victron energy 48-3000 Phoenix Smart Inverter
SAFETY INSTRUCTIONS
General
Please familiarize yourself with the safety features and instructions by first reading the documentation supplied with this product before using the equipment. This product has been designed and tested in accordance with international standards. The equipment must be used exclusively for the purpose for which it was designed.
WARNING: ELECTRIC SHOCK HAZARD.
The product is used in combination with a permanent energy source (battery).
Even if the equipment is switched off, a dangerous electrical voltage can
occur at the input and/or output terminals. Always disconnect the battery
before performing maintenance.
The product has no internal user-serviceable components. Do not remove the
front plate or operate the product if any panels have been removed. All
servicing must be undertaken by qualified personnel.
Never use the product where there is a risk of gas or dust explosions. Consult
the battery manufacturer’s information to ascertain that the product is
intended for use in conjunction with the battery. Always comply with the
battery manufacturer’s safety instructions.
WARNING : Do not lift heavy loads without assistance.
Installation
Read the installation instructions in the installation manual before
installing the equipment.
This is a Safety Class I product (supplied with a protective grounding
terminal). The chassis must be grounded. A grounding point is located on
the outside of the product. Whenever it is likely that the grounding
protection has been damaged, the product must be turned off and secured
against unintended operation; please contact qualified service staff.
Ensure that the DC and AC input cables are fused and fitted with circuit
breakers. There is no internal fuse inside this product. Never replace a
safety component with a different type. Consult the manual to determine the
correct component.
During installation ensure that the remote connector with wire bridge is
removed (or switch off the remote on/off switch if installed) to be sure that
the inverter cannot be switched on unexpectedly.
Before applying power, ensure that the available power source matches the
configuration settings of the product as described in the manual.
Ensure that the equipment is used under the correct ambient conditions. Never
operate the product in a wet or dusty environment.
Ensure there is adequate free space for ventilation around the product and
check that the ventilation vents are not blocked.
Ensure that the required system voltage does not exceed the product’s
capacity.
Transport and Storage
Ensure that the mains power and battery leads have been disconnected before
storing or transporting the product.
No liability can be accepted for any transport damage if the equipment is
shipped in non-original packaging.
Store the product in a dry environment; the storage temperature must be
between -20°C and 60°C.
Consult the battery manufacturer’s manual in respect of transport, storage,
charging, recharging and disposal of the battery.
DESCRIPTION
General
Bluetooth built-in: fully configurable with a tablet or smartphone
- Low battery voltage alarm trip and reset levels
- Low battery voltage cut-off and restart levels
- Dynamic cut-off: load dependent cut-off level
- Output voltage: 210 – 245V
- Frequency: 50 Hz or 60 Hz
- ECO mode on/off and ECO mode sense level
- Alarm relay
Monitoring:
- In- and output voltage, % load and alarms
For more information, refer to the VictronConnect manual.
VE.Direct communication port
The VE.Direct port can be connected to a computer (VE.Direct to USB interface
cable needed) to configure and monitor the same parameters.
Proven reliability
The full bridge plus toroidal transformer topology has proven its reliability
over many years.
The inverters are short circuit proof and protected against overheating,
whether due to overload or high ambient temperature.
High start-up power
Needed to start loads such as power converters for LED lamps, halogen lamps or
electric tools.
ECO mode
When in ECO mode, the inverter will switch to standby when the load decreases
below a preset value (min load turn on level: 10VA; and min load turn off
level: 0VA). Once in standby the inverter will switch on for a short period
(adjustable, default: every 3 seconds). If the load exceeds a preset level,
the inverter will remain on.
Remote on/off
A remote on/off switch can be connected to a two pole connector, between
battery plus and the left hand contact of the two pole connector or between
battery minus and the right hand contact of the two pole connector.
LED diagnosis
See section 3.3
To transfer the load to another AC source: the automatic transfer switch
For our low power inverters we recommend our Filax Automatic Transfer Switch.
The Filax features a very short switchover time (less than 20 milliseconds) so
that computers and other electronic equipment will continue to operate without
disruption. Alternatively use a MultiPlus with built-in transfer switch.
OPERATION
On/Off Push button
When switched to “on” with the pushbutton, the product is fully functional.
The inverter will come into operation and the LED “inverter” will light up. By
pushing the push button subsequently, within a short period of time, the
inverter toggles between “on”, “ECO” and “off”.
