Regul8OR Digital High -Performance Programmable Power Supply Controller User Manual
- June 3, 2024
- Regul8OR
Table of Contents
- Regul8OR Digital High -Performance Programmable Power Supply Controller
- CT and #NC or pins #CT and #NO shall never exceed 1 A. Maximum current rating
- Terminal2 shall never exceed 0.4 A. Do not apply voltage between any input
- 3-16-4
- 17-5
- 18-6
- 19-1
- 20-1
- 3, #4, #7, #8 #5 #6 #9
- 1, #7
- 2, #8 #3 #4 #5 #6
- 2
- 3
- 4
- 1
- 2, #7
- 3, #4
- 5
- 6
- 8
- 9
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Regul8OR Digital High -Performance Programmable Power Supply Controller
MAGNET POWER SUPPLY SYSTEMS
REGUL8OR User’s Manual
REGUL8OR
Digital High-Performance Programmable Power Supply
Controller
User’s Manual
All Rights Reserved © CAEN ELS s.r.l. Rev. 1.2 May 2021
1
REGUL8OR User’s Manual
This product is
compliant.
CAEN ELS s.r.l. in AREA Science Park S.S. 14 km 163,5 loc. Basovizza 34149
Trieste (TS)
Italy Mail: info@caenels.com Web: www.caenels.com
Registered office: via Vetraia 11 55049 Viareggio (LU) – Italy
2
REGUL8OR User’s Manual
User’s Manual Models Options Custom Models
This manual covers the following standard REGUL8OR models:
· REGUL8OR · REGUL8OR-PWM
For technical assistance please refer to the following contact: CAEN ELS
S.R.L. SS14 km 163,5
34149 loc. Basovizza Trieste (TS), Italy (c/o Area Science Park Building
Q1) Phone: +39 040 375 6610 Fax: +39 040 375 6611
3
REGUL8OR User’s Manual
Table Of Contents
1. INTRODUCTION………………………………………………………………………………….10
1.1 REGUL8OR OVERVIEW …………………………………………………………………… 10 1.2 REGUL8OR AT A GLANCE
…………………………………………………………………13
DCCT Direct Current Transducer………………………………………………..15 Digital Control
Loop……………………………………………………………………..15 1.3 OPERATION MODES
………………………………………………………………………….. 17 Regulation Mode
………………………………………………………………………….. 17 Control Mode ……………………………………………………………………………….
17 Update Mode………………………………………………………………………………..18 1.4 EXTERNAL INTERLOCKS AND
STATUS SIGNALS …………………………………….. 19 Interlock Enable/Disable
Mask……………………………………………………….19 Interlock Activation Level Mask
…………………………………………………….. 19 Interlock Intervention
Time…………………………………………………………….20 Interlock Isolation
………………………………………………………………………… 20 Output Status Signal User-
Defined……………………………………………….20 1.5 TRIGGER AND ANALOG CONTROL
INPUTS……………………………………………..21 Trigger input ……………………………………………………………………………….. 21
Analog Control Input ……………………………………………………………………. 22 1.6 EXTERNAL SENSORS
…………………………………………………………………………. 24 1.7 SYNCHRONIZATION OF MULTIPLE UNITS
……………………………………………… 25 1.8 EXTERNAL SPI………………………………………………………………………………….25 1.9
OUTPUT CONNECTORS ………………………………………………………………………. 26 1.10 INPUT VOLTAGE AND
CURRENT CONNECTORS ………………………………………. 27 1.11 FRONT PANEL INDICATORS
…………………………………………………………………28 1.12 INTERNAL
PROTECTIONS…………………………………………………………………….29
Regulation Fault ………………………………………………………………………. 29 OVerTemperature – OVT
…………………………………………………………… 29 1.13 WAVEFORM ……………………………………………………………………………………..30
2. INSTALLATION ………………………………………………………………………………….. 31
2.1 PREPARATION FOR USE ……………………………………………………………………… 31 2.2 INITIAL INSPECTION
………………………………………………………………………….. 31 2.3
MOUNTING……………………………………………………………………………………….32
Rack Mounting …………………………………………………………………………….. 32 2.4 AC INPUT POWER CONNECTION
…………………………………………………………. 32
AC Source Requirements ………………………………………………………………. 33 AC Input
Cord………………………………………………………………………………33 2.5 EXTERNAL POWER SUPPLY CONNECTION
…………………………………………….. 34 2.6 CABLE LENGTH…………………………………………………………………………………34 2.7
INTERLOCK AND STATUS SIGNALS ………………………………………………………. 36 2.8 EXTERNAL SENSORS
…………………………………………………………………………. 39 2.9 EXTERNAL
SPI………………………………………………………………………………….40 2.10 TRIGGER AND ANALOG CONTROL INPUTS
……………………………………………. 41 2.11 ISOLATED OUTPUT CONNECTORS ………………………………………………………..
42 2.12 SYNC IN AND SYNC OUT………………………………………………………………..43 2.13 CURRENT AND
VOLTAGE INPUTS ………………………………………………………… 44 2.14 INSULATION
…………………………………………………………………………………….. 45
4
REGUL8OR User’s Manual
2.15 MATING CONNECTORS……………………………………………………………………….46 3. LOCAL CONTROL
……………………………………………………………………………… 47
3.1 NAVIGATION SWITCH………………………………………………………………………… 47 3.2
DISPLAY…………………………………………………………………………………………..47
Power-up …………………………………………………………………………………….. 48 Home Screen
………………………………………………………………………………..49 Menu Page …………………………………………………………………………………..
51
Control Page………………………………………………………………………….52 Config
Page…………………………………………………………………………..53 Advanced
Page………………………………………………………………………54 4. MECHANICAL
DIMENSIONS……………………………………………………………..55 5. TECHNICAL SPECIFICATIONS
………………………………………………………… 56
5
REGUL8OR User’s Manual
Document Revisions
Revision
Date
1.0
October 2nd, 2020
1.1
October 7th, 2020
1.2
May 21st, 2021
First Release
Comment
Corrections made on several sections
Updated Local Control Section
6
REGUL8OR User’s Manual
Safety information
The following table shows the general environmental requirements for a correct
operation of instruments referred in this User’s Manual:
Environmental Conditions Environment Operating Temperature Operating Humidity Altitude Pollution degree Overvoltage Category Storage Temperature Storage Humidity
Requirements Indore use 0°C to 40°C 20% to 80% RH (non-condensing) Up to 2000 m 2 II -10°C to 60°C 5% to 90% RH (non-condensing)
The following symbols are used within this manual or are reported in the box and along this manual:
·
CAUTION Risk of Electrical Shock
·
Caution: Documentation must be consulted in all cases where
this symbol is marked
0 ·
Off (Power)
I ·
On (Power)
WARNING
·
The WARNING sign denotes a hazard. An attention
to a procedure is called. Not following the procedure correctly could result in
personal injury. A WARNING sign should not be skipped and all indicated
conditions must be fully understood and met.
