UNI-T UT253A Large Jaw Leakage Current Clamp Meter User Manual

June 6, 2024
UNI-T

UNI-T logo

UNI-T UT253A Large Jaw Leakage Current Clamp Meter

UNI-T UT253A Large Jaw Leakage Current Clamp Meter
image

warnings
Thank you for purchasing UNIT large jaw leakage current clamp meter. In order to use the product properly, please follow instructions below:

Read the user’s manual carefully. Strictly observe safety rules and notes mentioned in this manual.

  • Please use the meter carefully under any circumstance.
  • Pay attention to word labels and symbols on front and back panels
  • Clamp jaw should be kept clean, regularly maintained and prevented from any severe strike
  • Do not place and store the meter on sites exposed to high temperature, humidity, moisture condensing or strong sunshine
  • Please timely change battery when low battery is indicated.
  • Remove the battery away if the meter is not in use for a long time.
  • Please ensure right polarity is selected when changing battery.
  • Only authorized staff is allowed to use, discharge and repair the meter.
  • Stop using the meter and pack immediately for authorized treatment if further operation will cause potential risks.
  • danger symbol is used on the meter and in the manual to require the operator should observe safety rules
  • extreme danger mark is used in the manual to require the operator should strictly conform to the safety rules.

Introduction

UNIT large jaw leakage current clamp meter, supported by latest CT and digital integration technologies and coupled with large diameter clamp(80mm x 80mm, able to enclose 80mm cable or 96mm x 4mm flat steel ground wire) and automation function, is a professional tool for measuring leakage current, current and voltage. It can simultaneously measure one-way leakage current and three-way voltages and offer simultaneous display on the screen, which all together allow users to operate easily and quickly. The meter is widely used in electric power, communications, meteorology, railway, oil field, construction, metrology, R&D institutes, mining, etc. This kind of meter is designed with clamp iron core made with special alloy and latest magnetic screening technology, which make it able to avoid magnetic interference from outside and ensure high accuracy, stability and reliability all the year around. It contains interface that allows its maximum storage of sets of data to transfer into PC, thus facilitating further operations such as on-line monitoring, history lookup, dynamic display, history data recall, save and printing. Other functions such as backlight and data hold together with those mentioned above turn the meter a necessary tool for electrical safety testing.

Model Comparison

Model Range Resolution Jaw Size
UT253A 0.00mA~1200A 0.01mA 80mmX80mm
UT253B 0.0mA~2000A 0.1mA 80mmX80mm

Electric Symbols

Extreme danger! To avoid personal injury or accidents due to electric shock, observe safety rules strictly.

Danger! To avoid personal injury or accidents due to electric shock, please follow safety regulations.
Warning! Conform to safety notes, otherwise it may cause personal injury or damage to the meter.
Dual insulation
Alternating Current ( AC )
Direct Current C DC)

Technical Specifications

Functions

| to measure leakage current, current and three-phase

AC voltage

---|---

Power

| 6V DC(LR6 X 4 Alkaline dry battery,12 hours of battery

life)

Measuring Mode| Clamp-shape CT, integral mode

Jaw Size

| 80mm x 80mm (Able to clamp ct> 80mm conductor or 96mm X 4mm flat steel ground line)
Range| Current: AC 0.00mA~ 1200A
Resolution| Current: AC 0.01mA
Conductor Location| Placed at the center of clamp jaw
Data Save| Maximum 99 sets, indicated by ” FULL ” flash icon.
USB Port| Yes, for data transmission to PC for further data analysis
Measuring Accuracy (23°C ± 3°C, < 70%

RH, conductor located

at the center of jaw

| 0.00mA~ 300A: ± 1.5% ± 3dgt

300A~ 1200A: ± 2%± 3dgt

1200A~ 2000A: ± 3%± 3dgt

---|---
Communication Line| USB type, 1.8 meters long
Frequency| Self-identification between 50Hz and 60Hz
Function Switchover| Automatic
Sample Rate| about 2 times per second
Circuit Voltage| To measure AC voltage below 600V
Display Mode| LCD

Display Zone: 47 X 28.5mm

Dimensions| ( Long x wide x thick)275mm x 145mm x 40mm
Backlight| Controlled by I LIGHT I button
Data Hold| Data maintained: Indicated by ” HOLD” icon
Overload Display| Out of range, indicated by ” OL” icon
---|---
Auto Power Off| Automatically 15minutes later after power on, to

conserve power energy

Battery Voltage| Low battery icon displays with battery voltage

below 5.2V, please change batteries.

Weight| The meter,830g(battery and accessories included)
Operating Temperature/ Humidity|

0

-10 OC~  40 C :   < 80%rh

Storage Temperature/ Humidity|

O                                   0

-10 C~ 60 C: < 70%rh

Insulation Strength| AC 2kV/rms(Between iron core and housing)
Safety Standards

Followed

| IEC1010-1, IEC1010-2-032, Pollution Class 2, CAT III (600V)

Meter Description

  1. Clamp Jaw
  2. Function Buttons
  3. LCD display
  4. USB port
  5. Trigger
  6. Screws
  7. Battery cover
  8. Screw (to lock battery cover, 1pc)

Operating Instructions

  1. Power on/off
    Press I POWER I button to power on, display LCD and enter into measuring mode, repress to turn off the meter. The meter will automatically switch off 15 minutes later after power on. You should change the battery if dark LCD appears after power on and may be caused by low battery voltage. Under data save status, you need to press I HOLD I button to cancel the operation before press I POWER I button to power off the meter.

  2. Backlight Control
    Use I LIGHT I button to control backlight, suitable for dark sites and at night. The default is backlit status after power on.

  3. Data Hold and Save
    Under measuring mode, press I HOLD I button to maintain displayed data, indicated by “HOLD” icon, and repress to cancel the operation. The meter will automatically number current data at the time of saving, indicated by
    group number such as “SAVE NO.: 001” . Maximum data storage sets and is achieved when the “FULL” icon shows

  4. Data Access and Exit
    Under measuring mode, Press I MENU I to access data research with indication of “READ” icon. You can start data research from “R: 001″ , press ” [l:lfil ” button to increment by 1, I down I button to increment by 10 and I MENU I button to exit this status and return to measuring mode.

  5. Data Transmission to PC
    The accessory connection line is used for communication of the meter with PC. With the meter power on and the software running, several following operations such as history lookup, data recall, save, report sheet, history printing can all be performed. The more data the meter saves, the more time it will take to readout. History data can be saved in Txt or Excel format.

  6. Data Delete
    Press I CLEAR I button to select data clearing option under data access mode, then use I Left I or I Right I button to move the cursor for selecting “YES” or “NO” , finally press I MENU I button to confirm the operation or return to the measuring mode.

  7. Leakage Current, Current and Voltage Measurements.

| Dangerous Voltage! To avoid personal injury or accidents in case of electric shock, only trained and authorized staff is allowed to operate and must strictly observe safety rules
---|---
****| Danger! To avoid any damage to the meter or personal injury in

case of electric shock do not measure voltage above 600V

| Please Keep the jaw properly open or close when measuring

leakage current or current.

Try to place the conductor at the center of the jaw
****| Please keep the jaw clean and regularly maintained after finishing measurement.

Ensure correct wire connection to avoid short-circuit problem during voltage measurement

---|---
Disconnect test leads with measured lines before pulling them out of the meter in case of electric shock


| Clamping live and neutral wires is to measure leakage current of

electric instruments(2 wires needed)

Clamping the ground wire is to measure its leakage current (single

wire needed)

Clamping all three phases and four wires is to measure total

leakage current(four wires needed)

Clamping the main wire is to measure current of the main circuit

(single wire needed).

Measuring Reference Figure:

UNI-T UT253A Large Jaw Leakage Current Clamp Meter fig
8

Battery Replacement

Warning

  • To avoid potential risks do not measure when battery cover is not well placed.
  • Please ensure the right battery polarity, otherwise, it will damage the meter.
  • Change batteries timely when low battery icon displayed.
  • Take out batteries when not used for a long time.
    • The low battery icon displays with voltage lower than 5.2V, please change the battery timely.
    • Press the I POWER I button to switch off, loosen one screw on battery cover and open it after confirming the meter is off, finally change with new specified batteries and close the battery cover.
    • Press the ” I POWER I ” button to switch on and check if batteries are successfully replaced, if not, repeat the second step.

Packing List

The Meter|
---|---
Carrying case|
Data transmission software CD|
USB cable|
Battery(LR6 Alkaline Dry Battery)| 4PCs
Giftbox/User’s Manual/ Warranty Card/Certificate| 1 set

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>