Dormont ES-D SafetyShield Premium Yellow Coated Stainless Steel Gas Connectors Instructions

June 4, 2024
Dormont

Dormont-LOGO

Dormont ES-D SafetyShield Premium Yellow Coated Stainless Steel Gas

Connectors

Dormont-ES-D-SafetyShield-Premium-Yellow-Coated-Stainless-Steel-Gas-
Connectors-PRODUCT

SafetyShield® Premium Yellow Coated Stainless Steel Gas Connectors

SafetyShield® enhanced coating increased safety, durability, and longevity

Antimicrobial additive inhibits the growth of bacteria, mold, and mildew.

  • Improved UV, humidity, and corrosion protection
  • Enhanced flame and smoke resistance Consistent coverage provides protection along the entire length of the connector.Dormont-ES-D-SafetyShield-Premium-Yellow-Coated-Stainless-Steel-Gas-Connectors-FIG-1

Features and Specifications

  • Tubing: Annealed, 304 stainless steel (ASTM A240)
  • Coating: Custom Formulated Premium Yellow Polymer
  • Flare nuts: Brass or plated steel
  • Adapters: Brass or plated steel
  • Approved for indoor/outdoor use with stationary gas appliances/equipment
  • Temperature rating of connector with adapters: -40°F to 150°F
  • Temperature rating with valves: -40°F to 125°F
  • 100% factory leak tested
  • When installing a new appliance or when an existing appliance is moved to a new location a NEW gas connector must be used per manufacturer’s installation instructions and per product standards

ANSI Z21.24/CSA 6.10 and ANSI Z21.75/CSA 6.27

  • Not engineered for high temperature applications such as gas logs, fireplace inserts or free-standing fireplaces
  • Designed for occasional movement after installation. Repeated bending, flexing or extreme vibration must be avoided. Normal operation of a clothes dryer, rooftop HVAC unit or SIMILAR

OUTDOOR APPLIANCE DOES NOT constitute extreme vibration or movement

  • Limited lifetime warranty – for details visit www.watts.com/resources/warranty-information

Standards

  • ANSI Z21.24/CSA 6.10 – Connectors for Gas Appliances
  • ANSI Z21.75/CSA 6.27 – Connectors for Outdoor Appliances and Manufactured Homes
  • City of New York – MEA #376-92-M
  • Approved by the Commonwealth of Massachusetts Board of State Examiners of Plumbers and Gas Fitters – connector length may not exceed 48″

WARNING

All installations must completely comply with all Dormont® manufacturing company warnings and instructions, national, state and local codes and all applicable ansi standards. Dormont product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Dormont Technical Service. Dormont reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Dormont products previously or subsequently sold. Refer to the owner’s manual for warranty information.

Minimum Flow Capacity

Connector Minimum Flow Capacity – For Natural Gas (per ANSI Z21.24/CSA 6.10 & ANSI Z21.75/CSA 6.27) Straight Length Capacity – BTU per Hr 0.64 SG., 1000 BTU per Cu. Ft. at 0.5 inch Water Column Pressure Drop

CONFIGURATION CONNECTOR LENGTH [INCHES]

SERIES

| Nominal OD

in

| Nominal ID

in

| 12

in

| 18

in

| 24

in

| 30

in

| 36

in

| 48

in

| 60

in

| 72

in

10C| 3⁄8| 1⁄4| 48,000| 43,800| 40,000| 36,400| 33,400| 28,300| 24,900| 23,100
20C| 1⁄2| 3⁄8| 102,000| 93,100| 85,000| 77,100| 71,000| 60,500| 53,200| 49,100
30C| 5⁄8| 1⁄2| 180,000| 164,200| 150,000| 136,000| 125,000| 106,000| 93,200| 86,000

Connector Minimum Flow Capacity – For LP Gas (per ANSI Z21.24/CSA 6.10 & ANSI Z21.75/CSA 6.27) Straight Length Capacity – BTU per Hr 1.55 SG., 2500 BTU per Cu. Ft. at 0.5 inch Water Column Pressure Drop

CONFIGURATION CONNECTOR LENGTH [INCHES]

SERIES

| Nominal OD

in

| Nominal ID

in

| 12

in

| 18

in

| 24

in

| 30

in

| 36

in

| 48

in

| 60

in

| 72

in

10C| 3⁄8| 1⁄4| 76,800| 70,080| 64,000| 58,240| 53,440| 45,280| 39,840| 36,960
20C| 1⁄2| 3⁄8| 163,200| 148,960| 136,000| 123,360| 113,760| 96,800| 85,120| 78,560
30C| 5⁄8| 1⁄2| 288,000| 262,720| 240,000| 217,600| 200,000| 169,600| 194,120| 137,600

Applications

Indoor

  • Range
  • Dryer
  • Water Heater
  • Gas Fireplace
  • Garage Heater
  • Wall Heater
  • Tankless Water Heater
  • Furnace
  • Space Heaters

Outdoor

  • Rooftop Units
  • Outdoor Dryer
  • Stationary Outdoor Grills
  • Gas Fire Pits

Manufactured Home

  • Mobile Home Gas Meter
  • Cross-over Gas Connection Kits

NOTICE
The minimum flow capacity values in the charts are at 0.5″ w.c. pressure drop (inlet pressure minus outlet pressure). If your gas system has more available pressure drop then a general rule of thumb approximate calculation is as follows: Minimum Flow Capacity @ your pressure drop = Square Root (your pressure drop/0.5) x value from chart Example: What is the approximate minimum flow capacity (natural gas) of the Dormont 30 Series x 24″ @ 1″ wc pressure drop? Answer: Square Root (1/0.5) x 150,000 = 212,132 BTU/hr