7
REGUL8OR User’s Manual
CAUTION
·
The CAUTION sign denotes a hazard. An attention to
a procedure is called. Not following procedure correctly could result in
damage to the equipment. Do not proceed beyond a CAUTION sign until all
indicated conditions are fully understood and met.
CAEN ELS s.r.l. will repair or replace any product within the guarantee period if the Guarantor declares that the product is defective due to workmanship or materials and has not been caused by mishandling, negligence on behalf of the User, accident or any abnormal conditions or operations.
Please read carefully the manual before operating any part of the instrument
WARNING
Do NOT open the TOP COVER of the BOX
CAEN ELS s.r.l. declines all responsibility for damages or injuries caused by
an improper use of the Modules due to negligence on behalf of the User. It is
strongly recommended to read thoroughly this User’s Manual before any kind of
operation.
CAEN ELS s.r.l. reserves the right to change partially or entirely the
contents of this Manual at any time and without giving any notice.
8
REGUL8OR User’s Manual
Disposal of the Product The product must never be dumped in the Municipal
Waste. Please check your local
regulations for disposal of electronics products.
WARNING · Do not use this product in any manner not specified by
the manufacturer. The protective features of this product may be impaired if
it is used in a manner not specified in this manual. · Do not use the device
if it is damaged. Before you use the device, inspect the instrument for
possible cracks or breaks before each use. · Do not operate the device around
explosives gas, vapor or dust. · Always use the device with the cables
provided. · Turn off the device before establishing any connection. · Do not
operate the device with the cover removed or loosened. · Do not install
substitute parts or perform any unauthorized modification to the product. ·
Return the product to the manufacturer for service and repair to ensure that
safety features are maintained
9
REGUL8OR User’s Manual
1. Introduction
This chapter describes the general characteristics and main features of the
REGUL8OR controller series.
1.1 REGUL8OR Overview
The REGUL8OR is a high-performance and high-stability digital controller and
can be used with all the COTS (Commercial Off-The-Shelf) programmable power
supplies that accept an analog control input ranging from:
· 0 V … +5 V (UNIPOLAR) · 0 V … +10 V (UNIPOLAR) · -5 V … +5V (BIPOLAR) · – 10
V … +10 V (BIPOLAR)
or a current 4-20 mA input to improve their specifications over different
aspects.
Thanks to the GUI (Graphic User Interface), the control and configuration of
the REGUL8OR is straightforward, while the several interfaces present on the
rear panel of the module allow for a quick and easy connection to the external
power supply adding several functionalities.
The extreme versatility of the device is given by the possibility to choose,
on the same hardware module, between several current and voltage input ranges,
as listed in the following Table 1.
Input Type Current [A] Voltage [V]
Ranges
± 100 ± 150 ± 200 ± 300 ± 400 ± 600 ± 1000
± 5
± 10
± 20
± 50 ± 100
Table 1: configurable ranges for the REGUL8OR
± 200
10
REGUL8OR User’s Manual
The REGUL8OR module is housed in a compact mechanical format and it fits in a
single 19″ – 1U standard crate. The device implements a completely digital
control loop with a 1-MSPS, 20-bit Digital-to-Analog Converter (DAC) that
allows adapting the system to basically any general-purpose programmable power
supplies. The behavior of device is schematically descripted in Figure 1:
Figure 1: schematic representation of the REGUL8OR coupled to an external
power supply. The digital controller generates a voltage analog signal to
control the external power supply, which in turn acts as an amplifier and
generates the current (or voltage) desired. The REGUL8OR then closes the
voltage and current loops and elaborates the values in a digital PID.
The REGUL8OR is a digital control device that uses two 24-bit Analog-toDigital
Converters (ADCs), one for the voltage input path and the other for the
current input path, to sense the external current and voltage generated by the
general-purpose power unit controlled, in order to compute them in a digital
PID controller which in turn produces the analog voltage output (or the 4-20
mA) to control the COTS power supply.
The control board houses a dedicated SoC (System on Chip), including an FPGA
with an integrated dual-core ARM CPU. The loop regulation task is performed
directly by the FPGA logic, in order to have high performance and
deterministic loop control. An embedded Linux OS is installed on the ARM CPU,
supervising all processes as well as communication, diagnostics and local
interface handling.
Remote communication is guaranteed by means of an Ethernet 10/100/1000 Mbit
autosensing socket present on the front panel of the device on a RJ45
connector.
11
REGUL8OR User’s Manual
The REGUL8OR can be also monitored and controlled via a navigation switch and
a graphic high-resolution color display featuring user-friendly menus.
In addition to the standard Ethernet interface, it is possible to communicate
with the unit using the SFP-ports on the front panel. This interface allows
communicating with the unit using a proprietary protocol (packet structure
with a very high update rate (more than 10 kHz) for fast applications. These
ports are connected directly to the FPGA logic and so the given packet is
elaborated directly by the hardware logic.
This approach eliminates the software stratification that manages the packet
and the computational time is smaller and deterministic, allowing a very high
update rate of the setpoint, giving the user more flexibility and excellent
rates for the digital remote control of the power supply.
12
REGUL8OR User’s Manual
1.2 REGUL8OR at a glance
The REGUL8OR system is composed by a single 19-inch 1U crate. The unit and its
I/O connections can be easily seen in Figure 2 (front view),
Figure 3 (rear view) and Figure 4 (rear view with optical
transmitters/receivers – optional).
Figure 2: REGUL8OR front view On the front side of the REGUL8OR unit there are
placed respectively: a power switch, a colour graphic display with navigation
switch for the local control of the module, three communication sockets (2
SFPs and one Ethernet port), four status LEDs and one USB device connector.
Figure 3: REGUL8OR rear view without opto-transmitters
Figure 4: REGUL8OR rear view with optional opto-transmitters
13
REGUL8OR User’s Manual
On the rear side of the unit are placed: AC power line input and all the connectors for the communication with other external devices. A brief description of the connector used are described in the Table 2.
Connector Name Optical
Transmitters and
Interlocks [OPTIONAL] Interlocks and
Status Signals
Trigger Input
Sync In and
Sync Out
External SPI
External Sensors
Analog Input
DCCT Current Transducer
Output Voltage DAC
Connector Type
D-SUB25 Isolated BNC
SMA
Description
There is the possibility to install 8 optical transmitter and 2 optical input
receivers. This can be used to generate high resolution PWM signals to be fed
to a power stage. Two optical input interlocks are also available e.g.
interlocks from IGBT modules 6 external interlocks (four dry-contact types and
two 24-V type ones) that can be used to capture external faults. Six signal
status are also present on the same connector: 2 TTL signals (5 V), 2 magnetic
relays with NO and NC contacts and 2 solid state relays Trigger Input
connectors, can be used as a hardware start, or for the execution of a
preloaded waveform Used to connect many power supplies in parallel or to
synchronize their operation: SYNC IN and SYNC OUT signals is used to maintain
different units in-phase.
8-pin
This connector allows to add new modules to
Right-Angle the REGUL8OR
D-SUB9 Male
Isolated BNC
D-SUB9 Female
Isolated BNC
Used to connect external sensors to the REGUL8OR, e. g. external temperature sensor or a hall probe. The control board can be controlled not only using the digital communication interface but also with an external analog signal. Input voltage range span from -10 V to +10 V (or can be selected 5 V range) Thanks to this connector an external DCCT, for the measure of the current, can be connected to the REGUL8OR BNC used to control the external power supply. The voltage output is also available on the LEMO connector together with the 4-20 mA output
14
REGUL8OR User’s Manual
Connector Name 4-20 mA DAC Voltage Input
Connector Type
LEMO
Isolated Banana
Description
Allows using the REGUL8OR in a 4-20 mA control loop
Two isolated banana connectors are installed to sense the external voltage on
the load
Table 2: short description of the connectors on the rear panel of the REGUL8OR
DCCT Direct Current Transducer
To achieve high performance in terms of stability and low noise in the current
readout, and so on the current regulation, the REGUL8OR takes advantage of the
DCCT transducers of the < series manufactured by CAEN ELS.
The main characteristics of this technology are:
· Extreme low-noise values; · Temperature Coefficient at sub-ppm level; ·
Monitoring of DC and AC current; · Galvanic insulation from the conductor to
be measured i.e. current
can be measured at a high voltage potential.
The use of this technology greatly improves specifications respect to the most
common requirements. The signal-conditioning network that converts the
secondary current of the transducer to a voltage is then fed to the Analog to
Digital Converter (ADC) is also a specific state-of-the-art know how.
Digital Control Loop
The core of the system is PID controller which is completely digital and it
uses state-of-art technology on the FPGA and the DAC to implement a controller
able to adapt to and to obtain maximum performance from any external power
supply and any load condition.
15
REGUL8OR User’s Manual
Figure 5: schematic representation of the system
The implementation of the digital control loop via the REGUL8OR adds
flexibility to any analog existing system, allowing it to be tuned to any load
condition easily and remotely.
16
REGUL8OR User’s Manual
1.3 Operation Modes
The REGUL8OR system has multiple features and multiple configurations that
allow using the unit for a very widespread scenario of applications and with a
large variety of loads.
A brief summary of the basic configurations that the unit is able to handle
are hereafter presented.
Regulation Mode The REGUL8OR can be used as current-controlled or voltage-
controlled bipolar or monopolar unit. The regulation types are:
· C.C. mode: it is the Constant Current (CC) regulation mode. The device
regulates the output current produced by an external power supply and set by
the user;
· C.V. mode: it is the Constant Voltage (CV) regulation mode. The device
regulates the output voltage produced by the external power supply and set by
the user.
Control Mode The REGUL8OR unit can be controlled in three main different ways
that are hereafter listed:
· LOCAL control: the unit can be controlled directly via the front panel color
display and the navigation switch. When the unit is set in LOCAL mode it is
possible to perform readings and monitor from the remote interface but any
setting command is denied;
· REMOTE control: the unit is controlled via the TCP-IP Ethernet interface.
The setting and control of the unit can be performed exclusively via this
interface while monitoring is still possible from the local display;
· FAST-INTERFACE control: this interface allows controlling the unit via a
proprietary protocol over the SFP/SFP+ interfaces (optical or electrical) and
it is meant to be used for very fast applications. Update rates of more than
10 kHz are reachable by using this communication channel.
17
REGUL8OR User’s Manual
Update Mode The current or voltage setting of the unit can also be performed
in four different modes: · NORMAL: the update of the set-point (current or
voltage, depending on the
operation mode i.e. CC or CV respectively) is performed as soon as a new
set-point is received via the remote, local or fast interfaces · WAVEFORM: the
update of the set-point is performed on a specific timing (defined as a
“waveform” attribute, more information on the Waveform section) and it is done
internally · TRIGGER: the set-point is updated by an external event i.e. a
hardware trigger coming from the rear BNC connector · ANALOG INPUT: the unit
is controlled by an external signal that is fed to the rear BNC connector. The
unit acts as a C.C. or C.V. controller depending on the pre-set Regulation
Mode
18
REGUL8OR User’s Manual
1.4 External Interlocks and Status Signals
The system is provided with 6 (six) external interlock inputs that can be
easily configured using the Web Interface (embedded in the power unit) or
directly using the standard power supply commands. A description of the
configuration of the external interlocks using the power supply commands is
hereafter described.
The REGUL8OR also presents 6 (six) output status signals that are divided
into:
· 2 (two) magnetic relays with the NO, NC and COMMON taps; · 2 (two) solid
state relays with two contacts; · 2 (two) isolated TTL signals (0-5 V).
All these signals can be connected with other internal signals or status’
(e.g. module ON, module OFF, all the interlocks and so on) to create
automations.
The configurability of the REGUL8OR series allows the users to decide what
interlocks are enabled or not, to set the interlock “trip” level (i.e. low or
high), the time of intervention (i.e. the time that an interlock signal has
stay at the “trip” level before generating a fault condition) and to associate
to each one an interlock name/identification.
This configuration can also be set and read using the Web Interface (provided
with the power module) or using the low-level device configuration commands,
which allows setting the advanced configuration parameters. All interlocks are
disabled by default.
External Interlocks and Status Signals are available on a D-SUB 25-pin Female
type on the rear panel of the REGUL8OR.
Interlock Enable/Disable Mask
The REGUL8OR series external interlocks can be enabled or disabled by writing
to the corresponding Interlock Enable/Disable Mask field of the advanced
configuration parameters. Refer to “Remote Control Manual” for additional
details.
Interlock Activation Level Mask
Each external interlock can be chosen to trip at HIGH or LOW logic level. The
dry-contact interlocks are hardware-activated when the input pins and their
corresponding return pin are shorted. The remaining two interlocks are
hardwareactivated when there is no voltage between the input pins and their
corresponding return pins. They are hardware-deactivated in case a 24-V
voltage source is applied.
19
REGUL8OR User’s Manual
It is necessary to write on the advanced configuration parameters with the Web
Interface or via standard power supply commands in order to configure the
interlock state mask.
Interlock Intervention Time The module also allows to setting the interlock
intervention time (the time that an interlock signal needs to be at its
activation level before tripping and thus generating a fault condition). The
parameters of the Intervention Time (expressed in milliseconds) are stored in
the device memory.
Interlock Isolation The interlock pins are galvanically isolated from ground
and outputs terminal, nevertheless the absolute maximum voltage, referred to
ground, that these pins can sustain is of 54 VDC. All the interlocks inputs
have their own return connection.
Output Status Signal User-Defined The solid-state relay signals (please
refer to the I/O connector section for more information) can be remotely
commanded by the user in order to change their states (open/shorted) for any
specific customer application. Solid State Relay Terminals shall not float
more than ±54 VDC above/below chassis ground and their maximum current rating
should never exceed 400 mA. The Signal Status can be set by writing to the
corresponding Signal Status Mask fields of the advanced configuration
parameters (refer to the “Remote Control Manual”) as well.
20
REGUL8OR User’s Manual
1.5 Trigger and Analog Control inputs
The standard version of the REGUL8OR includes inputs for a trigger signal and
for an analog control on the rear panel.
A brief description of these features and their functionalities is presented
hereafter.
Trigger input
The trigger input accepts TTL-compatible (5V) signals and should be driven by
a low-impedance source or generator. The trigger input is galvanically
isolated from ground and can float up to ±54 VDC respect to the chassis.
The logic levels are subject to a hysteresis that allows guaranteeing correct
operation of the trigger feature also in noisy installations/environment. The
trigger voltage logic levels are listed in Table 3:
Logic Level
Value
Low-to-HIGH
3.5 V
High-to-LOW
< 1.5 V
Table 3: Trigger Logic Levels
CAUTION
The absolute maximum rating for the Trigger Input signal is of 5.5 V (a higher
voltage level applied to this input can seriously damage the device).
A visual representation of the voltage levels for the trigger operation is
presented in the following Figure 6
21
REGUL8OR User’s Manual
Trigger Input
6
ABSOLUTE MAXIMUM
5
4
HIGH LEVEL
Trigger Signal
3
2
LOW LEVEL
1
0
Figure 6: Trigger Thresholds
Analog Control Input
An input that allows the REGUL8OR to be controlled remotely with an analog
signal is provided on the rear panel on an isolated BNC connector. This input
is labelled as “AN. INPUT” and it accepts signals ranging from -10 V to +10 V.
This isolated input acts as an input for a digital closed-loop amplifier and
it generates a control output signal (for the external unit) which is
proportional to the input signal.
This means that the REGUL8OR will regulate the output at -100 % for a 10 V
analog input voltage, a 0% for a 0 V analog input voltage and a +100 % for a
+10 V analog input voltage.
An example of the relation between the analog input signal and the output (can
be either current or voltage, depending on the Regulation mode) is shown in
Figure 7.
In order to avoid drifts, offset and external noise pick-up it is always
suggested to use the digital interface e.g. Ethernet to control the
external power unit in order to get the best performance.
22
REGUL8OR User’s Manual
+100%
Analog Control
+10V
-10V
AN CTRL
OUTPUT -100%
Figure 7: ANALOG CONTRL vs OUTPUT of the general-purpose power supply controlled
Please note that the bandwidth of the analog control input is internally limited to approximately 25 kHz.
23
REGUL8OR User’s Manual
1.6 External Sensors
The REGUL8OR is equipped with an input connector on the rear panel that allows
users to connect different external sensors useful for sensing an external
temperature or a magnetic field for example.
Having two different voltage supplies (1.8 V and 3.3 V referred to chassis
ground) for the external temperature sensor allows installing a variety of
different temperature sensors. The analog value is then conditioned by a low-
pass filtering network that has gain of ½ and a cut-off frequency of 68-Hz.
Then analog signal is converted by 12-bit ADC.
The REGUL8OR also includes an interface to supply and read an external Hall
probe. Some Hall probes needs to be supplied by a constant-current source
while others by a constant-voltage source: an internal relay selects the type
of supply to be used to power-up the Hall probe with:
· a constant voltage of 5 V OR
· a constant current of 20 mA. This option can be configured via the Web
Interface or via the corresponding
dedicated configuration commands.
Figure 8: schematic representation of the connection between the Regul8OR and
external temperature sensor and Hall Probe
24
REGUL8OR User’s Manual
1.7 Synchronization of Multiple Units
The SYNC IN and SYNC OUT connectors on the rear panel of the device (both SMA
type) allows connecting and synchronizing multiple REGUL8OR units. This
feature permits users to keep two or more REGUL8OR units in-phase.
The first unit will generate an internal clock signal that will be fed to the
SYNC OUT connector and needs to be connected to the SYNC IN input of the
following unit.
The SYNC IN and SYNC OUT signals are meant only for this dedicated application
and are ground-referred.
Figure 9: schematic representation of a synchronization of multiple units
1.8 External SPI
An isolated SPI interface is present on the rear panel of the REGUL8OR on an
8pin connector.
This 4-wire SPI allows interfacing external devices to the unit in order to
match specific applications.
Beside the 4 wires of the SPI interface i.e. MISO, MOSI, SCLK and CS – on
this connector are also present the pins for an isolated power supply rated a
2 W maximum. These voltage levels are isolated from chassis ground (they can
float up to 54 VDC) and they are rated at 5 VDC respect to the SPI ground
pins.
As an example, it could be possible to custom-design a 32-channel temperature
readout external module with a small microcontroller and this external module
could directly be powered and read by connecting it to this SPI interface
connector (all firmware and software would need to be developed).
25
REGUL8OR User’s Manual
Figure 10: schematic representation of a connection between the Regul8OR and a
generic external device made with the SPI
1.9 Output Connectors
The REGUL8OR has been designed to control an external power stage/programmable
power supply with an analog output voltage or, in specific cases, an analog
output current (to close a 4-20 mA loop).
Two connectors, an isolated BNC (voltage output) and a 4-pin LEMO (current
path and voltage output), are provided on the rear panel to feed the isolated
output signals.
Typically, a general-purpose programmable power supply can be controlled via
an external analog voltage with typical values ranging from 0 V to 10 V or
from 0 V to 5 V (unipolar operation). In some specific applications, these
signals can range from 10 V to +10 V or from -5 V to +5 V (bipolar operation).
The analog output voltage is generated by a state-of-the-art 20-bit 1-MSPS
Digital to Analog Converter (DAC).
The 4-20 mA current control loop is often used in industrial process control.
Its name refers to the current range used to control or to measure in the
loop, where the current spans from a minimum value of 4 mA (0 %) to a maximum
value of 20 mA (100 % or full-scale). The main reason for the use of this
current-based signal has to be found in the fact that current signals are less
sensitive to noise than voltage signals and are so sometimes preferred in
noisy environments e.g. industrial facilities. The chosen loop driver is a
single-channel, 16-bit converter.
26
REGUL8OR User’s Manual
1.10Input Voltage and Current connectors
The output current and the output voltage are sensed by connectors placed on
the device rear panel. The current is measured with a proprietary DCCT
supplied and connected from/to a DSUB9 female connector. This cable is
supplied together with the REGUL8OR unit.
The voltage, on the other side, is voltage is sensed using two isolated banana
connectors.
Both current and voltage values are conditioned with two independent analog
and digital networks that can be configured to read different ranges so to
optimize the regulation performance on several types and ratings of external
power stage or programmable power supplies.
27
REGUL8OR User’s Manual
1.11Front Panel Indicators
The REGUL8OR has four (4) front panel LED indicators as shown in the following
Figure 11.
Figure 11: front panel indicators The front panel indicators and their
behaviour are hereafter listed (clockwise starting from top-left): · C.C.:
Constant Current mode (blue). If turned on, the REGUL8OR is working in
constant-current (CC) mode. When off, it is regulating in constant-voltage
(CV) mode; · STAT (green): signals the correct operation of the module
diagnostics. The blinking signaling the correct operation has a 1-second
period; · OUT ON (blue): it signals if the output is enabled or not. The blue
LED is on if the output is enabled and it is regulating output current or
voltage; · ALARM (red): if turned on signals that the power unit has
experienced a fault condition. It is necessary to perform a “reset fault”
command in order to turn off this LED and to turn to module output again (only
if the fault condition/cause has been removed).
28
REGUL8OR User’s Manual
1.12 Internal Protections
The REGUL8OR is equipped with internal protections that allow configuring the
unit for optimal operation. These protections have the dual use of protecting
the unit and the connected load/external power unit/device from unwanted
damages or undesired operation conditions.
A brief description of the REGUL8OR internal protections is hereafter
presented with some more basic considerations on their operation and use.
Regulation Fault
This fault is generated when the power supply is not able to correctly
regulate the output current or the output voltage (in C.C. and C.V. mode
respectively).
Different thresholds for the differential current, differential voltage and
the intervention time can be set by experienced users.
A typical example of a regulation fault is represented by a 10- load on a
general-purpose power supply rated at 300 A and 50 V where the maximum power
supply output voltage is 50 V. By setting a current of 10 A to the load, the
output voltage should reach a value of 100 V which obviously is not feasible:
once the power unit supplies 5 A to the load it already reaches the maximum
output voltage condition. The REGUL8OR digital controller recognizes this
difference between the set-point i.e. 10 A and the actual output current,
thus generating a “regulation fault” condition.
The tripping of this fault implies an automatic turning off of the REGUL8OR
unit and the general-purpose power supply (if there is the possibility to shut
down the external unit with an external signal). A status reset i.e. reset
faults needs to be performed in order to turn the unit back on.
OVerTemperature – OVT
External monitoring of temperature is performed by using an external
temperature sensor connected to the External Sensor Connector (see Chapter
2.8). If the temperature reading is exceeding a pre-defined threshold, an OVT
condition is generated.
The threshold value [°C] can be set by experienced users. A reset fault
operation needs to be executed on the status register of the REGUL8OR before
turning the output off again.
29
REGUL8OR User’s Manual
1.13 Waveform
The REGUL8OR is also able to act as a waveform generator both in
constantcurrent (CC) and in constant-voltage (CV) regulation modes.
The waveform is stored internally in a point-by-point scheme and it gives a
lot of flexibility since the maximum number of points of the waveform can be
defined as well as the sampling period (of the waveform execution).
The minimum time interval for the waveform execution period is rated at 0.1 ms
= 100 µs, giving an equivalent output waveform update rate of 10 kHz.
In order to correctly execute the output waveform, it is necessary to “tune”
the PID regulator parameters of the entire system i.e. REGUL8OR + external
power supply to the specific load.
More information on the waveform feature can be found in the corresponding
command section.
30
REGUL8OR User’s Manual
2. Installation
This chapter contains the basic instructions for initial inspection and preparation for use of the REGUL8OR.
2.1 Preparation for Use
In order to be operational, the REGUL8OR must be connected to an appropriate
AC source. The AC source voltage should be within the device specification. Do
not apply power before reading, Section 2.2 and 2.4 Table 4 below, describes
the basic setup procedure. Follow the instructions in Table 2.1 in the
sequence given to prepare the power supply for use.
Step
Checklist
Description
1
Initial inspection
Physical inspection of digital controller
2
Mounting
Installing the digital controller, ensuring proper ventilation
3
AC Input Power Connection
Connect the digital controller to the AC source
5
Power Supply connection
Connect the digital controller to the external power supply
4
First switch-on
Switch-on checkout procedure
Table 4: Installation checklist
2.2 Initial Inspection
Prior to shipment, this digital controller was inspected and found free of
mechanical or electrical defects. Upon unpacking of the digital controller,
inspect for any damage which may have occurred in transit.
31
REGUL8OR User’s Manual
The inspection should confirm that there is no exterior damage to the digital
controller such as broken switch or connectors and all the panels and display
are not scratched or cracked. Keep all packing material until the inspection
has been completed. If damage is detected, compile the RMA form available from
the CAEN ELS website.
2.3 Mounting
The REGUL8OR module can be used either as a desktop unit or as a rack-mount
device since the unit form factor is designed to be installed in a standard
19-inch cabinet (1U space occupation).
CAUTION This unit is natural air-cooled; ventilation holes are present on the
front and rear panel. Allow minimum 10 cm of unrestricted air space at the
front and the read of the unit.
Rack Mounting The REGUL8OR units are designed to fit in a standard 19″
equipment rack.
CAUTION Use mounting rails to provide adequate support for the unit.
NO
2.4 AC Input Power Connection
The AC line input connector on the rear panel is a standard IEC 60320 C20 male
inlet socket. Mains fuse holders are on the bottom part of the connector;
required fuses characteristics for all the models are (T2AL250V):
32
REGUL8OR User’s Manual
· Size: 5 x 20 mm · Current rating: 2 A · Blow characteristic: Time delay ·
Breaking Capacity: 35 A · AC Voltage rating: 250 V
Figure 12: AC Power Line input socket
AC Source Requirements The REGUL8OR controllers are designed for universal AC
input range since it can operate with voltage from 90V to 240V and input
frequency ranging of 50 Hz or 60 Hz. Installation Category shall be CAT II so
maximum impulse voltage on the network mains must be below 2500 V.
AC Input Cord All the REGUL8OR digital controllers are directly shipped with
the corresponding power cord (suitable for the destination country of the
purchase). Power supply side connector is a standard IEC 60320 C19 plug.
Current rating for the connector is 2 A. Wire size for detachable power supply
cord, not longer than 2 m, shall be at least 0.75 mm2.
WARNING There is a potential shock hazard if the power supply chassis is not
connected to an electrical safety ground via the safety ground in the AC input
connector!
33
REGUL8OR User’s Manual
2.5 External Power Supply Connection
WARNING
Turn off the AC input power (of both REGUL8OR and external power supply)
before making or changing any rear panel connection. Ensure that all
connections are securely tightened before applying power. There is a potential
shock hazard when using a power supply with a rated output voltage greater
than 60 V.
The REGUL8OR needs a DCCT and an external power unit to work correctly. In the
device shipping box are included all the cables necessary to connect the
digital controller to the DCCT. If the REGUL8OR is bought together with the
external power supply also the connections to the external device are
included. Table 5 describes the cables in the shipping box:
Cable DCCT Voltage DAC
Interlock and signal status External Voltage
Description
Cable for the connection of the DCCT to the REGUL8OR, to read the current
Connect the output analog signal to the power unit to control it [OPTIONAL]
Necessary to read the external interlock and to apply the signal status to the
external power unit. [OPTIONAL] External voltage reading [OPTIONAL]
Table 5: description of the cable in the shipping box
WARNING
Turn off the AC input power (of both REGUL8OR and external power supply)
before setting or changing the DCCT. Set the digital controller (and the power
unit) in OFF state to connect or disconnect the DAC control cable for the
external power supply. Ensure that all connections are securely tightened
before applying power.
2.6 Cable Length
34
REGUL8OR User’s Manual
In the table below – Table 6 – are listed the recommended length for the cables that will be connected to the device.
Cable
Length
Output voltage DAC cable
< 3 m
Output current DAC cable
< 30 m
DCCT cable Analog Input Cable
< 3 m < 30 m
Input voltage cables Sync In and Sync Out cable
< 30 m < 3 m
Trigger Input cable Opto-Transmitter
< 3 m Not Applicable
Table 6: Recommended cable lengths
35
REGUL8OR User’s Manual
2.7 Interlock and Status Signals
The REGUL8OR module has four configurable dry-contact input interlocks, two
24-V interlocks, and six output status signals that are directly available on
the DSub 25 Pin Female connector on the rear panel (Figure 13).
A mating connector, a standard D-SUB 25-Pin Male type, can be installed in
order to use/access these available signals.
Pin #13
Pin #1
Pin #25
Pin #14
Figure 13: Interlock and Signal Status Connector
The pinout of the D-SUB 25 rear connector is summarized in the following table (Table 7):
Pin Number #1 #2 #3 #4 #5 #6 #7 #8 #9 #10 #11 #12 #13 #14 #15 #16 #17
Description TTL reference Magnetic Relay #1 Center Tap (CT) Magnetic Relay #2 Normally Closed (NC) Magnetic Relay #2 Normally Open (NO) Solid State Relay #1 – Terminal 2 Solid State Relay #2 – Terminal 2 Interlock #6 negative input Interlock #6 positive input Interlock #5 positive input Interlock #3 positive input Interlock #4 positive input Interlock #2 positive input Interlock #1 positive input Magnetic Relay #1 Normally Closed (NC) Magnetic Relay #1 Normally Open (NO) Magnetic Relay #2 Center Tap (CT) Solid State Relay #1 – Terminal 1
36
REGUL8OR User’s Manual
Pin Number #18 #19 #20 #21 #22 #23 #24 #25
Description Solid State Relay #2 – Terminal 1 TTL Signal 2 Output 5 V
(Reference signal pin #1) TTL Signal 1 Output 5 V (Reference signal pin #1)
Interlock #5 negative input Interlock #3 negative input Interlock #4 negative
input Interlock #2 negative input Interlock #1 negative input
Table 7: D-sub 25 Pin pin-out
WARNING
Magnetic Relay Contact (C-TAP, NO-TAP & NC-TAP) and Solid-State Relay
Terminals (Terminal #1 & #2) shall not float more than ±54 VDC above/below
chassis ground. Interlocks input and return pins shall not float more than ±54
VDC above/below chassis ground.
CAUTION
Voltage between relay C-TAP and NC-TAP or NO-TAP pins shall never exceed ± 54
V. Maximum current rating for the Magnetic Relays is 1 A; current trough pins
CT and #NC or pins #CT and #NO shall never exceed 1 A. Maximum current rating
for the Solid-State Relays is 400 mA; current trough pins #Terminal1 and
Terminal2 shall never exceed 0.4 A. Do not apply voltage between any input
interlock dry contact and its corresponding return.
The interlock pins are galvanically isolated from the chassis ground and
outputs terminal, nevertheless the absolute maximum voltage, referred to
chassis ground, that pins can sustain is 54V. The two interlocks inputs have
their own return connection. The interlock is hardware-activated when the
input pin and its corresponding return pin are shorted.
37
REGUL8OR User’s Manual
Relay Magnetic #1
Pins #14-2-15
Maximum Current
Max Voltage (to chassis ground)
1 A
54 V
Max Voltage (between
pins)
54 V
Magnetic #2
3-16-4
1 A
54 V
Solid State #1
17-5
400 mA
54 V
48 V
Solid State #2
18-6
400 mA
54 V
TTL Signal #1
19-1
10 mA (4 mA recommended)
54 V
TTL Signal #2
20-1
10 mA (4 mA recommended)
54 V
5.5 V 5.5 V
Table 8: Ratings of magnetic and solid-state relays and for TTL signals
38
REGUL8OR User’s Manual
2.8 External Sensors
This connector (Figure 14) allows the user to connect external sensors to the
REGUL8OR. Two pins are dedicated to supply an external voltage, one rated at
1.8 V and the other one rated at 3.3 V for a temperature sensor/transducer,
one pin is dedicated to supply a 5-V voltage or a 20-mA current (can be
selected via the Web Interface or via the relative configure commands for
example for a Hall-probe), four chassis-ground (GND) pins and two pins for the
input signals of the external sensors (one for a temperature sensor and one
for Hall probe). The pinout of the D-SUB 9 rear connector is listed in Table 9
Pin 1
Pin 5
Pin 6
Pin 9
Figure 14: External Sensors input connector
Pin Number #1 #2
3, #4, #7, #8 #5 #6 #9
Description Temperature voltage supply +1.8 V
Temperature voltage supply +3.3 V
GND (chassis ground) Supply for a Hall-probe: Voltage source (5 V) or Current
source (20 mA) External Input (Temperature Sensor 0 V/ +1.8 V)
External Input (Hall Probe 0 V/ +5 V)
Table 9: External Sensors connector pinout
CAUTION
Do not apply voltage greater than + 1.8 V on pin 6, this can cause damages to
the internal parts. (External Temperature Input pin). Do not apply a voltage
greater than + 5 V on pin 9, this can cause damages to the internal parts
(External Hall Probe Input pin).
39
REGUL8OR User’s Manual
Do not apply any sources to pin 1, 2, 3, 4, 7, 8, 9: this can cause damages to
the internal parts.
2.9 External SPI
To extend the possible applications of the REGUL8OR digital controller, an
external module can be supplied and connected to the unit by using the
isolated 8-pin SPI connector (Figure 15) on the rear panel. The pinout is
described in the table below.
Pin 7 Pin 8
Pin 1 Pin 2
Figure 15: Isolated SPI connector
Pin Number
Description
1, #7
External Voltage +5 V
2, #8 #3 #4 #5 #6
Ext SPI reference Chip Select SPI (CS
Serial Clock SPI Data Output SPI Data Input SPI
Table 10: External SPI connector pinout
CAUTION
Every output signal is limited in a range of 0 V to + 5 V.
Do not apply a voltage input greater than + 5 V and lower than 0 V to Data
Input pin (#6), this can cause damages to the internal parts.
40
REGUL8OR User’s Manual
2.10 Trigger and Analog Control Inputs
The isolated Analog Input connector can accept a voltage value in range of -10
V to +10 V and it can be used to control the REGUL8OR from an external voltage
source in order to take advantage of the digital control loop. The isolated
BNC connector is presented in the figure below (Figure 16).
Figure 16: Analog Input and Trigger connectors
The isolated Trigger Input (also on a BNC connector) can accept a voltage
ranging from 0 V to +5 V and it can be used as a start/update signal for the
REGUL8OR as explained in the dedicated sections.
CAUTION Do not apply voltage greater than + 10 V (or lower than -10 V) on the
analog input connector, this can cause damages to the internal parts. Do not
apply a voltage greater than + 5 V (or lower than 0 V) on the trigger input
connector, this can cause damages to the internal parts.
41
REGUL8OR User’s Manual
2.11 Isolated Output Connectors
The control output of the REGUL8OR, one from the DAC and one from the 420 mA
loop driver, is fed to isolated output connectors as shown in Figure 17. These
connectors are an isolated BNC for the DAC voltage output and a 4-pin LEMO
that includes both the DAC (i.e. the same signal present on the BNC connector)
and the 420 mA loop driver.
Pin 1
Pin 4
Pin 2 Pin 3
Figure 17: 4-20 mA and voltage outputs
Pin Number #1
Description Current output (for the 4-20 mA loop)
2
DO NOT CONNECT
3
DACs output reference
4
Output voltage DAC
Figure 18: Isolated LEMO connector pinout
Please note that the DAC voltage output has an output impedance of 10 .
The maximum source/sink capability of the DAC output is rated at ±25 mA.
CAUTION
Do not connect an external input supply to both OUTPUTS connectors because
this can cause damages.
42
REGUL8OR User’s Manual
2.12 SYNC IN and SYNC OUT
Multiple REGUL8ORs can be synced and so phase-locked by means of a clock
signal. This signal will be generated from a “master” REGUL8OR device on the
SYNC OUT connector and will then be connected to the SYNC IN connector of
another REGUL8OR unit. The synchronization can be done either connecting a
single SYNC OUT signal to multiple SYNC IN signals or, better, by connecting
the SYNC OUT, SYNC IN in daisy-chain mode. These signals are present on two
SMA connectors on the rear panel of the unit as shown in Figure 19.
Figure 19: SYNC IN and SYNC OUT connectors
The signal generated on the SYNC OUT connector is a serial clock signal with
logic levels of 0 V and +3.3 V.
CAUTION Do not connect an external input supply to both SYNC IN and OUT
because this can cause damages. PLEASE ONLY CONNECT THE SYNC OUT SIGNAL TO
SYNC IN INPUTS ON IDENTICAL REGUL8ORs. The signal input can be only a serial
clock with a voltage input that span between 0 V and +3.3 V.
43
REGUL8OR User’s Manual
2.13 Current and Voltage Inputs
The technology used on the REGUL8OR allows selecting how the digital PID
works. The internal digital controller can work basically in two different
modes: in the first mode the controller only considers one value (e.g. current
or voltage) to be regulated, while on the other mode takes into account both
the current and the voltage values.
Because of this last mode of operation, it is extremely important for the
device to have both the current and the voltage readback fed to it. As said,
both the voltage and the current networks can be remotely configured to have
different hardware input ranges.
The current readout is performed via the external DCCT transducer (to be
purchased separately depending on the desired range) and its pinout is shown
in Table 11. Please note that the REGUL8OR is shipped already with a cable
with the correct pinout to be connected to the chosen external DCCT
transducer.
Pin Number
Description
1
DCCT Neg (Current Return)
2, #7
N.C.
3, #4
GND (Chassis Ground)
5
-15 V
6
DCCT Pos (Current Signal)
8
DCCT Fault
9
+15 V
Table 11: DCCT connector pinout
Pin 5
Pin 1 Pin 2
Figure 20: Voltage and Current connectors
Pin 9
44
REGUL8OR User’s Manual
WARNING
Use only CAT IV BANANA connectors. Plug and unplug Banana connectors only if
the external controlled power supply is completely switched OFF.
CAUTION
The REGUL8OR is shipped with a specific voltage and current ranges set. All
the voltage ranges are calibrated while the current ranges are calibrated only
for the purchased DCCT corresponding ranges (e.g. for a purchase with a 600A
DCCT, only the ±600 A range is calibrated).
Do not exceed the rated values of both current and voltage because this can
cause damages to the internal parts.
2.14 Insulation
A list of the insulation ratings of the different connectors, in accordance to
the IEC Standard EVS-EN 61010-1:2010, are presented in the following table
(Table 12):
Connector Voltage Input Connector Current Input Connector
Analog Input Trigger Input Isolated BNC Voltage Output Isolated LEMO Current
Output Opto-Transmitter Interlock and Status Signal SYNC In and SYNC Out
External SPI
Insulation Value 500 V
Not Insulated 500 V 500 V 500 V 500 V
Not Applicable 500 V
Not Insulated 500 V
45
REGUL8OR User’s Manual
Connector External Sensors
Insulation Value Not Insulated
Table 12: Insulation values for the connectors
2.15 Mating Connectors
The mating parts for the connectors present on the rear panel of the REGUL8OR
are listed in Table 13. These parts are the recommended ones but equivalent
ones can be used.
Connector
LEMO
BNCs (Trigger Input, Analog Input, Output voltage DAC)
Input Voltage sheated banana 4mm (72913)
Sync Out to Sync In
Recommended Mating Part FGG. 0B.304.CLAD52Z
Coaxial male connector Banana Plug Sheathed 4mm.
CAT IV SMA
External SPI
IDC 8
D-SUB 25 (Interlock S.S.)
D-SUB 25 Male
D-SUB 9 (External Sensor)
D-SUB 9 Female
Table 13: mating parts for the rear connectors
46
REGUL8OR User’s Manual
3. Local Control
This chapter describes the local control functionalities that are provided by
the REGUL8OR and some useful information on how to use them.
The unit can work either in LOCAL mode or in REMOTE mode. The control mode
(LOCAL or REMOTE) can be set on the configuration page of the local display.
Please note that only readbacks are allowed from the remote communication
interfaces when the unit is in LOCAL mode (i.e. settings are inhibited).
