GTX12V630A-E2112-CS200-UL Installation Manual
NeverDie® Compact Series 200 Internal BMS
GTX12V630A-E2112-CS200-UL NeverDie Compact Intern BMS
Important Safety Guidelines
This guide contains important safety instructions for the
GTX12V630A-E2112-CS200-UL Battery System that must be followed during
installation procedures. Completely read this manual and become familiar with
all system componenbefore attempting nstallation. Save this installation
manual for future reference.
The following symbols and messages are used to identify potential hazards or
to clarify the procedure.
CAUTION
The CAUTION symbol indicates a hazardous situation which, if not avoided,
could result in moderate or minor injury.
DANGER
The DANGER symbol indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
Safety Information
-
Before using the Battery System, read all instructions and cautionary markings on the unit, the BMS, and all appropriate sections of this manual.
-
The information in this manual is intended for qualified personnel. Qualified personnel have training, knowledge, and experience in:
• Selecting and using Personal Protective Equipment (PPE).
• Installing electrical equipment.
• Applying all applicable local and national installation codes.
• Analyzing and reducing the hazards involved in performing electrical work. -
Use of accessories not recommended or sold by the manufacturer may result in a risk of fire, electric shock, or injury to persons.
-
To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not undersized. Do not operate the battery system with damaged or substandard wiring.
-
Do not operate the battery system if it has been damaged in any way.
-
This unit does not have any user-serviceable parts. Do not disassemble the battery system except where noted for connecting wiring and cabling. Attempting to service the unit yourself may result in a risk of electrical shock or fire. Internal cells remain charged after all power is disconnected.
-
To reduce the chance of short-circuits, always use insulated tools when installing or working with this equipment.
-
Remove personal metal items such as rings, bracelets, necklaces, and watches when working with electrical equipment.
CAUTION
HAZARD OF ELECTROLYTE VAPOR
- The battery may emit a non-toxic pressurized electrolyte vapor if punctured.
- Electrolyte vapor may cause temporary minor breathing congestion.
- Electrolyte vapor can decrease visibility in closed compartments.
CAUTION
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
- Always turn OFF all equipment connected to the system in addition to turning OFF the power switch provided on the system to isolate the batteries from other electrical circuits, before performing any repairs or maintenance on the system.
- Do not operate the system if it has received a sharp blow, been dropped, has cracks or openings in the enclosure.
- Do not disassemble any part of the system. Internal cells remain charged after all power is disconnected.
- Do not operate the system with damaged or substandard wiring.
- Always use proper wire sizes to connect the system to inverters, chargers or other equipment.
- Voltage is present at the connector and output terminals. Always ensure that the BMS output terminals have the insulated protective boots in place.
- Always use crimped connections to connect to the output terminals.
- Always use a properly rated voltage sensing device to confirm all circuits are deenergized.
CAUTION
HAZARD OF HEAVY EQUIPMENT
- Use two people to lift and mount the battery.
- Always use proper lifting techniques during installation to prevent injury.
- Do not lift the battery by its power or signal wires as they will become damaged.
If the system is operated outside of its limits and/or used in combination
with non-original components without authorization, the warranty is void.
Do not expose this unit to direct sunlight, external heat sources or
submersion in any liquid. This product is designed for closed compartment use
only. Damage to any part of the battery system caused from direct sunlight,
external heat sources or submersion in any liquid will not be covered by the
product warranty.
The Battery is tested to comply with UN DOT 38.3, the testing requirement for
Lithium Batteries per Part III; of the UN Recommendations on the TRANSPORT OF
DANGEROUS GOODS (Manual of Tests and Criteria, Fifth revised edition);
[ST/SG/AC.10/11/Rev.5].
This Battery contains no mercury and is RoHS Compliant. Please consult your
local municipal authority for proper disposal.
Notice of Copyright
GTX12V630A-E2112-CS200-UL Installation Manual Copyright © 2023 all rights
reserved. No part of this document may be reproduced in any form without the
express consent of Lithionics Battery®, Clearwater, FL 33765 USA. Lithionics
Battery® reserves the right to revise this document and make periodic changes
to the contents without notice.
Safety
- All electrical work shall be performed in accordance with local and national electrical codes.
- Assume that voltage is present at the battery terminals, use insulated tools and gloves while working on the system.
- Always turn OFF equipment connected to the battery in addition to turning OFF the Power button on the battery to isolate it from other electrical circuits before performing any repairs, maintenance, or diagnosis on the system.
- Always use proper wire sizes to connect the system to inverters, chargers, or other equipment.
