gulplug ZBRTC1 Harmony Wireless Current Sensor User Manual
- June 16, 2024
- gulplug
Table of Contents
**gulplug ZBRTC1 Harmony Wireless Current Sensor User Manual
**
Product
Product: Electric Energy Estimator
The ZBRTC1, ZBRTC2 and ZBRTC3 gulplug sensors are designed to estimate the consumption of electrical equipment. Wireless and battery-free, they communicate by ZigBee GreenPower radio with the Harmony Hub ZBRN1 / ZBRN2 product.
Contacts
Address : Schneider Electric SAS, 35 rue Joseph Monier
F-92506 Rueil Malmaison
Web : https://www.se.com/
Representative: Schneider Electric Limited Stafford Park 5
Telford, TF3 3BL, UK
To display, print or download the latest addition to the user manual, visit the website.
Safety instructions
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
DANGER
- Respect the measurement category and the voltage and current limits indicated in the product characteristics.
- Respect the type of cable on which the product must be installed.
- Do not put your finger inside the clamp during installation.
Failure to follow these instructions will result in death or serious injury.
EN : Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
ATTENTION
UNINTENDED EQUIPMENT OPERATION
- Always read the safety instructions before using this equipment.
- Read the instructions carefully.
- Only use this device for its intended purpose. Failure to do so could impair the protection provided by this device.
- Examine the product before installing and operating it, look for any cracks or defects.
- Check the insulation of the cable connecting the clamp and the box. If you detect any anomalies, do not install the product.
- Only use the product under environmental conditions for which it was designed.
- Comply with local and national safety standards.
- Only authorized persons may install the product.
- Use suitable PPE (personal protective equipment) when installing the product (mask, rubber gloves, regulatory clothing).
- Store the product according to the conditions indicated.
- Service the product according to the conditions indicated.
- Never open or dismantle the product.
Failure to follow these instructions can result in injury, or equipment damage.
Symbols
The table contains the list of symbols used on the product and throughout this manual.
Symbols | Description |
---|---|
Complies with European Union directives. | |
Warning, danger, refer to the manual. | |
Alternating current (AC). | |
The device should never be disposed of with household waste. | |
Do not apply to or remove from conductors at dangerous voltages. | |
CAT III | Measurement category III applies to the test and measurement circuits |
connected to parts of the building’s low-voltage network installation.
Installing the product
Since the product is a component, the installer must fit the electrical
enclosure. The product must be installed in equipment provided with its own
fire protection enclosure.
The product must be clamped on a cable respecting its characteristics and
including at least one insulating sheath corresponding to a main insulation.
The cable diameter and the currents must respect the values given below.
Otherwise, do not install the product.
ZBRTC1 | Ø ≤ 9,8 mm / 0,38 in | 0,5…35 A |
---|---|---|
ZBRTC2 | Ø ≤ 24 mm / 0,94 in | 2,5…180 A |
ZBRTC3 | Ø ≤ 35 mm / 1,38 in | 7…500 A |
The current clamp must be closed
Installation
Move the opening clamp of the ZBRTC* sensor around the voltage phase to be measured.
Close the clamp until you hear a “click”. Check that the clamp is closed: lug clipped.
Pairing the product with the Harmony Hub
Use the knob to browse through the menus of the Harmony Hub ZBRN1 / ZBRN2.
Turn the knob to select a value and press it to validate a selection. Return
to the previous menu by pressing twice quickly.
The statuses of the sensor locations are indicated as follows on the display
(example for input No. 1)
The input is free (no sensor paired with it).
The input already contains a paired sensor.
The input contains a sensor but indicates that the Harmony HUB is expecting a
communication from the sensor.
Pairing
Example of pairing a ZBRTC* (0xFFD0ABCD) on input No. 20 of the Harmony Hub
ZBRN1 / ZBRN2
*Modifying the ZBRTC parameters
* Example of modifying the voltage and power factor parameters of a ZBRTC
(0xFFD0ABCD) for which the voltage is changed from 230 V to 110 V and the
power factor from 1.0 to 0.8.
Harmony Hub Modbus registers
The ZBRTC is a Type 2 sensor in the Harmony Hub ZBRN1 / ZBRN2.
For sensor input N [0..59] of the Harmony Hub ZBRN1 / ZBRN2, the register
address is 10 + 33 N + Offset.
Type 2 data in the Harmony Hub ZBRN1 / ZBRN2. The following table lists the registers of the ZBRTC* sensor (Type 2):
Offset | Nom | Accès | Channel status | Description | Unité |
---|---|---|---|---|---|
+0 | Type Type | Bit 0..Bit 7 : transmitter type / Type de – 0 : none- | |||
[1..6] : transmitter type / Type de Bit 8..Bit 15 : Spare | Contains the |
transmitter type associated with the input le type de
+1| Timeout RSSI| R| Bit 0..Bit 7 : Timeout- True : 0xFF (timeout expired /
timeout )- False : 0x00Bit 8..Bit 15 : RSSI- (-127..127 dBm)- 128 : invalid
value / invalie| Contains the RSSI timeout and value (radio signal power)le
timeout et la du RSSI (puissance du signal radio)
+2| Timestamp| R| Two registers (Most Significant Byte first)Deux registres
(Most Significant Byte en premier)- 0xFFFF FFFF : invalid value / – 0x00FF
0000 : rolling value| Contains the timestamp details Contient le détail du
timestamp| µs/320
+3
+4| Spare| –| –| –
+5| Spare| –| –| –
+6| Temperature| R| – 0x8000 : invalid value / valeur invalide| Contains the
temperature| 0.01 °C / 32°F
+7| CurrentCourant| R| | Contains the le courant| 0.01 A
+8| Apparent power Puissance| R| Two registers (Most Significant Byte
first)Deux – 0xFFFF : invalid value /| Contains the apparent| 0.01 VA
+9
+10| Active power Puissance active| R| Two registers (Most Significant Byte
first)Deux (Most Significant Byte premier)- 0xFFFF : invalid value / invalid|
Contains the active power la puissance active(V *| 0.01 W
+11
+12| Sensor energy| R| Four registers (Most Significant Byte first)Quatre
(Most Significant Byte en premier)- 0xFFFF FFFF : invalid value| Contains the
sensor energy| 0.01 VA.h
+13
+14
+15
+16| Apparent energy| R| Four registers (Most Significant Byte first)Quatre
(Most Significant – 0xFFFF FFFF : invalid value| Contains the apparent| 0.01
VA.h
+17
+18
+19
+20| Active energy active| R| Four registers (Most Significant Byte
first)Quatre (Most Significant Byte premier)- 0xFFFF FFFF invalid value|
Contains the active| 0.01 Wh
+21
+22
+23
+24..32| Spare /| –| | –|
Servicing and cleaning the device
No special servicing is required.
For cleaning, reinstall the product and clean with a dry or slightly damp
cloth.