3.1 Navigation Switch
Each REGUL8OR controller module is equipped with a Navigation Switch on the
front panel of the unit as shown in the following Figure 21:
Figure 21: Navigation switch There are multiple actions that can be performed
via this front navigation switch: · Left, Right, Up, Down arrow push buttons;
· Internal encoder rotation (CW and CCW); · Central pushbutton (it will also
be referred to as “Enter”).
3.2 Display
The colour display on the REGUL8OR digital controller unit allows users to
visualize information about the power supply status and to control the unit in
order to use it locally. Screens and pages of the display can be navigated
from the navigation switch though user friendly menus and sub-menus.
47
REGUL8OR User’s Manual
By default, the display will be automatically turned off after 30 minutes from
the last local command or from the turning on of the power supply.
The user can disable this feature or change the turning off time; for more
information please refer to the “Remote Control Manual”.
Power-up The REGUL8OR, upon power-up or power-cycling, will display an empty
screen until the unit embedded OS is initialized. Please note that this
procedure will take approximately 25-seconds before the Home Screen is
displayed.
48
REGUL8OR User’s Manual
Home Screen The REGUL8OR home screen is the first loaded page upon power-up or
powercycling of the module, it is shown in Figure 22, and contains information
on: · the REGUL8OR model; · the module IP address; · output current readback
value [A] with the light blue status bar; · output voltage readback value [V]
with the green status bar; · the status of the output i.e. ON or OFF; · the
status of the control i.e. Local or Remote; · the module Identification
Name; · the regulation mode of the unit i.e. constant-current or constant-
voltage.
Regul8OR 20-40-600
Figure 22: Home Screen The Home screen presents some indications on the right
side as: · ON OFF: shows if the power supply output is enabled or not; · REM
LOC FCI: shows if the module is in Local, Remote or Fast Control Interface
control mode; · C.C. C.V.: shows if the module is working in C.C. or in C.V.
regulation mode. An example of the indications on the right side of the Home
screen is hereafter shown in Figure 23:
Figure 23: Home Screen indicators
49
REGUL8OR User’s Manual
If the module has experienced one or more faults e.g. interlock
intervention, over-temperature, etc. the home page screen would display a
list of the faults, turning also the module OFF.
The digital controller latches on every fault recognized by the internal logic
so that every type of fault is recorded: this means that the first fault
happening does not ban the other ones to be recorded so that, giving users
more information, permits a better investigation of the fault cause.
50
REGUL8OR User’s Manual
Menu Page The Menu page is reachable by performing any action on the
navigation switch when in the Home Screen. The Menu Page gives access to all
the local features of the REGUL8OR digital controller unit. There are five
different options that can be selected as shown in Figure 24:
Figure 24: Menu Page The accessible sub-pages and/or actions from this page
are hereafter listed (note that the selected sub-menu is lightened in a
lighter shade): · Control sub-page; · Config sub-page; · Advanced sub-
page; · Reset faults – action;
The access to each sub-menu (or action) is necessary to highlight the selected
description by using the encoder or the arrows of the navigation switch and
press the “Enter” button.
The Reset faults, once pressed, resets the status register of the controller
and sends back to the visualization of the Home Screen.
In order to Return to the Main screen, the back button in the control menu has
to be pressed. In addition, the back button can be used to return to the
previous screen in every menu or sub-menu.
51
REGUL8OR User’s Manual
Control Page The Control Page is reachable by selecting the corresponding
rectangle from the Menu Page. The Control Page gives access to the main
settings of the REGUL8OR controller unit. An example of a Control Page
visualization is shown in Figure 25:
Figure 25: Control Page From this screen it is possible to turn the power
supply unit ON and OFF and to set the output current or voltage (depending on
the regulation type, C.C. or C.V.). Actual values of output current and output
voltage (readbacks) can also be seen in the page.
52
REGUL8OR User’s Manual
Config Page The Config Page is reachable by selecting the corresponding
rectangle from the Menu Page. This page allows the user to set the control
mode of the power supply e.g. LOCAL or REMOTE to select the regulation
mode (C.C. or C.V.), to set the control mode (NORMAL or ANALOG INPUT) or to
set the polarity of the polarity inverter (DIRECT or INVERS). An example of a
Config Page visualization is shown in Figure 26:
Figure 26: Config Page The firmware installed version is shown at the bottom
of this page (FW Version).
53
REGUL8OR User’s Manual
Advanced Page The Advanced Page is reachable by selecting the corresponding
rectangle from the Menu Page. This page allows to locally set the power supply
Ethernet IP address, the Network Mas and the Gateway. An example of an
Advanced Page visualization is shown in Figure 27:
Figure 27: Advanced Page Network settings It is very important to notice
that once the “SET” button has been clicked, the user can remotely communicate
and get control of the power supply again only by opening a new TCP socket to
the IP that has just been set.
54
REGUL8OR User’s Manual
4. Mechanical Dimensions
The mechanical dimensions of the REGUL8OR unit are hereafter presented in
Figure 28:
Figure 28: REGUL8OR Mechanical Drawings
55
FAST-PS-1K5 User’s Manual
5. Technical Specifications
The main technical specifications for the standard REGUL8OR models are hereafter presented:
Technical Specifications
REGUL8OR
Input Current Range Input Voltage Range
±100 A ±5 V
±150 ±200 ±300 ±400 ±600 ±1000
A
A
A
A
A
A
±10 V ±20 V ±50 V ±100 V ±200 V
Topology
Bipolar or Monopolar
Control Mode
Constant Current (CC) and Constant Voltage (CV)
Analog Control Input
Yes
Current Setting Resolution
24 bit
Voltage Setting Resolution
24 bit
Output Readback Resolution
24 bit
Analog Output Resolution
20 bit DAC 23 bit DAC w/ dithering
Temperature Coefficient
< 0.0002 % / K (CC mode) < 0.005 % / K (CV mode)
Long Term Stability (8 h)
< 0.001 % / K (CC mode)
< 0.001 % / K (CV mode)
Accuracy RMS
< 0.01 % (CC mode)
< 0.01 % (CV mode)
Control/Communication Interface
Ethernet TCP-IP SFP/SFP+
Local Control
Color display with multi-function navigation switch
External Signals
6x External Interlocks (4x dry contact and 2x 24 V)
6x Status signals 2x magnetic, 2x solid-state, 2x TTL
Trigger Input
Analog Control Input
External Sensors (Temperature and Hall probe)
External SPI
SYNC IN and SYNC OUT
DCCT input
Output PWM (10 optical transmitter, 8x output and 2x
interlock inputs) only “PWM” version
56
REGUL8OR User’s Manual
Extra Features
Mechanical (L×W×H)
Dimensions
Waveform Execution Remote Firmware Update
Linux OS on-board
19″ x 1U x 283.5 mm
(without connectors)
Nominal Input Voltage
100-240 VAC 50-60 Hz
Input Voltage Range
90-264 VAC 47-63 Hz
Weight
< 2 kg
Operating Temperature
0 … 40 °C
Table 14: Technical Specifications
57
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>