The inverter goes into sleep mode with minimal current consumption when the
unit is turned off by the pushbutton.
Apart from the pushbutton; the inverter can also be switched on (normal or
ECO) and off with Bluetooth on a mobile device running iOS or Android and the
VictronConnect app. However when switched off via Bluetooth or the push
button; the unit cannot be switched on and off again via the wired
VE.Direct port.
On/Off Switch (5kVA only)
The 5kVA unit has a main on/off switch next to the cable entries on the right
side. This switch; when turned off, will cut off the supply current
completely.
Remote control
Remote control is possible with a simple on/off switch or with a Phoenix Inverter Control panel. A switch for remote control (on/off) can be connected to a two pole connector. The switch can also be connected between battery plus and the left hand contact of the two pole connector (marked “H”; see appendix A) or between battery minus and the right hand contact of the two pole connector (marked “L”; see appendix A).
For safety purposes, this product can be turned off completely (i.e. the inverter cannot be switched on via the push button or Bluetooth) by removing the remote connector and its default installed wire bridge (or switch off the remote on/off switch if installed). The user can then be certain that the inverter cannot be switched on accidently via Bluetooth by an unexpected other user.
LED definitions
Green LED | Status | Trouble shooting |
---|---|---|
Inverter on | Red LED Off |
status OK
Red LED On or blinking:
The Inverter is still on, but will shut down when the condition gets worse.
See red LED table for warning reason
| ECO mode| If the inverter keeps switching on and off while there is a load
connected, the load may be too small compared to the actual ECO mode
settings. Increase the load or change ECO mode settings. (minimum ECO mode
setting: 15W)
| O ff and waiting| Inverter did shut down because of a protection. The
inverter will restart automatically as soon as all alarm conditions are
cleared. See red LED state for the shutdown reason.
| Inverter off| Red LED Off
Check Remote on/off connector. Check DC cable connections and fuses.
Check operational mode by pushing push button one time.
Red LED On or blinking
The inverter did shut down because of a protection. It will no longer
automatically restart. The red LED indicates the reason for shutdown. Remove
the cause and then restart the inverter by switching it Off, and then back On.
| Off and frirmware update in progress or failed| Red LED Blinking ( )
Firmware update in progress or firmware update failed. When failed; retry firmware update.
Yellow LED | Status | Trouble shooting |
---|---|---|
ECO mode | Red LED Off |
status OK Red LED On or blinking: The Inverter is still on, but will shut
down when the condition gets worse. See red LED table for warning reason
| ECO mode off| Red LED Off
Check operational mode by pushing push button one time. Check Remote on/off connector. Check DC cable connections and fuses.
Red LED On or blinking
The inverter did shut down because of a protection. It will no longer automatically restart. The red LED indicates the reason for shutdown. Remove the cause and then restart the inverter by switching it Off, and then back On.
Red LED | Definition | Trouble shooting | |
---|---|---|---|
Solid on | Overload | Reduce load | |
Slow blink | Low batt. | Recharge or replace battery Check DC cable |
connections
Check cable cross section as it may be insufficient.
See section 4.2 Protections and automatic restarts for manual and automatic
restart behavior.
| Fast blink| High batt.| Reduce DC input voltage, check for faulty charger
| Double pulse| High temp.| Reduce load and/or move inverter to better
ventilated area
| Fast single pulse| High DC ripple| Check DC cable connections and cable
cross section.
Protections and automatic restarts
Overload
Some loads like motors or pumps draw large inrush currents in a start-up
situation. In such circumstances, it is possible that the start-up current
exceeds the over current trip level of the inverter. In this case the output
voltage will quickly decrease to limit the output current of the inverter. If
the over current trip level is continuously exceeded, the inverter will shut
down: wait 30 seconds and then restart.
After three restarts followed by another overload within 30 seconds of
restarting, the inverter will shutdown and remain off. The LEDs will signal
shutdown due to overload. To restart the inverter, switch it Off, then On.
Low battery voltage (adjustable)
The inverter will shut down when the DC input voltage drops below the low
battery shutdown level. After a minimum delay of 30 seconds, the inverter will
restart if the voltages rise above the low battery restart level.
After three restarts followed by a low battery shutdown within 30 seconds of
restarting, the inverter will shutdown and stop retrying.
The LEDs will signal low battery shutdown. To restart the inverter, switch it
Off, and then On, or recharge the battery: as soon as the battery has risen
and then stays above the Charge detect level for 30 seconds, it will switch
on.
See the Technical Data table for default low battery shutdown and restart
levels. They can be changed with the VictronConnect App.
High battery voltage
Reduce DC input voltage and/or check for a faulty battery- or solar-charger in
the system. After shutting down due to a high battery voltage, the inverter
will first wait 30 seconds and then retry operation as soon as the battery
voltage has dropped to acceptable level.
The inverter will not stay off after multiple retries.
High temperature
A high ambient temperature or enduring high load may result in shut down to
over temperature. The inverter will restart after 30 seconds. The inverter
will not stay off after multiple retries. Reduce load and/or move inverter to
better ventilated area.
High DC ripple
High DC ripple is usually caused by loose DC cable connections and/or too thin
DC wiring. After the inverter has switched off due to high DC ripple voltage,
it waits 30 seconds and then restarts.
After three restarts followed by a shutdown due to high DC ripple within 30
seconds of restarting, the inverter will shutdown and stops retrying. To
restart the inverter, switch it Off and then On.
Continuous high DC ripple reduces the inverter life expectancy.
INSTALLATION
This product should be installed by a qualified electrician.
During installation ensure that the remote connector with wire bridge is removed (or switch off the remote on/off switch if installed) to be sure that the inverter cannot be switched on unexpectedly.
Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at least 10cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never mount the appliance directly above the batteries.
The product is suitable for wall mounting. For mounting see appendix A.
The appliance can be mounted horizontally as well as vertically; vertical
mounting is preferable. The vertical position offers optimum cooling.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heatresistant environment if it is used with equipment where a substantial amount of power is to be converted. You should prevent the presence of e.g. chemicals, synthetic components, curtains or other textiles, etc., in the immediate vicinity.
Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should be used. See table.
| 12/1600| 24/1600| 48/1600| 12/2000| 24/2000| 48/2000
---|---|---|---|---|---|---
Recommended fuse| 250A| 125A| 60A| 300A| 150A| 80A
Recommended cross section (mm2)| | | | | |
0 – 5 m| 70| 35| 16| 70| 50| 25
5 -10 m| Not recommended| 70| 25| Not recommended| 95| 50
| 12/3000| 24/3000| 48/3000| 24/5000| 48/5000
---|---|---|---|---|---
Recommended fuse| 400A| 250A| 125| 400A| 200A
Recommended cross section (mm2)| | | | |
0 – 5 m| 2x 95| 1x 50| 1x 35| 2x 95| 1x 70
5 -10 m| Not recommended| 2x 50| 2x 35| 2x 95| 2x 70
*One cable must be sized to carry the rated fuse current without overheating.
Do not locate battery cables in a closed conduit.
Please follow local installation rules.
| 12/1600| 24/1600| 48/1600| 12/2000| 24/2000| 48/2000
---|---|---|---|---|---|---
| | | | | |
Recommended battery capacity (Ah)| 300 – 800| 150 – 400| 75 – 200| 350 – 1000|
200 – 500| 100 – 250
| 12/3000| 24/3000| 48/3000| 24/5000| 48/5000
---|---|---|---|---|---
| | | | |
Recommended battery capacity (Ah)| 400 – 1200| 200 – 700| 100 – 400| 300 –
1500| 150 – 700
Remark : Internal resistance is the important factor when working with low capacity batteries. Please consult your supplier or the relevant sections of our book “electricity on board”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect the battery cables: the + (red) and the – (black), to the battery see
appendix A.
Reverse polarity connection (+ to – and – to +) will cause damage to the
product.
Secure the nuts tightly in order to reduce the contact resistance as much as
possible.
Connection of the AC cabling
This is a Safety Class I product (supplied with a protective grounding
terminal).
The neutral wire of the AC output of this inverter is connected to the chassis
(see appendix B for 1600VA/2000VA and appendix C for 3000VA/5000VA).
This is to ensure proper functioning of a GFCI (or RCCB) to be installed in
the AC output of the Inverter.
The chassis of the product must be connected to ground, to the frame (of a
vehicle) or the ground plate or hull (of a boat).
Procedure
The terminal points are indicated clearly. From left to right: “L” (phase),
“N” (neutral) and “PE” (earth).
Optional Connections
A number of optional connections are possible:
Remote on/off switch & remote Control panel
The product can be remotely controlled in three ways.
- With a smart phone (iOS or Android) and the Victron Connect app.
- With an external switch (connected to the two pole remote connector). Operates only if the switch on the Inverter is set to “on”.
- With a Phoenix Inverter Control VE.Direct panel (connected to the two pole remote connector; see appendix A). Operates only if the switch on the inverter is set to “on”.
Programmable relay
The inverters are equipped with a multi-functional relay that by default is programmed in the normal operation mode (VictronConnect software needed to change relay functionality). The different relay modes can be summerized as follows:
-
Normal operation (“inverter” in VictronConnect app) – default
Relay closed during normal operation, and open when the inverter has switched off itself in alarm, has been switched off by a user and also open (of course) when there is no power available on the terminals, ie. battery disconnected. In ECO mode, the relay will be closed both when searching for a load and when fully on, ie. load detected.
Use this option when you want the relay to signal that there is power available on the output of the inverter. -
Warnings and alarms (“alarm” in VictronConnect app)
Similar to above, but then the relay will also open when there is a warning. For example because the battery voltage dropped to the cutoff value, or when loaded to the point where it will almost shut down due to overload. In ECO mode, the relay will be closed both when searching (no load) and when fully on (load detected), except when there is a warning.
Use this option when you want the relay to signal that it is time to do something (charge the battery, reduce the load, and so-forth), in order to prevent a power outage. -
Low battery (“Low battery” in VictronConnect app)
Relay on during normal operation. The relay will switch off once there is a low battery warning. It will remain off in case the inverter shuts down due to low voltage, and will only switch back on again once the inverter is operational and the battery voltage is above the prealarm reset level. Use this option for load shedding, or to automatically start a generator. Note that this can only be considered a poormans generator start/stop. For more and better options, see here. -
External fan (“fan” in VictronConnect app)
Relay is off, unless the fan inside the inverter is running. Use this option to switch an external fan, for situations when the inverter is in a small enclosed space. -
Disabled relay (“off” in VictronConnect app)
This option sets the relay in the OPEN position. Use this option if you do not plan to use the relay function.
CONFIGURATION
Settings may only be changed by a qualified engineer.
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during charging.
Standard settings: ready for use
On delivery, the Phoenix inverter is set to standard factory values. In general, these settings are suitable for stand-alone operation.
Standard factory settings
- Inverter frequency 50 Hz
- Inverter voltage 230 VAC
- Search mode off
- Programmable relay alarm function
- Dynamic cut-off off
Explanation of settings
Inverter frequency
Output frequency
Adjustability: 50Hz; 60Hz
Inverter voltage
Adjustability: 210 – 245V
ECO Mode
If ECO mode is ‘on’, the power consumption in no-load operation is decreased
by approx. 80…90%. In this mode the Phoenix Inverter Smart, when operating in
inverter mode, is switched off in case of no load or very low load, and
switches on every two and a half seconds for a short period (adjustable). If
the output current exceeds a set level, the inverter will continue to operate.
If not, the inverter will shut down again.
The ECO Mode can be set with the push button on the front of the inverter.
The ECO Mode “shut down” and “remain on” load levels can be set with Victron
Connect .
The factory settings are:
Shut down: 50 Watt (linear load).
Turn on: 100 Watt (linear load).
Programmable relay
By default, the programmable relay is set as an alarm relay, i.e. the relay
will de-energise in the event of an alarm or a pre alarm (inverter almost too
hot, ripple on the input almost too high, battery voltage almost too low).
Dynamic Cut-off
Use VictronConnect to enable and configure Dynamic Cut-off (see
https://www.victronenergy.com/live/ve.direct:phoenixinvertersdynamic-cutoff
for details). Do not use Dynamic Cut-off in an installation that also has
other loads connected to the same battery: the battery voltage will drop
because of the extra load, but the Dynamic Cut-off algorithm in the Inverter
is not aware of that load: hence the Inverter will shut down too early with an
under voltage alarm.
Configuration by computer
All settings can be changed by means of a smartphone, tablet or computer
For changing settings with a smartphone or tablet, the following is required:
-
VictronConnect software: can be downloaded free of charge at www.victronenergy.com.
For changing settings with the computer, the following is required: -
VictronConnect software: can be downloaded free of charge at www.victronenergy.com.
-
A VE.Direct to USB interface.
MAINTENANCE
The Phoenix Inverter Smart does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.
Technical Data
Phoenix Inverter Smart| 12/1600
24/1600
48/1600| 12/2000
24/2000
48/2000| 12/3000
24/3000
48/3000| 24/5000
48/5000
---|---|---|---|---
Parallel and 3-phase operation| No
INVERTER
Input voltage range (1)| | 9,3 – 17V| 18,6 – 34V| 37,2 – 68V|
Output| Output voltage: 230VAC ±2% 50 Hz or 60Hz ± 0,1% (1)
Cont. output power at 25ºC (2)| 1600 VA| 2000 VA| 3000 VA| 5000 VA
Cont. output power at 25ºC| 1300 W| 1600 W| 2400 W| 4000 W
Cont. output power at 40ºC| 1200 W| 1450 W| 2200 W| 3700 W
Cont. output power at 65ºC| 800 W| 1000 W| 1700 W| 2800 W
Peak power| 3000 W| 4000 W| 6000 W| 10000 W
Dynamic (load dependent) DC low shut down (fully configurable)
Max. efficiency 12/ 24 /48 V
| Dynamic cut-off, see https://www.victronenergy.com/live/ve.direct:phoenix-
inverters-dynamic-cutoff
92 / 94 / 94%| 92 / 94 / 94%| 93 / 94 / 95%| 95 / 96%
Zero load power 12 / 24 / 48 V| 8 / 9 / 11 W| 8 / 9 / 11 W| 12 / 13 / 15 W| 18
/ 20 W
Zero load power in ECO mode| 0.6 / 1.3 / 2.1 W| 0.6 / 1.3 / 2.1 W| 1.5 / 1.9 /
2.8 W| 2.2 / 3.2 W
GENERAL
Programmable relay (2)| Yes
Stop & start power ECO-mode| adjustable
Protection (3)| a – g
Bluetooth wireless
communication
| For remote monitoring and system integration
VE.Direct communication port| For remote monitoring and system integration
Remote on-off| Yes
Common Characteristics| Operating temperature range: -40 to +65ºC (fan
assisted cooling)
Humidity (non-condensing): max 95%
ENCLOSURE
Common Characteristics| Material & Colour: steel (blue RAL 5012; and black RAL
9017) Protection category: IP 21
Battery-connection| M8 bolts| M8 bolts| 12 V/24 V: 2+2 M8 bolts
48 V: M8 bolts| 24 V: 2+2 M8 bolts
48 V: M8 bolts
230 V AC-connection| Screw terminals
Weight| 12kg| 13kg| 19kg| 29kg / 28kg
Dimensions (hxwhd)| 485 x 219 x 125mm| 485 x 219 x 125mm| 533 x 285 x 150mm
(12 V)
485 x 285 x 150mm (24 V/48 V)| 595 x 295 x 160mm (24 V)
555 x 295 x 160mm (48 V)
STANDARDS
Safety| EN-IEC 60335-1
Emission Immunity| EN 55014-1 / EN 55014-2 / EN-IEC 61000-6-1
EN-IEC 61000-6-2 / EN-IEC 61000-6-3
Automotive Directive| ECE R10-5
-
Non-linear load, crest factor 3:1
-
Programmable relay that can a.o. be set for general alarm, DC under voltage or genset start/stop function.
AC rating : 230 V / 3 A
DC rating : 3 A up to 30 VDC, 0.2A up to 70 VDC -
Protection key:
a ) output short circuit
b ) overload
c ) battery voltage too high
d ) battery voltage too low
e ) temperature too high
f ) 230 V AC on inverter output input voltage ripple too high
Appendix A: Inverter control
Appendix B: Installation Information 1600VA/2000VA
This ground wire “G“ connects the output neutral to ground. It must be
repositioned to a ‘dummy’ terminal if a floating output is required.
When a floating output is obtained the current reading at no load can show an
offset of around 100…150mA. Also beware that the GFCI (or RCCB) will not
function properly.
Installation Information 3000VA/5000VA
This ground wire “G“ connects the output neutral to ground. It must be
repositioned to a ‘dummy’ terminal if a floating output is required.
When a floating output is obtained the current reading at no load can show an
offset of around 100…150mA. Also beware that the GFCI (or RCCB) will not
function properly.
Customer Support
Victron Energy B.V.
De Paal 35 | 1351 JG Almere
PO Box 50016 | 1305 AA Almere | The Netherlands
General phone : +31 (0)36 535 97 00
E-mail : sales@victronenergy.com
www.victronenergy.com