WALTLOW DIN-A-MITE Style B Solid State Power Controller
DIN-A-MITE Solid-State Power Controller
Please consult this user’s manual when you place your new DIN-A-MITE into
service. It contains all the necessary information to mount and wire the
product into the application. This manual also contains all user-pertinent
specifications and semiconductor fusing recommendations. Refer to national and
local electrical code safety guidelines whenever you install electrical
equipment.
This DIN-A-MITE product is capable of switching up to 40 amps single-phase; 33
amps 3-phase, 2-leg; and 22 amps 3-phase, 3-leg at 600VÅ (ac). (See the output
rating curve in the specifications section of this manual.) The DIN- A-MITE
is electrically touch-safe, and includes DIN rail or standard back panel
mounting. An optional shorted SCR (silicon controlled rectifier) alarm feature
is available on specific models. UL® 508-listed, C-UL® and CE with filter.
The DIN-A-MITE solid-state power controller is designed and manufactured by
Watlow in Winona, Minnesota.
General Specifications
Operator Interface
- Command signal input and indication light
- Alarm output and indication light
- Input indicator LED
Amperage Rating
- See the output rating curve chart on page 3.
- Ratings are into a resistive heater load.
- Maximum surge current for 16.6 milliseconds, 380 A peak
- Maximum I2t for fusing is 4000 A2s
- Latching current: 200mA minimum
- Holding current: 100mA minimum
- Off-state leakage 1mA at 25°C (77°F) maximum
- Power Dissipation: 1.2 watts per amp switched
- 200KA SCCR type 1 and 2 approved with the recommended fusing (see page 3)
Line Voltage
- 24 to 48V~ (ac) units: 20.4V~ minimum to 53V~ maximum
- 120 to 240V~ (ac) units: 48V~ minimum to 265V~ maximum
- 277 to 600V~ (ac) units: 85V~ minimum to 660V~ maximum
Control Mode, Zero-Cross
- Input Control Signal Type C: VÃŽ (dc) input contactor. To increase service life, the cycle time should be less than 3 seconds.
- Input Control Signal Type K: V~ (ac) input contactor. To increase service life, the cycle time should be less than 3 seconds.
- Input Control Signal Type F: 4 to 20mAÃŽ (dc) proportional variable time base control.
Input Command Signal
- AC contactor 24VÅ ±10%, 120VÅ +10%/-25%, 240VÅ (ac) + 10%/-25% @ 25mA maximum per controlled leg
- Do not use the DIN-A-MITE Vac-input models with a temperature controller that includes an RC snubber circuit across its output. Remove the RC snubber circuit before placing the DIN-A-MITE into service.
- DC Contactor 4.5VÃŽ to 32VÃŽ (dc): maximum current @ 4.5VÃŽ (dc) is 6.0mA per leg, plus 2mA per LED used.
- Loop powered linear current 4mAÎ to 20mAÎ (dc): loop-powered. Input Type F0 option only. (Requires current source with 8.0VÃŽ (dc) available. No more than two DIN-A-MITE inputs connected in series)
- Linearity (Input Control Signal Type F)
- Full on point 19.5 to 19.9mAÎ (dc), maximum voltage of 6.2V peak.
- ±5% input to output power accuracy, 0% to 100% of span (4.3 to 19.7mA).
- Temperature stability is less than 0.15%/°C change. Alarm (not available on multizone models)
Shorted SCR Alarm Option
- Alarm state when the input command signal off and a 10 A or more load current is detected by the current transformer (two turns required for 5A and three turns for 2.5A).
Alarm output
- Energizes on alarm, non-latching
- Triac 24 to 240V~ (ac), external supply with a current rating of 300mA @ 25°C (77°F), 200mA @ 50°C (122°F), 100mA @ 80°C (176°F) and a holding current of 200µA with a latching current of 5mA typical.
Agency Approvals
- ROHS
- CE with proper filter: 2004/108/EC Electromagnetic Compatibility Directive EN 61326: Industrial Immunity Class A emissions 2006/95/EC Low Voltage Directive EN 50178 Safety Requirements Installation category III, pollution degree 2
- ®UL508 listed and C-UL®, File E73741
Input Terminals
- Compression: Will accept 0.2 to 1.5 mm2 (24 to 16 AWG) wire
- Torque to 0.5 Nm (4.4 in-lb) maximum with a 3.5 mm (1/8 in) blade screwdriver
- Wire strip length 5.5 mm (0.22 in)
- Line and load wire insulation rating must be 75C or higher, copper conductor only
Line and Load Terminals
- Compression: Will accept 0.75 to 10 mm2 (18 to 8 AWG) wire
- Torque to 1.4 Nm (12 in-lb) with a 6.4 mm (1/4 in) blade screwdriver, or a Type 1A #2 Pozi driver.
