solarMD SS4143-01 Advanced Lithium-Ion Battery Instruction Manual
- June 4, 2024
- solarMD
Table of Contents
Advanced Lithium-Ion Battery
Instruction Manual
SS4143-01
Advanced Lithium-Ion battery
Introduction
This manual is intended to provide assistance to an installer for the
installation and commissioning of the range of Solar MD Lithium Ion phosphate
(LiFePO4) energy storage solutions.
Product Description
The SS4143-01 battery solution is available in one standard size and can be
paralleled to meet most residential applications. The rated voltage is 51.2V
nominal (to suit 48V systems). Larger systems are provided by Solar MD based
on specific project requirements.
WARNING: Read the entire document before installing or using the Solar MD
attery. Failure to comply with the instructions or warnings in this document
could result in electrical shock or serious injury that can result in death or
damage to the product that can render the SS4143 Solar MD battery inoperable.
Product Specifications
All SS4143-01 specifications & descriptions contained in this document are
verified to be accurate at the time of printing. Solar MD reserves the right
to make any product revisions & improvements at any time.
Errors or Inaccuracies
To communicate any inaccuracies, omissions or to provide general feedback
regarding this manual, send an email to
info@solarmd.co.za
Copyrights
All information in this document is subject to the copyright of Solar MD (Pty)
Ltd. Additional information is available upon request.
Safety Information
This manual contains important instructions and warnings that must be followed
when using SS4143-01. Read all instructions before installing and using the
SS4143-01.
Warnings
Cautions
- Use SS4143-01 only as instructed.
- For communication and other information please read the BMS manual.
- Do not attempt to disassemble, repair, modify, or tamper with this battery unit.
- Do not insert foreign objects into any part of the battery unit.
- Avoid exposure to any moisture.
- Do not expose to extreme temperatures.
- Do not drill any holes into the box.
- Use only an approved Solar MD installer to install this product. Failure to comply will void the warranty
Specification
Solar MD 14.3kWh SS4143-01 specification
Battery type| Lithium Iron Phosphate| Scalability| Yes
Battery module| SS4143| Communication| CANBUS 500kbps / CAN 2.0B
Rated battery capacity| 14336 Wh| Can BUS termination| Single 120
Ohm
Output power| Max 10 kW| Canbus ID range:| 256 – 499
Usable battery energy @ 0.3 ℃| 13.00 kWh| Protection method| Cell
level: uv / ov / oc Position: x / y / xAcceleration: x / y / z Temperature: ot
/ ut
Nominal voltage| 51.2V| Protection phy| Mechanical relay NO
Rated Current (Ampere)| 200A| C Rating| 0.71C
Number of battery modules| 1 module| Com (CANBUS ) isolation| Yes
1.5kV
Weight| 118kg| Transportation protection| Yes
Operating voltage| 44.8V – 55.6Vdc| Indicator| Led, programmable
Communication| CANBUS| Addition IO| 3 GPO
Dimensions of SS4143: h/w/d (mm)| 650/600/210| Cell balancing|
Passive balancing
Net Weight of SS4143| 118 kg| Counters| Cycle counters and SoH
Battery cycle life [+25 ℃ ]| > 4000| AUX power output| 5V 1A
max
Charging efficiency| 99%| Storage duration| 6 months@+25℃
Operating temperature| -5℃ ~+50℃| Safety standards compliance| IEC
62619/UN 38.3/UL1642
Transport| UN3480 & UN38.3| Cell Certificate| TUV / CE / RCM /
UL1642
Mechanical installation
The middle triangle just serves as spacing. No fastening of this piece to the
wall is necessary.
Holes 1 & 5 are the most important. Should at least have these 4 secured.
Holes 3 & 6 can be the next to be used.
Please use the correct mounting screws for the specific wall surface. Make use
of M8 screws/bolts.
Installing the top cover plate
Move lid maximum 36mm up, then move lid
towards yourself. Be mindful of the button that’s still connected.
Figure 3. Top cover installation single or multiple batteries in line
Installation stacked should be spaced a minimum 50mm vertically and a minimum
of 15mm horizontally.
Figure 3b Battery spacing – installation single or multiple batteries in line
Figure 3c Battery feet – installation of battery feet
Electrical installation
Step 1. Before connecting anything be sure that the battery ON/OFF switch is at OFF position. (figure 4)
Figure 4 BMS board component locations
Connecting Inverters/chargers/UPS to the battery unit while it is ON can
cause big sparks due to capacitors inside the connected device. This can be
harmful to people.
Connecting the main battery terminal must be with the correct size cable
based on the rated current of the battery and the charger/inverter in case
it’s lower.
Step 2. Connect the negative cable to the battery negative busbar and the
positive cable to the battery positive busbar as shown in figure 5.