- Always use crimped connections to connect to the battery terminals.
- Read and follow the inverter, charger, or other equipment manufacturers safety precautions prior to connecting the battery to that equipment.
- Always use charging equipment compatible with Lithium Iron Phosphate battery chemistry. See battery charging section below.
Overview
This Guide is intended to be used by qualified individuals in the installation of the GTX12V630A-E2112-CS200-UL battery system.
System Components
1.1 Components
- GTX12V630A-E2112-CS200-UL Battery
- Accessory Harness (#75-H1FCR-CS2-UL)
- DC Circuit Breaker (Sensata #JLE-1-41340-250)
- Protective DC Terminal Covers (Red & Black, not shown)
- Two Sets of M8x12x1.25mm Bolts and Lock Washers for the Terminals
Reference | Feature | Description |
---|---|---|
A | OptoLoop®+ Connector | RV-C CANBus Data, Remote Display Unit |
B | Accessory Connector | FCC, Remote Power Button |
C | Positive Terminal | Brass, Nickel Plated, M8-1.25 Thread, Torque to 108 |
-132in-lbs (12.2 – 14.9N-m)
D| Vent| Pressure Balancing Vent
E| Power Button| Power Button with Status Light
F| Negative Terminal| Brass, Nickel Plated, M8-1.25 Thread, Torque to 108
-132in-lbs (12.2 – 14.9N-m)
G| DC Circuit Breaker| Auxiliary DC Circuit Breaker for UL Compliance
H| Accessory Harness| Enables Integration of FCC and Remote Power Button
1.2 DC Circuit Breaker
The Auxiliary DC Breaker is one of the components required that enables the
system to be a UL1973 Listed system.
UL1973 Listing represents a high degree of safety tested by Underwriter
Laboratories.
The battery operates by using the Auxiliary DC Breaker as a redundant
disconnect device if the battery must be isolated from its loads. The
Auxiliary DC Breaker replaces the need for a fuse and serves as a manual
disconnect for storage and maintenance viaits toggle switch.
The required and included DC breaker model is the Sensata Circuit Breaker
JLE-1-41340-250. The 2 control wires for this feature are wired via the
battery accessory connector.
1.3 Accessory Harness
The Accessory Harness connects to the battery and is used to access the BMS’s
ported features. This allows implementation of the features shown
below.
System Specifications
2.1 Operating Specifications
Table 1
System Model: | GTX12V630A-E2112-CS200-UL |
---|---|
Capacity | 630Ah |
Nominal Voltage | 12.8V |
Recommended Charging Voltage | 14.4V |
Maximum Charging Voltage | 14.8V @ 200A |
Over-discharge Voltage Protection | 10.0V @ 230A |
Standard Charging Current | 150A |
Maximum Charging Current | 200A |
Charge Termination Current | 10A |
Standard Discharging Current/Load | 150A |
Maximum Discharge Current/Load | 230A |
System Impedance at Terminals | ≤ 2.20mΩ |
Ibf Bolted Fault Current at Nominal Voltage (N2) | 5818A |
Maximum Charging Temperature Range (N1) | 32 to 131°F (0 to 55°C) |
Maximum Discharging Temperature Range (N1) | -4 to 131°F (-20 to 55°C) |
Battery Dimensions | 20.3″ x 12.3″ x 10.6″ (516 x 312 x 269mm) |
Battery Weight | 128lb (58.0kg) |
Notes for Table 1:
(N1) Maximum charging and discharging rates apply depending upon the ambient
temperature and duty cycle of the system. UL1973 tests of maximcharge and
discharge current were performed at 25°C/77°F.
(N2) “Bolted Fault Current” per NFPA-70E. See section 1.2 for details.
2.2 Arc Flash Energy Specifications
- An arc flash is the light and heat produced from an electric arc supplied with sufficient electrical energy to cause substantial damage, harm, fire, or injury.
- An example of an arc flash event could be a direct short circuit caused by a metallic object such as a tool bridginbetween the positive and negative of an energized circuit.
- Table 3 below quantifies the hazard level of arc flash energy that each battery system is capable of producing.
