HYDROSOFT PLUS WS1 Water Treatment Equipment Control Valve User Manual

June 13, 2024
HYDROSOFT PLUS

HYDROSOFT PLUS WS1 Water Treatment Equipment Control Valve

HYDROSOFT PLUS WS1 Water Treatment Equipment Control

Control Valve Function and Cycles of Operation

This glass filled Noryl1 (or equivalent) fully automatic control valve is designed as the primary control center to direct and regulate all cycles of a water softener or filter. When the WS1 or the WS1.25 control valve is manufactured as a softener, the control valve can be ordered to perform downflow or up flow regeneration. When the WS1 or WS1.25 control valve is set up as a filter, the control valve can be set to perform downflow regeneration or simply backwash. The control valve can be set to regenerate on demand (consumption of a predetermined amount of water) and/or as a time clock (passage of a particular number of days). The control valve can be set so that a softener can meet the Water Quality As association (WQA) Standard S100 or NSF/ANSI Standard 44 efficiency rating.

It is not recommended to change control valves from downflow to up flow brining or vice versa in the field. The valve bodies for downflow and up flow are unique to the regeneration type and and should not be interchanged. A mismatch of valve body and regeneration piston will result in hard water bypass during service.

The control valve is compatible with a variety of regenerates and resin cleaners. The control valve is capable of routing the flow of water in the necessary paths to regenerate or backwash water treatment systems. The injector regulates the flow of brine or other regenerates. The control valve regulates the flow rates for backwashing, rinsing, and the replenishing of treated water into are gene rant tank, when applicable.

The control valve uses no traditional fasteners (e.g. screws); instead clips, threaded caps and nuts and snap type latches are used. Caps and nuts only need to be firmly hand tightened because radial seals are used. Tools required to service the valve include one small blade screw driver, one large blade screw driver, pliers and a pair of hands. A plastic wrench is available which eliminates the need for screwdrivers and pliers. Disassembly for servicing takes much less time than com pa rabble products currently on the market. Control valve in stellation is made easy because the distributor tube can be cut ½” above to ½” below the top of tank thread. The distributor tube is held in place by an O-ring seal and the control valve also has a bayonet lock feature for upper distributor baskets.

The power supply comes with a 15 foot power cord and is designed for use with the control valve. The power supply is for dry location use only. The control valve remembers all settings for up to 8 hours if the power goes out and the battery is not depleted. After 8 hours, the only item that needs to be reset is the time of day; other values are permanently stored in the nonvolatile memory. If a power loss lasts less than 8 hours and the time flashes on and off, the time of day should be reset and the non rechargeable battery should be replaced.

Table 1 shows the order of the cycles when the valve is set up as a softener. When the WS1 or WS1.25 control valve is used as a downflow softener, two backwashes always occur. When the WS1 or WS1.25 control valve is used as an up flow softener,  only one backwash occurs after brining. The OEM has the option of having the regenerate refill after the rinse cycle or have the regenerantpre fill before re gen elation. If the OEM chooses to have the regenerate prefill before regeneration, the prefill starts two hours before the re gen elation time set. During the 2-hour period in which the brine is being made, treated (softened) water is still available. For example: regeneration time = 2:00 am, prefill option selected, downflow softener. Fill occurs at 12:00 a.m., start of backwash cycle occurs at 2:00 a.m.

Table 1
Regeneration Cycles Softening

WS1 & WS1.25 Downflow Regenerate Refill After Rinse| WS1 & WS1.25 Downflow Regenerate Prefill| WS1 & WS1.25

Upflowed Regenerate Refill After Rinse

| WS1 & WS1.25

Upfnow Regenerate Prefill

---|---|---|---
1st Cycle: Backwash| 1st Cycle: Fill/Dissolve| 1st Cycle: Regenerate| 1st Cycle: Fill/Dissolve
2nd Cycle: Regenerate| 2nd Cycle: Backwash| 2nd Cycle: Backwash| 2nd Cycle: Regenerate
3rd Cycle: Backwash| 3rd Cycle: Regenerate| 3rd Cycle: Rinse| 3rd Cycle: Backwash
4th Cycle: Rinse| 4th Cycle: Backwash| 4th Cycle: Fill/Dissolve| 4th Cycle: Rinse
5th Cycle: Fill/Dissolve| 5th Cycle: Rinse| 5th Cycle: Service| 5th Cycle: Service
6th Cycle: Service| 6th Cycle: Service| |

  1. Noryl is a trademark of Sabic Innovative Plastics IP B.V. Company
    When set up as a softener the backwash and rinse cycles automatically increase with increasing salt dosage. Backwashes can  be set to be ORMAL or LONGER. The option selected will apply to all backwashes. Tables 2 and 3 show the length of the cycles when the valve is set up as a softener. Table 2
    Backwash Normal Length Softener Cycle Times in Minutes
    | WS1 & WS1.25 Downow Softener| WS1 & WS1.25 Upow Softener
    ---|---|---
    Grains Capacity/lb NaCl| 6000 to 3501| 3500 to 2501| 2500 to 1700| 6000 to 3501| 3500 to 2501| 2500 to 1700
    lbs NaCl/cu ft resin2| Less than 7.5| 7.5 to 12| More than 12| Less than 7.5| 7.5 to 12| More than 12
    Cycle time in Minutes| Backwash Normal| 6| 8| 8| | |
    Regenerate| 45| 60| 75| 45| 60| 75
    Backwash Normal| 3| 8| 10| 6| 10| 12
    Rinse| 3| 4| 6| 3| 4| 6
    Total3| 57| 80| 99| 54| 74| 93

Table 3
Backwash Longer Length Softener Cycle Times in Minutes 

| WS1 & WS1.25 Downow Softener| WS1 & WS1.25 Upow Softener
---|---|---
Grains Capacity/lb NaCl| 6000 to 3501| 3500 to 2501| 2500 to 1700| 6000 to 3501| 3500 to 2501| 2500 to 1700
lbs NaCl/cu ft resin2| Less than 7.5| 7.5 to 12| More than 12| Less than 7.5| 7.5 to 12| More than 12
Cycle time in Minutes| Backwash Longer| 8| 10| 12| | |
Regenerate| 45| 60| 75| 60| 70| 80
Backwash Longer| 8| 10| 12| 12| 14| 16
Rinse| 4| 6| 8| 5| 7| 9
Total3| 65| 86| 107| 77| 91| 105

Table 4 shows the order of the cycles when the valve is set up as a filter. When the control valve is used as a downflow re gen eating filter, the OEM has the option to specify one backwash or two backwashes. If the control valve is set to regenerate for a filter, the OEM has the option of having the regenerate refill after the rinse cycle or have the regenerate prefill before regeneration. If the OEM chooses to have the regenerate prefill before regeneration, the prefill starts two hours before the regeneration time set. During the 2-hour period in which the regenerate is being made, treated water is still available. For example: regeneration time = 2:00 am, prefill option selected, downflow filter. Fill occurs at 12:00 a.m., start of backwash cycle occurs at 2:00 a.m. There is only one rinse. Backwashes can be set to normal or longer. The option selected will apply to all backwashes. Tables 5 and 6 show the length of the cycles when the valve is set up as a filter.

When the control valve is used as a non-regenerating filter, the OEM has the option to specify one backwash or two backwashes. If two backwashes are specified, two rinses occur. Tables 5 and 6 show the length of the cycles when the valve is set up as a filter. When used as a non-regenerating filter, the downflow piston must be installed, the regenerate piston removed, injector plugs must be installed in both the DN and UP injector locations and the refill elbow must be replaced with a refill port plug.

  1. These are reference numbers that approximate the amount of salt needed. The actual capacity in grains per pound of salt is used in calculations.
  2. Total time does not include fill time, which is dependent upon the amount of salt needed. When in the fill mode the system is providing treated water.

Table 4
Regeneration Cycles Filtering

WS1 & WS1.25 Downflow Regenerate Refill After Rinse| WS1 & WS1.25 Downflow Regenerate Prefill| WS1 & WS1.25

No Regeneration

---|---|---
1st Cycle: Backwash| 1st Cycle: Fill| 1st Cycle: Backwash
2nd Cycle: Regenerate| 2nd Cycle: Backwash| 2nd Cycle: Rinse
3 rd Cycle: Second Backwash*| 3rd Cycle: Regenerate| 3 rd Cycle: Second Backwash*
4th Cycle: Rinse| 4 th Cycle: Second Backwash*| 4 th Cycle: Second Rinse**
5th Cycle: Fill| 5th Cycle: Rinse| 5th Cycle: Service
6th Cycle: Service| 6th Cycle: Service|

*Second backwash is optional
**Second rinse only occurs if Second Backwash option is selected.

