables may vary slightly. Ground impedance is also important because all measurements are referenced to ground (GND). For automatic mode, communication between the GX device and the EVCS is mandatory. GX devices may or may not be installed for manual and scheduled mode.
9.2.11. Q11: I would like to control the EVCS via Modbus TCP. Is it possible and if so how?
Yes, it is possible. Modbus TCP offers a much higher degree of flexibility and control and provides access to a wider range of settings than described in the manual or accessible through common user interfaces. The recommended method for support on Modbus-TCP issues is to use the Mods section of the Victron Community. It is frequented by many by people using Modbus TCP and other methods of integration with Victron products. Page 26 Troubleshooting Note that setting changes via Modbus TCP will cancel any support. The list of EVCS Modbus TCP registers can be downloaded from the product page in the download area

Technical specification

EV Charging Station

Input voltage range (V AC) 170 – 265VAC 50Hz
Rated charge current 32A / phase
Nominal power 22kW
Current output range 6 – 32A
Wi-Fi standards 802.11 b/g/n (2.4Ghz only)
Self-consumption 15mA@230V
Configurable Max. Current 10-32A
Configurable Min. Current 6A up to 1A below max. value
Connector type IEC 62196 Type 2

GENERAL
Means to Disconnect| Depending on available input power and cable cross- section – max 40A
Configurable price/kWh calculator (EUR)| Default setting: 0.13 (adjustable)
Control type| Touch Screen, Web page, GX device over Modbus TCP, VictronConnect via Bluetooth
Light Ring| 55 configurable light effects available
Protection| External RCD is required
Operating temperature| -25°C to +50°C
Storage temperature| -40 °C to +80 °C
Humidity| 95%, non-condensing
Data communication| ModbusTCP over WiFi, Bluetooth
ENCLOSURE
Enclosure colour| Light Blue (RAL 5012)
Power terminals| 6-10 mm² / AWG 10-8
Protection category| IP44
Ventilation| not required
Weight| 3 kg
Dimensions (h x w x d)| 377 x 307 x 148mm
STANDARDS
Safety| IEC 61851-1, IEC 61851-22
Detection for Relay Contact welded
Detection for missing protective conductor
Detection for missing Ground
Detection for shorted CP

FAQ

11.1. Q1: How do I prevent the charging station from being used by unauthorised persons?

Make sure EV charger autostart is disabled in general settings. This prevents the charging station from starting to charge automatically once it is connected to an EV. Also ensure the Lock charger display setting on the general tab of the web interface or in the Remote console of the GX device is enabled. Charging can then only be started or stopped via the web interface, VRM App widget, VRM controls and VictronConnect.

11.2. Q2: Does the EV Charging Station have RFID?

No. To prevent the charging station from being used by unauthorised persons, see Q1.

11.3. Q3: The light ring is annoying my neighbours very much during night, how can I disable the light ring?

You can completely disable the light ring in the light ring menu, changing the brightness to 0 or a lower level if you like.

11.4. Q4: Why isn't my car recognized when I connect the charging cable?

Try calibrating the CP line (general tab in the web interface or in the VictronConnect settings). This is sometimes necessary because the charging cables can differ slightly. Ground impedance is also important as all measurements are relative to ground (GND).

Appendix

12.1. Dimensions

victron energy 22kW EV Charging Station - Appendixvictron energy - logo

Documents / Resources

| victron energy 22kW EV Charging Station [pdf] Instruction Manual
22kW EV Charging Station, 22kW, EV Charging Station, Charging Station, Station
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

victron energy User Manuals

Related Manuals