- Retorque after 48 hours to minimize wire cold flow.
- Retorque line and load terminals every 3 to 6 months.
- Wire strip length 6.35 mm (0.25 in)
- Ground terminal use spade terminal for No. 8 screw, with upturned lugs.
Operating Environment
- See the output rating curve.
- 0 to 90% RH (relative humidity), non-condensing
- Storage temperature: -40 to +85°C (-40 to 185°F)
- Insulation only tested to 3,000 meters
DIN Rail Mount
- DIN EN 50022, 35 mm by 7.5 mm
- Minimum clipping distance: 34.8 mm (1.37 in)
- Maximum clipping distance: 35.3 mm (1.39 in)
Note: Mount cooling fins vertically.
Back Panel Mount
- Four mounting holes M4 (No. 8) fastener
Weight
- 0.7 kg (1.6 lb)
Specifications are subject to change without notice.
DIN-A-MITE B Ordering Information
To order, complete the code number on the right with the information below:
Note:
- Recommended fusing options to meet 200KA SCCR, type 1 and 2 approved. All other fuse and SCR combinations are defaulted to 5KA SCCR per UL508A and NEC guidelines.
Recommended Fuse and Fuse Holder
Fuse| Watlow Semiconductor| Bussmann Semiconductor| Watlow
Combination| Bussmann Combination
20A| 17-8020| FWC20A10F| 0808-0325-0020| DFJ20
25A| 17-8025| FWC25A14F| 0808-0325-0025| DFJ25
32A| 17-8030| FWP32A14F| 0808-0325-0030| DFJ30
40A| 17-8040| FWP40A14F| 0808-0325-0040| DFJ40
50A| 17-8050| FWP50A14F| 0808-0325-0050| DFJ50
**Holders (single)
Fuse| Watlow| Bussmann| Ferraz| Bussmann Combination**
20A| 17-5110| – – – –| USM1i| – – – –
25A| 17-5110| – – – –| USM1i| – – – –
32A| 17-5114| – – – –| USM141i| – – – –
40A| 17-5114| – – – –| USM141i| – – – –
15 to 30A| 0808-0326-1530| – – – –| – – – –| CH30J1i
35 to 60A| 0808-0326-3560| – – – –| – – – –| CH60J1i
Mount
- Push the unit in and down to catch the rail hook on top of the rail.
- Rotate the bottom of the unit in toward the rail.
- The rail clasp will audibly “snap” into place. If the DIN-A-MITE does not snap into place, check to see if the rail is bent.
- Mount the cooling fins vertically.
Dismount
- Press down on the release tab while rotating the unit up and away from the rail.
Unit Dimensions – Rail-Mounted
WARNING : Only authorized and qualified personnel should be allowed to
install and perform preventive and corrective maintenance on this unit.
Failure to follow this guideline could result in damage to equipment, and
personal injury or death.
WARNING: Hot surface, do not touch the heat sink. Failure to follow this
guideline could result in personal injury. Mount the cooling fins vertically.
Input Wiring
WARNING: Use National Electric (NEC) or other country-specific standard
wiring practices to install and operate the DIN-A-MITE. Failure to do so may
result in damage to equipment and property, and/or injury or loss of life.
WARNING: Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above
configuration. In phase-to-neutral, 100 VÅ (ac) and above applications, L2 is
neutral and must not be fused or switched. Failure to follow this guideline
could result in personal injury or death.
Multizone Input Wiring
WARNING: Only authorized and qualified personnel should be allowed to
install and perform preventive and corrective maintenance on this unit.
Failure to follow this guideline could result in damage to equipment, and
personal injury or death.
WARNING: Do not use the DIN-A-MITE Vac-input models with a temperature
controller that includes an RC snubber circuit across its output. Remove the
RC snubber circuit before placing the DIN-A-MITE into service.
NOTE: Shorted SCR (silicon- controlled rectifier) alarm option not
available with multizone input option.
Multizone Output Wiring
NOTE: Independent loads do not have to be on the same phase.
NOTE: Terminals 2 and 5 not to exceed 40A.
NOTE: Use a grounding conductor terminal plate (fork terminal) having
upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm2
(10 AWG) wire.
Torque Guidelines
- Properly torque line and load terminals to 1.4 Nm (12 in-lb).
- Retorque after 48 hours to minimize wire cold flow.
- Retorque line and load terminals every 3 to 6 months.
Single-phase Output
3-phase, 2-leg Output
WARNING:
Use National Electric (NEC) or other country-specific standard wiring
practices to install and operate the DIN-A-MITE. Failure to do so may result
in damage to equipment and property, and/or injury or loss of life.
WARNING:
Wiring examples show L2 in phase-to-phase, 200VÅ (ac) and above configuration.
In phase-to-neutral, 100VÅ (ac) and above applications, L2 is neutral and must
not be fused or switched. Failure to follow this guideline could result in
personal injury or death.
3-phase, 3-leg Output
WARNING:
Only authorized and qualified personnel should be allowed to install and
perform preventive and corrective maintenance on this unit. Failure to follow
this guideline could result in damage to equipment, and personal injury or
death.
NOTE:
Use a grounding conductor terminal plate (fork terminal) having upturned lugs
or the equivalent to hold the wire in position. Maximum 6 mm2 (10 AWG) wire.
Torque Guidelines
- Properly torque line and load terminals to 1.4 Nm (12 in-lb).
- Retorque after 48 hours to minimize wire cold flow.
- Retorque line and load terminals every 3 to 6 months.
Current Transformer and Alarm Wiring
3-phase, 2-leg Current Transformer Wiring
WARNING: Use National Electric (NEC) or other country-specific standard
wiring practices to install and operate the DIN-A-MITE. Failure to do so may
result in damage to equipment and property, and/or injury or loss of life.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to
include an intermediate relay for each DIN-A-MITE used.
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above
configuration. In phase-to-neutral, 100VÅ (ac) and above applications, L2 is
neutral and must not be fused or switched. Failure to follow this guideline
could result in personal injury or death.
3-phase, 3-leg Current Transformer Wiring
WARNING:
Only authorized and qualified personnel should be allowed to install and
perform preventive and corrective maintenance on this unit. Failure to follow
this guideline could result in damage to equipment, and personal injury or
death.
Torque Guidelines
- Properly torque line and load terminals to 1.4 Nm (12 in-lb).
- Retorque after 48 hours to minimize wire cold flow.
- Retorque line and load terminals every 3 to 6 months.
System Wiring Example
WARNING: Use National Electric (NEC) or other country-specific standard
wiring practices to install and operate the DIN-A-MITE. Failure to do so may
result in damage to equipment and property, and/or injury or loss of life.
WARNING: Wiring examples show L2 in phase-to-phase, 200 VÅ (ac) and above
configuration. In phase-to-neutral, 100 VÅ (ac) and above applications, L2 is
neutral and must not be fused or switched. Failure to follow this guideline
could result in personal injury or death.
WARNING: Only authorized and qualified personnel should be allowed to
install and perform preventive and corrective maintenance on this unit.
Failure to follow this guideline could result in damage to equipment, and
personal injury or death.
NOTE: If you plan to wire multiple DIN-A-MITE alarm outputs, you need to
include an intermediate relay for each DIN-A-MITE used.
Torque Guidelines
- Properly torque line and load terminals to 1.4 Nm (12 in-lb).
- Retorque after 48 hours to minimize wire cold flow.
- Retorque line and load terminals every 3 to 6 months.
Latching Alarm Option (models DB – – S _ )
Alternative Latching Alarm Circuit
If there is a need for a latching alarm, the DIN-A-MITE alarm circuit could be
used as shown at right in the latching alarm example. If the DIN-A-MITE triac
alarm output energizes, it will energize the RY1
(external alarm relay) mechanical relay coil. Once the RY1 coil is energized
it will latch on (via the RY1A normally open contact) until the power to the
relay is removed. You could cycle the power via a reset switch. The RY1B
contact can be used for alarm signaling.
Ungrounded Delta or Wye Load
Non-latching Alarm Option (models DB – – S _ )
Shorted SCR (silicon-controlled rectifier) Alarm Non-latching Operation
The shorted SCR detector compares the input command signal and actual load
current. If load current is present without an input signal then the shorted
SCR alarm will energize the alarm triac output. This is a non-latching alarm.
This output can be used to drive various indication devices, such as a coil,
light, buzzer, etc. See the alternative latching circuit section below.
NOTE: Use a grounding conductor terminal plate (fork terminal) having
upturned lugs or the equivalent to hold the wire in position. Maximum 6 mm2
(10 AWG) wire.
NOTE: The current transformer must be in the center uncontrolled leg on a
2-leg DIN-A-MITE.
Declaration of Conformity
DIN-A-MITE® “B” Power Controller
WATLOW Electric Manufacturing Company 1241 Bundy Blvd. Winona, MN 55987 USA
Declares that the following products:
- Designation: DIN-A-MITE® “B” Power Control
- Model Numbers: DB (1, 2, 3, 4, 8 or 9) 0 – (02, 24 or 60)(CX, FX, K1, K2, K3) – (0 or S)(followed by any 3 letters or numbers) (where X = any number 0-9)
- Classification: Power Control, Installation Category III, Pollution degree 2, IP20
- Rated Voltage: 24 to 600 V~ (ac), 50 or 60 Hz
Meets the essential requirements of the following European Union Directives by
using the relevant standards show below to indicate compliance.
2004/108/EC Electromagnetic Compatibility Directive
- EN 61326-1: 2013 Electrical equipment for measurement, control and laboratory use – EMC requirements (Industrial Immunity, Class A1,2,4 Emissions) Not for use in a Class B environment without additional filtering.
- EN 61000-4-2:2009 Electrostatic Discharge Immunity
- EN 61000-4-3:2010 Radiated Field Immunity 10V/m 80 MHz- 1GHz, 3V/m 1.4GHz-2.7GHz
- EN 61000-4-4:2012 Electrical Fast-Transient / Burst Immunity
- EN 61000-4-5:2006 Surge Immunity (Reviewed to IEC 61000-4-5 2014)
- EN 61000-4-6:2014 Conducted Immunity
- EN 61000-4-11:2004 Voltage Dips, Short Interruptions and Voltage Variations
- EN 61000-3-2:2009 Harmonic Current Emissions (Reviewed to IEC 61000-3-2 2014)
- EN 61000-3-3:2013 Voltage Fluctuations and Flicker3 ≤ 16A
- EN 61000-3-11:2000 Voltage Fluctuations and Flicker ≤ 75A with conditional connection
NOTES
- Use of an external filter is required to comply with conducted emissions limits. See note 4 below.
- A Line Impedance Stabilization Network (LISN) was used for conducted emissions measurements.
- To comply with flicker requirements, command signal models F0 and F1 will require a reduced source impedance. Cycle time on ON/OFF models CX, and K1, K2, K3 may need to be up to 175 seconds at 16A or have a reduced source impedance.
2006/95/EC Low-Voltage Directive
Required External EMI Filters for DIN-A-MITE with More Than 6 Amp Loads
An external ElectroMagnetic Interference (EMI) filter must be used in
conjunction with the DIN-A- MITE for loads in excess of six amperes (6A) at
150 to 250 KHz. Watlow has verified that a tank filter will suppress EMI
created by SCR power controllers to comply with the conducted emissions
limits.
DIN-A-MITE EMI Filters
Description| Crydom Filter| Watlow Filter
Single-phase, 230VÅ (ac)| 1F25| 14-0019
Three-phase, 440VÅ (ac)| 3F20| 14-0020
WARNING: Tank filters may suppress desirable communications carried on
power lines in the 150 to 250 KHz region. The filters may suppress carrier
current such as that used for infant monitors and medical alert systems.
Verify that suppressed carrier current or other desirable communications on
power lines creates no hazard to people or property. Failure to observe this
warning could result in damage to property, and or injury to death for
personnel.
WARNING: All filter installation and wiring must be performed by
qualified personnel and conform to local and national electrical codes. In-
line power filters have been shown to properly suppress EMI; however, these
filters must be rated for the entire load current and are generally more
expensive than the tank filter specified. An In-line filter may be required if
carrier current communications are used on site.
Warranty
The Watlow DIN-A-MITE is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow’s obligations hereunder, at Watlow’s option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, abuse or improper fusing.
Technical Assistance
If you encounter a problem with your Watlow power controller, review your configuration information to verify that your selections are consistent with your application: inputs, outputs, alarms, limits, etc. If the problem persists, you can get technical assistance from your local Watlow representative, by e-mailing your questions to wintechsupport@watlow.com or by dialing +1 507-494-5656 between 7 a.m. and 5 p.m., Central Standard Time (CST). Ask for an Applications Engineer. Please have the following information available when calling:
- Complete model number
- All configuration information
- User’s Manual
- Wiring diagram of your system
The DIN-A-MITE B User’s Manual is copyrighted by Watlow, Inc., © January 2016, with all rights reserved.
Return Material Authorization (RMA)
- Call Watlow Customer Service, 507-454-5300, for a Return Material Authorization (RMA) number before returning any item for repair. We need this information:
- Ship to address
- Bill to address
- Contact name
- Phone number
- Method of return shipment
- Your P.O. number
- Detailed description of the problem
- Any special instructions
- Name and phone number of person returning the product.
- Prior approval and an RMA number from the Customer Service Department is needed when returning any product for credit, repair or evaluation. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis.
- After we receive your return, we will examine it and try to verify the reason for returning it.
- In cases of manufacturing defect, we will enter a repair order, replacement order or issue credit for material returned.
- To return products that are not defective, goods must be be in new condition, in the original boxes and they must be returned within 120 days of receipt. A 20 percent restocking charge is applied for all returned stock controls and accessories.
- If the unit is unrepairable, it will be returned to you with a letter of explanation.
- Watlow reserves the right to charge for no trouble found (NTF) returns.
How to Reach Us
Corporate Headquarters
Watlow Electric Manufacturing Company 12001 Lackland Road
St. Louis, MO 63146
Sales: 1-800-WATLOW2
Manufacturing Support: 1-800-4WATLOW Email:
info@watlow.com
Website: www.watlow.com
From outside the USA and Canada:
Tel: +1 314-878-4600
Fax: +1 314-878-6814
Latin America
Watlow de México S.A. de C.V.
Av. Fundición No. 5
Col. Parques Industriales
Querétaro, Qro. CP-76130
Mexico
Tel: +52 442 217-6235
Fax: +52 442 217-6403
Europe
Watlow France
Tour d’Asnières.
4 Avenue Laurent Cély
92600 Asnières sur Seine France
Tél: + 33 (0)1 41 32 79 70 Télécopie: + 33(0)1 47 33 36 57 Email:
info@watlow.fr
Website: www.watlow.fr
Watlow GmbH
Postfach 11 65, Lauchwasenstr. 1 D-76709 Kronau
Germany
Tel: +49 (0) 7253 9400-0
Fax: +49 (0) 7253 9400-900 Email: info@watlow.de
Website: www.watlow.de
Watlow Italy S.r.l.
Viale Italia 52/54
20094 Corsico MI
Italy
Tel: +39 024588841
Fax: +39 0245869954
Email: italyinfo@watlow.com Website:
www.watlow.it
Watlow Ibérica, S.L.U.
C/Marte 12, Posterior, Local 9
E-28850 Torrejón de Ardoz Madrid – Spain
T. +34 91 675 12 92
F. +34 91 648 73 80
Email: info@watlow.es
Website: www.watlow.es
Watlow UK Ltd.
Linby Industrial Estate
Linby, Nottingham, NG15 8AA United Kingdom
Telephone: (0) 115 964 0777
Fax: (0) 115 964 0071
Email: info@watlow.co.uk Website:
www.watlow.co.uk
From outside The United Kingdom: Tel: +44 115 964 0777
Fax: +44 115 964 0071
Asia and Pacifi c
Watlow Singapore Pte Ltd.
16 Ayer Rajah Crescent,
06-03/04,
Singapore 139965
Tel: +65 6773 9488 Fax: +65 6778 0323
Email: info@watlow.com.sg Website:
www.watlow.com.sg
Watlow Australia Pty., Ltd.
4/57 Sharps Road
Tullamarine, VIC 3043
Australia
Tel: +61 3 9335 6449
Fax: +61 3 9330 3566
Website: www.watlow.com
Watlow Electric Manufacturing (Shanghai) Company
1118 Fangyuan Road, Anting Industrial Park, Jiading, Shanghai, PRC 201203
People’s Republic of China
Tel: +86 21 39509510
Fax: +86 21 5080-0906
Email: info@watlow.cn
Website: www.watlow.cn
Tel: 03-3518-6630 Fax: 03-3518-6632
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>