LILYTECH ZL-6231A Temperature Controller Instruction Manual
- June 4, 2024
- LILYTECH
Table of Contents
LILYTECH ZL-6231A Temperature Controller
Introduction
ZL-6231A thermostat is for cooling or heating control, with IP65 front panel, buzzer beeping and warning function. There is a multifunction timer which is for incubator air exhaustion, or egg tray turning, or other application.
Specification
- Power supply: 185~245Vac, 50/60Hz
- Sensor: NTC, wire length is 2 meters
- Output: 10A, 250Vac resistance
- Setting range: -40~120℃
- Display range: -40~130℃
- Working: -10~45℃, 5~90%RH without dew
- Dimension: W78 x H34.5 x D71 (mm)
- Installation drilling : W71 x H29 (mm)
- Case materials: PC + ABS fire proof
- Protection level: IP65 (Front side only)
Display
Icon | Function | On | Off | Blinking |
---|---|---|---|---|
**** | R1 temp. control output | R1 Temp. Output energized | R1 Temp. Output | |
de-energized | Within protecting delay | |||
**** | **** |
Work mode
| Cooling mode| ****
—-
| ****
Setting set-point
| Heating mode
| Maintenance| —-| No failure| Has failure
| Warning| —-| No warning| Has warning
| R2 output| R2 energized| R2 de-energized|
**| Egg turn times reached| —-| —-| U46 > U45 (when U45 not equal zero)
Display| Remark**
---|---
E01| Sensor failure (short or open)
Hi| Room temp. is higher than the high limit
Lo| Room temp. is lower than the low limit
EE| Memory error
Err| Password error
iA| External warning
UnL| Parameters Will restore to factory default settings
Power up Display
The model (ZL-6231A) and software version (Version 2.0) will display after
power supplied:
Operation
Set Set-Point (Factory Default Setting = 37.8℃)
- Keep〖S〗depressed for 3 seconds to enter into the status. The current set-point value displays.
- Press〖▲〗or〖▼〗to set the value (keeping depressed can fast set).
- Press〖S〗to exit, and save the settings.
The status will exit, and the setting will not be saved if no key operation within 30 seconds.
Set System Parameters
- Keep〖P〗depressed for 3 seconds, digits show “—0”.
- Press〖▼〗to select the digit of the password, press〖▲〗to set the value of the digit.
- Press〖S〗to confirm: If the password is correct, enter into the parameter setting status, else display “Err”, and exit.
Set in parameter setting status:
- Press〖▲〗or〖▼〗to select the parameter code (see parameter code table below).
- Press〖S〗to display the value of the code. Press〖▲〗or〖▼〗to set the value. Press〖S〗to return to parameter code selection.
- Keep〖P〗depressed for 3 seconds to exit, and save the settings.
The status will exit, and the settings will not be saved if no key operation for 30 seconds.
Parameter Code Table
Code | Function | Range | Remark | Factory Default |
---|---|---|---|---|
U10 | Minimum time for Temp. Output to keep de-energized | 0 ~ 100 min | Only for | |
cooling | 0 | |||
U20 | Sensor calibration | -9.9 ~ +9.9℃ | 0.0 | |
U22 | Hysteresis for temperature control | 0.1 ~ +10.0℃ | 0.1 | |
U40 | Timer period 1, time unit | 0 ~ 2 | 0: sec; 1: min; 2: hour | 0 |
U41 | Timer period 1, time | 1 ~ 9999 | R2 on | 30 |
U42 | Timer period 2, time unit | 0 ~ 2 | 0: sec; 1: min; 2: hour | 1 |
U43 | Timer period 2, time | 1 ~ 9999 | R2 off | 60 |
U44 | R2 working mode | 1 ~ 2 | 1: Timer output |
2: Timer output + limit_protection
| 2
U45| Timer repeats times| 0 ~ 9999| If 0: Timer never stops running
Else: R2 never on, when U46 reaches U45
| 0
U46
| Timer counter
(the value saved to permanent memory once every hour, keeps even without power supply)
| ****
0 ~ 9999
| One period = timer period 1 + timer period 2
Clear to 0 before every hatching
| ****
0
U52| Over temp. warning delay| 0 ~ 180 min| | 0
U53| 1st over temp. warning delay after power supplied| 0 ~ 180 hour| 0:
disable| 0
U54| Temp. up limit (relative value)| 0.0 ~ 120.0℃| Absolute point = (Set-
point + U54)| 0.2
U55| Temp. low limit (relative value)| 0.0 ~ 120.0℃| Absolute point = (Set-
point – U55)| 37.8
U60
| ****
External input warning mode
| ****
0 ~ 4
| 0: disable 3: NC, locked
1: NO, locked 4: NC, unlocked
2: NO, unlocked
| ****
0
U61| Delay for external input warning| 0 ~ 120 min| | 0
U62| Buzzing warning| 0 ~ 1| 0: no waring / 1: enable warning| 0
U90| Control mode| CO/HE| CO: cool / HE: heat| HE
U99| Password| 0000 ~ 9999| When 0000, equals no password| 0000
Note:
- U46 will be saved to permanent memory once every hour.
