1.1 Mounting instructions
Document code: DPD01577A
1.1.1 QDSH Simple operator panel kit

Factory Controls Vacon 20 X Simple Operator Panel - spare
kit

Frame size Description and type code Item Quantity
__ MU2 __ MU2 QDSH option spare kit 60S01208 Main switch 40A NLT40 and
operator panel assembly 1
MU2 cover for main switch 1
M4x14 screw 2
M5x23 screws 4
__ MU3 __ MU3 QDSH option spare kit 60S01209 Main switch 40A NLT40 and
operator panel assembly 1
MU3 cover for main switch 1
M4x14 screw 2
M5x23 screws 6

Table 1. Simple operator panel kit content.

1.1.2 Installation

  1. • Remove the cover from the drive. See the Figure 2.Factory Controls Vacon 20 X Simple Operator Panel - drive
  2. • Open only the inlet holes where you need to run the cables. Cables pass through this inlet hole.
  3. • Connect the supply cable to the Mains switch passing through the cable gland from the bottom side (use the cable gland for sealing the cable to the drive) and then through the terminal box as shown in the figure below.
  4. • Place the Simple Operator panel assembly with the cables inside the drive and fix it with its screws.
  5. • Connect the cables from the Mains switch to the line terminals. The cables have to be connected to the terminals L1, L2 and L3.
  6. • Fix the cables with the cable clamp.Factory Controls Vacon 20 X Simple Operator Panel - panel connected
  7. • Connect the GROUND wire to the proper terminal (see the yellow-green cable on Figure 3.
  8. • Connect the cables from the potentiometer and from the selector to the I/O control terminals. The cables have to be connected to the I/O terminals as shown in the Figure 3 and in the Table 2.
  9. • RED, BLUE and BLACK wires are signals from the potentiomenter.
  10. • YELLOW, WHITE and GREY wires are signal from the selector switch.
    Table 2. Control I/O terminal signal connections to the simple operator panel.

Standard I/O terminals

Terminal| Signal
A| RS485_A| Serial bus, negative
B| RS485_B| Serial bus, positive
1| +10 Vref| Reference output
2| AI1+| Analogue input, voltage or current
3| GND| I/O signal ground
6| 24Vout| 24V aux. voltage
7| DIN COM| Digital inputs common
8| DI1| Digital input 1
9| DI2| Digital input 2
10| DI3| Digital input 3
4| AI2+| Analogue input, voltage or current
5| GND| I/O signal ground
13| DO1| Digital output 1 common
14| DI4| Digital input 4
15| DI5| Digital input 5
16| DI6| Digital input 6
18| AO1+| Analogue signal (+output)
20| DO1+| Digital output 1
Function| Description| Wire colors| Terminal
---|---|---|---
Potentiomenter| 10V reference output| RED wire| 1
AI1+| BLUE wire| 2
AI1-| BLACK wire| 3
Switch selector| 24V auxiliary voltage| YELLOW wire| 6
digital input DI1| WHITE wire| 8
digital input DI2| GREY wire| 9
11. • Mount the plastic cover onto the drive with its screws and the HMI cap: the installation process has been completed.