LG MULTI V WATER IV Air to Water Heat Pump Owner’s Manual

June 12, 2024
LG

LG MULTI V WATER IV Air to Water Heat Pump

LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-product

Product Information

  • Product Name: MULTI V WATER IV
  • Available Configurations: Heat Pump & Heat Recovery
  • Key Features:
    • Energy savings
    • Space savings
    • Convenient installation
    • High Efficiency System Regardless of External Conditions
    • Uses geothermal applications
    • Economical and highly efficient
  • Technical Specifications:
    • Longest piping length after 1st branch (Conditional application): 40m (90m)
    • Longest piping length from ODU ~ IDU (Equivalent): 150m(175m)
    • Total Piping Length: 300m
    • Height between IDU ~ IDU: 40m
    • Height between ODU ~ IDU: 50m

Product Usage Instructions

  1. Installation:
    • Ensure proper space for installation to save space.
    • Follow convenient installation guidelines provided in the user manual.
  2. Operation:
    • MULTI V WATER IV operates independently of weather conditions.
    • It utilizes geothermal applications using underground heat sources like soil, ground water, lakes, and rivers.
    • Circulate water or antifreeze solution through the closed loop HDPE pipes buried beneath the earth’s surface.
    • Control the system using the control panel.
    • Choose the desired mode of operation: cooling based simultaneous operation or heating based simultaneous operation.
  3. Energy Saving:
    • The MULTI V WATER IV system provides energy savings through heat recovery unit and external energy saving between heat recovery systems.
    • It is designed to be highly efficient regardless of outdoor temperature and other environmental conditions.
    • The inverter compressor with extended compressor speed ensures rapid operation response and increased part load efficiency.
    • Features like HiPORTM, active oil control, and LG’s 4th generation inverter compressor contribute to maximum COP (Coefficient of Performance) and energy savings.

Highlight

  • Water Cooled VRF Heat Pump & Heat Recovery
  • 22.4 ~ 201.6kW (Cooling capacity based)
  • 3Ø, 380 ~ 415V, 50Hz
  • Outdoor unit installed indoor

How does it work?

LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig 2

Available in Heat Pump & Heat Recovery Configuration

INNOVATIVE TECHNOLOGIES

High Efficiency System Regardless of External Conditions

Regardless of outdoor temperature and other environmental conditions, MULTI V WATER IV is the optimal solution.

MULTI V WATER IV System for Geothermal Applications

Uses underground heat sources like soil, ground water, lakes, rivers and more as renewable energy for cooling and heating. Water or antifreeze solution is circulated through the closed loop HDPE (High Density Poly-Ethylene) pipes buried beneath the earth’s surface.

  • The Circulating water temperature range is between -5°C ~ 45°C
  • Antifreeze should be applied depending on the applicationLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig 5

Chiller – FCULG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
6

Multi V Water IV

ENERGY SAVING

Economical, Highly Efficient System

LG’s key technologies are integrated to inverter compressor
With 4th generation inverter compressor, the Multi V Water IV boasts top-class energy efficiency.LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
8

Maximum COPLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
9

Economical, Highly Efficient System

LG’s 4th Generation Inverter Compressor

Integrated Part Load Efficiency

WATER SAVINGS

Variable Water Flow Control (OPTION)

In support of green building initiatives
The world’s first variable water flow control system for water cooled VRF system. LG applied Variable Water Flow Control to optimize water flow control regarding partial cooling or heating load conditions. Because of this it’s also possible to reduce circulation pump energy consumption.LG-MULTI-V
-WATER-IV-Air-to-Water-Heat-Pump-fig 13 LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig 14

Note

  1. Location : Paris, France
  2. Office, 68,000m2
  3. Operation time : 1,344 hours (Cooling period)

Project Example : 63F (Pump : 20,064 LPM, 42.4mAq x 4ea)

  1. Inverter pump with MULTI V Water and variable water flow control kit
  2. Constant pump (Step control) with Water cooled VRF

10 years energy cost ($)LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
15

__

Unit

__

Constant pump

| 5 years| 10 years
---|---|---
Energy Use (kWh)

__

7,952,040

| Pump Running Cost ($)

__

1,142,441

| Energy Use (kWh)

__

15,904,080

| Pump Running Cost ($)

__

2,600,518

Inverter pump| 5,054,940| 726,225| 10,109,880| 1,653,093

FLEXIBLE DESIGN & SPACE SAVINGS

Largest Capacity

Sufficient pipe length limitation provides flexible design and installation
Providing 8 ~ 20HP (22.4 ~ 56kW) with single unit, and up to the world’s largest capacity 80HP (224kW) by combination.LG-MULTI-V-WATER-IV-Air-to-
Water-Heat-Pump-fig 16

Longest Piping Length

Sufficient pipes length limitation in design and Installation for various buildings
Provide flexible installation up to 300m of total piping length. As water pipes are not connected to indoor units, users are free from water leakage problems.

Actual longest piping length (Equivalent) **** 150m (175m)

Longest piping length after 1 st branch (Conditional application)| 40m (90m)
---|---
Height difference between ODU ~ IDU| 50m
Height difference between IDU ~ IDU| 40m

Compact Size
Thanks to compact size of product, it provides more space for commercial or public use as much as possible.
The optimal design of the compact, lightweight outdoor unit enables double stacking, which results in 50% savings in installation space.

Conventional

Multi V Water IV

Lightweight
Nothing or Decrease additional load reinforcement work at building
Easier to transport and install, thanks to 18% reduction in overall weight .LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig 20

TECHNICAL DATA

NomenclatureLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
21

Outdoor Units FunctionLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
22

Operation LimitsLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
24

Note

  1. These figures assume the following operating conditions:
  2. Equivalent piping length :7.5m
  3. Level difference : 0m

Position of Sound Pressure Level Measuring

Note

  1. Data is valid at free field condition
  2. Data is valid at nominal operating condition
  3. Sound level will vary depending on a range of factors such as the construction (Acoustic absorption coefficient) of particular room in which the equipment is installed
  4. Sound level can be increased in static pressure mode or air guide application.