Specifications
The product requires no calibration throughout its lifetime. If the current estimations are incorrect, return the product to us. The product specifications are given below /
Operation
Environment …………………………………………………………………………………………………………Indoor
Altitude / Altitude …………………………………………………………………………………………………………………………..0…2000 m
Temperatures / Températures…………………………………………………………………………………………………………..-20…60 °C
/ -4…140 °F
Maximum relative humidity, no condensation / Humidité relative maximum, sans
condensation………………90 %…35 °C / 95 °F
75 %…40 °C / 104 °F
45 %…50 °C / 122 °F
Pollution degree / Degré de pollution
………………………………………………………………………………………………..Poll 2
Network voltage fluctuation / Fluctuation de la tension sur réseau : +-10 % of
the rated voltage / +-10% de la tension
Accepts the occurring on the power supply network / mentation
Storage
Altitude …………………………………………………………………………………………………………………………..0…2000 m
Temperatures / Températures…………………………………………………………………………………………………………..-30…90 °C
/ -22…194 °F
Maximum relative humidity, no condensation condensation………………90 %…35 °C / 95
°F
75 %…40 °C / 104 °F
45 %…50 °C / 122 °F
Dimensions / Dimensions (L×l×h)……………………………………………………………………………………………………….16 × 4
× 4 cm / 0.63 x 0.16 x 0.16 in
Weight / Poids
ZBRTC1…………………………………………………………………………………………………………………………………………..60 g
ZBRTC2…………………………………………………………………………………………………………………………………………..240 g
ZBRTC3…………………………………………………………………………………………………………………………………………..426 g
Measurement category / …………………………………………………………………………………………………CAT III
Overvoltage category surtension………………………………………………………………………………………………..CAT III
Safety
General / Générale …………………………………………………………………………………………………… CEI 61010-1 :
pollution degree 2
Measurement ……………………………………………………………………………………………. CEI 61010-2-032 : CAT III
Electromagnetic compatibility (EMC) / (CEM)……………………………………………….. EN 61326-1
Weight ZBRTC1 …………………………………………………………………………………………………………..60 g
ZBRTC2………………………………………………………………………………………………240 g
ZBRTC3…………………………………………………………………………………………………………………………426 g
Measurement category ……………………………………………………………………………………….CAT III
Overvoltage category surtension………………………………………………………………………………………….CAT III
General ……………………………………………………………………………………………. CEI 61010-1 : pollution degree
2
Measurement / ………………………………………………………………………………… CEI 61010-2-032 : CAT III
Electromagnetic compatibility (EMC) ………………………………………….. EN 61326-1
Electrical characteristics
Measured current range / Plage de courant
ZBRTC1 …………………………………………………………………………………………………………………………….. 0,5 A…35 A
ZBRTC2 …………………………………………………………………………………………………………………………….. 2,5 A…180 A
ZBRTC3 …………………………………………………………………………………………………………………………….. 7 A…500 A
Maximum voltage
ZBRTC1 ………………………………………………………………………………………………………….. 300 Vac
ZBRTC2 …………………………………………………………………………………………………………. 600 Vac
ZBRTC3 …………………………………………………………………………………………………………… 600 Vac
Accuracy ……………………………………………………………………………………………….. +/- 3% FSD (Full Scale Deflection)
Estimated power range at 230 V
ZBRTC1 ………………………………………………………………………………………………………………………….. 115 W…8 050 W
ZBRTC2 …………………………………………………………………………………………………………………………… 575 W…41 400 W
ZBRTC3 …………………………………………………………………………………………………………………….. 1 610 W…115 000 W
Estimated power range at 110 V
ZBRTC1 …………………………………………………………………………………………………………………………….. 55 W…3 050 W
ZBRTC2 …………………………………………………………………………………………………………………………….. 275 W…19 800 W
ZBRTC3 …………………………………………………………………………………………………………………………….. 770 W…55 000 W
Energy estimation unit ………………………………………………………….. kWh
Operating frequency …………………………………………………………………….. 50 Hz et 60Hz
Temperature accuracy……………………………………………………………….. +/- 5% FSD (Full Scale Deflection)
Diameter of measured conductor
ZBRTC1 ……………………………………………………………………………………………………………………. ≤ 9.8 mm / 0,38 inch
ZBRTC2 ……………………………………………………………………………………………………………….. ≤ 24 mm / 0,94 inch
ZBRTC3 ……………………………………………………………………………………………………………………. ≤ 35 mm / 1,38 inch
Calibration………………………………………………………………………………………………….. Non
Radio protocol radio……………………………………………………………………………………….. ZigBee Green Power
Radio repeater radio…………………………………………………………………………………………. Non
Radio frequency ……………………………………………………………………………………. 2,4 GHz
Radio power radio……………………………………………………………………………………………. +5 dBm
Radio transmission rate (Time interval between 2 radio transmissions)
ZBRTC1 …………………………………………………………………………………………………………………………. 27s…0,5 A
0,3s…35 A
ZBRTC2 ………………………………………………………………………………………………………………………. 27s…2,5 A
0,3s…180 A
ZBRTC3 ……………………………………………………………………………………………………………….. 27s…7 A
0,3s…500 A