Table 5
Regenerating Filter Cycle Times in Minutes

| WS1 & WS1.25 Single Backwash| WS1 & WS1.25 Double Backwash
---|---|---
Normal| Longer| Normal| Longer
Backwash| 14| 16| 8| 12
Regenerate| 60| 60| 60| 60
2nd Backwash| | | 10| 12
Rinse| 8| 10| 8| 10
Total4| 82| 86| 86| 94

Table 6
Non-Regenerating Filter Cycle Times in Minutes

| WS1 & WS1.25 Single Backwash| WS1 & WS1.25 Double Backwash
---|---|---
Normal| Longer| Normal| Longer
Backwash| 14| 16| 8| 12
Rinse| 8| 10| 6| 6
2nd Backwash| | | 10| 12
2nd Rinse| | | 8| 10
Total| 22| 26| 32| 40

The control valve with a water meter can be set for Demand Initiated Regeneration (DIR) only, Time Clock operation only  or DIRand Time Clock which ever comes first, depending upon what settings are selected for Day Override and Gallon Capacity.5 See Table 7.

If a control valve does not contain a meter, the valve can only act as a time clock, and day override should be set to any number and gallon capacity should be set to off.

4 Total time does not include fill time, which is dependent upon the amount of fill needed. When in the fill mode the system is providing treated water.
5 See Installer Display Settings Step 3I, OEM Softener Setup Step 6S and OEM Filter Setup Step 5F for ex planation’s of Day Over ride and Gallon Capacity

Table 7
DIR/Time Clock Options

DIR Time Clock Reserve Capacity Softener Filter Settings6
Regenerant Backwash Only Day Override Gallon Capacity
Yes Automatically Calculated Yes
Yes If desired enter a value less than estimated capacity Yes Yes Yes
Off Any Number
Yes Yes Automatically Calculated Yes
Yes Yes If desired enter a value less than estimated capacity Yes Yes
Yes Any Number Any Number
Yes None Yes Yes Yes Any Number

For DIR Softeners, there are two options for setting the Gallons Capacity. The Gallons Capacity is automatically calculated if set to AUTO. Reserve Capacity is automatically estimated based on water usage if AUTO is used. The other option is to set the  Gallons Capacity to a specific number. If specific c number is set, reserve capacity is zero, unless the value is manually set (i.e. the man factor er intentionally sets the gallon capacity number below the calculated capacity of the system).

The WS1 & WS1.25 control valves can also be set to regenerate immediately or at the next regeneration time by changing the Regeneration Time Option. There are three choices for settings:

  1. “NORMAL” means regeneration will occur at the preset regeneration time.
  2. “on 0” means regeneration will occur when the gallons capacity reaches zero.
  3. “NORMAL + on 0” means the regeneration will occur at the preset regeneration time unless the gallons capacity reaches zero.
    If the gallons capacity reaches zero the regeneration will begin 10 minutes after no water usage.

The user can initiate manual regeneration. The user has the option to request the manual regeneration at the delayed regeneration time or to have the regeneration occur immediately:

  1. Press and release REGEN. “Regen Today” will flash on the display and the regeneration will occur at the delayed re gen eration time. The user can cancel the request by pressing and releasing REGEN. This method of manually initiating regeneration is not allowed when the system is set to “on 0”, i.e. to immediately regenerate when the gallon capacity reaches zero.
  2. Pressing and holding REGEN for approximately 3 seconds will immediately start the regeneration. The user cannot cancel this request, except by resetting the control by pressing NEXT and REGEN simultaneously for 3 seconds.

A unique feature of this control valve is the ability to display actual water usage for the last 63 days. The values are initially stored as “—-”. This means the value is unknown. As days pass values are stored as “0” for no flow or the actual number of gallons. The counting of the gallons starts at the regeneration time. If no regeneration time can be set (i.e. when the valve is set for immediate regeneration) the counting of gallons starts at 12 a.m. Day 1 is yesterday, day 2 the day before yesterday, etc.

Another unique feature is that the valve automatically calculates a reserve capacity when set up as a softener with “Gallons Capacity” set to “AUTO” and the “Regeneration Time Option” set to “Normal” or “Normal + on 0”. The actual reserve capacity is com pared to the gallons capacity remaining immediately prior to the preset regeneration time. A regeneration will occur if the actual reserve capacity is less than the gallons capacity remaining. The actual reserve capacity is calculated by using the estimated reserve capacity and adjusting it up or down for actual usage.

The estimated reserve capacity for a given day of the week is the maximum value stored for the last three non-trivial water usages (i.e. more than 20 gallons/day) in seven day intervals.

OEM General In struc tions

The control valve offers multiple procedures that allow the valve to be modified to suit the needs of the installation. These pro cedars are:

OEM Softener Setup
OEM Filter Setup
Installer Displays & Settings
User Displays & Settings
Diagnostics
Valve History

These procedures can be accessed in any order. Details on each of the procedures are provided on the following pages.

At the discretion of the manufacturer, the field technician can access all settings. To “lock out” access to diagnostic and valve history displays and modify cations to settings except hardness, day override, time of regeneration and time of day by anyone but the manufacturer, press ▼, NEXT, ▲, and SET CLOCK in sequence after settings are made. To “unlock”, so other displays can be viewed and changes can be made, press ▼, NEXT, ▲, and SET CLOCK in sequence.

