JYC OPzV2-3000 2V Tubular Gel Series VRLA Battery User Guide
- June 9, 2024
- JYC
Table of Contents
OPzV2-3000 2V Tubular Gel Series VRLA Battery
User Guide
OPzV2-3000 2V Tubular Gel Series VRLA Battery
Complied standards
- IEC 60896-21/22
- DIN40742
- IEC61427
- YD/T1360
- Eurobat guide, long life
- BS6290 part 4
- UL1989
The OPzV series adopts an Immobilized Gel and Tubular Positive Plate
technology. It offers high reliability and stable performance. By using die-
casted positive grid and patented active material formula, it exceeds the DIN
standard values and offer 20+ years design life in float service. It is very
suitable for cyclic use under extreme operating conditions. This series is
recommended for telecom outdoor applications, renewable energy systems and
other harsh environment applications.
SPECIFICATIONS
Nominal Voltage (V) | 2 |
---|---|
Designed Floating Life(20t) | 20+ Years |
Nominal Capacity (20C) | 3000 Ah @ Coo (to 1.80Vpc) |
Demensions | L576mm xW212mmx H807mm |
Approx. Weight | 220 kg (485 Ibs) |
Terminal Type | Female Copper Insert M8 (torque:10-12N.m) |
Internal Resistance | Approx. 0.16mOhm (fully charged @ 20°C) |
Max. Charge Current | 600 A |
Max. Discharge Current (5S) | 4000 A |
Short Circuit Current | 12000 A |
Self Discharge | Approx. 2% per month @ 20°C |
Ambient Temperature | Discharge: -40-65°C |
Charge: -30-65°C
Storage: -25-45°C
Float Charge Voltage (20-25C)| 2.25-2.29V (-3mV /°C/ cell)
Equalize Charge Voltage (20-25°C)| 2.35-2.40V (-5mV /°C/ cell)
Container Material| ABS(UL94-VO optional)
DIMENSIONS
BATTERY DISCHARGE TABLE
Constant Current Discharge Characteristics: Amps (20°C)
F.V/Time| 10min| 15min| 30min| 1h| 2h| 3h|
5h| 8h| 10h
---|---|---|---|---|---|---|---|---|---
1.90V| 1062| 1033| 965| 815| 701| 588| 435| 311| 257
1.87V| 1447| 1351| 1197| 951| 784| 648| 472| 331| 272
1.85V| 1665| 1525| 1312| 1038| 864| 697| 503| 346| 283
1.83V| 1940| 1698| 1419| 1145| 923| 736| 515| 357| 288
1.80V| 2171| 1969| 1587| 1261| 974| 772| 525| 362| 300
1.75V| 2302| 2162| 1862| 1373| 1017| 794| 535| 368| 303
1.70V| 2504| 2374| 2046| 1450| 1056| 809| 544| 373| 309
1.65V| 2924| 2673| 2229| 1542| 1086| 823| 556| 379| 315
1.60V| 3184| 2934| 2364| 1591| 1108| 838| 567| 386| 320
Constant Power Discharge Characteristics: W/cell (20°C)
F.V/Time| 10min| 15min| 30min| 1h| 2h| 3h|
5h| 8h| 10h
---|---|---|---|---|---|---|---|---|---
1.90V| 2051| 1999| 1879| 1599| 1385| 1171| 872| 627| 520
1.87V| 2742| 2570| 2293| 1836| 1532| 1276| 938| 661| 545
1.85V| 3110| 2860| 2481| 1981| 1669| 1358| 989| 686| 562
1.83V| 3581| 3149| 2651| 2160| 1764| 1419| 1000| 701| 567
1.80V| 3950| 3600| 2929| 2352| 1839| 1473| 1010| 703| 573
1.75V| 4121| 3891| 3387| 2524| 1894| 1491| 1016| 706| 583
1.70V| 4422| 4214| 3670| 2632| 1943| 1502| 1022| 710| 590
1.65V| 5072| 4670| 3938| 2761| 1975| 1511| 1031| 713| 595
1.60V| 5414| 5022| 4097| 2800| 1985| 1516| 1041| 719| 600
PARAMETERS FOR SOLAR & WIND APPLICATIONS
Long time discharge capacity for Solar & Wind applications
Capacity| (Ah) 20| (Ah) 24| (Ah) 48| (Ah) 72| (Ah)
100| (Ah) 120| (Ah) 240
---|---|---|---|---|---|---|---
OPzV2-3000| 3215| 3279| 3620| 3710| 3780| 3800| 3860
Final Voltage| 1.80V| 1.85V
Solar & Wind applications parameters settings
Over voltage disconnect: | 2.45±0.01V/cell @ 2025°C |
---|---|
Regulation/equalize voltage: | 2.40±0.01V/cell @ 20-25°C |
Array roconnection voltage: | 2.25±0.005V/cell @ 20′-’25°C |
Float voltage setting: | 2.27±0.005V/cell @ 20—’25°C |
Low voltage alarm voltage: | 1.95±0.005V/cell @ 20’25°C |
Low voltage disconnect: | 1.90±0.005V/cell @ 2O-25°C |
Load reconnect voltage: | 2.09±0.01V/cell @ 20-’25°C |
Temp. compensate coefficienty: | -5mV/cell/°C |
CHARACTERISTICS
DT-WP-MKT-F-A02
Documents / Resources
| JYC
OPzV2-3000 2V Tubular Gel Series VRLA
Battery
[pdf] User Guide
OPzV2-3000 2V Tubular Gel Series VRLA Battery, OPzV2-3000, OPzV2-3000 VRLA
Battery, 2V Tubular Gel Series VRLA Battery, Gel Series VRLA Battery, VRLA
Battery, VRLA, Battery
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>