Optional Accessories

Multi V Water IV Heating Dissipation Value by ModelLG-MULTI-V-WATER-IV-
Air-to-Water-Heat-Pump-fig 26

Test condition : Indoor air temperature : DB 40℃, WB : 32℃
※ A design stage should be considered to ventilation system in mechanical room.

ARWN080LAS4 / ARWN100LAS4
ARWN140LAS4 / ARWN200LAS4LG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
27

Individual Installation

Water Piping InstallationLG-MULTI-V-WATER-IV-Air-to-Water-Heat-Pump-fig
29

Precaution of Installation

  1. Do not install the unit at the outdoors. (Installation of the unit outdoors could result in fire or electric shock.) Recommended ambient temperature of outdoor unit is between 0 ~ 40°C.
  2. Keep the water temperature between 10 ~ 45°C. Standard water supply temperature is 30°C for cooling and 20°C for heating.
  3. Establish an anti-freeze plan for the water supply when the product is stopped during the winter.
  4. Be careful of the water purity control. Ensure water purity control to avoid breakdown due to water pipe corrosion. Refer to ‘Standard Table for Water Purity Control’ in PDB (Product Data Book).
  5. The water pressure resistance of the water pipe system of this product is 1.98MPa.
  6. Always install a trap so that the drained water does not back flush.
  7. Install a pressure gauge and temperature gauge at the inlet and outlet of the water pipe.
  8. Flexible joints must be installed not to cause any leakage from the vibration of pipes.
  9. Install a service port to clean the heat exchanger at the each end of the water inlet and outlet.
  10. It is mandatory to install the flow switch to the water collection pipe system connecting to the outdoor unit. (Flow switch acts as the 1st protection device when the heat water is not supplied.)
  11. When setting the flow switch, it is recommended to use the product with default set value to satisfy the minimum flow rate of this product. (The minimum flow rate range of this product is 50%.)
  12. To protect the water cooling type product, you must install a strainer with 50 mesh or more on the heat water supply pipe. If not installed, it can result in damage of heat exchanger by the following situation.
  13. Heat water supply within the plate type heat exchanger is composed of multiple small paths.
  14. If you do not use a strainer with 50 mesh or more, alien particles can partially block the water paths.
  15. When running the heater, the plate type heat exchanger plays the role of the evaporator, and at this time, the temperature of the refrigerant side drops to drop the temperature of the heat water supply, which can result in icing point in the water paths.
  16. As the heating process progresses, the water paths can be partially frozen to lead to damage in plate type heat exchanger.
  17. As a result of the damage of the heat exchanger from the freezing, the refrigerant side and the heat water source side will be mixed to make the product unusable.

REFERENCE SITE

Bouygues Challenger
LG MULTI V Water Solution with Geothermal Application.LG-MULTI-V-WATER-IV-
Air-to-Water-Heat-Pump-fig 30

Site Information
The industrial group Bouygues was established in France in 1952. It now maintains operations in 80 countries and employs more than 131,000 people. In 1988, after two years of construction, the new headquarters for Bouygues Construction was officially opened for business. Named Challenger, the complex became a technological showcase for late 20th century architecture.

LG Solution
Bouygues decided to convert their headquarters into an eco-conscious building by significantly reducing its energy footprint. The LG MULTI V Water system was chosen as the ideal HVAC solution for this project. The system not only saves energy but also reduces water usage as it recycles water
in order to regulate the temperature of the building. With LG’s advanced technology, the building’s water consumption was reduced by more than 70 percent.

MULTI V WATER IV HEAT PUMP

ARWN080LAS4 / ARWN100LAS4 ARWN140LAS4

HP/8/10/14


Model Name

| Combination Unit| ARWN080LAS4| ARWN100LAS4| ARWN140LAS4
---|---|---|---|---
Independent Unit| ARWN080LAS4| ARWN100LAS4| ARWN140LAS4


Capacity

| Cooling (Rated)| kW| 22.4| 28.0| 39.2
Heating (Rated)| kW| 25.2| 31.5| 44.1


Input

| Cooling (Rated)| kW| 3.86| 5.09| 7.84
Heating (Rated)| kW| 4.2| 5.34| 8.17
EER| 5.80| 5.50| 5.00
COP **** Rated Capacity| 6.00| 5.90| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 10.7| 15.8| 28.6
Rated Water Flow| LPM| 77| 96| 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 1| (Inverter) x 1| (Inverter) x 1
Motor Output x Number| W x No.| 4,200 x 1| 4,200 x 1| 4,200 x 1
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 2,800| 2,800| 2,800
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø9.52 (3/8)| Ø9.52 (3/8)| Ø12.7 (1/2)
Gas Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø25.4 (1)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 1| (755 x 997 x 500) x 1| (755 x 997 x 500) x 1
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 1
Net Weight| kg x No.| 127 x 1| 127 x 1| 127 x 1
Shipping Weight| kg x No.| 137 x 1| 137 x 1| 137 x 1
Sound Pressure Level| Cooling| dB(A)| 47| 50| 58
Heating| dB(A)| 51| 53| 57


Sound Power Level

| Cooling| dB(A)| 59| 62| 70
Heating| dB(A)| 63| 65| 69
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 5.8| 5.8| 5.8
t-CO2eq| 12.108| 12.108| 12.108
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 13 (20)| 16 (25)| 23 (35)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN200LAS4 / ARWN160LAS4 ARWN180LAS4


Model Name

| Combination Unit| ARWN200LAS4| ARWN160LAS4| ARWN180LAS4
---|---|---|---|---
Independent Unit| ARWN200LAS4| ARWN080LAS4 ARWN080LAS4| ARWN100LAS4 ARWN080LAS4


Capacity

| Cooling (Rated)| kW| 56.0| 44.8| 50.4
Heating (Rated)| kW| 63.0| 50.4| 56.7


Input

| Cooling (Rated)| kW| 11.20| 7.72| 8.95
Heating (Rated)| kW| 11.67| 8.40| 9.54
EER| 5.00| 5.80| 5.63
COP **** Rated Capacity| 5.40| 6.00| 5.94


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1| 10.7 + 10.7| 15.8 + 10.7
Rated Water Flow| LPM| 192| 77 + 77| 96 + 77




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 1| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 5,300 x 1| 4,200 x 2| 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 3,000| 5,600| 5,600
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø12.7 (1/2)| Ø12.7 (1/2)| Ø12.7 (1/2)
Gas Pipe| mm (inch)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 1| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| 140 x 1| 127 x 2| 127 x 2
Shipping Weight| kg x No.| 150 x 1| 137 x 2| 137 x 2
Sound Pressure Level| Cooling| dB(A)| 54| 50| 52
Heating| dB(A)| 60| 54| 55


Sound Power Level

| Cooling| dB(A)| 66| 62| 64
Heating| dB(A)| 72| 66| 67
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 3.0| 11.6| 11.6
t-CO2eq| 6.263| 24.215| 24.215
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 32 (50)| 26 (40)| 29 (45)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN220LAS4 / ARWN240LAS4 ARWN280LAS4


Model Name

| Combination Unit| ARWN220LAS4| ARWN240LAS4| ARWN280LAS4
---|---|---|---|---
Independent Unit| ARWN140LAS4 ARWN080LAS4| ARWN140LAS4 ARWN100LAS4| ARWN140LAS4 ARWN140LAS4


Capacity

| Cooling (Rated)| kW| 61.6| 67.2| 78.4
Heating (Rated)| kW| 69.3| 75.6| 88.2


Input

| Cooling (Rated)| kW| 11.70| 12.93| 15.68
Heating (Rated)| kW| 12.37| 13.51| 16.34
EER| 5.26| 5.20| 5.00
COP **** Rated Capacity| 5.60| 5.60| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 28.6 + 10.7| 28.6 + 15.8| 28.6 + 28.6
Rated Water Flow| LPM| 135 + 77| 135 + 96| 135 + 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 2| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 4,200 x 2| 4,200 x 2| 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 5,600| 5,600| 5,600
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Gas Pipe| mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| 127 x 2| 127 x 2| 127 x 2
Shipping Weight| kg x No.| 137 x 2| 137 x 2| 137 x 2
Sound Pressure Level| Cooling| dB(A)| 58| 59| 59
Heating| dB(A)| 58| 58| 58


Sound Power Level

| Cooling| dB(A)| 70| 71| 72
Heating| dB(A)| 70| 70| 71
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 11.6| 11.6| 11.6
t-CO2eq| 24.215| 24.215| 24.215
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 35 (44)| 39 (48)| 45 (56)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN300LAS4 / ARWN340LAS4 ARWN400LAS4


Model Name

| Combination Unit| ARWN300LAS4| ARWN340LAS4| ARWN400LAS4
---|---|---|---|---
Independent Unit| ARWN200LAS4 ARWN100LAS4| ARWN200LAS4 ARWN140LAS4| ARWN200LAS4 ARWN200LAS4


Capacity

| Cooling (Rated)| kW| 84.0| 95.2| 112.0
Heating (Rated)| kW| 94.5| 107.1| 126.0


Input

| Cooling (Rated)| kW| 16.29| 19.04| 22.40
Heating (Rated)| kW| 17.01| 19.84| 23.34
EER| 5.16| 5.00| 5.00
COP **** Rated Capacity| 5.56| 5.40| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 15.8| 30.1 + 28.6| 30.1 + 30.1
Rated Water Flow| LPM| 192 + 96| 192 + 135| 192 + 192




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 2| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 5,300 x 1 + 4,200 x 1| 5,300 x 1 + 4,200 x 1| 5,300 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 5,800| 5,800| 6,000
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Gas Pipe| mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø41.3 (1-5/8)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| (140 x 1) + (127 x 1)| (140 x 1) + (127 x 1)| 140 x 2
Shipping Weight| kg x No.| (150 x 1) + (137 x 1)| (150 x 1) + (137 x 1)| 150 x 2
Sound Pressure Level| Cooling| dB(A)| 55| 59| 55
Heating| dB(A)| 61| 61| 61


Sound Power Level

| Cooling| dB(A)| 67| 72| 68
Heating| dB(A)| 73| 74| 74
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 8.8| 8.8| 6.0
t-CO2eq| 18.370| 18.370| 12.525
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 49 (60)| 55 (64)| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance withoutdoor units combination (160% ~ 200%).  The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN420LAS4 / ARWN440LAS4 ARWN480LAS4


Model Name

| Combination Unit| ARWN420LAS4| ARWN440LAS4| ARWN480LAS4
---|---|---|---|---


Independent Unit

| ARWN200LAS4 ARWN140LAS4 ARWN080LAS4| ARWN200LAS4 ARWN140LAS4 ARWN100LAS4| ARWN200LAS4 ARWN140LAS4 ARWN140LAS4


Capacity

| Cooling (Rated)| kW| 117.6| 123.2| 134.4
Heating (Rated)| kW| 132.3| 138.6| 151.2


Input

| Cooling (Rated)| kW| 22.9| 24.13| 26.88
Heating (Rated)| kW| 24.04| 25.18| 28.01
EER| 5.14| 5.11| 5.00
COP **** Rated Capacity| 5.50| 5.50| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 28.6 + 10.7| 30.1 + 28.6 + 15.8| 30.1 + 28.6 + 28.6
Rated Water Flow| LPM| 192 + 135 + 77| 192 + 135 + 96| 192 + 135 + 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 3| (Inverter) x 3| (Inverter) x 3
Motor Output x Number| W x No.| 5,300 x 1 + 4,200 x 2| 5,300 x 1 + 4,200 x 2| 5,300 x 1 + 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 8,600| 8,600| 8,600
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Gas Pipe| mm (inch)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)



Water Connecting Pipes

| ****

Inlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)


Outlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3
Net Weight| kg x No.| (140 x 1) + (127 x 2)| (140 x 1) + (127 x 2)| (140 x 1) + (127 x 2)
Shipping Weight| kg x No.| (150 x 1) + (137 x 2)| (150 x 1) + (137 x 2)| (150 x 1) + (137 x 2)
Sound Pressure Level| Cooling| dB(A)| 60| 60| 60
Heating| dB(A)| 62| 62| 62


Sound Power Level

| Cooling| dB(A)| 72| 72| 74
Heating| dB(A)| 74| 74| 76
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 14.6| 14.6| 14.6
t-CO2eq| | 30.478| 30.478| 30.478
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN500LAS4 / ARWN540LAS4 ARWN600LAS4

HP 50 54 60

Model Name

| Combination Unit| ARWN500LAS4| ARWN540LAS4| ARWN600LAS4


Independent Unit

| ARWN200LAS4 ARWN200LAS4 ARWN100LAS4| ARWN200LAS4 ARWN200LAS4 ARWN140LAS4| ARWN200LAS4 ARWN200LAS4 ARWN200LAS4


Capacity

| Cooling (Rated)| kW| 140.0| 151.2| 168.0
Heating (Rated)| kW| 157.5| 170.1| 189.0


Input

| Cooling (Rated)| kW| 27.49| 30.24| 33.60
Heating (Rated)| kW| 28.68| 31.51| 35.01
EER| 5.09| 5.00| 5.00
COP **** Rated Capacity| 5.49| 5.40| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 15.8| 30.1 + 28.6 + 28.6| 30.1 + 30.1 + 30.1
Rated Water Flow| LPM| 192 + 192 + 96| 192 + 192 + 135| 192 + 192+ 192




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 3| (Inverter) x 3| (Inverter) x 3
Motor Output x Number| W x No.| 5,300 x 2 + 4,200 x 1| 5,300 x 2 + 4,200 x 1| 5,300 x 3
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 8,800| 8,800| 9,000
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Gas Pipe| mm (inch)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)



Water Connecting Pipes

| ****

Inlet

| ****

A (inch)

| 40A (PT 1-1/2) +40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)


Outlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3
Net Weight| kg x No.| (140 x 2) + (127 x 1)| (140 x 2) + (127 x 1)| 140 x 3
Shipping Weight| kg x No.| (150 x 2) + (137 x 1)| (150 x 2) + (137 x 1)| 150 x 3
Sound Pressure Level| Cooling| dB(A)| 58| 60| 56
Heating| dB(A)| 63| 62| 62


Sound Power Level

| Cooling| dB(A)| 70| 74| 70
Heating| dB(A)| 75| 76| 76
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 11.8| 11.8| 9.0
t-CO2eq| 24.633| 24.633| 18.788
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN620LAS4 / ARWN640LAS4 ARWN680LAS4



Model Name

| Combination Unit| ARWN620LAS4| ARWN640LAS4| ARWN680LAS4
---|---|---|---|---


Independent Unit

| ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 ARWN080LAS4| ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 ARWN100LAS4| ARWN200LAS4 ARWN200LAS4 ARWN140LAS4 ARWN140LAS4


Capacity

| Cooling (Rated)| kW| 173.6| 179.2| 190.4
Heating (Rated)| kW| 195.3| 201.6| 214.2


Input

| Cooling (Rated)| kW| 34.10| 35.33| 38.08
Heating (Rated)| kW| 35.71| 36.85| 39.68
EER| 5.09| 5.07| 5.00
COP **** Rated Capacity| 5.47| 5.47| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 28.6 + 10.7| 30.1 + 30.1 + 28.6 + 15.8| 30.1 + 30.1 + 28.6 + 28.6
Rated Water Flow| LPM| 192 + 192 + 135 + 77| 192 + 192 + 135 + 96| 192 + 192 + 135 + 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 4| (Inverter) x 4| (Inverter) x 4
Motor Output x Number| W x No.| 5,300 x 2 + 4,200 x 2| 5,300 x 2 + 4,200 x 2| 5,300 x 2 + 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 11,600| 11,600| 11,600
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø22.2 (7/8)
Gas Pipe| mm (inch)| Ø44.5 (1-3/4)| Ø44.5 (1-3/4)| Ø53.98 (2-1/8)



Water Connecting Pipes

| Inlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Outlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4
Net Weight| kg x No.| (140 x 2) + (127 x 2)| (140 x 2) + (127 x 2)| (140 x 2) + (127 x 2)
Shipping Weight| kg x No.| (150 x 2) + (137 x 2)| (150 x 2) + (137 x 2)| (150 x 2) + (137 x 2)
Sound Pressure Level| Cooling| dB(A)| 61| 61| 61
Heating| dB(A)| 64| 64| 63


Sound Power Level

| Cooling| dB(A)| 73| 73| 75
Heating| dB(A)| 76| 76| 77
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 17.6| 17.6| 17.6
t-CO2eq| 36.740| 36.740| 36.740
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWN700LAS4 / ARWN740LAS4 ARWN800LAS4



Model Name

| Combination Unit| ARWN700LAS4| ARWN740LAS4| ARWN800LAS4
---|---|---|---|---


Independent Unit

| ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN100LAS4| ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN140LAS4| ARWN200LAS4 ARWN200LAS4 ARWN200LAS4 ARWN200LAS4
Capacity| Cooling (Rated)| kW| 196.0| 207.2| 224.0
Heating (Rated)| kW| 220.5| 233.1| 252.0


Input

| Cooling (Rated)| kW| 38.69| 41.44| 44.80
Heating (Rated)| kW| 40.35| 43.18| 46.68
EER| 5.07| 5.00| 5.00
COP **** Rated Capacity| 5.46| 5.40| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 30.1 + 15.8| 30.1 + 30.1 + 30.1 + 28.6| 30.1 + 30.1 + 30.1 + 30.1
Rated Water Flow| LPM| 192 + 192 + 192 + 96| 192 + 192 + 192 + 135| 192 + 192

  • 192 + 192


Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.|  | (Inverter) x 4| (Inverter) x 4| (Inverter) x 4
Motor Output x Number| W x No.| 5,300 x 3 + 4,200 x 1| 5,300 x 3 + 4,200 x 1| 5,300 x 4
Oil Type|  | FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 11,800| 11,800| 12,000
Refrigerant Connecting Pipes| Liquid Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø22.2 (7/8)
Gas Pipe| mm (inch)| Ø53.98 (2-1/8)| Ø53.98 (2-1/8)| Ø53.98 (2-1/8)



Water Connecting Pipes

| Inlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Outlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)| 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4
Net Weight| kg x No.| (140 x 3) + (127 x 1)| (140 x 3) + (127 x 1)| 140 x 4
Shipping Weight| kg x No.| (150 x 3) + (137 x 1)| (150 x 3) + (137 x 1)| 150 x 4
Sound Pressure Level| Cooling| dB(A)| 59| 61| 57
Heating| dB(A)| 65| 63| 63


Sound Power Level

| Cooling                     dB(A)| 71| 75| 71
Heating| dB(A)| 77| 77| 77
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 14.8| 14.8| 12.0
t-CO2eq|  | 30.895| 30.895| 25.050
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units 1)| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB080LAS4 / ARWB100LAS4 ARWB140LAS4


Model Name

| Combination Unit| ARWB080LAS4| ARWB100LAS4| ARWB140LAS4
---|---|---|---|---
Independent Unit| ARWB080LAS4| ARWB100LAS4| ARWB140LAS4


Capacity

| Cooling (Rated)| kW| 22.4| 28.0| 39.2
Heating (Rated)| kW| 25.2| 31.5| 44.1


Input

| Cooling (Rated)| kW| 3.86| 5.09| 7.84
Heating (Rated)| kW| 4.20| 5.34| 8.17
EER| 5.80| 5.50| 5.00
COP| Rated Capacity|  | 6.00| 5.90| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 10.7| 15.8| 28.6
Rated Water Flow| LPM| 77| 96| 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 1| (Inverter) x 1| (Inverter) x 1
Motor Output x Number| W x No.| 4,200 x 1| 4,200 x 1| 4,200 x 1
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 2,800| 2,800| 2,800


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø9.52 (3/8)| Ø9.52 (3/8)| Ø12.7 (1/2)
Low Pressure Gas Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø25.4 (1)
High Pressure Gas Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 1| (755 x 997 x 500) x 1| (755 x 997 x 500) x 1
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 1
Net Weight| kg x No.| 127 x 1| 127 x 1| 127 x 1
Shipping Weight| kg x No.| 137 x 1| 137 x 1| 137 x 1
Sound Pressure Level| Cooling| dB(A)| 47| 50| 58
Heating| dB(A)| 51| 53| 57


Sound Power Level

| Cooling| dB(A)| 59| 62| 70
Heating| dB(A)| 63| 65| 69
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 5.8| 5.8| 5.8
t-CO2eq| 12.108| 12.108| 12.108
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units 1)| 13 (20)| 16 (25)| 23 (35)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB200LAS4 / ARWB160LAS4 ARWB180LAS4LG-MULTI-V-WATER-IV-Air-to-Water-
Heat-Pump-fig 47


Model Name

| Combination Unit| ARWB200LAS4| ARWB160LAS4| ARWB180LAS4
---|---|---|---|---
Independent Unit| ARWB200LAS4| ARWB080LAS4 ARWB080LAS4| ARWB100LAS4 ARWB080LAS4


Capacity

| Cooling (Rated)| kW| 56.0| 44.8| 50.4
Heating (Rated)| kW| 63.0| 50.4| 56.7


Input

| Cooling (Rated)| kW| 11.20| 7.72| 8.95
Heating (Rated)| kW| 11.67| 8.40| 9.54
EER| 5.00| 5.80| 5.63
COP| Rated Capacity|  | 5.40| 6.00| 5.94


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1| 10.7 + 10.7| 15.8 + 10.7
Rated Water Flow| LPM| 192| 77 + 77| 96 + 77




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 1| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 5,300 x 1| 4,200 x 2| 4,200 x 2
Oil Type| FVC68D(PVE)| FVC68D(PVE)| FVC68D(PVE)
Oil Charge| cc| 3,000| 5,600| 5,600


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø12.7 (1/2)| Ø12.7 (1/2)| Ø12.7 (1/2)
Low Pressure Gas Pipe| mm (inch)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)
High Pressure Gas Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

| 20A (PT 3/4)

(External Thread)

Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 1| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 1| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| 140 x 1| 127 x 2| 127 x 2
Shipping Weight| kg x No.| 150 x 1| 137 x 2| 137 x 2
Sound Pressure Level| Cooling| dB(A)| 54| 50| 52
Heating| dB(A)| 60| 54| 55


Sound Power Level

| Cooling| dB(A)| 66| 62| 64
Heating| dB(A)| 72| 66| 67
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 3.0| 11.6| 11.6
t-CO2eq| 6.263| 24.215| 24.215
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 32(50)| 26(40)| 29(45)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance withoutdoor units combination (160% ~ 200%).  The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB220LAS4 / ARWB240LAS4ARWB280LAS4


Model Name

| Combination Unit| ARWB220LAS4| ARWB240LAS4| ARWB280LAS4
---|---|---|---|---
Independent Unit| ARWB140LAS4 ARWB080LAS4| ARWB140LAS4 ARWB100LAS4| ARWB140LAS4 ARWB140LAS4


Capacity

| Cooling (Rated)| kW| 61.6| 67.2| 78.4
Heating (Rated)| kW| 69.3| 75.6| 88.2


Input

| Cooling (Rated)| kW| 11.70| 12.93| 15.68
Heating (Rated)| kW| 12.37| 13.51| 16.34
EER| 5.26| 5.20| 5.00
COP| Rated Capacity|  | 5.60| 5.60| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 28.6 + 10.7| 28.6 + 15.8| 28.6 + 28.6
Rated Water Flow| LPM| 135 + 77| 135 + 96| 135 + 135




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 2| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 4,200 x 2| 4,200 x 2| 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 5,600| 5,600| 5,600


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Low Pressure Gas Pipe| mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)
High Pressure Gas Pipe| mm (inch)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| 127 x 2| 127 x 2| 127 x 2
Shipping Weight| kg x No.| 137 x 2| 137 x 2| 137 x 2
Sound Pressure Level| Cooling| dB(A)| 58| 59| 59
Heating| dB(A)| 58| 58| 58


Sound Power Level

| Cooling| dB(A)| 70| 71| 72
Heating| dB(A)| 70| 70| 71
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 11.6| 11.6| 11.6
t-CO2eq| 24.215| 24.215| 24.215
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 35 (44)| 39 (48)| 45 (56)

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB300LAS4 / ARWB340LAS4 ARWB400LAS4


Model Name

| Combination Unit| ARWB300LAS4| ARWB340LAS4| ARWB400LAS4
---|---|---|---|---
Independent Unit| ARWB200LAS4 ARWB100LAS4| ARWB200LAS4 ARWB140LAS4| ARWB200LAS4 ARWB200LAS4


Capacity

| Cooling (Rated)| kW| 84.0| 95.2| 112.0
Heating (Rated)| kW| 94.5| 107.1| 126.0


Input

| Cooling (Rated)| kW| 16.29| 19.04| 22.40
Heating (Rated)| kW| 17.01| 19.84| 23.34
EER| 5.16| 5.00| 5.00
COP| Rated Capacity|  | 5.56| 5.40| 5.40


Exterior

| Color| Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type| Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 15.8| 30.1 + 28.6| 30.1 + 30.1
Rated Water Flow| LPM| 192 + 96| 192 + 135| 192 + 192




Compressor

| Type| Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 2| (Inverter) x 2| (Inverter) x 2
Motor Output x Number| W x No.| 5,300 x 1 + 4,200 x 1| 5,300 x 1 + 4,200 x 1| 5,300 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 5,800| 5,800| 6,000


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Low Pressure Gas Pipe| mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø41.3 (1-5/8)
High Pressure Gas Pipe| mm (inch)| Ø28.58 (1-1/8)| Ø28.58 (1-1/8)| Ø34.9 (1-3/8)



Water Connecting Pipes

| Inlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Outlet| A (inch)| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2| (755 x 997 x 500) x 2
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2| (804 x 1,143 x 630) x 2
Net Weight| kg x No.| (140 x 1) + (127 x 1)| (140 x 1) + (127 x 1)| 140 x 2
Shipping Weight| kg x No.| (150 x 1) + (137 x 1)| (150 x 1) + (137 x 1)| 150 x 2
Sound Pressure Level| Cooling| dB(A)| 55| 59| 55
Heating| dB(A)| 61| 61| 61


Sound Power Level

| Cooling| dB(A)| 67| 72| 68
Heating| dB(A)| 73| 74| 74
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name| R410A| R410A| R410A
Precharged Amount in Factory| kg| 8.8| 8.8| 6.0
t-CO2eq| 18.370| 18.370| 12.525
Control| Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 49 (60)| 55 (64)| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB420LAS4 / ARWB440LAS4 ARWB480LAS4


Model Name

| Combination Unit| ARWB420LAS4| ARWB440LAS4| ARWB480LAS4
---|---|---|---|---


Independent Unit

|  | ARWB200LAS4 ARWB140LAS4 ARWB080LAS4| ARWB200LAS4 ARWB140LAS4 ARWB100LAS4| ARWB200LAS4 ARWB140LAS4 ARWB140LAS4


Capacity

| Cooling (Rated)| kW| 117.6| 123.2| 134.4
Heating (Rated)| kW| 132.3| 138.6| 151.2


Input

| Cooling (Rated)| kW| 22.9| 24.13| 26.88
Heating (Rated)| kW| 24.04| 25.18| 28.01
EER|  | 5.14| 5.11| 5.00
COP| Rated Capacity|  | 5.50| 5.50| 5.40


Exterior

| Color|  | Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)|  | RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type|  | Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 28.6 + 10.7| 30.1 + 28.6 + 15.8| 30.1 + 28.6 + 28.6
Rated Water Flow| LPM| 192 + 135 + 77| 192 + 135 + 96| 192 + 135 + 135




Compressor

| Type|  | Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.|  | (Inverter) x 3| (Inverter) x 3| (Inverter) x 3
Motor Output x Number| W x No.| 5,300 x 1 + 4,200 x 2| 5,300 x 1 + 4,200 x 2| 5,300 x 1 + 4,200 x 2
Oil Type|  | FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 8,600| 8,600| 8,600


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Low Pressure Gas Pipe| mm (inch)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)
High Pressure Gas Pipe mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)



Water Connecting Pipes

| ****

Inlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)


Outlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3
Net Weight| kg x No.| (140 x 1) + (127 x 2)| (140 x 1) + (127 x 2)| (140 x 1) + (127 x 2)
Shipping Weight| kg x No.| (150 x 1) + (137 x 2)| (150 x 1) + (137 x 2)| (150 x 1) + (137 x 2)
Sound Pressure Level| Cooling| dB(A)| 60| 60| 60
Heating| dB(A)| 62| 62| 62


Sound Power Level

| Cooling| dB(A)| 72| 72| 74
Heating| dB(A)| 74| 74| 76
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name|  | R410A| R410A| R410A
Precharged Amount in Factory| kg| 14.6| 14.6| 14.6
t-CO2eq|  | 30.478| 30.478| 30.478
Control|  | Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance withoutdoor units combination (160% ~ 200%).  The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB500LAS4 / ARWB540LAS4 ARWB600LAS4


Model Name

| Combination Unit| ARWB500LAS4| ARWB540LAS4| ARWB600LAS4
---|---|---|---|---


Independent Unit

|  | ARWB200LAS4 ARWB200LAS4 ARWB100LAS4| ARWB200LAS4 ARWB200LAS4 ARWB140LAS4| ARWB200LAS4 ARWB200LAS4 ARWB200LAS4


Capacity

| Cooling (Rated)| kW| 140.0| 151.2| 168.0
Heating (Rated)| kW| 157.5| 170.1| 189.0


Input

| Cooling (Rated)| kW| 27.49| 30.24| 33.60
Heating (Rated)| kW| 28.68| 31.51| 35.01
EER|  | 5.09| 5.00| 5.00
COP| Rated Capacity|  | 5.49| 5.40| 5.40


Exterior

| Color|  | Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)|  | RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type|  | Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 15.8| 30.1 + 28.6 + 28.6| 30.1 + 30.1 + 30.1
Rated Water Flow| LPM| 192 + 192 + 96| 192 + 192 + 135| 192 + 192+ 192




Compressor

| Type|  | Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.|  | (Inverter) x 3| (Inverter) x 3| (Inverter) x 3
Motor Output x Number| W x No.| 5,300 x 2 + 4,200 x 1| 5,300 x 2 + 4,200 x 1| 5,300 x 3
Oil Type|  | FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 8,800| 8,800| 9,000


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø19.05 (3/4)| Ø19.05 (3/4)| Ø19.05 (3/4)
Low Pressure Gas Pipe| mm (inch)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)
High Pressure Gas Pipe mm (inch)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)| Ø34.9 (1-3/8)



Water Connecting Pipes

| ****

Inlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)


Outlet

| ****

A (inch)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

| 40A (PT 1-1/2) + 40A (PT 1-1/2)

+ 40A (PT 1-1/2)

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3| (755 x 997 x 500) x 3
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3| (804 x 1,143 x 630) x 3
Net Weight| kg x No.| (140 x 2) + (127 x 1)| (140 x 2) + (127 x 1)| 140 x 3
Shipping Weight| kg x No.| (150 x 2) + (137 x 1)| (150 x 2) + (137 x 1)| 150 x 3
Sound Pressure Level| Cooling| dB(A)| 58| 60| 56
Heating| dB(A)| 63| 62| 62


Sound Power Level

| Cooling| dB(A)| 70| 74| 70
Heating| dB(A)| 75| 76| 76
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name|  | R410A| R410A| R410A
Precharged Amount in Factory| kg| 11.8| 11.8| 9.0
t-CO2eq|  | 24.633| 24.633| 18.788
Control|  | Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB620LAS4 / ARWB640LAS4 ARWB680LAS4



Model Name

| Combination Unit| ARWB620LAS4| ARWB640LAS4| ARWB680LAS4
---|---|---|---|---


Independent Unit

|  | ARWB200LAS4 ARWB200LAS4 ARWB140LAS4 ARWB080LAS4| ARWB200LAS4 ARWB200LAS4 ARWB140LAS4 ARWB100LAS4| ARWB200LAS4 ARWB200LAS4 ARWB140LAS4 ARWB140LAS4
Capacity| Cooling (Rated)| kW| 173.6| 179.2| 190.4
Heating (Rated)| kW| 195.3| 201.6| 214.2


Input

| Cooling (Rated)| kW| 34.10| 35.33| 38.08
Heating (Rated)| kW| 35.71| 36.85| 39.68
EER|  | 5.09| 5.07| 5.00
COP| Rated Capacity|  | 5.47| 5.47| 5.40


Exterior

| Color|  | Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)|  | RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type|  | Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 28.6 + 10.7| 30.1 + 30.1 + 28.6 + 15.8| 30.1 + 30.1 + 28.6 + 28.6
Rated Water Flow| LPM| 192 + 192 + 135 + 77| 192 + 192 + 135 + 96| 192 + 192 + 135 + 135




Compressor

| Type|  | Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 4| (Inverter) x 4| (Inverter) x 4
Motor Output x Number| W x No.| 5,300 x 2 + 4,200 x 2| 5,300 x 2 + 4,200 x 2| 5,300 x 2 + 4,200 x 2
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 11,600| 11,600| 11,600


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø22.2 (7/8)
Low Pressure Gas Pipe| mm (inch)| Ø44.5 (1-3/4)| Ø44.5 (1-3/4)| Ø53.98 (2-1/8)
High Pressure Gas Pipe mm (inch)| Ø41.3 (1-5/8)| Ø41.3 (1-5/8)| Ø44.5 (1-3/4)



Water Connecting Pipes

| Inlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Outlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4
Net Weight| kg x No.| (140 x 2) + (127 x 2)| (140 x 2) + (127 x 2)| (140 x 2) + (127 x 2)
Shipping Weight| kg x No.| (150 x 2) + (137 x 2)| (150 x 2) + (137 x 2)| (150 x 2) + (137 x 2)
Sound Pressure Level| Cooling| dB(A)| 61| 61| 61
Heating| dB(A)| 64| 64| 63
Sound Power Level| Cooling| dB(A)| 73| 73| 75
Heating| dB(A)| 76| 76| 77
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name|  | R410A| R410A| R410A
Precharged Amount in Factory| kg| 17.6| 17.6| 17.6
t-CO2eq|  | 36.740| 36.740| 36.740
Control|  | Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

ARWB700LAS4 / ARWB740LAS4 ARWB800LAS4



Model Name

| Combination Unit| ARWB700LAS4| ARWB740LAS4| ARWB800LAS4
---|---|---|---|---


Independent Unit

|  | ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB100LAS4| ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB140LAS4| ARWB200LAS4 ARWB200LAS4 ARWB200LAS4 ARWB200LAS4
Capacity| Cooling (Rated)| kW| 196.0| 207.2| 224.0
Heating (Rated)| kW| 220.5| 233.1| 252.0


Input

| Cooling (Rated)| kW| 38.69| 41.44| 44.80
Heating (Rated)| kW| 40.35| 43.18| 46.68
EER|  | 5.07| 5.00| 5.00
COP| Rated Capacity|  | 5.46| 5.40| 5.40


Exterior

| Color|  | Warm Gray / Morning Gray| Warm Gray / Morning Gray| Warm Gray / Morning Gray
RAL Code (Classic)|  | RAL 7044 / RAL 7030| RAL 7044 / RAL 7030| RAL 7044 / RAL 7030



Heat Exchanger

| Type|  | Stainless Steel Plate| Stainless Steel Plate| Stainless Steel Plate
Maximum Pressure Resistance| kgf/cm2| 45| 45| 45
Head Loss| kPa| 30.1 + 30.1 + 30.1 + 15.8| 30.1 + 30.1 + 30.1 + 28.6| 30.1 + 30.1 + 30.1 + 30.1
Rated Water Flow| LPM| 192 + 192 + 192 + 96| 192 + 192 + 192 + 135| 192 + 192

  • 192 + 192


Compressor

| Type|  | Hermetically Sealed Scroll| Hermetically Sealed Scroll| Hermetically Sealed Scroll
Combination x No.| (Inverter) x 4| (Inverter) x 4| (Inverter) x 4
Motor Output x Number| W x No.| 5,300 x 3 + 4,200 x 1| 5,300 x 3 + 4,200 x 1| 5,300 x 4
Oil Type| FVC68D (PVE)| FVC68D (PVE)| FVC68D (PVE)
Oil Charge| cc| 11,800| 11,800| 12,000


Refrigerant Connecting Pipes

| Liquid Pipe| mm (inch)| Ø22.2 (7/8)| Ø22.2 (7/8)| Ø22.2 (7/8)
Low Pressure Gas Pipe| mm (inch)| Ø53.98 (2-1/8)| Ø53.98 (2-1/8)| Ø53.98 (2-1/8)
High Pressure Gas Pipe mm (inch)| Ø44.5 (1-3/4)| Ø44.5 (1-3/4)| Ø44.5 (1-3/4)



Water Connecting Pipes

| Inlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Outlet| A (inch)| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

| PT 40 + PT 40 + PT 40 + PT 40

(Internal Thread)

Drain Outlet| A (inch)| 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread) 20A (PT 3/4) (External Thread)
Dimensions (W x H x D)| mm x No.| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4| (755 x 997 x 500) x 4
Dimensions (W x H x D) Shipping| mm x No.| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4| (804 x 1,143 x 630) x 4
Net Weight| kg x No.| (140 x 3) + (127 x 1)| (140 x 3) + (127 x 1)| 140 x 4
Shipping Weight| kg x No.| (150 x 3) + (137 x 1)| (150 x 3) + (137 x 1)| 150 x 4
Sound Pressure Level| Cooling| dB(A)| 59| 61| 57
Heating| dB(A)| 65| 63| 63
Sound Power Level| Cooling| dB(A)| 71| 75| 71
Heating| dB(A)| 77| 77| 77
Communication Cable| mm2 x No. (VCTF-SB)| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C| 1.0 ~ 1.5 x 2C



Refrigerant

| Refrigerant Name|  | R410A| R410A| R410A
Precharged Amount in Factory| kg| 14.8| 14.8| 12.0
t-CO2eq|  | 30.895| 30.895| 25.050
Control|  | Electronic Expansion Valve| Electronic Expansion Valve| Electronic Expansion Valve
Power Supply| Ø, V, Hz| 3, 380-415, 50| 3, 380-415, 50| 3, 380-415, 50
Number of Maximum Connectable Indoor Units| 64| 64| 64

Note

  1. Maximum numbers are prepared based on assumption that all 2.2kW indoor units are connected. The numbers in parentheses means maximum connectable indoor units in accordance with
    outdoor units combination (160% ~ 200%). The recommended ratio is 130%.

  2. Due to our policy of innovation some specifications may be changed without notification

  3. Performances are based on the following conditions

    • Cooling : Indoor temp 27°C (80.6°F) DB / 19°C (66.2°F) WB, Water inlet temp 30°C (86°F)
    • Heating : Indoor temp 20°C (68°F) DB, Water inlet temp 20°C (68°F)
    • Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
  4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
    Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
    Therefore, these values can be increased owing to ambient conditons during operation.

  5. This product contains Fluorinated Greenhouse Gases. (R410A, GWP (Global warming potential) = 2,087.5)

  6. Add an anti freeze to circulation water when outdoor unit is operating under 10°C (50°F), and change the DIP switch on main PCB. (For more information on installation section.)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>