Per NFPA 70E D.5.1 “Maximum Power Method”
Iarc = 0.5 x Ibf
IEm = 0.01Vsys Iarc*Tarc/D²(Arc Flash Energy)
Table 3
Tarc= 80mS circuit breaker clearing time| Configuration| Vsys| Impedance mΩ|
Ibf, calc.| Iarc| IEm cal/cm^2| 3x IEm cal/cm^
2| Distance where
IEm=1.2 (Arc
Boundary), inches.| Hazard level
---|---|---|---|---|---|---|---|---|---
GTX12V630A-E2112-CS200-UL| 12.8| 2.20| 5818| 2909| 0.36| 1.079| 9| 0
Hazard/risk classification as per NFPA 70E-2000
Category | Energy Level | Typical PPE Examples |
---|---|---|
0 | N /A | Non-melting. flammable materials (e.g. untreated cotton. wool. rayon, |
etc.)
1| 5 ca1/cm²| FR shirt and FR pants
2| 8 ca1/cm²| Cotton underwear plus FR shirt & pants
3| 25 ca1/cm²| Cotton underwear plus FR shirt & pants plus FR coverall
4| 40 ca1/cm²| Cotton underwear plus FR shirt & pants plus double layer
switching coat and pants
2.3 Manufacturing Date Code Format
- MMDDYYYY001
- MM: Month of Manufacture
- DD: Day of that Month
- YYYY: Year of Manufacture
- 001: Sequence of Battery Produced on That Day
- Example: 01012020001 = manufactured on January 1, 2020 and it was the first battery produced on that day.
System Installation
3.1 Circuit Breaker
- The battery system must be operated with the included circuit breaker. The model listed in this document was evaluated and tested by Underwriter Laboratories. The circuit breaker is to be provided downstream of the battery on the positive side before the load or supply in all cases. The use of any other circuit breaker voids the UL Listing of the model.
- The circuit breaker must be installed into an enclosure with a NEMA Type 4 rating or better, see Reference 1 and Figure 2 below.
- Lithionics Battery can supply a pre-made mounting enclosure which can be ordered under part number 41-206.
- The circuit breaker must NOT be installed with the handle/lever facing up or down, see the Permitted Orientations in Figure 6 below.
- Use 10-32 screws to mount the circuit breaker into the enclosure. The screw depth into the circuit breaker (not including the enclosure material thickness) must be within .230 to .315 max. Torque the 10/32 screws between 1012 Inch Pounds.
Reference 1 Enclosure Rating
Enclosure Rating| National Electrical Manufacturers Association (NEMA
Standard 250)| Underwriters Laboratories, Inc. (UL50 and UL 508)
---|---|---
Type 4| Indoor or outdoor use to provide a degree of protection to personnel
against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects
(falling dirt and windblown dust); to provide a degree of protection with
respect to harmful effects on the equipment due to the ingress of water (rain,
sleet, snow, splashing water, and hose directed water); and that will be
undamaged by the external formation of ice on the enclosure.| Indoor or
outdoor use to provide a degree of protection to personnel against incidental
contact with the enclosed equipment; to provide a degree of protection against
falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-
directed water; and that will be undamaged by the external formation of ice on
the enclosure.
3.2 Battery Environment and Mounting orientation
- The Battery needs to be mounted in an environment that does not receive direct sunlight, pressurized water or road debris.
- To avoid power interruption, your installation may need to consider controlling the ambient operating temperature.
- Mount the Battery in an upright position, i.e. black lid faces up.
- Other orientations are NOT permitted and will void the warranty.
3.3 Battery Power Terminals (see Figure 5 for diagram)
- Connect the Battery Negative Terminal to your DC negative bus.
- Use 2/0 wire and 2/0 3/8” stud ring terminals.
- The battery negative wire is recommended to be 3ft or less.
- Torque the battery negative power terminal to 108 – 132in-lbs (12.2 – 14.9N-m).
- Connect the Battery Positive Terminal to either one of the power terminals on the circuit breaker (Figure 3, A).
- Use 2/0 wire and 2/0 3/8” stud ring terminals.
- The battery positive wire (between battery and circuit breaker) is recommended to be 3ft or less.
- Torque the battery positive power terminal to 108 – 132in-lbs (12.2 – 14.9N-m).
- Torque the 3/8” nuts on the circuit breaker to 220-230 in-lbs (24.9 – 26.0N-m).
- Never stack ring terminals.
- Never place the stainless-steel washer or lock-washer between the conductive power terminal and ring terminal lug (see Figure 4 on Page 12).
- Connect the opposite end circuit breaker power terminal to your DC positive bus.
- Use 2/0 wire and 2/0 3/8” stud ring terminals.
- The battery positive and negative wires are recommended to be 3ft or less.
3.4 Accessory Harness
- Connect the 2x #10 stud ring terminals to the Circuit Breaker (Figure 3, B).
- Torque the 2x 5/16” nuts to 30-40 inch pounds.
- Connect the Accessory Harness to the Accessory Connector on the Battery (Figure 1, B).
3.5 Initial Charge Cycle
- Initially the system must be FULLY charged once to calibrate the Battery. Please read and follow the next section to perform this.
System Operation
4.1 Powering the System On
- Ensure that the circuit breaker lever is in the ON position.
- Short-press the Power switch for 1 second.
- The switch will illuminate once power is enabled.
- Check that there is voltage at the Power Terminals with a voltmeter.
4.2 Powering the System Off
- Long-press the Power switch for 3 seconds.
o The switch will cease to illuminate once power is disabled.
o Check that there is 0V at the output terminals with a voltmeter.
o NOTE: During normal operation, the circuit breaker can be left in the ON position when powering off the battery.
For maintenance/storage turn the circuit breaker OFF.
4.3 Charging
- The charging device(s) connected to the Lithium Battery System must be programmed as per Table 1.
- Charging may be performed at any time the system is powered On.
- NOTE – The Battery will disconnect power if the voltage, amperage, or temperature limits are exceeded during charging.
- Only use a Lithionics Battery approved charging source. Please contact Lithionics Battery for charger approval.
4.4 Initial Charging Cycle
- The initial charging cycle is required as it calibrates the Battery for accurate State of Charge percentage (SoC) monitoring.
- During the initial charging cycle, the system must reach a voltage level that is equal to the Standard Full Charging Voltage indicated in Table 1.
- Enable the charging device(s) so that they may complete a charge cycle. It is recommended to not have any discharge loads active during the initial charging cycle, especially towards the end of charging.
4.5 Discharging
- Discharging may be performed at any time the system is powered On.
- NOTE – The Battery will disconnect power if the voltage, amperage, or temperature limits are exceeded during discharging.
- The NeverDie feature allows the system to have a “reserve” amount of energy left in the battery. Once the system is discharged to 12.0V or 10% State of Charge (SoC), whichever comes first, power will be disabled to leave a “reserve” amount of energy still left in the battery.
- To enable the remaining reserve energy of the system, short-press the Power switch for 1 second.
- NOTE – Once the reserve range is enabled the battery should be charged as soon as possible.
- WARNING – If the reserve energy is used and the battery is left in a deeply discharged state without immediate charging, the battery will become permanently damaged.
4.6 System Storage Procedure
- Storing your battery at the correct specifications is important as it keeps the battery in the healthiest state possible for the fastest deployment when needed.
- If the Lithium Battery System will not be in use for greater than 2 weeks, it is recommended to enable system storage.
- Storage mode is simply a fully charged system in the Powered Off state.
- To enable System Storage:
- Perform a full charge cycle, ensure that the System voltage reaches the Standard Full Charging Voltage indicated in Table 1.
- Power off the System, long-press the Power switch for 3 seconds. Check that the switch is no longer illuminated.
Check that there is 0V at the Power Terminals with a voltmeter.
Table 3
Storage Temperature & Humidity Range| < 1 Month| -4~95°F (-20~35°C),
45~75%RH
---|---|---
< 3 Months| 14~86°F (-10~30°C), 45~75%RH
Long Term Storage| If the battery needs to be stored for > 3 months the
voltage should be 13.2V (50%SOC), and stored at the recommended storage
specifications shown above. Additionally, the battery needs at least one
charge & discharge cycle every six months.
Self-discharge rate| ≤3% per month
Storage conditions < 3 months:
- Fully charge the battery.
- Turn the battery OFF by the Power/Reset switch.
- Store the battery in an environment according to the specifications shown above.
Storage conditions > 3 months:
- Reduce the battery SOC to 13.2V which is 50% ±10% SOC.
- Turn the battery OFF via the Power/Reset switch.
- Store the battery in an environment according to the specifications shown in table 3 above.
- Every 6 months charge the battery to 100% SOC, then discharge the battery to LVC, then charge it to 50% ±10% SOC.
NOTE – For further system installation and operation please refer to the Advanced Series User Guide available at: http://www.lithionicsbattery.com /user-guides/
NON- Permitted DC Circuit Breaker Orientations:
Contact Information
For technical or warranty support please first contact the dealer where the
system was purchased.
Additionally, for factory support please send an email with your battery’s
serial number to
Support@LithionicsBattery.com.
LITHIONICS BATTERY, 1770 CALUMET ST,
CLEARWATER, FL 33765 USA
PH: 727.726.4204
FAX: 727.797.8046
WEB:LITHIONICSBATTERY.COM