When in operation normal user displays such as time of day, gallons remaining or days remaining before regeneration are shown. When stepping through a procedure, if no buttons are pressed within five minutes the display returns to a normal user display. Any changes made prior to the five minute time out are incorporated.

To quickly exit OEM Softener Setup, OEM Filter Setup, Installer Display Settings, Diagnostics or Valve History press SET CLOCK. Any changes made prior to the exit are incorporated.

When desired all information in Diagnostics may be reset to zero when the valve is moved to a new location. To reset to zero, press NEXT and ▼ simultaneously to go to the Service/OEM 1 screen, and release. Press ▲ and ▼ simultaneously to reset diagnostic values to zero. Screen will return to User Display.

Sometimes it is desirable to have the valve initiate and complete two regenerations within 24 hours and then return to the preset regeneration procedure. It is possible to do a double regeneration if the control valve is set to “NORMAL” or “NORMAL + on 0” in Step 9S or Step 7F. To do a double regeneration:

  1. Press REGEN once. REGEN TODAY will flash on the display.
  2. Press and hold REGEN for three seconds until the valve regeneration initiates

Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the preset regeneration time.

OEM Softener System Setup Quick Reference

This is a quick reference setup procedure. See OEM Softener System Setup Detail for more information on available settings.

STEP 1S – Press NEXT and ▼ simultaneously for 3 seconds. If screen in step 2S does not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT, ▲, and SET CLOCK in se quince, then press NEXT and ▼ si mulita onerously for 3 seconds.

STEP 2S – Choose Softening using ▼ or ▲. Press NEXT to go to Step 3S. Press REGEN to exit OEM Softener System Setup

STEP 3S – Enter the ion exchange capacity in grains of hardness as calcium carbonate for the system based on test data using ▼ or ▲. Press NEXT to go to Step 4S. Press REGEN to return to previous step.

STEP 4S – Enter the pounds of salt per regeneration using ▼ or ▲. Press NEXT to go to Step 5S. Press REGEN to return to previous step.

STEP 5S – Backwash: Select “NORMAL” or “LONGER” using ▼ or ▲. See Tables 2 or 3 for backwash times. Press NEXT to go to Step 6S. Press REGEN to return to previous step.

STEP 6S – Set Gallons Capacity using ▼ or ▲:

  • “AUTO” (reserve capacity automatically estimated and gallons capacity au to mat ically calculated from grains capacity and water hardness);
  • “oFF” (regeneration based on day override); or
  • number of gallons (20 to 50,000).
    See Setting Options Table for more detail. Press NEXT to go to Step 7S. Press REGEN to return to previous step.

STEP 7S – Set Refill option using ▼ or ▲:

  •  “PoST” to refill the brine tank after the final rinse; or
  • “PrE” to refi ll the brine tank two hours before the regeneration time set.
    Press NEXT to go to Step 8S. Press REGEN to return to previous step.

STEP 8S – Set regenerate downflow or up flow using ▼ or ▲:
• “dn” if the regenerate is to flow downward through the media; or
• “UP” if the regenerate is to flow upward through the media.
Prior to selecting a regenerate flow direction, verify the correct valve body, main piston, regenerate piston, and stack are being used, and that the injector or injector plug(s) are in the correct locations. See Valve Body Compliance Table in WS1 & WS1.25 Drawings and Service Manual.

Press NEXT to go to Step 9S. Press REGEN to return to previous step.

STEP 9S – Set Regeneration Time Option using ▼ or ▲:

  • “NORMAL” means regeneration will occur at the preset time;
  • “on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
  • “NORMAL + on 0” means regeneration will occur at one of the following:
  • the preset time when the gallons capacity falls below the reserve or the specified number of days between regenerations is reached which ever comes first; or
  • after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
    See Setting Options Table for more detail. Press NEXT to exit OEM Softener System Setup. Press REGEN to return to previous step.

Setting Options Table

Filters should only use shaded options.

Volume Capacity Regeneration Time Option Day Override Result7
AUTO NORMAL oFF Reserve capacity automatically estimated.

Regeneration occurs when volume capacity falls below the reserve capacity at the next Regen Set Time

AUTO| NORMAL| Any number| Reserve capacity automatically estimated.

Regeneration occurs at the next Regen Set Time when volume capacity falls below the reserve capacity or the specied number of days between regenerations is reached.

Any number| NORMAL| oFF| Reserve capacity not automatically estimated.

Regeneration occurs at the next Regen Set Time when volume capacity reaches 0.

oFF| NORMAL| Any number| Reserve capacity not automatically estimated.

