Murray NYC Metering – Siemens ULTISH60 Multifamily Metering Power Instructions

June 10, 2024
Murray NYC Metering - Siemens

NYC Metering – Siemens ULTISH60 Multifamily Metering
Power Instructions

Installation Instructions

DANGER
Hazardous voltage. Will cause death, serious injury or substantial property damage. Turn off power supplying this equipment before won cinq inside_
Note:
These nstructions outline the recommended installation procedure. However, they do not cover all details or variations in equipment, nor do they provide for every possible contingency to be met in connection with installation. For questions or assistance, contact a qualified electrical contractor.
WARNING
Failure to install and use this product in accor-dance with all applicable ratings, instructions and the National Electrical Code°, could result in death or serious Injury to the installer or other persons, or substantial property damage.
Only persons familiar with the construction and op-eration of the equipment and the hazards involved should install this product If there we any ratings, instructions or Code requirements which you do not understand, consult a qualified electrical contractor or inspector before installing this product.
IMPORTANT
Pythium-based chemical solvent paints of arty type, water and various other contaminants can damage the interior components of this product. Do not allow these contaminants to contact the Enteric( components. Be sure any cable connection to tie top of the endostre uses proper fittings and es permanently sealed to pre-vent water entry. If the meter socket is to supply a load center or other equipment at a Sewer elevation, con-nect the service cable or conduit to one of the lower knockouts of the bed center or equipment to ensure rainwater leakage cannot damage the circuit breakers or Wier components.

GENERAL

Refer to the label on the inside of the enclosure for product ratings, acceptable components and acces-sories. and specific application requirements. Meter sockets generally must be approved by the serving utility. Check prior to installation.

MOUNT BOX – REMOVE KNOCKOUTS

First mount Line Trough Enclosure (Cat Type ULT) us-rig fasteners. Align Vertical Meter Stacks (Cat. Types UVS) with openings in the mourted Lrie Trough and attach with the provided hardware kits. Next, mount the Breaker Trough (Cat. Type UBT) aligning its open-ings with the mounted Vertical Meter Stacks. Attach with the provided hardware kits. Attach Enchvalls and Coupling Kits as required with provided fasteners.
Required knockouts in the Breaker Trough and Endwalls (Cat. No. UEW1216) may be removed prior to mount-ing. On multiple ring knockout design, first remove Cen-ter section by striking at point furthest from tie (Figure 1). Bend back and forth to break tie. Remove larger rings, one at a trne, by prying with screwdriver and bend-rng back and forth with piers, as shown in Figure 2.

®National Electrical Code is a registered trademark o’ the National Fire Protection Isolation.
DANGER
Hazardous voltage. Will cause death, serious Injury or substantial property damage. Turn off power supplying this equipment before working inside.
INSTALL PHASE BLOCK ASSEMBLIES & LINE TERMINALS
Install appropnata Phase Block Assertories (Cat. Type UPB) with provided fasteners in suggested locations (see etath ed schematic). Remove keps nut and washer from bolt and attach Line Terminals (Gat. Type ULK) as depicted n schematic for applicable wire entry. Torque kegs nut with torque wrench to 210-230 lb-ins.
Use a 10- Line Trough Spacer Kit (Cat. No. ULT1OSP) when required to ensure proper wire bending space.
PULL UNE CABLE – WIRE TERMINALS
Utilize proper fittings to secure and provide proper pro-tection to conductor insulation.
Ground enclosure by connecting it to a metal raceway or metal: c cable sheath.
Pull applicable wire/cable into Line Trough and secure to appropriate Line Terminals. When aluminum con-doctors are used, applicatory of a UL-Sited conductor termination compound is recommended. Torque re-quirements for wire binding screws are as follows:

ULX1350 375lb-in
ULX1550 500 lb-in
ULX2550 500 lb-in

Rater to markings inky device for add tonoi terminal-toile rti rig :torque raquirarr end’s,
Install Line Trogulid Cover and torque fasteners with torque *Trench to 24-30 lb- Lens_
WIRE VERTICAL METER STACKS
Refer to wire diagram
INSTALLING & WIRING BRANCH BREAKERS
Install and wire correct type branch crowd breakers (Fig. 3) in accordance MTh wing diagram label requirements. AP electrical connections must be tightened to roqute-ments as spec t6ed on wring diagram label and on each branch C Kai it breaker label before energizing.
INSTALL COVER ON VERTICAL STACKS
Fasten the Meter Socket Cover to the enclosure. Pro-tect the interlor parts of the socket from contaminates until the utility installs the meter.
REMOVE TWISTOUTS-INSTALL COVER FOR LOAD TROUGH
Remove the required twist outs by up and data) motion with pliers. !ROM Trim/Door assembly with fasteners provided. Torque fasteners with torque wrench to 24-30 lb-ins. All twist out openings must be closed with breakers or Mier plates’.

Murray NYC Metering - Siemens ULTISH60 Multifamily Metering Power -
Fig2

‘Applicable accessories are tested on the wiring diagram

SCHEMATIC FOR WIRE ENTRY ON LEFT

Murray NYC Metering - Siemens ULTISH60 Multifamily Metering Power -
Fig3

SCHEMATIC FOR WIRE ENTRY ON Right

Murray NYC Metering - Siemens ULTISH60 Multifamily Metering Power -
Fig4

Nam: Modular Melsrirg, L/V3 Sarin Pc No.- X 46411 REV 1221100
For uss with: 411.1111/40,1AWT713-SO, UEW1216. UPEI3, UP BS, UP812, ULJK1350, ULX1500, ULIK2930
Accessories: UCP1216, ULT10SP, LX100FP Raptor tot Parts: UMCVR, UMBCVR

Documents / Resources

| Murray NYC Metering - Siemens ULTISH60 Multifamily Metering Power [pdf] Instructions
ULTISH60 Multifamily Metering Power, ULTISH60, Multifamily Metering Power, Metering Power
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals