AERMEC FCZ300A Fan Coil Floor Fan Installation Guide

June 6, 2024
AERMEC

FCZ

Fan coil for universal and floor installation
Cooling capacity 0,65 ÷ 7,62 kW Heating capacity 1,45 ÷ 17,02 kW

AERMEC FCZ300A Fan Coil Floor Fan1
A • Very quiet
• Touch controller mounted on-board. allows remote control with smart devices

AERMEC FCZ300A Fan Coil Floor Fan

DESCRIPTION

fan coil can be installed in any 2/4 pipe system and operates with any heat generator even at low temperatures, and thanks to varied versions and settings, it is easy to pick the ideal solution for any need.

FEATURES

Case
Protective metal cabinet with anti-corrosion polyester RAL 9003 paint, whereas the head with the air distribution grille is in RAL 7047 plastic. Depending on the version, the distribution grille may be adjustable.

Ventilation group

Consisting of double suction centrifugal fans that are particularly silent, statically and dynamically balanced, and directly coupled with the motor shaft. The motor is wired for a single-phase and has three speeds, with a capacitor. The motor is fitted on sealed for life bearings and is secured on anti-vibration and self-lubricating mountings. Extractable shrouds for easy, effective cleaning

Heat exchanger coil

With copper pipes and aluminum louvers, the standard or oversized main coil and the possible secondary coil have female gas water connections on the left side and the manifolds have air vents. The coil is not suitable for use in a corrosive atmosphere or in environments where aluminum may be subject to corrosion. Reversibility of the water connections during installation only for units with a standard or boosted main coil, or standard with BV accessory. Not reversible in all other configurations. In any case, units with the coil water connections on the right are available at the time of ordering.

Condensate drip

Provided standard in plastic and fixed to the interior structure; with external condensate discharge.

Air filter

class Coarse 25% for all versions easy to pull out and clean.
FCZ_Y_UN50_09

– With a built-in selector.
FCZ_As — Coerpotibury nth VW vine,'” — Without installed switch
FCZ_ACT — With <lemony thematic for 2-pipe systems only.
FCLAPC — Ninth <Anionic thermoset for ]-pipe system only.
— Cold Nernst purifier

FCLAF — Without installed switch
— a community with AU system
— Front intake grille.

Versions with adjustable and fixed grille (universal)

FCZ_U
— CorripotbrAy with Will system.
— Without instated switch
— °intention grief with adjusted< low/eft Sues I, 2 and 3 have a single seine whereas sues 4, X. 0. 7. 8. 9 and 10 have three grilles fully independent of each other. When all the fins have closed the unit switches off.
— vertical and horizontal installation lot 2-pipe and 4-pipe systems.
FCZ_UF
— Convo with IMF system
— Without installed switch
— Mr &freely rle with adjustable lowers,
— Front intake rile FCZ_UA — Compaidukey with VMF system
— Without installed switch
— Air distribution grille with fixed louvers.
Vertical and horizontal installation for 2-pipe and 4-pipe systems.

ThermApp

In units with a T-Touch-I electronic thermostat and the ThermApp application, the operating mode can be set and the weekly timer programmed by simply resting the smart device on the fan coil. The graph-ic interface of the app also gives access to a lot more information such as the alarm list, the closest SAT, etc.
Available for Android operating systems. AERMEC FCZ300A Fan Coil Floor
Fan - fig1

GUIDE TO SELECTING THE POSSIBLE CONFIGURATIONS

Field Description
1,2,3 FCZ
4 Size 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
5 Main coil
0 Standard
5 Oversized
6 Secondary coil
0 Without coil
1 Standard
2 Oversized
7 Version
Only vertical installation.
--- ---
A High, with fixed air distribution grille and built-in command
ACT High, with air distribution grille and electronic thermostat
ACP High, without built-in command but with front intake
AF High, with air distribution grille, electronic thermostat and Cold Plasma

purifier
AS| Freestanding without installed switch
| Vertical and horizontal installation.
---|---
U| Universal, with adjustable air distribution grille but without a built-in thermostat
UA| Universal, with fixed air distribution grille but without a built-in thermostat
AF| Universal, with adjustable air distribution grille but without built-in thermostat and with front intake grille

SIZE AVAILABLE FOR VERSION

ACCESSORIES
Control panty;
AERS031R: Flush-mounting thermostat with a backlit display, capacitive keypad, and infrared receiver, for controlling both brushless fan coils and those with an asynchronous motor. In 2-pipe systems, the thermostat can control standard fan coils or those equipped with an electric heater, with air purifying devices (Cold Plasma and germicidal lamp), with a radiant plate, or with FCZ-D twin delivery (Dualjet). In addition, it can control systems with radiant panels or mixed (fan coil and radiant floor) systems. Being equipped with an infrared receiver, it can, in turn, be controlled by the VMF-IR remote control.
PX2Z: On-board electromechanical switch. SAS: air probe kit (L = 15 m) with probe-locking cable grommet.
SIT3: Thermostat Interface Card allowing the creation of a network of fan coils (max. 10) commanded by a central control panel (selector or thermostat). Commands the 3 fan speeds and must be installed on each fan coil within the network; receives the commands from the selector or the SITS card. In case you decide to install Aermec thermostats and the current absorbed by the unit exceeds 0.7 A. you’re obliged to include the SIT3 accessory. /
SITS: Thermostat Interface Card allows the creation of a network of fan coils (max. 10) commanded by a central control panel. Commands the 3 fan speeds and up to 2 valves (four-pipe systems); send the thermostat commands to the fan coil network.
SW3: Water probe (L = 2.5 m) for controlling the minimum and maximum and to allow automatic seasonal switching for electronic thermo-stats fitted with the waterside changeover.
SWS: water probe kit (1 = 15m) with a probe-holder connection point, fixing clip, and probe-holder from the heat exchanger.
T-TOUCH: Touch control onboard the machine, for controlling fan coils with asynchronous motors. In 2-pipe systems, it can control standard fan coils or those equipped with an electric heater, with air purifying devices or with FCZ-D twin delivery (Dualjet). In 4-pipe systems, only standard fan coils. The ThermApp application is also available for remote control with smart devices with the Android operating system.
TX: Wall-mounting thermostat for controlling either brushless fan coils or those with asynchronous motors for 2/4 pipe. In 2-pipe systems, the thermostat can control standard fan coils a those equipped with an electric heater, with air purifying devices, radiant plate or FCZ-D twin delivery (Dualjet).
TXB: Wall-mounting thermostat for controlling either brushless fan coils or those with asynchronous motors for 2/4 pipe. In 2-pipe systems, the thermostat can control standard fan coils or those equipped with an electric heater, with air purifying devices, radiant plate or FCZ-D twin delivery (Dualjet).
WMTOS: Electronic thermostat with thermostated ventilation.
WMT06: Electronic thermostat with continuous ventilation.
WMT10: Electronic thermostat, white, with thermostated or continuous ventilation. VA* system
VMF-EOX: Thermostat to be secured to the side of the fan coil, fitted as standard with an air probe and a water probe.
VMF-E19: Thermostat to be secured to the side of the fan coil, fitted as standard with an air probe and a water probe.
VMF-E2Z: User interface on the machine, to be combined with the VMF-EOX, VMF-E19 or VMF-E191 accessory.
VMF-E3: Wall-mounted user interface, to be combined with accessories VMF-E19, VMF-E191, VMF-EOX with grids GLF_N/M and GLL_N, can be controlled with VMF-1R control. VMF-E4DX: Wall-mounted user interface. Grey front panel PANTONE 42 SC (METAL). VMF-E4X: Wall-mounted user interface. Light grey front panel PAN-TON E COOL GRAY 1C. VMF-IR:
User interface compatible with the AER5031R, VMF-E3 thermostat and with all the grids of cassettes equipped with the infrared receiver compatible with the VMF system. VMF-SW: Water probe (L = 2.5m) used if required in place of the stand-ard unit supplied with the VMF-EOX. VMF-E19 and VMF-E191 thermo-stats for mounting it upstream of the valve
VMF-SW1: Additional water probe (L = 2.5m) to be used if required for 4-pipe systems with the VMF-E19 and VMF-E191 thermostats for maximum control in the cold range Water valves
VCZX: 3-way valve kit for single-coil fan coil, RH connections, (VCZ X4R) or LH (VCZ X41) for 4-pipe systems. With totally separate ‘heat-mg” and ‘cooling’ circuits. This kit consists of two 3-way insulated valves and four connections, complete with electrothermal actuators, insulating shells for the valves, and the relative hydraulic couplings. X4L version for fan coils with LH connections, and X4R for fan coils with RH connections. 230V-50Hz power supply.
VCZ: 3-way motorized valve kit. The kit consists of a valve with its insulating shell, an actuator, and relative pipe fittings. It can be installed on fan coils with both rights and left connections. If the valve is combined with the BCZS or BCZ6 condensate drain pan, to ensure better housing it is possible to remove the 3-way insulating shell. The kit consists of a valve with its insulating shell, an actuator, and relative pipe fittings. It can be installed on fan coils with both rights and left connections. If the valve is combined with the BCZS or BCZ6 condensate drain pan, to ensure better housing it is possible to remove the insulating shell. VCF44 – 45 – for the secondary coil: The 3-way motorized valve kit for the secondary coil heat only. The kit consists of a valve with its insulating shell, actuator, and relevant water fittings; it is suitable to be installed on the fan coils with right and left water connections.
VCZD: 2-way motorized valve kit. The kit consists of a valve, an actuator, and relative pipe fittings. It can be installed on fan coils with both rights and left connections.
VIP: Control and balancing combination valve for 2 and 4 pipe systems to install outside the unit, supplied without fittings and hydraulic components. The valve, can guarantee a constant water flow rate in the terminal, within its operating range. (Heating only) additional coil By: Single row hot water heat exchanger.
RX: Armoured electric coil with safety thermostat. Installation accessories
PC: Metal panel for the unit rear closing, SPCZ brackets are necessary to fix floor standing fan coils.
GA: Lower intake grille for encapsulated fan coils. Can also be used in wall- mounted or floor installations, the FIKIT accessory is needed only in the case of floor installation.
FIKIT: Metal supports for vertical installation of the GA grille
DSCZ4: Condensate drainage device.
BCZ: Condensate drip. If the valve is paired with the BCZS or BCZ6 condensate drip tray. the insulating shell can be removed to ensure better housing.
AMP: Wall mounting kit

Control panels

  1. Wall-mounting. If the unit intake exceeds 0.7A, or several units need to be managed with a single thermostat, board SIT3 and/or SITS is required.
  2. Probe for AER503IR-TX thermostats, if fitted.
  3. Cards for AER503IR-TX thermostats, if present, to be installed if the unit absorption exceeds 0,7 Ampere.
  4. Probe for AER503IR-TX thermostats, if fitted.
  5. Installation on the fan coil.

VMF system

For more information about the VMF system, refer to the dedicated documentation.
VMF system

Installation accessories

PERFORMANCE SPECIFICATION

AERMEC FCZ300A Fan Coil Floor Fan - dimmision1

Aermec reserves the right to make any modifications deemed necessary.
All data is subject to change without notice. Aermec does not assume responsibility or liability for errors or omissions.
FCZ_Y_UN50_09
www.aermec.com
Aermec S.p.A.
Via Roma, 996 – 37040 Bevilacqua (VR) – Italia Tel. 0442633111
-Telefax 044293577 www.aermec.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AERMEC User Manuals

Related Manuals