Regeneration occurs at the next Regen Set Time when the specied number of days between regenerations is reached.

Any number| **** NORMAL| Any number| Reserve capacity not automatically estimated.

Regeneration occurs at the next Regen Set Time when volume capacity reaches 0 or the specified number of days between regenerations is reached.

AUTO| On 0| oFF| Reserve capacity not automatically estimated.

Regeneration occurs immediately when volume capacity reaches 0. Time of regeneration will not be allowed to be set because regeneration will always occur when volume capacity reaches 0.

Any number| On 0| oFF| Reserve capacity not automatically estimated.

Regeneration occurs immediately when volume capacity reaches 0. Time of regeneration will not be allowed to be set because regeneration will always occur on 0.

AUTO| NORMAL + on 0| oFF| Reserve capacity automatically estimated.

Regeneration occurs when volume capacity falls below the reserve capacity at the next Regen Set Time or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.

AUTO| NORMAL + on 0| Any number| Reserve capacity automatically estimated.

Regeneration occurs at the next Regen Set Time when volume capacity falls below the reserve capacity or the specified number of days between regenerations is reached or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.

Any number| NORMAL + on 0| Any number| Reserve capacity not automatically estimated.

Regeneration occurs at the next Regen Set Time when the specifiednumber of days between regenerations is reached or regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.

OEM Filter System Setup Quick Reference

This is a quick reference setup procedure. See OEM Filter System Setup Detail for more information on available settings.

STEP 1F – Press NEXT and ▼ simultaneously for 3 seconds. If screen in step 2F does not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT,  ▲, and SET CLOCK in sequence, then press NEXT and ▼ simultaneously for 3seconds.

STEP 2F – Choose Filtering using ▼ or ▲. Press NEXT to go to step 3F. Press REGEN to exit OEM Filter System Setup.

STEP 3F – Enter “oFF” if regenerate is not used (i.e. backwash only) or enter the refill volume (in gallons) using ▼ or ▲. Prior to selecting oFF or regenerate volume, verify the correct valve body, main piston, regenerate piston, and stack are being used, and that the  injector or injector plug(s) are in the correct locations. See Compliance Table in Service Instructions under Injector Cap, Screen, Injector Plug and Injector section and Figure 6.
Press NEXT to go to step 4F. Press REGEN to return to previous step.

STEP 4F – Backwash: Select using ▼ or ▲:

  • “NORMAL” for one “NORMAL” backwash (14 minutes);
  • “NORMAL 2” for two “NORMAL” backwashes (8 minutes each);
  • “LONGER” for one “LONGER” backwash (16 minutes); or
  • “LONGER 2” for two “LONGER” backwashes (12 minutes each).
    See Tables 5 and 6 for additional details. Press NEXT to go to step 5F. Press REGEN to return to previous step.

STEP 5F – Set Gallons Capacity using ▼ or ▲:

  • “oFF” (regeneration based on day override); or
  • number of gallons (20 to 50,000).
    See Setting Options Table for more detail. Press NEXT to go to step 6F. Press REGEN to return to previous step.

TEP 6F – Set Refill option using ▼ or ▲:

  • “PoST” to refill the brine tank after the final rinse; or
  • “PrE” to refill the brine tank two hours before the re gen eration time set.
    Press NEXT to go to step 7F. Press REGEN to return to previous step.

STEP 7F – Set Regeneration Time Option using ▼ or ▲:

  • “NORMAL” means regeneration will occur at the preset time;
  • “on 0” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or
  • “NORMAL + on 0” means regeneration will occur at one of the following:
  • the preset time when the specified number of days between regenerations is reached; or
  • after 10 minutes of no water usage when the gallon capacity reaches 0 (zero). This display will not appear if Step 5F is set to oFF.
    See Setting Options Table for more detail. Press NEXT to exit OEM Filter System Setup. Press REGEN to return to previous step.

Installer Display Settings

STEP 1I – Press NEXT and ▲ simultaneously for 3 seconds.

STEP 2I – Hardness: Set the amount of hardness in grains of hardness as calcium car bon ate per gallon using ▼ or ▲. The default is 20 with value ranges from 1 to 150 in 1 grain increments. Note: The grains per gallon can be in creased if soluble iron needs to be reduced. This display will show “–nA–” if “FILTER” is selected in Step 2F or if ‘AUTO’ is not selected in Step 6S. Press NEXT to go to step 3I. Press REGEN to exit Installer Dis play Settings.

