eLICHENS Avolta Wireless Gas Leak Detector
Introduction
Avolta is a wireless, battery-operated, Natural Gas leak detector. It embeds the Foxberry CH4NB sensor from eLichens, a cutting-edge NDIR (Non-dispersive Infrared), dual-channel sensor designed specifically to detect Methane, and only Methane. The sensor ultra-high selectivity has been validated by the Chicago Gas Technology Institute (GTI) and prevents the generation of false alarms by volatile hydrocarbons. The Foxberry CH4NB sensor is based on eLichens’ patented technology including a proprietary IR micro-source, patented optical design and advanced signal processing algorithms. It provides the lowest power consumption on the market and is a key differentiator for battery-powered safety products. Avolta leak detector is battery-powered, and has an autonomy of more than 10 years, with the sensor constantly ON and a LoRaWAN heartbeat message sent every 8 hours.
Features
- Ultra-low power NDIR sensor
- Ultra-high CH4 selectivity: No false alarm
- Best sensitivity, detection as low as 5%LEL
- LoRaWAN + BLE connectivity
- Battery operated, 10-year lifetime
- Driftless, no recalibration required
- Fast response time
- Temperature & Humidity sensor
- Audible & visual alarms, test button
- UL1484 & EN50194 compliant
- Ingress protection IP54
avolta at a glance
Global view
Test button
LEDs
Outline
Battery and start-up sequence
Avolta is powered by a 3.6V primary lithium thionyl chloride battery pack with a capacity of 11.6Ah. The battery is non-rechargeable and lasts 10 years.
Battery replacement needs to be performed by a trained operator only.
At delivery, the battery is inside the product but disconnected. Just unscrew the transparent battery cover and plug the battery connector. Put the cover back in place and tighten the screws to ensure water tightness.
After first battery installation, the product will initialize, the LEDs will blink one by one and the green LED will blink every 3 seconds until the product is connected to the network. If connection is successful, the green LED will blink three times and stop. If it fails, the yellow LED will blink three times and stop.
The product will then need 6 more minutes to be fully functional. Be sure to keep the product in a methane-free environment during these 6 first minutes, as the sensor is initializing.
Alarms
Several alarms are integrated in the product: gas level, temperature level, battery or electronics alarm.
Gas alarm
An alarm is triggered if the measured gas level goes above one of the three thresholds programmed in the product: small leak, alarming leak, large leak. Note that the levels can be reprogrammed using downlink commands.
Threshold | Default value | Consequence |
---|---|---|
Small leak | 10%LEL | o Alarm message sent through LoRaWAN, with acknowledge, |
every 5min
o Red LED blink + Beep + Pre-recorded message, every minute
o Stops when gas level drops below threshold for >5 minutes and a LoRaWAN message is sent
Medium leak| 20%LEL| o Alarm message sent through LoRaWAN, with acknowledge, every 5min
o Red LED blink + Beep + Pre-recorded message, every minute
o Stops when gas level drops below threshold for >5 minutes and a LoRaWAN message is sent
Large leak| 50%LEL| o Alarm message sent through LoRaWAN, with acknowledge, every 2min
o Red LED blink + Beep + Pre-recorded message, every minute
o Stops when gas level drops below threshold for >5 minutes and a LoRaWAN message is sent
Temperature alarm
An alarm is triggered if the measured temperature rises at a rate superior or equal to 3°C every 2 minutes (=37F every 2 minutes).
Threshold | Default value | Consequence |
---|---|---|
T° rise | 3°C / 2min (37F / 2min) | o Alarm message sent through LoRaWAN, with |
acknowledge, every 2min
o Red LED blink + Beep, every minute
o Stops automatically after 15 minutes
Battery/electronics alarm
The product is constantly self-testing itself, so if a problem is detected an alarm is immediately raised.
Alarm type | LoRaWAN | Product |
---|---|---|
Low battery | Alarm message sent through LoRaWAN, with acknowledge, every | |
30min | Yellow LED blink, every minute Beep, every minute |
Electronics
LoRaWAN join request
To connect the device to a LoRaWAN network, a join request must be initiated. To do this, just press the test button for more than 10 seconds. After 3 seconds, a first beep will sound, and after 10 seconds two beeps will sound, you can release the button.
Green LED will blink every 3 seconds during the join sequence. If join is successful, the green LED will blink twice quickly and stop blinking. If the join sequence failed, the yellow LED will blink three times quickly and stop. If the join request fails, try again, it can sometimes take 2 to 3 tries before working. Else, just let the product ON and it will automatically retry every 8 hours (heartbeat message interval) or if an alarm is raised.
Note: An automatic join request is performed at battery connection, so if everything went fine at startup, this “manual” join request is not useful and the LEDs sequence described above happens right after startup.
Payload format
Avolta sends two types of LoRaWAN payloads:
- A heartbeat payload every 8 hours to notify that the product is ON and fully functional.
- An alarm payload in case one of the thresholds is reached (CH4 level or temperature) or if an issue has been detected in the product (low battery or electronics failure). The product is constantly self-checking itself and the CH4 sensor is always ON, so if any alarm payload is sent in less than 30 seconds.
The payloads format is described in the tables hereafter (please note that all words are MSB first).
Heartbeat: every 8 hours on LoRaWAN port 1, without acknowledge.
Payload version| Runtime since power ON| Averaged gas
concentration| Temperature| Relative Humidity| Battery
voltage
---|---|---|---|---|---
Always
= 0x01
1 byte
| Unit: hours
4 bytes
| Unit: %LEL Averaged 1hour
1 byte
| Unit: 0.1°C Averaged 1hour
2 bytes (signed)
| Unit: %
1 byte (unsigned)
| Unit: 0.01V
1 byte (unsigned)
Alarm: every 2-5 minutes in case of an alarm on LoRaWAN port 2, with acknowledge. If acknowledge fails, retry (max 3 times).
Payload version| CH4 level| T°| Alarm status| CH4
alarm
---|---|---|---|---
Always
= 0x02
1 byte
| Unit: %LEL
1 byte
| Unit:
°C
1 byte
| 1st bit: 1 gas concentration alarm / 0 no gas alarm
2nd bit: detector error
3rd bit: battery level error 4th bit: temperature alarm
1 byte
| 0x00: no gas alarm
0x01: small leak (≥10%LEL) 0x02: medium leak (≥20%LEL) 0x03: large leak (≥25%LEL) 3th…8th bit: reserved
1byte
Downlink commands
Downlink commands can be sent through the LoRaWAN network. Please see hereafter for their description. Note that the frame counter can be kept to zero.
Read commands
Name | Description | Frame request | Frame answer |
---|---|---|---|
Read Gas thresholds | Get concentration thresholds (small, alarming, high) in | ||
%LEL | [0]: Frame counter [1]: 0x92 | [0]: Frame counter [1]: 0x92 [2]: small |
gas leak threshold (%LEL) [3]: medium gas leak threshold (%LEL) [4]: large gas
leak threshold (%LEL)
Read payload| Get the payload thought BLE service| [0]: Frame counter [1]:
0x95| [0]: Frame counter [1]: 0x95 [2]: Payload version [3-6]: running time in
hours [7]: Last gas concentration [8-9]: Last temperature value [10]: Humidity
[11]: Battery voltage
Speaker status during alarm| Speaker status during an alarm| [0]: Frame
counter [1]: 0x96| [0]: Frame counter [1]: 0x96 [2]: 0 sound alarm is
disabled; 1 sound alarm is enabled during an alarm
Write commands
Name| Description| Frame request| Frame answer (if frame
request is correct)
---|---|---|---
Gas thresholds| Set the values of the concentration alarms (small, alarming,
high)| [0]: Frame counter [1]: 0x82 [2]: small gas leak threshold (%LEL) [3]:
alarming gas leak threshold (%LEL) [4]: large gas leak threshold (%LEL) Check:
Request LoRa payload| Send a LoRa payload, if not join, will generate a join|
Speaker status during alarm| Enable/Disable the speaker during an alarm
(enabled by default)
| [0]: Frame counter [1]: 0x86 [2]: 0 disables the speaker during alarm, 1 enables the speaker during alarm| [0]: Frame counter [1]: 0x86
Errors
Name | Description | Frame request | Frame answer |
---|---|---|---|
Error return | [0] : Frame counter [1] : 0x32 command unknown |
(SDCS_V2_FAIL_INVALID_CMD) 0x33 missing arguments (SDCS_V2_FAIL_INVALID_DATASIZE) 0x34 incorrect parameters (SDCS_V2_FAIL_INVALID_VALUE)
Web data access (eLichens gateway or TTN)
If you are using a gateway provided by eLichens or if your area is covered by
The Things Network (TTN), all the collected data are directly accessible
through a dedicated web interface, available here:
https://lab.elichens.com/dashboard
Account creation
To access it, connect to https://lab.elichens.com and create an account.
Please take care of the strong password policy as you will need to enter a
password with:
- at least 8 characters
- at least 1 upper case [A-Z]
- at least 1 lower case [a-z]
- at least 1 digit [0-9]
- at least 1 special character [$@$!%*#?&,;:]
Associate a device
In the left menu, select « My stations ». At your first visit, no station is
visible. Select « Associate a station » at the top right corner of the page
(green button on the picture hereafter).
To go further, you need to enter the token provided by your eLichens’ contact
or inside the package you received. It is a unique code in the format AAA-BBB-
CCC. Enter this code in the dedicated space and select « Associate the station
».
The following confirmation message will display (see next figure).
Devices’ access
All the connected devices are accessible through the left column. The buttons
on the bottom right side of the interface are used to change the history
length and a click on “Advanced view” brings the user to an advanced dashboard
where data can be exported in a .CSV file.