CE T Microgrids Established Energy Saving and Power Resilience Instruction Manual
- June 13, 2024
- CE T
Table of Contents
- CE T Microgrids Established Energy Saving and Power Resilience
- Product Information
- Product Usage Instructions
- Disclaimer
- About This Document
- Glossary of Terms
- Important Safety Instructions
- Overview
- System Rating
- Reference Document
- Microgrid Operation – Synchronous Vs Asynchronous
- Microgrid Operation
- Microgrid Operation – SEL Method
- Microgrid Operation – Single Wire Command Method
- Microgrid Operation – Modbus Command Method
- Documents / Resources
CE T Microgrids Established Energy Saving and Power Resilience
Product Information
The product is a Stabiliti converter, designed and manufactured by CE+T America. It utilizes leading conversion and storage technology for energy saving and power resilience. The product is protected by several international patents and trademarks.
For more information, please visit www.cet-america.com.
Product Usage Instructions
Important Safety Instructions
The following safety symbols are used in this manual:
- Important Information: Includes key information for the operation of this equipment or specific instructions to maintain the warranty.
- Personal Protective Equipment: This symbol indicates that the use of personal protective equipment is highly recommended, including insulated gloves, steel-toed boots, hard hat, reflective fire-resistant vests, and protective eye goggles.
- Danger: All instructions regarding the configuration of this device must be followed. Failure to follow may result in injury, death, or damage to equipment.
- Danger: To avoid electric shock, verify that the Converter’s external AC and DC Disconnects are open (off). Wait for at least five (5) minutes after opening AC and DC Disconnects to allow the Converter’s internal capacitors to discharge to zero voltage before performing any work on the Converter. Utilize lockout procedures to ensure that both AC and DC Disconnects remain in the off position during all service periods.
It is important to note that the equipment must be handled, installed, and
operated by qualified engineers/technicians with proper training on handling
high/medium voltage electrical equipment. Local and national electrical codes
must be followed
during installation and operations to ensure safety. Failure to observe safety
standards could result in personal injury or damage to equipment/environment.
Overview
This document serves as a quick start guide to Stabiliti’s microgrid operation. It provides an overview of the different methods and their pros and cons for commanding Stabiliti to form a grid (microgrid operation). For detailed information, refer to the applicable detailed application notes.
System Rating
The maximum number of Stabiliti that can be used to form a microgrid is 8, with a total capacity of 240 kW (30 kW per Stabiliti). There is no minimum limit, and microgrid function can be achieved with a single Stabiliti as well.
Synchronous operation means that upon receipt of appropriate commands and grid conditions, all Stabiliti in the system will start forming or following the grid at the exact same time. This type of operation is required when the load that needs to be powered up is exactly equal to the size of the Stabiliti installation. Achieving this requires the use of islanding switchgear or following the single-wire microgrid method, which adds cost and complexity to the overall control.
Leadi ng Conversion and Storage Technology for Energy Saving and Power Resilience
The contents in document are subject to change without notice.
The products presented are protected by several international patents and
trademarks. All rights reserved.
Disclaimer
This document is provided “as is” and CE+T America makes no representations warranties, expressed or implied, with respect to the information contained herein. CE+T America has made reasonable efforts to ensure the accuracy of information herein and at the time of publication. However, information is constantly evolving and CE+T America does not purport the information provided is correct, comprehensive, or exhaustive. This document is for informational purposes only. You should not act upon information without consulting CE+T America or its authorized distributors.
© Copyright 2020, CE+T America. All rights reserved. No parts of this document may be reproduced in any form without the express written permission of CE+T America. CE+T America logo are trademarks of CE+T America. All other trademarks and service marks belong to their respective owners.
About This Document
This document is CE+T America proprietary. It is a customer facing document aimed to serve as an operational guide for Stabiliti converter’s microgrid operation.
Document Revision History:
Date | Revision | Notes |
---|---|---|
Sept 15th, 2021 | A | Initial draft |
Contact Information
CE+T America, Austin, Texas
g.mittal@cet-power.comDate
Glossary of Terms
Acronym of Term & Full Expression
-
AWG
American wire gauge -
CEC
California Energy Commission -
GFDI
Ground fault detection current -
IMI
Isolation monitor interrupter -
BESS
Battery energy storage system, specifically e-ON’s. Based on context in the manual, BESS may refer to complete system including eON batteries and PCS. -
PCS
Power conversion system, specially Stabiliti 30C3 -
PV
Photovoltaic -
LCD
Liquid Crystal Display -
RSS
Rapid shutdown system -
RSE
Rapid shutdown equipment -
BoS
Balance of system components -
BAMS
Battery array management system -
MBMS
Master battery management system -
CAN
Communication protocol -
Modbus
Communication protocol -
SoC
State of charge of batteries, specified in percentage. -
UPS
Uninterrupted power supply -
HMI
Human machine interface, touch screen or web interface -
PPE
Personal Protective Equipment -
CCS
Customer Control System
Important Safety Instructions
The following safety symbols are used in this manual:
-
Danger – Procedure or situations that require action to prevent personal injury/death or damage to equipment/environment.
-
Warning – Indicates a potentially hazardous situation that, if not avoided, can result in serious injury or death.
-
Important Information: Includes key information for the operation of this equipment or specific instructions to maintain the warranty.
-
Personal Protective Equipment: This symbol means that use of personal protective equipment is highly recommended. This includes insulated gloves, steel toed boots, hard hat, reflective fire-resistant vests, and protective eye goggles.
Note that the equipment must be handled, installed, and operated by qualified engineer/technician with proper training on handling high/medium voltage electrical equipment. Local and national electrical code must be used during installation and operations. Failure to observe safety standards could result in personal injury or damage to equipment/environment. -
Danger – All instructions regarding the configuration of this device must be followed. Failure to follow may result in injury, death, or damage to equipment.
-
Danger – To avoid an electric shock, verify that the Converter’s external AC and DC Disconnects are open (off). A minimum wait time of five (5) minutes is required after opening AC and DC Disconnects to assure that the Converter’s internal capacitors have discharged to zero voltage before performing any work on the Converter. Utilize lockout procedures to ensure that both AC and DC Disconnects remain in the off position during all service periods.
-
Danger – The enclosure contains exposed high voltage conductors. The enclosure front access door must remain closed, except during installation, commissioning, or maintenance by trained service personnel. Do not remove the front doors if extreme moisture is present (rain, snow, or heavy dew).
-
Danger – To avoid an electric shock, verify that the Converter’s external AC and DC Disconnects are open (off). A minimum wait time of five (5) minutes is required after opening AC and DC Disconnects to assure that the Converter’s internal capacitors have discharged to zero voltage before performing any work on the Converter. Utilize lockout procedures to ensure that both AC and DC Disconnects remain in the off position during all service periods.
-
Warning – These instructions DO NOT contain any information on the operation of battery systems outside of this product. Refer the manufacturer for the battery system for installation and servicing instructions.
-
Danger – Ensure that the equipment is adequately installed and grounded per NFPA and all applicable NEC codes.
-
Danger – Do not leave foreign objects in the enclosure. Keep the area around the enclosure clear of trash, debris, and other combustible materials.
-
Warning – Personnel Qualification: Inspections and operations requiring access to lethal AC or DC voltages, should only be performed by qualified personnel.
-
Warning – All field wiring must conform to the codes set forth in the National Electric Code ANSI/NFPA 70.
-
Warning – Replace damaged warning and precautionary labels.
Refer to “Reference Documents” section of this manual for details on manuals/documents that should be read first before proceeding.
Overview
This document serves as a quick start guide to Stabiliti ’s microgrid operation. There are different ways Stabiliti s can be commanded to form grid (i.e., microgrid operation) and this guide will cover all different methods and their pros and cons. This document is aimed at providing a “bird’s eye view” only for all different microgrid operation method. Refer to applicable detailed app notes for further details.
System Rating
Note that the max number of Stabiliti that can be used to form microgrid is 8 (240 kw total as one Stabiliti is 30 kw). There is no minimum limit though. Microgrid function can be achieved via a single Stabiliti as well.
Reference Document
- MAN – 00115 – Stabiliti Series 30 KW – Installation and Operation Manual – V1.0 6.2.
- MAN – 00114 – Stabiliti Series 30 KW – Quick Start Guide – V1.0
- DOC – 00063 – App Note – Single Wire Microgrid Guide
- DOC – 000xx – App Note – Islanding Switchgear Guide
- DOC – 503 – App Note – Rapid Backup Power Solution Guide
- DOC – 00033 – App Note – Transformer & Interconnection
Also refer to PCS’ modbus map for details.
Microgrid Operation – Synchronous Vs Asynchronous
In essence, microgrid operation means that the Stabiliti will form grid and
keep the loads running even when the grid is lost. For Stabiliti to be able to
do so, there are specific software settings and specific ways to set the whole
system up from wiring standpoint. The exact settings depend on desired
microgrid operation. Before we go into further details, its important to
understand the difference between synchronous and asynchronous microgrid
function.
Synchronous means that upon receipt of appropriate commands (and grid
conditions), ALL Stabiliti s in the system will start forming (or following)
the grid at the exact same time. Such operation is required when the load that
needs to be powered up is exactly equal to the size of Stabiliti installation.
To achieve this, a use of islanding switchgear or following “single wire
microgrid” method is crucial. This of course adds cost and adds some
complexity to the overall control.
If the load that is supposed to be protected is controllable, meaning it can be gradually brought online then an asynchronous way of controlling microgrid is a cheaper alternative. In asynchronous mode, individual Stabiliti are brought online one by one. They may all receive “microgrid command” at the same time but there might be a slight delay for individual units to start forming microgrid. Due to this limitation, this method is ideally suited for completely off grid applications.
Microgrid Operation
There are three different ways of achieving microgrid operation. Each one has their own pros and cons. Note that there is a max limit of 8 converters while forming microgrid. Refer to the table below for details:
Refer to the section below to gain better understanding of each term used in the table above.
Definitions:
- On grid means system is normally connected to grid. But when grid is lost, the Stabiliti system is required to form microgrid to support the loads.
- Off grid means the system has no connection to the grid at all and there will never be an actual grid connection.
- Black start refers to a mode of operation where the load is required to be brought online from a completely offline state.
Here is a summary of pros and cons of all three methods:
Microgrid Operation – SEL Method
This is how the system shall be interconnected when using CE+ T supplied islanding switchgear:
Field Wiring:
The AC connection from Stabiliti will go into an AC distribution panel (not
shown above) and then into “Islanding Switchgear”. From there, it will connect
to the grid. Note that the “power supply and digital control signals will go
from “Islanding switchgear” to one Stabiliti and then connection to subsequent
Stabiliti will be daisy chained from this Stabiliti. Note that the “Islanding
Switchgear” design may look different (look and feel) than the one shown in
figure above. The field connections and functionality will remain the same.
This is the most recommended mode of operation for all “on grid” applications.
System Startup – Initial Start of System:
The system must be set up when the grid is present. Upon interconnecting
everything, the SEL relay will engage 24 volts to the two digital signals
connected to Stabiliti and at the same time it will energize/close the Grid
Interconnect Contactor (GIC). At this time the load is powered via the grid.
Now each stabiliti should be manually commissioned and brought online. Note
that Stabiliti’s AC port must be set in “FPWR” mode. When grid is present and
SEL relay is not commanding the Stabiliti to form the grid, Stabiliti will
wait for a Customer Control System (CCS) to send a power command to support
the load.
Follow to Form Operation – Loss of Grid:
When the grid is lost, the SEL relay detects the loss of grid and notifies the
Stabiliti to start getting ready to form the microgrid. After this, SEL relay
opens the GIC. Upon successful GIC operation, SEL reports back to Stabiliti
that its ok to form microgrid now. This whole process takes around 100 ms.
Note that once Stabiliti are forming the grid, they will ignore power command
sent by CCS and will keep the loads on by appropriately taking power from the
two DC ports.
The Stabiliti’s on board control systems are normally powered via the 480-vac
connection. During the “following to forming” transition, the UPS within the
Islanding switchgear provides power to keep the internal Stabiliti controls
running.
Form to Follow Operation – Grid is Back:
When the grid is back, SEL ensures that the grid formed by Stabiliti is in
sync (phase, voltage, frequency) with the grid and upon successful sync, SEL
relay closes the GIC and releases both microgrid command signals from
Stabiliti. This transition is almost seamless.
Application:
Using this method adds cost to the system but it greatly automates the
microgrid function. A customer control system will have to make no decision to
enable any of “forming to follow” or “follow to forming” transitions. This is
best suited for all “on grid” applications.
Refer to “DOC – 000xx – App Note – Islanding Switchgear Guide” for additional
details.
Microgrid Operation – Single Wire Command Method
This is how the system shall be interconnected when using “Single Wire Method”:
Field Wiring:
The “power supply and digital control signals will go from “Islanding Assist
Box” to one Stabiliti and then connection to subsequent Stabiliti will be
daisy chained from this Stabiliti. CCS must control both the “Islanding Assist
Box” and the GIC to achieve the same operation as performed by CE+T supplied
Islanding Switchgear (as described in the previous section). It is customer’s
responsibility to design appropriate wiring and control algorithm to achieve
the same. The figure above serves as a guide to achieve required field wiring.
