ENTRON EN6001 Microprocessor Based Weld Sequence Controls Instruction Manual
- June 10, 2024
- ENTRON
Table of Contents
TRANSGUN APPLICATION NOTE
700252A
UPDATED 12/13/22
EN6001 SERIES CONTROLS
MICROPROCESSOR BASED
Weld Sequence Controls
With
Solid State Thyristor Contactors
Wiring Diagram 421533-001 “D” Cabinet
Intended for use with firmware version 8.04 and higher
ENTRON Controls, LLC.
1402 S. Batesville Road
Greer, South Carolina 29650
864-416-0190
FAX: 864-416-0195
www.entroncontrols.com
GF GROUND FAULT OPTION (HAND-HELD TRANSGUN)
The design of the optional GF (Ground Fault) circuit is meant to fulfill the
recommended requirements of RWMA’s Bulletin 5-015.68.04 (Figure 2.1) and AWS
J1.1. (Figure 2.2) The recommended standard is typically called out to protect
operators in hand-held transgun applications.
To understand the operation in more detail, see Wiring Diagram 421533-001 and
the Weldsafe 5000 manual in Appendix A. Since CR1 (Weldsafe 5000) operation is
discussed in Appendix A, its design will not be discussed further. The GF
option monitors specifically the transformer load and the ground connection to
it.
GROUND FAULT DETAILS
Weld transformer primary wires are passed through T5 (transformer/coil).
Current will be summed by T5 and the difference sent to CR1. CR1 will monitor
this current and will close a contact at the RWMA specification of 15 mA.
These contacts pass 120 VAC, developed on the primary of PS1 (power supply 1),
to the ST (shunt trip) on CB1 (circuit breaker 1). When the voltage is
applied, the contacts of the breaker will open. Timing of this action will be
within the RWMA recommendation of 60 ms.
A push-to-test circuit is composed of SW2 (push button switch 2) and R80 (10k
resistor). When SW2 is closed, a current is developed from the primary voltage
windings (120 VAC) of PS1, through R80 (approximately 20 mA), and is passed
through T5.
GROUND DETECTOR
It is important that the control and gun be well grounded in the case of a
high current fault to ground. This low impedance will allow properly designed
upstream breakers to open before the voltage on the gun gets over 48 VAC. To
insure a low resistance connection between the gun and control, CR1 (Weldsafe
5000) monitors the connection between the gun case and control ground via
R82-2. The detect wire is routed from the gun case through the transgun cable
to R82-2. From there, the signal is passed through SW4 and on to CR1. SW 4 is
a push-to-test switch for the GND detection circuit. When pressed, R82 (1 ohm
resistor) is inserted in series with this detect lead to perform the push-
totest feature.
When the CR1 measures 1 ohm or greater in the ground path, a separate set of
contacts in CR1 relay will close. These contacts are in parallel with the EL
and GF contacts and will pass 120 VAC from the primary windings of the Valve
transformer to the ST of the CB1 and remove voltage to the control within 60
ms.
RESISTANCE WELDER MANUFACTURERS’ ASSOCIATION OCT. 1995
BULLETIN 5-015
SAFETY STANDARDS FOR CONSTRUCTION AND
GUIDE FOR INSTALLATION AND OPERATION
BUL 5-015.68 GROUNDED CIRCUITS AND EQUIPMENT GROUNDING
.04 Special considerations for Portable Transguns (a) Portable Transguns
shall be grounded per Article 250 of the National Electrical Code and require
the use of (1),(2) and (3) listed below:
NOTE– Conduit or Raceways shall not be used as the grounding conductor.
NOTE– The intention of these requirements is to ensure that the grounding
conductor to the transgun is sized correctly to allow sufficient ground fault
current to flow for a time long enough to trip an upstream circuit breaker or
other protection device. As a general guideline, the resistance of a grounding
conductor should be maintained at a value to ensure the continuous and
unrestricted flow of available ground fault short circuit current until the
circuit protection device removes voltage from the equipment.
(1) Grounding Integrity The welding gun transformer case and secondary shall be grounded and protected by fail safe circuitry designed to immediately disconnect line voltage from the transgun via a circuit breaker with shunt trip or a circuit breaker with under voltage trip. The combined clearing time shall not exceed 60 mS. A sensed value of grounding conductor resistance in excess of one ohm by the ground integrity monitor would be considered an inadequate ground [referred to in paragraph 5-015.68.04(a)(2)]. A pushto-test circuit providing a 1 ohm resistance between the sense lead and ground will be included to verify the operation of the ground integrity circuit.
NOTE– The ground integrity monitor operation shall not depend on a
programmable device.
(2) Ground Fault Current Relay A sensitive, fail safe, ground fault relay
with a maximum trip point of 15mA must be used to provide protection against
differential ground fault leakage currents. The ground fault relay must
immediately disconnect line voltage from the Portable Transgun via a circuit
breaker with shunt trip or a circuit breaker with under voltage trip. The
combined clearing time shall not exceed 60 mS. A push-to-test circuit
supplying a test fault current, through the sense coil of 20mA maximum will be
included to verify the operation of the ground fault relay. Only three wires
are allowed to pass through the ground fault relay current pickup transformer:
two welding transformer primary conductors and the push-to-test circuit.
NOTE– The ground fault current relay operation shall not depend on a
programmable device.
NOTE– If an Isolation Contactor is used, ground fault current will only be
detected when this Isolation Contactor is closed.
NOTE– In (1) and (2) above, combined clearing time is the reaction time of
the ground fault relay plus the clearing time of the shunt trip or under
voltage trip of circuit breaker.
(3) Ground shielded cable The weld transformer primary cable conductors
between the weld control and the Portable Transgun must be surrounded by
grounded shield. This shield must be tied to an appropriate ground lug at the
control. In addition to the two primary conductors, ground conductor and
shield, a ground sense wire must be included with the cable.
NOTE– The grounded shield provides a current path should a metallic component
cut through the shield to a power conductor within the cable. This current
path will then cause the ground fault current relay to trip.
Reproduced from RWMA Bulletin 5 Resistance Welding Control Standards,
October 1995.
Figure 2.1 RWMA recommended standards for grounded circuits
ENTRON Controls, LLC. · 700752A · Page 3
AWS J1.1M/J1.1:2013 Specification for Resistance Welding Controls
ANSI STANDARD
Manual Transgun Control
This control system employs additional devices necessary to ensure safe
operation of manual transguns. Since the operating (line) voltage and ground
wires connect to the transgun by means of a flexible power cable, supplemental
systems within the welding control monitor the system for ground faults and
ground circuit integrity. These supplemental systems provide an added level of
operator protection in the event the ground connection is lost or there is an
electrical current leakage to ground. Such faults could indicate a component
of the transgun is no longer adequately grounded or perhaps has become
dangerously energized. A manual transgun control shall incorporate
supplemental safety devices including a ground integrity monitor, ground fault
detector, and a grounded-shield power cable.
Ground Integrity Monitor
A ground integrity monitor shall be provided in the manual transgun control
system. This monitor senses the value of ground circuit resistance to identify
conditions where there may be an inadequate bonding connection between the
welding control and the transgun. In the event a fault is detected, the
electrical supply shall be disconnected from the transgun in accordance with
the performance specified in clause 7.9.1. A pushto-test circuit shall be
included to enable verification of the ground integrity monitor operation.
Ground Fault Monitor
A sensitive, fail-safe, ground fault monitor shall be provided in the manual
transgun control system. The earth-leakage detector, the most commonly applied
system, uses a current coil surrounding supply and return conductors to detect
differential current indicative of an undesired active path. In the event a
fault is detected, the electrical supply shall be disconnected from the
transgun in accordance with the performance specified in clause 7.9.2. The
disconnecting means employed in 4.2.4.1 above also functions in this case. A
push-to-test circuit supplying a test fault current, through the sense coil
will be included to verify the operations of the ground fault monitor.
Grounded-Shield Power Cable
The weld transformer primary cable conductors between the weld control and the
manual transgun shall be surrounded by a grounded conductive shield. This
shield will provide a current path to ground within the cable should it be
penetrated with something conductive. This shield shall be tied to an
appropriate ground lug at the control. In addition to the two primary
conductors, ground conductor and shield, a ground sense wire must be included
within the cable to facilitate verification of the bonding connection between
the resistance welding control and transformer.
Reproduced from AWS J1.1M/J1.1:2013 Specification for Resistance Welding
Controls
Figure 2.2. AWS WELD CONTROL STANDARD
WELDSAFE 5000
combination ground fault sensing and ground checking relay for AC 50-60 Hz
applications manual transgene applications
Features
- 10mA trip point setting for ground fault sensing
- C.T. loop monitoring
- 1 ohm single trip point for ground checking
- Voltage Build-up Detection
- Optional End-of-Line Resistor for crush fault detection
- Harmonic filtering
The WedSafe 5000 combination ground fault curtain and ground check relay bas been deigned to provide sensitive ground fault protection and continuous ground checking for ac, 50-60 Hz manual transgenes in accordance with RWMA Bulletin 5 standards.
Ground Fault Sensing Operation
The WedSafe 5000 protects operators and equipment from dangerous leakage currents that may occur when a circuit is energizcd. The device has harmonic filtering to prevent nuisance tripping and a pick-up response time of < 25ms.
Ground Fault Protection
The Weld sate 5000 ground fault function has two ground fault settings which
will typically correspond to the size of the manual transgene. Setting 1 is
the factory setting. This setting should always be used whenever practicable.
Generally, Setting | will work for transgenes smaller than 100 KVA. For manual
guns larger than 100 KVA or with very high amperages (~40,000A), Setting 2 can
be selected. All settings meet or exceed current RWMA recommendations. To
determine which setting 1s correct, consult with your service operator.
C.T. Loop Monitoring
The WedSafe 5000 also continuously monitors the connection to the current
transformer to ensure proper functioning of the ground fault sensing. If this
connection is broken, the unit will immediately operate.
C T600/…/WKE Series Current Transformers
The ground fault protection function of the Weldsafe 5000 operates together
with a CT600 series current transformer. There are different sizes available
ranging from 1” to 5 1/8” depending upon the size of the load conductors
passing through window.
The C.T. is connected across terminals 16 and 17. Only the load carrying
conductors pass through the C.T.. The ground wire must remain outside the C.T.
core. It is also important that the cables passing through the C.T. be as
straight as possible (see diagram) to minimize the possibility of core
saturation.
CT600/60/2 for High Current Applications
In applications where very high current is present, as in the case of a
very large hand-held welding gun (>1 OOK VA, 40,000A), this high current may
influence the operation of the CT and cause nuisance tripping. The mounting
and location of the CT within the control panel is very important. In order to
get optimum results from the CT, it 1s recommended that the CT be mounted on
the output side. This reduces the influence of any internal leakage caused by
components in the welding control. For systems above 100 KVA, it is advisable
to use either coaxial cable or order the CT600/60/2. This CT has been
specifically designed with a 6″ metal core insert and provides the same
shielding from the high current as the coaxial cable.
Ground Checking Operation
The Weldsafe 5000 has several protective methods to ensure proper grounding
of fixed or portable equipment. If the unit senses any one of the following
conditions, it activates the alarm relay (K2).
Pilot Wire Ground Integrity Check
The Weldsafe 5000 monitors the resistance of the return path to ground via
a ground connection from terminal 30 and a standard loop pilot wire going to
the equipment from terminal 27. The unit continuously sends a measuring signal
around the ground loop circuit. This circuit comprises the main equipment
grounding conductor, a section of the equipment casing and a pilot conductor
return path. When the Weldsafe 5000 detects a loop resistance in excess of 1
Q, it will activate the output alarm relay (K2). The response time will vary
depending upon the actual loop resistance value. The Weldsafe will react in <
30 ms for values approaching “open circuit” (see table 1).
Earth Voltage Build-up
The Weldsate 5000 can also detect large ground fault currents that may
cause unsafe voltage build-up on the ground path. If the unit senses a voltage
30 V ac on the ground path, it will immediately react to this condition.
Optional End-of-Line Resistor (EOL)
The Weldsafe 5000 ground-checking operation has an additional protection
feature. The unit can detect crush or parallel faults.
This situation occurs when the cable ground wire becomes unintentionally
connected to the equipment pilot wire. To sense this fault, a grounding
resistor 1s connected at the end of the pilot wire from terminal 29. In this
configuration, the Weldsafe 5000 will alarm if the ground wire ever comes into
contact with the equipment pilot wire. This grounding resistor must have a
value of 49.9 ohms with a high tolerance of |/- 0.1% to ensure proper function
of the Weldsafe 5000. Circuit Savers can supply this resistor on request.
Please note: this end-of-line (EOL) will not affect the operation of the earth
voltage build-up function.
Technical Information
Mounting and Wiring
The Weldsafe 5000 can be either DIN rail-mounted (35mm) or screw-mounted by
the 2 holes at the corners of the device. Terminals are clearly marked for
connection.
Input Power Supply
The Weldsafe 5000 requires an auxiliary power supply of either 24Vdc,
24Vac, 120Vac or 230Vac 50-60 Hz. Customer must specify.
Trip/Alarm Output Relays
Two sets of changeover trip/alarm contacts (one for ground fault, one for
ground check) are provided rated at 250 V, 5 A. These two relays can be set
for tripping or remote indication. They can be configured for either failsafe
or active operation, manual or auto reset. Factory settings are Failsafe and
Auto Reset. To adjust relay for Failsafe/Active operation for either ground
fault or ground check, open front cover. There is a small blue button in the
left and nght lower areas. The switch on the left changes the ground fault,
the one on the right changes the ground check. For Hand reset close contacts
between 18-19, open for Auto.
LEDs
In addition to the trip relays there are six LED indicators on the front
cover. The green LED indicates POWER ON. There are two red LEDs for the ground
fault function:
- “GF” indicates leakage in excess of present trip level
- “C.T.” indicates C.T. connection broken
- There are three T.EDs indicating different conditions on the ground check function
- “10” indicates ground loop resistance in excess of 1 ohm
- “Link” indicates ground wire connected to pilot wire
-
V” indicates voltage build-up in excess of 30 V AC
Test/Reset
The test facilities on the Weldsafe SQ0O may be operated locally or remotely.
They test both the ground fault sensing and the ground checking circuits. The
test button, $1] is used to simulate a ground fault condition internally as a
means of testing the relay function. An external test button can also be used
to perform the same function test.
CT600 Current Transformers
CT600/25/WKE
CT600/60/WKE
CT600/95/WKE
CT600/130/WKE
CT600/60/2| REET ES
1” mitermal diameter
2 1/3” internal diameter
3 3/4” internal diameter
5 1/8” internal diameter
2 1/3″ internal diameter for high current applications, 6″ metal insert
---|---
Power Supply
Voltage
Us| Order
Number
---|---
DC:24V| 17007031
AC24V| 17007041
AC120V| 17007051
Technical Data
Nominal AC insulation voltage | 500 V ac |
---|---|
Insulation group to UL 1053 and VDE 011 0(01.83) | Dirty group 2 |
Test voltage | 3000 V ac |
Operation Class | Continuous |
Input supply voltage | 24V ac, 24V de, 120V ac, 230V ac 50-60Hz |
working range | +/-15% |
Maximum self-consumption | 10 VA |
Alarm relay contacts | Volt-free NO/NC |
Switching capacity | 1100VA |
Rated contact voltage | 250V |
Continuous CUITEN | 5A |
Breaking capacity At: 240V ac, P.F.=O.4 | 3A |
At: 110V do, @L/R=0 | 0.3A |
Adjustable function | Failsafe/Active |
Relay alarm memory | Manual/Auto reset |
Factory Settings | Failsafe/Auto |
Operating ambient temperature | 10° to +60° C |
Storage ambient temperature | 40% to +70° C |
Mounting
Terminal | M 2.5 |
---|---|
Terminal capacity | O.5 to 4 mm2 |
Weight | 575 g |
Dimension | 2.96″ X 3,.94″W x 4.33 |
Ground fault function
Trip level
Setting 1| factory setting
---|---
S8 closed| 10 mA, +0%/-15%, ac 50-60 Hz
Response time| 20 -25 ms Response time
Setting 2
SS OPEN| 10 MA, +O%/-15%, ac 50-60 Hz
Response time to current| inverse time curve
see below
Current transformer| CT600/…/WKE or CT600/60/2
SIZES| l”—5 1/8” internal diameter
Ground check function
Loop resistance measuring current | DC 20 mA |
---|---|
Trip Level | 1Ω, +/- 15% |
Stray voltage (terminals 30-27 or 30-29) | Max. 300 V ac (<5 sec) |
Response time 0.5Ω. – Open circuit | < 30 ms |
response time curve | see table 1 |
Hysteresis | Approx. 2% |
Voltage response | >30 V ac |
Industry Standards | RWMA 5-015.68.04 |
Weldsafe 5000 Ground Fault Setting 2 reaction time
Response Time for Ground Loop value change 0.5Ω to RΩ
4.5 Ω – 2Ω| =1.8 s
0.5 Ω- 5Ω| =1.8 s
0.5 Ω- 8Ω| =1.8 s
0.5 Ω- 10 Ω| =1.8 s
0.5 Ω- 20 Ω| = 310 ms
0.5 Ω- 50 Ω| = 100 ms
0.5 Ω- 100 Ω| = 60 ms
0.5 Ω- 200 Ω| = 42 ms
0.5 Ω- Open| – 21 ms
Table 1
WELDSAFE 5000
combination ground fault sensing and ground checking relay for AC 50-60 Hz
applications manual transgene applications
Connection Diagram E699001-2
Legend
Hl LED green POWER ON
H2 LED red GROUND FAULT
H3 LED red CT FAULT
H4 LED red LOOP RESISTANCE > 1Q
H5 LED red CRUSH FAULT
H6 LED red VOLTAGE BUILD-UP
K1Ground fault alarm relay
K2 Ground check alarm relay
S1 Internal test button
S2 Internal reset button
S3 Switch for ground fault Failsafe/Active (behind front cover) Closed=active
Open=failsafe
S4 Switch for ground check Failsafe/Active (behind front cover) Closed=active
Open=failsafe
S5 External test button
S6 External reset button for ground fault sensing
S7 Extremal reset button for ground checking
S8 Trip level adjustment (behind front cover) Closed = 10 mA fixed = factory
setting Open = 10 mA inverse response
**R1 Loop resistance adjustment – see instructions
**R1 Loop Resistance Adjustment
This is an internal adjustment that must made when cable length is very long
and the loop resistance is high (0.5..0.8Ω). Please check with manufacturer
about your specific application.
PLEASE NOTE:
TO CHECK UNIT FUNCTION DURING COMMISSIONING, WE RECOMMEND TESTING THE
WELDSAFE 5000 UN.
DER TRUE FAULT CONDITIONS. FOR TIE GROUND FAULT FUNCTION, A SMALL RESISTOR.
(e.g. 30 KΩ AT 480V WILL GENERATB APPROX 16 mA) CAN BE USED TO CREATE THIS
CONDITION, FOR THE GROUND CHECKING FUNCTION, OPEN THE PI- LOT WIRE.
Terminals
2-3 Input power supply
8-9-10 Contact for K1 alarm relay — ground fault
12-13-14 Contact for K2 alarm relay ground check
16-17. C.T. connection
18-19 Ground fault external reset, Hand-closed Auto-open
22-23 External test button (optional)
25-26 Ground check external reset, Hand=closed Auto=open
27 Pilot wire if using standard ground check monitoring
29 Pilot wire if using EOL monitoring
30 Ground connection
EOL End-of-line resistor, 49.902, +/-0.1
WELDSAFE 5000 MODIFICATION NOTES
APPENDIX C TRANSGUN MODEL NUMBER DEFINITIONS
APPLICATION NOTE 700204-001
TRANSGUN MODEL NUMBER DEFINITIONS
NOTICE
This Application Note applies only to controls with operators using transguns. Non-hand-held guns can use standard non-GF (ground fault) controls.
A. Determine control type — 6001. For EN6001.
B. Determine transgun type
BLANK -— no connector; valve voltage and valve power supply to be called out
in column G. CES, ERG, PW, TGA are no longer manufactured. OEMs and end users
can add specific
connectors as needed.
C. Determine contactor and Cab. size — 300D or 1200D.
D. All transguns must have ground fault (GF).
E. Choose breaker
1. First digit — choose 1 for 100 amp; choose 2 for 200 amp (100 or 200 amp
only).
2. Second digit — 0
3. Third digit — choose 3 for 3 pole for single phasc guns.
F, All controls with GF need shunt trip (ST).
G. ACV Option for AC Valves when required. Adds AC Valve PCB and 150 VA Valve
power supply with both 24 and 120 VAC outputs.
APPENDIX D RWMA PRECAUTIONARY LABELING
PRECAUTIONARY LABELS FOR TRANSGUNS
02/21/08
| LABEL #: 460118B
SIZE: 8.0″W x 9.5″H
DESCRIPTION: GF SAFETY NOTICE
PLACEMENT: On interior of control on door of controls with Ground Fault
protection
PURPOSE: To assist installers with installation of Ground Fault System
Compilation of 460122, 460198, 460343, 460344, 460348, 460349, 460350
---|---
| LABEL #: 460122B
SIZE: 1.0″W x 3.0″H
DESCRIPTION: DANGER GF COIL
PLACEMENT: On exterior of GF coll
PURPOSE: To keep only the push totest wire and weld transformer wires as
the only wires that go through this coil; otherwise GF detection may not work
| LABEL #: 460144C
SIZE: 2.625″W x 3.25″H
DESCRIPTION: HAZARDOUS VOLTAGE GND/PE
PLACEMENT: On interior of control of weld controls at GROUND connection
PURPOSE: To advise control must be grounded and this is the point
| LABEL #: 460198B
SIZE: 2.625″W x 3.25″H
DESCRIPTION: SHOCK HAZARD TEST OPERATOR PROTECTION
PLACEMENT: On exterior of control on door near Push to Test switches on
controls with Ground Fault detection and Earth Leakage Detection
PURPOSE: To advise touse Push to Test buttons regularly
| LABEL #: 460281B
SIZE: 2.625″W x 3.25″H
DESCRIPTION: DO NOT DEFEAT OR REMOVE PROTECTION DEVICES
PLACEMENT: On interior of control near protection devices
PURPOSE: To assist Maintenance/Service personnel to not defeat protection
devices
| LABEL #: 460343
SIZE: 2.6290’W x 3.29″H
DESCRIPTION: HAZARDOUS VOLTAGE TRANSGUN
PLACEMENT: Oninterior of control of controls with Ground Fault Detection
PU R POSE: To advise installer of proper installation requirements
| LABEL #: 460344
SIZE: 2.625”W x 3.25″H
DESCRIPTION: NOTICE THIS WELD CONTROL…
PLACEMENT: Onexterior of controls with Ground Fault
PURPOSE: To advise operator that weld control meets RWMA requirements
| LABEL #: 460348
SIZE: 2.625’W x 8.5′”H
DESCRIPTION: NOTICE THIS WELD CABLE…
PLACEMENT: Onweld cables of transguns
PURPOSE: To advise operator that weld cable meets RWMA requirements
| LABEL #: 460349
SIZE: 2.625″W x 3.25″H
DESCRIPTION: SHOCK HAZARD THIS HAND-HELD TRANSGUN…
PLACEMENT: On transgene
PURPOSE: To advise to use correct control and cable
| LABEL #:
460350
SIZE: 9’W x 1.7″H
DESCRIPTION: VOLTAGE HAZARD GROUNDED DEVICE
PLACEMENT: Onground protection devices as some devices may not be
understood to be such
PURPOSE: To advise maintenance personnel that this is a ground protection
device
APPENDIX E GF ADDITIONAL WIRING DIAGRAM
APPENDIX F EN6001 GF SCHEMATIC
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>