- Limit Protection:
- Troom: Temperature of the room.
- SP: Temperature set point.
- When U44 = 2:
If Troom ≥ SP + U54 in heating mode (U90 = HE), or if Troom ≤ SP – U55 in cooling mode (U90 = CO), then R2 will be energized.
Control
-
Cooling Control (U90 = C0)
- If Troom ≥ Set-point + U22, and Temp. Output has been de-energized for U10, then Temp. Output energized.
- If Troom ≤ Set-point, then Temp. Output de-energized.
-
Heating Control (U90 = HE)
- If Troom ≤ Set-point – U22, then Temp. Output energized.
- If Troom ≥ Set-point, then Temp. Output de-energized.
-
Temp. Output Load Delay Protection (only for cooling control)
- After power supplied, Temp. Output could be energized after U10;
- After Temp. Output de-energized, it could be energized again after U10.
-
Buzzer Function
Every key press, there will be a short beep. Every confirmation key press, there will be a long beep. Every error operation, there will be three short beeps.
When there is failure, or external warning input: If U62 = 0, no buzzing warning. If U62 = 1, there will be continuous buzzing of warning.
The waring will stop, if press〖P〗, or warning condition disappears. -
External Warning Input
- NO: normal open. If open, no warning; if closed, warning.
- NC: normal close. If closed, no warning; if open, warning.
- Locked: Warning keeps after the external warning disappeared. Press〖P〗 to stop warning.
- Unlocked: Warning stops after the external warning disappeared.
Note: When there is external warning, the output(s) will be de-energized.
-
Sensor Fail
R1 stop energized. -
Sensor Calibration
The sensor can be calibrated by U20. -
Restore to Factory Default Settings
Keep〖P〗and〖▲〗depressed simultaneously for 5 sec, there will be a beep, and “UnL” displays.
Press〖▼〗twice, there will be a beep, all settings will be restored to factory default settings.
Installation
1st: Insert into drilling hole
Attention
- Wiring work should be manipulated by certified technicians.
- Wrong connection could damage the controller, and the loads. Power supply to terminal 7 and 8 to check the controller. If there is a multimeter, check the outputs, as well as input, by the help of settings.
- Sensor and input signal wires should not be laid together with power supply wire, and even in same pipe.
- Sensor wire is better as short as possible. Not wind the redundant length wire to electrical noise equipment.
- The loads should be within the specification of the controller output driving ability. If using ac/dc module as load, or tungsten lamp, or motor, following the below requirements to avoid surging current damaging or shorten the lifetime of the controller outputs:
- For ac/dc module as load, the rated current should be no more 1/10th of output specification under pure resistance.
- For tungsten lamp as load, the rated current should be no more 1/15th of output specification under pure resistance.
- For motor, the rate current should be no more 1/5th of output specification under pure resistance.
- For example: if drive a 1500W tungsten lamp with 7A (pure resistance spec.) relay, the relay contactor will be burnt immediately.
- Don’t touch inside components.
- Avoid installing controller in the following environment:
More wet than 90%RH, or easily dew; Vibrating, or will be shocked; Possible sprayed; Under erosive air; Under explosive air.
Electrical Wiring