Note: Regarding the “Islanding Assist Box”, CE+T can provide design
documentation but will not be able to have one built for the customer. It will
be customer’s responsibility to build one as per provided documentation. It is
also customer responsibility to design the CCS to control the “Islanding
Assist Box”.
Refer to “DOC – 503 – App Note – Rapid Backup Power Solution Guide” for
additional details.
System Startup – Initial Start of System:
The system must be set up when the grid is present. Upon interconnecting
everything, the CCS shall engage 24 volts to the one digital signal connected
to Stabiliti and at the same time it shall energize/close the Grid
Interconnect Contactor (GIC). At this time the load is powered via the grid.
Now each stabiliti should be manually commissioned and brought online. Note
that Stabiliti’s AC port must be set in “FPWR” mode. When grid is present and
CCS is not commanding the Stabiliti to form the grid, Stabiliti will wait for
CCS to send a power command to support the load.
Follow to Form Operation – Loss of Grid:
When the grid is lost, the CCS must detect the loss of grid and before
commanding the Stabiliti to form microgrid, it must ensure the system is
isolated from the grid by opening up GIC. Upon successful GIC operation, it
must command Stabiliti to form microgrid. Note that if CCS is not fast enough
to make these decisions, the load may be dropped, and additional coordination
will be required to black start the loads. This will be solely customer’s
responsibility to ensure reliable Stabiliti operation.
The Stabiliti’s on board control systems are normally powered via the 480-vac
connection. During the “following to forming” transition, the UPS within the
Islanding switchgear provides power to keep the internal Stabiliti controls
running.
Form to Follow Operation – Grid is Back:
When the grid is back, CCS must ensure that the grid formed by Stabiliti is in
sync (phase, voltage, frequency) with the grid and upon successful sync, CCS
can close the GIC and release the microgrid command signal from Stabiliti.
Again, this will be solely customer’s responsibility to ensure reliable
Stabiliti operation
Application:
This method is best suited for customers who do not wish to use CE+T provided
islanding switchgear. While this method saves upfront cost (no cost added for
Islanding Switchgear) it adds significant amount of work for the customer to
build the ““Islanding Assist Box” and also make changes to CCS to control
“Islanding Assist Box” and GIC.
Disclaimer:
Note that in this case, the full operation is solely controlled by “Customer
Control System”. CE+T shall not be held liable for damage or harm caused to
equipment or personnel due to incorrect system operation.
Refer to “DOC – 00063 – App Note – Single Wire Microgrid Guide” for additional details.
Microgrid Operation – Modbus Command Method
This is how the system shall be interconnected when using “Modbus Method”:
Field Wiring:
The UPS box must be connected to 24 volts dc power supply pins within
Stabiliti. Apart from this, there is no additional/special field wiring.
Note: Regarding the “UPS Box”, CE+T can provide design documentation but will
not be able to have one built for the customer. It will be customer’s
responsibility to build one as per provided documentation.
System Startup – Initial Start of System:
Before reaching the project site, the UPS box must be fully charged. Ensure
the load is physically disconnected from the Stabiliti system. Use the “UPS
box” to power up Stabiliti. Once Stabiliti is on, the AC port must be set to
“FPWR”. Once set, start Stabilitis one by one. Once all the Stabilitis are on,
ensure they are all reporting “Forming” status on the LCD panel. Once this is
confirmed, then provided there is enough PV, storage or DC power sources
(connected to Stabiliti’s DC port), the Stabiliti system can now be connected
to the load.
Follow to Form Operation – Loss of Grid:
Not applicable.
Form to Follow Operation – Grid is Back:
Not applicable.
Application:
This method is best suited for projects which are completely off grid.
Disclaimer:
Note that in this case, the full operation is solely controlled by “Customer
Control System”. CCS must control all DERs appropriately to ensure reliable
operation. CE+T shall not be held liable for damage or harm caused to
equipment or personnel due to incorrect system operation.
End of Document
Documents / Resources
| CE T
Microgrids Established Energy Saving and Power
Resilience
[pdf] Instruction Manual
Microgrids Established Energy Saving and Power Resilience, Microgrids,
Established Energy Saving and Power Resilience, Energy Saving and Power
Resilience, Power Resilience, Resilience
---|---
References
- Homepage | Power Integrations
- CE+T America - World class provider of backup power and energy management solutions.
- CE+T Power - We provide power solutions to keep your business going.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>