Resource Data Management RS485 Modbus Interface User Guide

June 9, 2024
Resource Data Management

Resource Data Management RS485 Modbus Interface
Resource Data Management RS485 Modbus Interface

USB to RS485 Modbus® Interface

Resource Data Management

Modbus network support can be enabled using the RDM USB to RS485 Modbus network adaptor, part number PR0623/ PR0623 DIN. A single adapter is supported by the DMTouch and allows for two RS485 Modbus networks, with up 32 devices on each network line. Similarly when used in conjunction with the intuitive plant TDB, it can also support the two network lines with 32 devices on each.
Support is provided for a range of Modbus devices and new devices are being added continuously. Contact RDM Technical support to obtain the most up to date list of supported devices.

Note: This feature requires Data Manager software version V1.53.0 or above.
Resource Data Management

  • Optional dependent on application
    Mechanical
    Dimensions 35 x 22 x 260mm
    Weight 50g (1.7 oz)
    Resource Data Management

Mechanical
Dimensions 112 x 53 x 67mm
Weight 110g (3.8 oz)

RS485 Configuration

Note the RS485 configuration defaults of the Adapters are the following:

Baud rate 9600
Data bits 8
Parity No
Stop Bits 1

When connected to a DMTouch with software V3.1 or above or an Intuitive TDB with software V4.1 or above the adapter can be configured with the following set up.

Baud Rate Data Bits Parity Stop Bits
1200 8 E 1
1200 8 N 2
2400 8 E 1
2400 8 N 2
4800 8 E 1
4800 8 N 2
9600 8 E 1
9600 8 N 2
19200 8 E 1
19200 8 N 2
38400 8 E 1
38400 8 N 2

Specifications

DC Voltage 5V
Rated Current 0.1A (USB Powered)

Adding a Modbus Device

DMTouch
On the DMTouch the adapter/ software needs to be activated before it will communicate to the Modbus devices. Please consult RDM sales for activation.
Adding a Modbus Device

When activated, it will open a number of useable ‘templates’ for devices to communicate with the DMTouch.
Currently the following Modbus® devices are supported:

Modbus ® Energy Meters SIRIO Energy Meter
4MOD Pulse Counter Socomec Diris A20
AcuDC 240 Socomec Diris A40
AEM33 Power Monitor SPN ILC Energy Meter
Autometer IC970 VIP396 Energy Meter
Carlo Gavazzi EM21 VIP396 Energy Meter (IEEE)
Carlo Gavazzi EM24-DIN RDM Energy Meter
Carlo Gavazzi WM14
Compact NSX
Countis E13, E23, E33, E43, E53 Other Modbus ® Devices
Cube 350 Gas Detection
Dent Powerscout Energy meter CPC Infrared RLDS Unit 1
EMM R4h Energy meter TQ4200 Mk 11 (16 Chan)
Enviro ENV900 TQ4200 Mk II (24 Chan)
Enviro ENV901 TQ4000 (4 Chan)
Enviro ENV901-THD TQ4300 (12 Chan)
Enviro ENV903-DR-485 TQ4300 (16 Chan)
Enviro ENV910 Single Phase TQ8000 (24 Chan)
Enviro ENV910 Three Phase TQ8000 (16 Chan)
Flash D Power Monitor TQ8000 (8 Chan)
Flash D Power Monitor (3 Wire ) TQ100 (30 Chan)
ICT Energy Meter EI Safety Gas Detection System
ICT Energy Meter EI Flex – 1phase Carel Gas Detection
ICT Energy Meter EI Flex – 3phase MGS Gas 404A Detector
IME Nemo 96HD Others
Integra 1530 Toshiba FDP3 A/C Interface
Integra Ci3/Ri3 Energy Meter Polin Bakery Controller
Janitza UMG 604 ISpeed Inverter Drive
Janitza UMG 96S RESI Dali Lighting System
Kamstrum Multical 602 Sabroe Unisab III
Measurlogic DTS AirBloc SmartElec2
Nautil 910 Energy Meter Emerson Control Techniques VSD
Schneider Masterpact NW16 H1 Daikin ZEAS Remote Condensing units 11-

26

Schneider PM710| NXL Vacon Inverter Template
Schneider PM750| NSL Vacon Inverter Template
Shark Energy Meter|

Note: Please be aware that the templates listed above were generated on request and designed to the customers’ requirements. Please contact RDM Technical Support for information regarding the template.
Furthermore, if you have a Modbus® device which is not listed please contact RDM Technical Support.

The USB dongle is not ‘plug & play’, for the DMTouch to recognise the device, it must be present when powered up (or restarted).
To add a Modbus device, log in and navigate through the following menus:
Adding a Modbus Device

Selecting the ‘Add device’ option, will show the following page:
Adding a Modbus Device

Within the page, all fields will need to be entered:

Device Type: Select Modbus/ USB device
Name: The six character name which appears on the ‘device list’
Alias: Enter an appropriate description for the device
Type: Select the device from the drop down menu.
USB Line: Select either Line 1 or Line 2, depending on the network line the controller is physically connected.
Modbus Address: Enter the Modbus address of the device.

Once details are entered, the Modbus controller will show in the device list.

Intuitive Plant TDB

With the Intuitive Plant TDB, the Modbus USB is already activated. Therefor similar to the dmTouch, the adapter needs to be present when the controller is booting up (restart). Currently, the following Modbus devices are listed within the intuitive controller:

Device Device
Flash D Power Mon (4 Wire) Schneider PM710
VIP396 Energy Meter Flash D Power Mon (3 Wire)
4MOD Pulse Counter Sirio Energy Meter
Autometer IC970 VIP396 Energy Meter (IEEE)
Socomec Diris A20 Shark Energy Meter
AEM33 Power Monitor Powerscout
Enviro ENV901 Enviro ENV900
AEM33 Power Monitor

Note: Please be aware that the templates listed above were generated on request and designed to the customers’ requirements. Please contact RDM Technical Support for information regarding the template.
Furthermore, if you have a Modbus® device which is not listed please contact RDM Technical Support.
To add a Modbus device, log in and navigate through the following menus: Network – Add Device
Intuitive Plant TDB

Within the page, all fields will need to be entered:

Device Type: Select Modbus/ USB device
Name: The six character name which appears on the ‘List’ page
Type: Select the device from the drop down menu.
Modbus Address: Enter the Modbus address of the device.
Network Line: Select either Line 1 or Line 2, depending on the network line the controller is physically connected.

Once details are entered, the Modbus controller will appear within the ‘List’ of devices under Network – List.
Intuitive Plant TDB

Disclaimer

The specifications of the product detailed in this document may change without notice. RDM Ltd shall not be liable for errors or omissions, for incidental or consequential damages, directly or indirectly, in connection with the furnishing, performance or misuse of this product or document

Modbus® is a registered trademark of the Modbus Organisation, Inc.

Revision History

Revision Date Changes
1.0 08/09/2015 First document
1.0a 03/05/2017 New documentation format.
1.0b 18/12/2019 Update to US Offices
1.0c 03/02/2022 USB Modbus setup table added

Group Offices

RDM Group Head Office
80 Johnstone Avenue
Hillington Industrial Estate
Glasgow
G52 4NZ
United Kingdom
+44 (0)141 810 2828
support@resourcedm.com

RDM USA
9441 Science Center Drive
New Hope
Minneapolis
MN 55428
United States
+1 612 354 3923
usasupport@resourcedm.com

RDM Asia
Sky Park at One City
Jalan USJ 25/1
47650 Subang Jaya
Selangor
Malaysia
+603 5022 3188
asiatech@resourcedm.com

Visit www.resourcedm.com/support for more information on RDM solutions, additional product documentation and software downloads.

While every effort is made to ensure the information given within this document is accurate, Resource Data Management Ltd shall not be liable for errors or omissions, for incidental or consequential damages, directly or indirectly, in connection with the furnishing, performance or misuse of this product or document. All specifications are subject to change without notice.
See www.resourcedm.com for terms and conditions of sales.
Copyright © Resource Data Management

Resource Data Management logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals