HK INSTRUMENTS DPT-2W 2-Wire Differential Pressure Transmitter User Guide
- June 12, 2024
- HK INSTRUMENTS
Table of Contents
DPT-2W 2-Wire Differential Pressure Transmitter
User Guide
Introduction
Thank you for choosing an HK Instruments DPT series differential pressure
transmitter. The DPT series is intended for use in commercial environments.
The DPT-2W series differential pressure transmitter provides a 4…20 mA loop
output.
All DPT-2W differential pressure transmitters are available with display.
1.1 About this user guide
This user guide contains important information about the installation, wiring,
configuration and use of the product.
Read this guide carefully before you install the product, connect the wires,
or operate the product. Make sure that you fully understand all instructions
before you start work. If you are not sure what the instructions mean, contact
the seller or the manufacturer.
Follow all instructions in this user guide carefully. Always obey the
applicable local rules and regulations.
The original instructions were written in English. If there are differences
between the English instructions and the translations, refer to the English
instructions.
If you find a mistake in the English instructions or in the translations,
please send the details to the manufacturer.
1.2 Intended use
The DPT-2W differential pressure transmitter is intended to be used to
measure differential pressure in ventilation ducts.
These transmitters are intended to be connected to building automation systems
in the HVAC/R industry.
1.3 Applications
DPT-2W devices are commonly used in HVAC/R systems for:
- fan, blower and filter monitoring
- pressure and flow monitoring
- valve and damper control
- pressure monitoring in cleanrooms
Description of the product
This section introduces the main parts of the product and contains the
technical specifications.
2.1 Overview of the main parts
A Display connectors
B Zeroing button
C Indicator light
D Pressure range selection jumpers
E Pressure sensor
F Wiring terminal
2.2 Technical specifications
Property | Value |
---|---|
Supply | 10…35 Vdc |
Pressure measurement ranges | |
-250 models | ±25 /±50 /±100 /±150 / 0…25 / 0…50 / 0…100 PO…250 Pa |
-2500 models | ±100 / 0…100 / 0…250 / 0…500 / 0…1000 / 0…1500 / 0…2000 / *0…2500 Pa |
-7000 models | 0…750 / 0…1000 / 0…1250 / 0…2250 / 0…2500 / 0…3750 / 0…5000 / *0…7000 Pa |
Accuracy (temperature compensated) | ±1.5 % + 2 Pa from value |
Overpressure | |
Proof pressure | 25 kPa |
Burst pressure | 30 kPa |
Long term stability | |
-250 and -2500 models | typ. -8…8 Pa / year |
-7000 models | typ. -22…22 Pa / year |
Response time | *0.8 s / 4 s |
Zeroing | Manually by push button |
Sensor | MEMS, no flow-through |
Output | |
Signal | 4…20 mA, >20 C) |
Accuracy | typ. ±0.04 mA at 25 °C, load 100 0 |
Display (-D models) | 3 1/2 digit display |
Operating conditions |
Property
Temperature| Value
-10…50 °C
---|---
Humidity| 0…95 %rH (non-condensing)
Wire| 0.2…1.5 mm2 (24…16 AWG)
Housing|
Materials| ABS and PC plastic
Protection class| IP54
Cable gland| M16
Mounting| 2 x 04.3 mm screw holes, one slotted
Dimensions (w x h x d)| 90 x 95 x 36 mm
Weight| 150 g
Storage temperature| -40…70 °C
Conformance| CE UKCA
EMC| 2014/30/EU S.I. 2016 No. 1091
RoHS| 2011/65/EU S.I. 2012 No. 3032
WEEE| 2012/19/EU S.I. 2013 No. 3113
| * factory setting
2.3 Dimensions
Safety precautions
The product is developed, manufactured and tested according to high quality
standards. However, instructions for safe use shall be taken account when
installing, using or disposing the product or parts of product.
Read this user guide carefully before commissioning, using or servicing this
device. To avoid any kind of damage to people or property, follow the
instructions carefully. HK Instruments is not liable for any hazards or
damages to people or property which are caused by ignoring the using or
installation instructions.
To avoid electrical shock or damage to equipment, disconnect power before
installing or servicing the product. Use only a proper wiring rated for the
full operating voltage and maximum current in the system even in the event of
a fault.
To avoid potential fire and/or explosion, do not use the product in
potentially flammable or explosive atmosphere. The product condition must be
checked before installation. Do not drop the product or use excessive force
during installation. Do not use the product if any damages are visible.
After installation the product will be part of a system whose specifications
and performance characteristics are not designed or controlled by HK
Instruments. Refer to national and local authorities to ensure that the
installation is functional and safe.
The product should only be used in professionally designed applications.
Unauthorized modifications are not allowed. The product must not be used in
relation with any equipment that in case of a failure may threaten, directly
or indirectly, human health or life or result in danger to human beings,
animals or property. In this document, there are different kind of warnings
and notes. The warning and note types are defined in the following table.
Sign | Description |
---|---|
WARNING: | The warning symbol indicates a potentially hazardous |
situation which, if not avoided, could result in death or serious injury.
CAUTION:| The caution symbol indicates a potentially hazardous situation
which, if not avoided, could result in minor or moderate injury.
Important:| The important symbol indicates a potentially hazardous
situation which, if not avoided, could result in damage to the device or
property.
Note:| The note symbol indicates a useful tip or a recommended way to
complete a task. These notes also provide information that is useful but not
critical to the user.
Commissioning
4.1 Mounting the product
WARNING: Handle the product with care. Dropping the product may cause
internal damage and unwanted functions in the connected system.
- Check that the product is not damaged during transportation.
- Select the mounting location.
CAUTION: Place the product outside the reach of children and animals.
Important: The product may only be installed in a location where the ambient conditions meet the operating condition requirements.
Operating conditions
Temperature | -20…50 °C |
---|---|
Humidity | 0…95 %rH (non condensing) |
-
Mount the product on flat surface using the mounting points.
A. Mounting point
Mounting orientation:
Select the mounting screws according to the mounting surface. The maximum screw diameter is 4.3 mm.
Important: Don’t use excessive force when tightening the mounting screws. -
Install the measuring hoses carefully so that the hoses don’t bend too tightly. Too tight curves may prevent the air flow to the sensor.
4.2 Measuring range selection
Settings for -250 models
4.3 Selecting response time
The response time affects how fast the transmitter reacts to changes in the
system. The response time is the time the device takes to reach 63 % of the
measured value. To smooth out unstable pressure fluctuations in applications,
select a longer response time.
- Open the cover.
- Press the zeroing button briefly. The indicator light and display (-D models) indicate the selected response time.
Indicator light| Display| Response time
---|---|---
Three short flashes| 0.8| 0.8 seconds
Two long flashes| 4| 4 seconds - Close the cover.
4.4 Wiring
4-20 mA | 10…35 Vdc | **** Wiring polarity is free. |
---|
4-20 mA
The possible zero point drifting can be eliminated by using the zeroing button
on the circuit board.
Note: Supply voltage must have been connected for one hour prior the
zeroing.
- Disconnect both pressure measurement hoses.
- Push the zeroing button until the indicator light turns on. The indicator light turns on approximately after 4 seconds.
- Release the zeroing button. Zeroing starts and the indicator turns off. The zeroing is complete when the indicator light flashes two times.
- Connect the pressure measurement hoses.
Disposal
The device is considered as electrical and electronic equipment for disposal in terms of the applicable European Directive. At the end of life the product must enter the recycling system at an appropriate collection point.
- The device must be disposed through channels provided for this purpose.
- The disposal must be completed according to the local and currently applicable laws and regulations.
Generally all metals can be recycled as material. Plastics and cardboard packaging material can be used in energy recovery. Printed circuit boards need selective treatment according to IEC 62635 guidelines. To aid recycling, plastic parts are marked with an appropriate identification code. Contact your local HK Instruments distributor for further information on environmental aspects and recycling instructions for professional recyclers.
Warranty policy
The seller is obligated to provide a warranty of five years for the delivered goods regarding material and manufacturing. The warranty period is considered to start on the delivery date of the product. If a defect in raw materials or a production flaw is found, the seller is obligated, when the product is sent to the seller without delay or before expiration of the warranty, to amend the mistake at his/her discretion either by repairing the defective product or by delivering free of charge to the buyer a new flawless product and sending it to the buyer. Delivery costs for the repair under warranty will be paid by the buyer and the return costs by the seller. The warranty does not comprise damages caused by accident, lightning, flood or other natural phenomenon, normal wear and tear, improper or careless handling, abnormal use, overloading, improper storage, incorrect care or reconstruction, or changes and installation work not done by the seller. The selection of materials for devices prone to corrosion is the buyer’s responsibility, unless otherwise is legally agreed upon. Should the manufacturer alter the structure of the device, the seller is not obligated to make comparable changes to devices already purchased. Appealing for warranty requires that the buyer has correctly fulfilled his/her duties arisen from the delivery and stated in the contract. The seller will give a new warranty for goods that have been replaced or repaired within the warranty, however only to the expiration of the original product’s warranty time. The warranty includes the repair of a defective part or device, or if needed, a new part or device, but not installation or exchange costs. Under no circumstance is the seller liable for damages compensation for indirect damage.
Copyright HK Instruments 2023
www.hkinstruments.fi
User guide Version 1.0 2023
Information is subject to change without prior notice.