Switching the Battery ON
Step 1. Make sure all DC cables are tightened according to specifications.
Step 2. If the battery operates in parallel with other energy sources, make
sure that the difference between battery voltage and DC bus is not more than
2.5V. If greater than 2.5V please charge or discharge the other source
accordingly until the voltage difference is in a safe range under 2.5V.
Caution! A hot connection with the difference in voltage can cause a very
high equalization current which can burn the fuses of the battery!
Caution! Measure the voltage of the battery before connecting the DC
cables.
Step 3. Turn the BMS board ON/OFF switch to the ON position (figure 4).
Step 4. Connect the Multipurpose button if not connected to the BMS board
connector (figure 4).
Step 5. Hold the multi-purpose button until the light comes on.
Warning! If the battery does not switch the main protection contactor ON
in
7 sec, please check the BMS board indication LED for faults. See section BMS
Error and Warnings.
Multicolor multipurpose button
Figure 6: Multicolor / Multipurpose button.
Button functions
The new Solar MD Multipurpose button has an extended functionality in
combination with the BMS-EX. The Multipurpose Button can be used to directly
execute 6 predefined functions and a shutdown instruction. In combination with
the 6 Indication LEDs on BMS-EX, the user can choose between each function by
holding the button until the LED count matches the number of the function. By
releasing the button while moving through the functions, the LEDs will start
blinking and wait for the user to press the button again within 3 seconds.
The predefined functions are:
- Reserved
- Change indication LED function between Show Capacity, Show Current, and Off
- Reserved
- Wake up if Sleep mode is active
- Activate Override Off state for 60sec
- Activate Override On state for 60sec
If the button is held continuously after function 6, shutdown mode is
activated and the battery will send a signal to switch off in 4sec. Further
holding the button causes the BMS to delay complete shutdown for a maximum of
3 minutes. This operation is used when the technician wants to continue to
read or write parameters after shutdown.
Button indication
Access to all features in future development
The Multipurpose button’s advanced indication functionality, allows the user
to choose between 5 different states. Mixed combinations are also allowed when
a combination of multiple batteries with BMS-EX is used. The User can change
the preferred stage by logging into their mypower24 Energy Portal and go to
the Battery Settings.
Illumination off
For future development
When this state has been selected, the button serves as an on/off switch
without illumination (fixed color).
Color based on capacity When this state has been selected, the button shows
static illumination in a color based on the state of charge from RED at 0% SoC
(State of Charge) to GREEN at 100% state of charge.
Color based on capacity with current direction based on shading.
For future development
When this state has been selected, the button shows flashing illumination in a
color based on the state of charge and flashing code based on the electrical
current direction (charge/discharge). From RED at 0% SoC (State of Charge) to
GREEN at 100% state of charge. The flashing code for charge goes through
illumination interruption for 1 interval and slow illumination into the color
based on the SoC for 5 intervals. The flashing code for discharge represents
the opposite of charge – study color for 1 interval and low loss of color
following illumination interruption. Solar MD users refer for both as
charging/discharging waves. Fixed color with current direction based in
shading
**For future development
When this state has been selected, the button shows illumination in a color
based on the user choice and flashing code based on the electrical current
direction (charge-discharge) The flashing code for charge goes through
illumination interruption for 1 interval and slow illumination for 5
intervals. The flashing code for discharge represents the opposite of charge –
study color for 1 interval and slow loss of color following illumination
interruption. Solar MD users refer for both as charging/discharging waves.
BMS Warnings and Errors**
Method of displaying general warnings and errors:
Figure7: Display general warnings and errors, main status LEDs, and indication LEDs. The Status LEDs determine what the indicator LEDs will show.
-
If the Status LED is Green the indication LEDs will show:
a) Battery capacity
b) Current flow and direction
c) Off The functionality of the indicator LEDs are configurable, see more on this: multifunction push button. -
If the Warning LED is Orange
a) The indication LEDs will show the warning number in binary, which corresponds to that tabulated below in the warning register. -
If the Error LED is Red
a) The indication LEDs will show the error number in binary, which corresponds to that tabulated below in the error register.
Warning Register
Warning Code|
Visual Representation
| Description If the Warning LED blinks ORANGE, refer to the indication
LEDs to find the corresponding warning event in the table below
---|---|---
30|
| Pending Awake High
29| | Pending Awake Low
28| | Positive fuse blown
27| | Negative fuse blown
26| | Override ONactive
25| | Override OFF active
11| | Discharge current too high
10| | Charge current too high
---|---|---
9| | Cell temperature too low
8| | Cell temperature too high
2| | Battery cell voltage too high
1| | Battery cell voltage too low
Error Register
Error Code|
**Visual Representation
**
| Description If the Error LED blinks RED, refer to the indicator LEDs to
find the corresponding Error event in the table below
---|---|---
31| | Max 14921 not responding (Cell monitoring)
30| | Max 14921 thermal shutdown
29| | Open cell detected
28| | Internal EEPROM error
27| | External EEPROM error
26| | Balancing error internal FET circuit
25| | ADC reference not correct
24| | Override On out of range
---|---|---
23| | Internal fault
22| | Cell overvoltage
21|
| Charge Over current
20| | Pack overvoltage
19| | Pack Undervoltage
18| | Pack Undervoltage
17| | Over-current charge
16| | Over-current discharge
15| | User shutdown init
14| | Remote shutdown init
10| | Relay coil over current
---|---|---
9| | Relay fuse blown
8| | Relay coil open
7| | Gyro Z out of range
6| | Gyro Y out of range
5| | Gyro X out of range
4|
| Ext NTC 3 fault
3|
| Ext NTC 2 fault
2| | Ext NTC 1 fault
1| | Cell temperature too high
CANBUS connection.
Bms EX used CAN 2.0B @ 500000 kb. Connecting other devices operating at
different speed rates is not allowed. For connection please use twisted pair
wires in a shielded cable o minimize RF emissions. RJ45 connections can be
used for daisy chaining BMS EX together using a straight Ethernet cable. The
output of the Bms EX CAN transceiver is galvanically isolated.
Figure 8: BMS-E connection to the CANBUS.
CANBUS warnings
Figure 9 CANBUS Termination resistor and Warning LED location.
pules ON
pules OFF
The Orange LED (WARN) is used to display a warning for canbus only. Reading
this warning is possible with pulse counting.
– CANBUS line open or no termination resistor set. [1]
-CAN BUS line in the initialization stage. Canbus init occurs when the line is opened and then established. The minimum period for initialization is 30sec. In this period all nodes are scanned in the network and scanned for ID and serial number collisions. [2]
– Duplicate CAN ID detected with no “auto-ID” set. [3]
– Duplicate Serial number detected. [4]
CANBUS Internal fault. [5]
Troubleshooting Warnings/Errors
Code | Cause | Solution |
---|
Warnings ( Figure 6)
1-2| 1. inverter/rectifier settings may not be correct.
2. Battery cells may be imbalanced| 1. Check the battery settings
2. Contact Solar MD support
3-4| The system design is not correct.| Add additional battery, decrease
charging / discharging current from your inverter / rectifier / load
5-6| Manual override| Manual override has been activated – please check with
your installer
29-30| The BMS is ready to switch on after deep discharge/charge| Connect
charger / load to the Battery
Errors (Figure 7 & 8)
5,6,7| The battery is not installed in the upright position| Install the
battery in the right position
15,16,17| The BMS has been shut down manually or remotely| Switch on the BMS
18,19| The absolute maximum charge/discharge current has been achieved| The
BMS will restart automatically, please contact support team or approved
installer
21| The BMS is set for different number cells in series as the actually
installed| Contact your installer or Solar MD support team
22| The battery cell voltage is way too low.| Fill in the failure report and
send to i nfo@solarmd.co.za
The unit needs to return to the factory for testing
23| Battery cell voltage way too high| The BMS will restart automatically
after pending awake condition
24,25,26, 27,28,30, 31| BMS Internal failure| Fill in the failure report and
send to i nfo@solarmd.co.za
The BMS will be dispatched to you for replacement
29| Battery factory failure| Fill in the failure report and send to i
nfo@solarmd.co.za
The unit needs to return to the factory for testing
CANBUS Warning (Figure 10)
1| 1. Canbus line open.
2. Single CANBUS resistor not terminated.| 1. Check if a minimum of two
nodes are connected on the line with the same transmission speed.
2. Check if the single resistor is terminated via the jumper. Located top
left of can LEDS(Fig 10).
Maximum charging / discharging voltages for nonsupported devices.
– Bulk charge (stop charging) 54.6V
– Float charge (if applicable) 53.8V
– Low battery discharge: 48V
Check that the Equalisation function are disabled, then verify if there is a
voltage difference on the inverter display and the battery terminals@0.3
Cdischarge/charge current. adjust the values above.
Please check if your inverter charger has been approved by Solar MD and it is
CAN compatible.
For the latest Solar, MD installation documents go to:
www.solarmd.com
To secure the full 12-year product warranty for the end user, be sure to
register your battery online –
login.mypower24.co.za.
SS4143.01 INSTALLATION
MAN UAL v1.0
Unit 23,
Alternator Park
Montague Gardens
Cape Town
7441 South Africa
Solar MD (PTY)
E: Info@solarrnd.co.za
T: (021) 555 2181.
References