LIGHTRONICS AT402 Architectural Wall Mount Dimmer Owner’s Manual
- June 12, 2024
- LIGHTRONICS
Table of Contents
- DESCRIPTION OF UNIT
- POWER REQUIREMENTS
- INSTALLATION
- INPUT POWER CONNECTIONS
- LOAD CONNECTIONS
- PRESET CONTROLS
- DMX CONTROLS
- DMX TERMINATION
- INITIAL SET UP
- OPERATION
- MANUAL PRESET OPERATION
- REMOTE SWITCH CONNECTIONS EXAMPLE
- MANUAL ALL ON / RESUME OPERATION
- FULL PROGRAMMING MENU STEPS
- OPERATIONAL SETTING OPTIONS
- MODEL NUMBERS AND CONFIGURATION
- MAINTENANCE
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
LIGHTRONICS AT402 Architectural Wall Mount Dimmer
DESCRIPTION OF UNIT
The AT series dimmer is specifically optimized for architectural applications.
It can be supplied with up to four 2400 Watt lighting circuits (channels) and
is provided with a fast acting 20 Amp magnetic circuit breaker for each
channel. The AT series dimmer can be operated from a DMX controller or
remotely located momentary contact closures to activate programmable presets.
A table at the end of this manual gives a description of the different AT
models.
POWER REQUIREMENTS
The AT Series dimmer requires a 120 VAC hot power feed line for each lighting circuit (channel), a common neutral, and an earth ground. Each of these feeds must be powered by a circuit providing a minimum of 20 Amps and supplies only one of the AT Series dimmer lighting circuits. The power feed for channel number one also powers the unit’s internal electronic circuitry. The internal circuitry is protected by a replaceable 1/2 Amp, 250 Volt, fast acting fuse. The AT dimmer may be operated from either single phase or three phase power and may be switched between these power types by the user. For 230 VAC option, a special option must be requested when ordering the AT dimmer.
INSTALLATION
LOCATION AND MOUNTING
The unit is for INDOOR USE ONLY. It is to be wall mounted using the mounting holes provided in the chassis. Orient the unit such that the circuit board is in the lower left corner of the chassis. The unit may (but is not required to be) spaced out from the wall approximately 1 inch. This may be desirable if the unit must be used in a location with a high ambient temperature. Standard sized knockout holes are provided in the top, bottom and right side of the chassis for wiring. Be sure that the vent holes in the chassis and cover are not obstructed since they are needed for proper cooling.
INPUT POWER CONNECTIONS
WARNING!
RISK OF ELECTRICAL SHOCK
Make sure that power is removed from all feed circuits before proceeding with
wiring Connect POWER INPUT leads to the lower terminal strip positions as
indicated on the terminal strip labels. A hot feed line is needed for each
channel.
Associated NEUTRALS are to be connected to the NEUTRAL bar provided. An EARTH
GROUND is required with the ground lug provided. The terminal strip connection
torque specification is 16 lb.-in.
max. The minimum wire size is AWG#12. Consult the applicable electrical codes
for your location for exact wire specifications. The power terminal
connections are intended for copper wire only. This unit will work on either
single or three phase power. Any dimmer channel may get power from any phase.
LOAD CONNECTIONS
The AT Series dimmer is a triac based dimmer meant for forward phase loads. You can connect up to 2400 Watts of lighting to each channel. Connect lighting loads to the upper terminal strip positions as indicated by the label in the unit (see Figure 1). The neutral bar and ground lug should be used for lighting loads. The terminal strip connection torque specification is 16 lb.-in. max.
PRESET CONTROLS
The AT Series dimmer provides a user interface on the circuit board as well as simple contacts to activate preset scenes. Almost any available low voltage wire may be used since these connections are just contact closures.
DMX CONTROLS
DMX control signals to the AT402 should be transmitted over a shielded twisted pair, low capacitance cable. The DMX bus should be daisy chained to all receiving units. It should NOT be connected in a star arrangement with multiple “home runs”.
DMX CABLE CONDUCTOR ARRANGEMENT FOR TWISTED PAIR, SHIELDED CABLE
DMX TERMINATION
A DMX bus should be terminated (only) at the last receiving device on the chain. This is done by connecting a 120 ohm, 1/4 watt resistor across the DMX DATA – and DMX DATA + terminals.
INITIAL SET UP
Set up of the AT Series dimmer is done using the two LED displays and the
three push buttons located at the bottom left corner of the low voltage
section of the circuit board inside of the unit. Use these controls to set the
unit to match the type of input power being applied to the unit.
Set the Input Power Phase for each dimmer channel. This must be set correctly
or dimming will not function properly
Symbol | Function | Value |
---|---|---|
P2 | Ch. 2 Input Phase | A, B, or C |
P3 | Ch. 3 Input Phase | A, B, or C |
P4 | Ch. 4 Input Phase | A, B, or C |
For P2-P4, set to A, B, or C depending on which phase each channel gets its power from. For single phase power set P2, P3, and P4 to “A”.
SINGLE PHASE POWER INSTALLATION
Press the NEXT button repeatedly until P2 appears on the LED display. This tells the unit which phase circuit 2 is getting its power from, hence P2 (phase – Channel 2). Use the UP/DOWN buttons to set the right hand display to “A”. Do the same for P3 and P4 (phase – Channel 3) (phase – Channel 4).
THREE PHASE POWER INSTALLATION
Press the NEXT button until P2 appears on the LED display. Use the UP/DOWN buttons to set the right hand display to “B” or “C”. If the unit does not fade smoothly between preset levels or some of the channels seem to operate in an OFF/ON only fashion, then you should change this setting to the other three phase choice (B or C).
OPERATION
CIRCUIT BREAKERS
AT Series dimmers use a 20 Amp magnetic circuit breaker for each dimming
channel located on the right side of the unit. To operate a channel, the
associated circuit breaker must be closed. Channel numbers for the circuit
breakers are labeled on the unit. If a circuit breaker will not remain closed
then there is an overload for that channel. This MUST be corrected before
operation can continue.
LED INDICATORS
There is a green LED indicator for each channel on the circuit board. These represent the current lighting intensity for the associated channel. The red LED indicator is lit brightly when a DMX signal is present or if the ALL ON feature is active.
DIMMING CURVE
Dimming curves can be set independently for each of the available channels in
an AT series unit. LL= LED (Lutron LED or IN=Incandescent). To set the dimming
curve, press NEXT until you see c1. Use the UP/DOWN buttons to select LL or
IN. Repeat on c2-c4 for each channel.
DMX OPERATION
The DMX channels are set by selecting the start address. The address is set on
two separate menus dH for the hundreds position (0-5, 0 represents any address
lower than 100) and dL for the ten’s and one’s position (0-99). To set the DMX
address press the NEXT button until dH appears on the LED DISPLAY. Set the dH
value to the first digit of the 3 digit address using the UP/DOWN buttons.
Then press the NEXT button again or until you see dL. Set the dL value to the
last two digits of the DMX address using the UP/DOWN buttons.
EXAMPLE: Start address of DMX 509 dH=05 dL=09
Note: When a valid DMX signal is present, the remote switch inputs will
be disabled.
Loss of DMX: If there is a loss of DMX control signal during operation,
the AT Series dimmer will revert back to the last active preset until DMX
operation returns.
MANUAL PRESET OPERATION
GENERAL REMOTE SWITCH OPERATION – A SMALL THEATER EXAMPLE
During theater operation, the lighting is controlled by external momentary
switch closures either manually or by automated equipment. The AT Series
dimmer is designed to activate preset lighting conditions in response to these
controls. A simple scenario is described in the following table. The table is
for an installation where a four channel unit is used. The AT-402 dimmer
channels 1 and 2 are connected to the house lights and AT-402 dimmer channels
3 and 4 are connected to the stage lights.
REMOTE SWITCH CONNECTIONS EXAMPLE
ACTIVITY or PRESET| HOUSE LIGHTING
Channel 1
| HOUSE LIGHTING
Channel 2
| STAGE LIGHTING
Channel 3
| STAGE LIGHTING
Channel 4
---|---|---|---|---
A Opening and Seating| 90% (5 sec. fade)| 90% (5 sec. fade)| 90% (5 sec.
fade)| 90%(5 sec. fade)
B
Introduction
| 50% (15 sec. fade)| 50% (15 sec. fade)| 0% (15 sec. fade)| 0% (15 sec. fade)
C Main Performance| 0% (5 sec. fade)| 0%(5 sec. fade)| 0%| 0%
D Closing| 60% (10 sec. fade)| 60% (10 sec. fade)| 0%| 0%
MANUAL ALL ON / RESUME OPERATION
The “All On / Resume” control may be activated by momentary external switch closure between one of the “Common” terminals and the “All On / Resume” terminal of the circuit board Control Terminal Strip. This function overrides all other switched channel controls and DMX input. It sets all channels to maximum intensity and remains in effect until the button is pushed again. At that time, the unit will “Resume” normal operation (return to the intensity settings provided by the other remote switch control signals).
FULL PROGRAMMING MENU STEPS
The LED’s will alternate between the SYMBOL (channel/preset level and preset fade) and its VALUE (intensity and fade time). There are 2 digits and 3 buttons to control everything. Press the NEXT button to advance through each SYMBOL. Press the UP and DOWN buttons to change the VALUE for the alternately displayed SYMBOL.
INDIVIDUAL CHANNEL PRESET INTENSITY 100% intensity on the LED display is indicated by “FL”.
SYMBOL | FUNCTION | VALUE |
---|---|---|
1A | Channel 1 Preset A intensity | 0-100% intensity |
1b | Channel 1 Preset B intensity | 0-100% intensity |
1C | Channel 1 Preset C intensity | 0-100% intensity |
1d | Channel 1 Preset D intensity | 0-100% intensity |
2A | Channel 2 Preset A intensity | 0-100% intensity |
2b | Channel 2 Preset B intensity | 0-100% intensity |
2C | Channel 2 Preset C intensity | 0-100% intensity |
2d | Channel 2 Preset D intensity | 0-100% intensity |
3A | Channel 3 Preset A intensity | 0-100% intensity |
3b | Channel 3 Preset B intensity | 0-100% intensity |
3C | Channel 3 Preset C intensity | 0-100% intensity |
3d | Channel 3 Preset D intensity | 0-100% intensity |
4A | Channel 4 Preset A intensity | 0-100% intensity |
4b | Channel 4 Preset B intensity | 0-100% intensity |
4C | Channel 4 Preset C intensity | 0-100% intensity |
4d | Channel 4 Preset D intensity | 0-100% intensity |
INDIVIDUAL CHANNEL FADE TIMES. You can STOP HERE, or continue and set the individual CHANNEL up/down fade times. (Applies to all presets).
SYMBOL | FUNCTION | VALUE |
---|---|---|
1┌┘ | Channel 1 Up fade time | 1-99 seconds |
1└┐ | Channel 1 Down fade time | 1-99 seconds |
2┌┘ | Channel 2 Up fade time | 1-99 seconds |
2└┐ | Channel 2 Down fade time | 1-99 seconds |
3┌┘ | Channel 3 Up fade time | 1-99 seconds |
3└┐ | Channel 3 Down fade time | 1-99 seconds |
4┌┘ | Channel 4 Up fade time | 1-99 seconds |
4└┐ | Channel 4 Down fade time | 1-99 seconds |
INDIVIDUAL PRESET UP/DOWN FADE TIMES These settings will over-ride the fade up/down settings in the previous section. If individual preset fade times do not need to be set, then skip these steps. (Decimal indicates 1st option, not seen on AT menu itself).
SYMBOL | FUNCTION | VALUE |
---|---|---|
.A1 | Chan. 1 Preset A up fade time | 1-99 seconds |
A1 | Chan. 1 Preset A down fade time | 1-99 seconds |
.b1 | Chan. 1 Preset B up fade time | 1-99 seconds |
b1 | Chan. 1 Preset B down fade time | 1-99 seconds |
.C1 | Chan. 1 Preset Cup fade time | 1-99 seconds |
C1 | Chan. 1 Preset C down fade time | 1-99 seconds |
.d1 | Chan. 1 Preset D up fade time | 1-99 seconds |
d1 | Chan. 1 Preset D down fade time | 1-99 seconds |
.A2 | Chan. 2 Preset A up fade time | 1-99 seconds |
A2 | Chan. 2 Preset A down fade time | 1-99 seconds |
.b2 | Chan. 2 Preset B up fade time | 1-99 seconds |
b2 | Chan. 2 Preset B down fade time | 1-99 seconds |
.C2 | Chan. 2 Preset Cup fade time | 1-99 seconds |
C2 | Chan. 2 Preset C down fade time | 1-99 seconds |
.d2 | Chan. 2 Preset D up fade time | 1-99 seconds |
d2 | Chan. 2 Preset D down fade time | 1-99 seconds |
.A3 | Chan. 3 Preset A up fade time | 1-99 seconds |
A3 | Chan. 3 Preset A down fade time | 1-99 seconds |
.b3 | Chan. 3 Preset B up fade time | 1-99 seconds |
b3 | Chan. 3 Preset B down fade time | 1-99 seconds |
.C3 | Chan. 3 Preset Cup fade time | 1-99 seconds |
C3 | Chan. 3 Preset C down fade time | 1-99 seconds |
.d3 | Chan. 3 Preset D up fade time | 1-99 seconds |
d3 | Chan. 3 Preset D down fade time | 1-99 seconds |
.A4 | Chan. 4 Preset A up fade time | 1-99 seconds |
A4 | Chan. 4 Preset A down fade time | 1-99 seconds |
.b4 | Chan. 4 Preset B up fade time | 1-99 seconds |
b4 | Chan. 4 Preset B down fade time | 1-99 seconds |
.C4 | Chan. 4 Preset Cup fade time | 1-99 seconds |
C4 | Chan. 4 Preset C down fade time | 1-99 seconds |
.d4 | Chan. 4 Preset D up fade time | 1-99 seconds |
d4 | Chan. 4 Preset D down fade time | 1-99 seconds |
OPERATIONAL SETTING OPTIONS
SYMBOL | FUNCTION | VALUE |
---|---|---|
P2 | Channel 2 Phase | A, B or C |
P3 | Channel 3 Phase | A, B or C |
P4 | Channel 4 Phase | A, B or C |
c1 | Channel 1 Curve | LL or IN* |
c2 | Channel 2 Curve | LL or IN* |
c3 | Channel 3 Curve | LL or IN* |
c4 | Channel 4 Curve | LL or IN* |
dH | Start DMX address – Hundreds | 0-5 |
dL | Start DMX address – Tens/Ones | 0-99 |
- Lutron LED or Incandescent
MODEL NUMBERS AND CONFIGURATION
The table below shows the number of channels for each model number.
An additional suffix may also appear in the model number. This suffix is “/2”
and indicated that the unit is for 230VAC applications.
For one and two channel versions, only the components, indicators, and
connection points for the applicable channels will be present in the unit.
MODEL NUMBER | DESCRIPTION |
---|---|
AT-402 | 4 Channels |
AT-202 | 2 Channels |
AT-102 | 1 Channel |
MAINTENANCE
WARNING!
RISK OF ELECTRICAL SHOCK
There are lethal voltages present in this product when power is applied to its
feed circuits. The cabinet should be opened only by a qualified electrician
WARNING!
RISK OF ELECTRICAL SHOCK
Make sure that all power is removed from feed circuits before changing the
fuse.
The only user servic able part in the AT Series dimmer is the Type ABC, ½ Amp,
250 Volt, fast acting fuse. The fuse may be replaced ONLY with an identical
fuse.
Service by other than the manufacturer’s authorized agents may void your
warranty. If service is required, contact the dealer from whom you purchased
the dimmer, or Lightronics, Service Department, 509 Central Drive, Virginia
Beach, VA 23454. Tel: 757 486 3588.
The best way to prolong the life of your unit is to keep it cool, clean, and
dry. It is important that the cooling intake and exit vent holes are clean and
unobstructed.
Lightronics recommends that you record the serial number of your AT402 for
future reference.
WARRANTY INFORMATION AND REGISTRATION – CLICK LINK BELOW
www.lightronics.com/warranty.html
www.lightronics.com
Lightronics Inc.
509 Central Drive, Virginia Beach, VA 23454 tel 757 486 3588
References
- Lightronics - Complete Lighting and Control Systems
- Lightronics Lighting Control Product Warranty Information
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>