STEP 3I – Day Override: When gallon capacity is set to off, Day Override sets the number of days between re gen er a tions. When gallon capacity is set to AUTO or to  a number, Day Override sets the maxi mum number of days between re gen er a tions. If value set to “oFF” re generation initiation is based solely on gallons used. If values set as a number (allowable range from 1 to 28) a re gen eration initiation will be called for on that day even if sufficient number of gallons were not used to call for are generation. Set Day Override using ▼ or ▲:

  •  number of days between regeneration (1 to 28); or
  • “oFF”.
    See Setting Options Table for more detail on setup. Press NEXT to go to step 4I. Press REGEN to return to previous step.

STEP 4I – Next Regeneration Time (hour): Set the hour of day for regeneration using ▼ or ▲. AM/PM toggles after 12. The default time is 2:00 a.m. This display will show “REGEN on 0 GAL” if “on 0” is selected in Step 9S or Step 7F. Press NEXT to go to step 5I. Press REGEN to return to previous step.

STEP 5I – Next Regeneration Time (minutes): Set the minutes of day for regeneration using ▼ or ▲. This display will not be shown if “on 0” is selected in Step 9S or Step 7F. Press NEXT to exit Installer Display Settings. Press REGEN to return to previous step.
To initiate a manual regeneration immediately, press and hold REGEN for three seconds. The system will begin to re gen er ate mime dirtily. The control valve may be stepped through the various re generation cycles by pressing REGEN.

User Display Settings

General Operation

When the system is operating one of two displays will be shown. Pressing NEXT will alternate between thesis plays. One of the displays is always the current time  of day. The second display is one of the following: days remaining or gallons remaining. Days remaining is the number of days left before the system goes through a  regeneration cycle. Capacity remaining is the number of gallons that will be treated before the system goes through a regeneration cycle. The user can scroll between the displays as desired.

If the system has called for a regeneration that will occur at the preset time of re gen elation, the words REGEN TODAY will appear on the display.
When water is being treated (i.e. water is fl owing through the system) the word “Softening” or “Filtering” flashes on the display if a water meter is installed.

Regeneration Mode

Typically a system is set to regenerate at a time of low water usage. An example of a time with low water usage is when a household is asleep. If there is a demand for water when the system is regenerating, untreated water will be used.

When the system begins to regenerate, the display will change to include information about the step of the regeneration process and the time remaining for that step to be completed. The system runs through the steps au to magically and will reset itself to provide treated water when the regeneration has been completed.

Manual Regeneration

Sometimes there is a need to regenerate the system sooner than when the system calls for it, usually referred to as manual generation. There may be a period of heavy water usage because of guests or a heavy laundry day.

To initiate a manual regeneration at the preset delayed regeneration time, when the regeneration time option is set to “NORMAL” or “NORMAL + on 0”, press and release REGEN. The words “REGEN TO DAY” will flash on the display to indicate that the system will reenter ate at the preset delayed re generation time. If you pressed REGEN in error, pressing the button again will cancel the request. Note: If the regeneration time option is set to “on 0” there is no set delayed regeneration time so “REGEN TODAY” will not activate if REGEN is pressed.

To initiate a manual regeneration immediately, press and hold REGEN for three seconds. The system will begin to regenerate immediately. The request cannot be cancelled.

Note: For softeners, if brine tank does not contain salt, fi ll with salt and wait at least two hours before regenerating.

Set Time of Day

The user can also set the time of day. Time of day should only need to be set after power outages lasting more than 8 hours, if the battery has been depleted and a power outage occurs, or when daylight saving time begins or ends. If a power outage lasting more than 8 hours occurs, the time of day will fl ash on and off which indicates the time of day should be reset. If a power outage lasts less than 8 hours and the time of day fl ashes on and off, the time of day should be reset and the battery replaced.

STEP 1U – Press SET CLOCK.

STEP 2U – Current Time (hour): Set the hour of the day using ▼ or ▲. AM/PM toggles after 12. Press NEXT to go to step 3U.

STEP 3U – Current Time (minutes): Set the minutes of the day using ▼ or ▲. Press NEXT to exit Set Clock. Press REGEN to return to previous step.\

Power Loss
If the power goes out, the system will keep time for up to 8 hours or until the battery is depleted. If a power outage of more than 8 hours occurs, the time of day will fl ash on and off which indicates the time of day should be reset. The system will remember the rest. If a power outage lasts less than 8 hours and the time of day fl ashes on and off, the non rechargeable battery should be replaced.

Error Message
If the word “ERROR” and a number are alternately flashing on the display contact the OEM for help. This indicates that the valve was not able to function properly.

STEP 1D – Press ▼ or ▲ simultaneously for three seconds. If screen in step 2D does not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT, ▲, and SET CLOCK in sequence, then press NEXT and ▼ simultaneously for 3 seconds.

STEP 2D – Days, since last regeneration: This display shows the days since the last re generation occurred. Press NEXT to go to Step 3D. Press REGEN to exit Diagnostics.

STEP 3D – Gallons, since last regeneration: This display shows the number of gallons that have been treated since the last re generation. This display will equal zero if a water meter is not installed. Press NEXT to go to Step 4D. Press REGEN to return to previous step.

STEP 4D – Gallons, reserve capacity used for last 7 days: If the valve is set up as a softener, a meter is installed and Set Gallons Capacity is set to “Auto,” this display shows 0 day (for today) and fl ashes the reserve capacity. Press ing ▲ will show day 1 (which would be yesterday) and fl ashes the reserve capacity used. Press ing ▲ again will show day 2 (the day before yesterday) and the reserve capacity. Keep pressing ▲ to show the gallons for days 3, 4, 5 and 6. ▼ can be pressed to move back wards in the day series. Press NEXT at any time to go to Step 5D. Press REGEN to return to previous step.

STEP 5D – Gallons, 63 day usage history: This display shows day 1 (for yesterday) and flashes the number of gallons treated yesterday. Pressing ▲ will show day 2 (which would be the day before yesterday) and fl ashes the number of gallons treated on that day. Continue to press ▲ to show the max i mum number of gallons treated for the last 63 days. This display will show dashes if a water meter is not installed.
Press NEXT at any time to go to Step 6D. Press REGEN to return to previous step.

STEP 6D – Flow rate, current: The flow rate in gallons per minute will be displayed. If fl ow stops the value will fall to zero in a few seconds. This display will equal zero if a water meter is not installed. Press NEXT to go to Step 7D. Press REGEN to return to previous step.

STEP 7D – Flow rate, maximum last seven days: The maximum fl ow rate in gallons per minute that occurred in the last seven days will be displayed. This display will equal zero if a water meter is not installed. Press NEXT to go to Step 8D. Press REGEN to return to previous step.

STEP 8D – Gallons, total used since last reset: The total number of gallons used since last reset will be displayed. This display will equal zero if a water meter is not installed. Press NEXT to go to Step 9D. Press REGEN to return to previous step.

STEP 9D – Days, total number since last reset: The total number of days the control valve has been in service since last reset will be displayed. Press NEXT to go to Step 10D. Press REGEN to return to previous step.

STEP 10D – Regenerations, total number since last reset: The total number of re generations that have occurred since last reset will be displayed. Press NEXT to exit Diagnose tics. Press REGEN to return to previous step.

When desired, all information in Diagnostics may be reset to zero when the valve is installed in a new location. To reset to zero, press NEXT and ▼ simultaneously to go to the Service/OEM screen, and release. Press ▼ and ▲ simultaneously to reset diagnostic values to zero. Screen will return to user display.

Valve History

STEP 1VH – Press ▲ and ▼ simultaneously for three seconds and release. Then press ▲ and ▼ simultaneously and release. If screen in step 2VH does not appear in 5 seconds the lock on the valve is activated. To unlock press ▼, NEXT, ▲, and SET CLOCK in sequence, then press ▲ and ▼ simultaneously for 3 seconds and release. Then press ▲ and ▼ simultaneously and release.

STEP 2VH – Software Version: This display shows the software version of the valve.
Press NEXT to go to Step 3VH. Press REGEN to exit Valve History.

STEP 3VH8 – Flow rate, maximum since startup: This display shows the maximum flow rate in gallons per minute that has occurred since startup. This display will equal zero if a water meter is not installed. Press NEXT to go to Step 4VH. Press REGEN to return to previous step.

STEP 4VH – Gallons, total used since start-up: This display shows the total gallons treated since startup. This display will equal zero if a water meter is not in stalled. Press NEXT to go to Step 5VH. Press REGEN to return to previous step.

STEP 5VH – Days, total since start-up: This display shows the total days since startup.
Press NEXT to go to Step 6VH. Press REGEN to return to previous step.

STEP 6VH – Regenerations, total number since start-up: This display shows the total number of regenerations that have occurred since startup. Press NEXT to go to Step 7VH. Press REGEN to return to previous step.

STEP 7VH – Error Log: This display shows a history of the last 10 errors generated by the control during operation. Press ▲ or ▼ to review each error recorded. Press NEXT to exit Valve History. Press REGEN to return to previous step.

RETURN TO NORMAL MODE

Front Cover and Drive Assembly

Drawing No. Order No. Description Quantity
1 V3175-01 WS1 FRONT COVER ASY 1
2 V3107-01 WS1 MOTOR 1
3 V3002-A WS1 DRIVE BRACKET ASY 1
4 V3108-11BOARD WS1 PCB XMEGA REPL 1
5 V3110 WS1 DRIVE REDUCING GEAR 12X36 3
6 V3109 WS1 DRIVE GEAR COVER 1
Not Shown V3186-06 WS1 POWER SUPPLY US 15VDC HOCP 1
V3186EU-06 WS1 POWER SUPPLY EU 15VDC HOCP
V3186UK-06 WS1 POWER SUPPLY UK 15VDC HOCP
V3186-01 WS1 POWER CORD 15FT
Power Supply U.S. International
--- --- ---
Supply Voltage 100-120 VAC 100-240 VAC
Supply Frequency 50/60 Hz 50/60 Hz
Output Voltage 15 VDC 15 VDC
Output Current 500 mA 500 mA

Revision History:

8/16/2017

PAGE 16:
Updates to table and drawing – Bracket and Spring Clip / Power Supply

5/8/2018

PAGE 16:
Updates to Power Supply table

6/8/2018

PAGE 16:

4 V3108-11BOARD WS1 PCB XMEGA REPL 1

6/11/2020

PAGE 16:
Removed #7 V3106-01 from table and drawing

Not Shown V3186-06 WS1 POWER SUPPLY US 15VDC HOCP 1
V3186EU-06 WS1 POWER SUPPLY EU 15VDC HOCP
V3186UK-06 WS1 POWER SUPPLY UK 15VDC HOCP
V3186-01 WS1 POWER CORD 15FT

 LIMITED WARRANTY

Hydro Soft Plus warrants the Hydro Soft Plus brand water treatment system manufactured by Hydro Soft Plus and installed by a duly authorized Hydro Soft Plus dealer, to be free from defects in materials and workmanship to the original residential purchaser (hereinafter CONSUMER) for a period of 5(five) years from the date of purchase. All aspects of this warranty are subject to the following limitations, terms and conditions.

DURATION OF WARRANTY
If the Hydro Soft Plus equipment consisting of the Mineral and Storage Tanks, Controls and Valves, Ion Exchange Resin and Treatment Media, is determined to have failed as a result of a manufacturing defect within the 5 year warranty period, the Hydro Soft Plus will, at its sole discretion, repair or replace the defective part at NO CHARGE to the CONSUMER (excluding labor, and applicable shipping and handling costs) for the duration of the warranty period.

LIMITATIONS OF COVERAGE
This warranty extends only to the original purchaser for damage resulting from defects in materials and workmanship, and does not include damage caused by the CONSUMER’S neglect or abuse, or by accident, to damage caused by wind, hail or abnormal weather conditions, or to damage caused by acts of God, civil insurrection or extraordinary circumstances beyond the control of Hydro Soft Plus.
Hydro Soft Plus shall not be liable for any direct or indirect damage resulting from the use of the equipment, and in no event shall the extent of this warranty coverage exceed the purchase price of the equipment.
Hydro Soft Plus cannot know the characteristics of a CONSUMER’S water supply or the purpose for which one is purchasing the Hydro Soft Plus equipment. Also, water qualities vary seasonally and over time. therefore, the Hydro Soft Plus assumes no liability for the determination of the proper equipment necessary to meet a CONSUMER’S requirements, nor does it authorize others to assume such obligations on its behalf.
This warranty excludes any equipment which was not manufactured by the Hydro Soft Plus and installed by an authorized Hydro Soft Plus dealer or on which the date code has been removed or altered. Any tampering or attempted repair performed by anyone other than an authorized dealer, including the CONSUMER, voids this warranty.

MISCELLANEOUS
In order to be considered for validation, all claims for warranty coverage must be accompanied by a copy of the purchase agreement indicating the date of initial installation, and a copy of the Consumer’s current utility bill. the Hydro Soft Plus reserves the right to inspect the the Hydro Soft Plus Equipment prior to honoring any warranty claim.
This warranty is only issued by the Hydro Soft Plus, and the CONSUMER is hereby advised that Hydro Soft Plus Electric Corporation is not the manufacturer of the equipment, and provides no additional or separate warranty whatsoever in connection with the equipment.
This warranty gives you specific legal rights, and you may have other rights which may vary from state to state. Any and all inquiries or claims under this warranty must be submitted in writing to the dealer you purchased the equipment from.

OPERATION PARAMETERS

Operating Temperatures Maximum 100°F (37.8°C) Minimum 40°F (4.4°C)
Operating Pressure Maximum 85psi (6.0 kg/cm2) Minimum 40psi (2.80 kg/cm2)
pH Parameters Maximum 11 Minimum 2
Iron Maximum 0.2 ppm
TDS (Total Dissolved Solids) < 1800 ppm
Turbidity < 5NTU

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals