frigicoll FRIAHUKZ-LCAC-02 Inverter Condensing Unit Control Module Owner’s Manual

June 12, 2024
frigicoll

**frigicoll FRIAHUKZ-LCAC-02 Inverter Condensing Unit Control Module Owner’s Manual

**

IMPORTANT NOTE:
Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference

Introduction

FRIAHUKZ-LCAC-02 control module enables to control inverter type outdoor unit without the needs of airconditioner factory produced indoor unit. It gives possibility to control outdoor unit capacity and state to produce heat or cooling for AHU or water heater/cooler.

FRIAHUKZ-LCAC-02 control module enables to control inverter condensing unit capacity between 0 – 10%~100% by external input 0~10VDC signal.

Dry contact signal is used to control outdoor unit to work in cooling or heating mode.

The installation and operation of outdoor unit as well controller must be done according to the manuals (i.e. User’s manual, Installation manual, Technical Specification, Service Manual).

Specification and packing list

Model FRIAHUKZ-LCAC-02
Casing Plastic
Dimension (h x w x d) 61 x100 x191mm
Weight 0.4KG
Operation Temperature Range -25 ~ +45 C
Operation Humidity Range 40-90 %
Power Supply 230VAC, 1 Phase, 50/60Hz
Voltage Range 208-240V
Fuse 15A, 250V
Resistance class IP54
**** Packing list Box body
Box cover 1 piece
Anti-water seal between box body and box cover 1 piece
Temp sensor 1 piece
Gland 3 pieces
Manual 1 piece

System design

System Design

Function and Setting

Function and Setting

Connection Terminal Introduction

L, N, S —Power Supply and communication with outdoor unit 230V,1-phase, 50Hz. Cable dimension 3×1.0 mm2.

ALARM —digital output 5A-250VAC or 5A-30VDC. When outdoor unit has malfunction signal is activated.

DEFROST— digital output 5A-250VAC or 5A-30VDC. When outdoor unit is in defrost mode is activated.

TEMP1— T2 temp sensor (evaporator coil temperature sensor) terminal. Temp sensor must be placed at middle of heat changer.

0-10V —Analog input terminal to control outdoor unit capacity.

Analog input Capacity output LED display
0-0.5V 0% None(Unit stopped)
0.5-1.5V 10% digit 1
1.5-2.5V 20% digit 2
2.5-3.5V 30% digit 3
3.5-4.5V 40% digit 4
4.5-5.5V 50% digit 5
5.5-6.5V 60% digit 6
6.5-7.5V 70% digit 7
7.5-8.5V 80% digit 8
8.5-9.5V 90% digit 9
9.5-10.5V 100% digit 10

Warning:
Negative(0/-) and Positive(10/+) terminals can not be mixed, otherwise it may destroy this control module. Signal input can not exceed 10.5VDC, otherwise it may destroy this control module.

COOL— Digital input. When terminals are closed, the unit will run in cooling mode and “COOL” LED will be on. Terminal A is Positive(+) and terminal B is Negative(-)
COOL

HEAT —Digital input. When terminals are closed, the unit will run in heating mode and “HEAT” LED will be on. Terminal C is Positive(+) and terminal D is Negative(-)

Note: Terminal B and D are connected as one Negative(-), so 3 cables to control cooling/heating are feasible.

ENC1 – knob for multi split connection to select indoor unit capacity. This knob is for multi indoor units connection only. This knob will not work at one indoor to one outdoor connection.

Knob selection| Indoor unit capacity| Knob selection| Indoor unit capacity
---|---|---|---
0| 2,0 kW unit| 6| 7,1 kW unit
1| 2,6 kW unit| 7| 9,0 kW unit
2| 3,2kW unit| 8| 10,5 kW unit
3| 3,5 kW unit| 9| 14,0 kW unit
4| 5,3 kW unit| A-F| 16,0 kW unit
5| 7,1 kW unit| |

LED lamps introduction

HEAT LED is lightened when the unit is operating in heating mode.

COOL LED is lightened when the unit is operating in cooling mode.

DEF LED is lightened when unit is in defrost mode

Malfunction and Error Code

Error Code Malfunction or Protection
E1 communication error with outdoor unit.
E5 evaporator coil temperature sensor T2 malfunction
F0 current overload protection
F1 outdoor unit ambient temperature sensor T4 malfunction
F2 outdoor unit condenser pipe temperature sensor T3 malfunction
F3 outdoor unit compressor discharge temperature sensor TP malfunction
F4 outdoor unit EEPROM parameter error
F5 outdoor unit fan speed is operating outside of the normal range
F6 outdoor unit T2b temperature sensor malfunction
P0 IPM malfunction or IGBT over-strong current protection
P1 over voltage or over low voltage protection
P2 top temperature protection of compressor
P3 outdoor low temperature protection
P4 compressor protection or malfunction
multi split indoor units cooling/heating mode conflict
P6 low pressure protection of compressor

For troubleshooting, please refer to outdoor unit factory technical manual and solution.

Dimensions (mm)

Dimensions

Appendix 1 Temperature Sensor Resistance Value Table (°C–K)

°C| K Ohm| °C| K Ohm| °C| K Ohm| ° C| K Ohm
---|---|---|---|---|---|---|---
-20| 115.266| 20| 12.6431| 60| 2.35774| 100| 0.62973
-19| 108.146| 21| 12.0561| 61| 2.27249| 101| 0.61148
-18| 101.517| 22| 11.5000| 62| 2.19073| 102| 0.59386
-17| 96.3423| 23| 10.9731| 63| 2.11241| 103| 0.57683
-16| 89.5865| 24| 10.4736| 64| 2.03732| 104| 0.56038
-15| 84.2190| 25| 10.000| 65| 1.96532| 105| 0.54448
-14| 79.3110| 26| 9.55074| 66| 1.89627| 106| 0.52912
-13| 74.5360| 27| 9.12445| 67| 1.83003| 107| 0.51426
-12| 70.1698| 28| 8.71983| 68| 1.76647| 108| 0.49989
-11| 66.0898| 29| 8.33566| 69| 1.70547| 109| 0.48600
-10| 62.2756| 30| 7.97078| 70| 1.64691| 110| 0.47256
-9| 58.7079| 31| 7.62411| 71| 1.59068| 111| 0.45957
-8| 56.3694| 32| 7.29464| 72| 1.53668| 112| 0.44699
-7| 52.2438| 33| 6.98142| 73| 1.48481| 113| 0.43482
-6| 49.3161| 34| 6.68355| 74| 1.43498| 114| 0.42304
-5| 46.5725| 35| 6.40021| 75| 1.38703| 115| 0.41164
-4| 44.0000| 36| 6.13059| 76| 1.34105| 116| 0.40060
-3| 41.5878| 37| 5.87359| 77| 1.29078| 117| 0.38991
-2| 39.8239| 38| 5.62961| 78| 1.25423| 118| 0.37956
-1| 37.1988| 39| 5.39689| 79| 1.21330| 119| 0.36954
0| 35.2024| 40| 5.17519| 80| 1.17393| 120| 0.35982
1| 33.3269| 41| 4.96392| 81| 1.13604| 121| 0.35042
2| 31.5635| 42| 4.76253| 82| 1.09958| 122| 0.3413
3| 29.9058| 43| 4.57050| 83| 1.06448| 123| 0.33246
4| 28.3459| 44| 4.38736| 84| 1.03069| 124| 0.32390
5| 26.8778| 45| 4.21263| 85| 0.99815| 125| 0.31559
6| 25.4954| 46| 4.04589| 86| 0.96681| 126| 0.30754
7| 24.1932| 47| 3.88673| 87| 0.93662| 127| 0.29974
8| 22.5662| 48| 3.73476| 88| 0.90753| 128| 0.29216
9| 21.8094| 49| 3.58962| 89| 0.87950| 129| 0.28482
10| 20.7184| 50| 3.45097| 90| 0.85248| 130| 0.27770
11| 19.6891| 51| 3.31847| 91| 0.82643| 131| 0.27078
12| 18.7177| 52| 3.19183| 92| 0.80132| 132| 0.26408
13| 17.8005| 53| 3.07075| 93| 0.77709| 133| 0.25757
14| 16.9341| 54| 2.95896| 94| 0.75373| 134| 0.25125
15| 16.1156| 55| 2.84421| 95| 0.73119| 135| 0.24512
16| 15.3418| 56| 2.73823| 96| 0.70944| 136| 0.23916
17| 14.6181| 57| 2.63682| 97| 0.68844| 137| 0.23338
18| 13.9180| 58| 2.53973| 98| 0.66818| 138| 0.22776
19| 13.2631| 59| 2.44677| 99| 0.64862| 139| 0.22231

Oficina Central Blasco
de Garay, 4-6 08960
Sant Just Desvern
Barcelona Tel: +34 93 480 33 22
http://www.frigicoll.es
Frigicoll France SARL
Parc Silic-Immeuble Panama 45 rue de Villeneuve 94150 Rungis
Tel. +33 9 80 80 15 14
http://www.frigicoll.es/fr

frigicoll Logo

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals