Zipato PIR Sensor ne-nas-pd01zt.eu Manual
- June 8, 2024
- Zipato
Table of Contents
- Zipato
- PIR Sensor
- SKU: ne-nas-pd01zt.eu
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Communication to a Sleeping device (Wakeup)
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Sensitivity Level Setting
- Parameter 2: ON/OFF Duration
- Parameter 3: BASIC SET LEVEL
- Parameter 4: PIR DETECTION FUNCTION ENABLED / DISABLED
- Parameter 5: AMBIENT ILLUMINATION LUX LEVEL
- Parameter 6: RE-TRIGGER INTERVAL SETTING
- Parameter 7: LIGHT SENSOR POLLING INTERVAL
- Parameter 8: 8
- Parameter 9: AMBIENT ILLUMINATION LUX LEVEL REPORT
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Zipato
PIR Sensor
SKU: ne-nas-pd01zt.eu
Quickstart
This is a ****
Alarm Sensor
for
CEPT (Europe).
Please make sure the internal battery is fully charged.
To add this device to your network execute the following action:
1.Remove the sensor cover. 2.Make sure the sensor is powered. 3.Set ZWave
controller or ZWave gateway into inclusion mode (Refer to the controller or
gateway operating manual) 4.Press the button three times within 1.5 second,
the device will enter inclusion mode. And the LED will flash on and off
alternately five times.
Please refer to the
Manufacturers
Manual for
more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Presence detector and illuminance meter in one device. Zipato PIR motion sensor offers elaborate security and ambient sensing options.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Reset procedure will delete all information on the ZWave network and ZWave controller or ZWave Gateway, and restore the sensor to factory default settings.1.Remove the device cover. 2.Make sure the sensor is powered. 3.Press and hold the button for 10 seconds, Led will blink once. 4.Release the button. Note: to use the reset procedure only when the primary controller is missing or inoperable.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
1.Remove the sensor cover. 2.Make sure the sensor is powered. 3.Set ZWave controller or ZWave gateway into inclusion mode (Refer to the controller or gateway operating manual) 4.Press the button three times within 1.5 second, the device will enter inclusion mode. And the LED will flash on and off alternately five times.
Exclusion
1.Remove the device cover. 2.Make sure the sensor is powered. 3.Set ZWave controller or ZWave gateway into exclusion mode (Refer to the controller or gateway operating manual) 4.Press the button three times within 1.5 second, the device will enter exclusion mode.
Communication to a Sleeping device (Wakeup)
This device is battery operated and turned into deep sleep state most of the
time
to save battery life time. Communication with the device is limited. In order
to
communicate with the device, a static controller C is needed in the
network.
This controller will maintain a mailbox for the battery operated devices and
store
commands that can not be received during deep sleep state. Without such a
controller,
communication may become impossible and/or the battery life time is
significantly
decreased.
This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the
desired
wakeup interval and the node ID of the controller. If the device was included
by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please
perform
the following action:
You can press the button once to wake up the device and send wakeup notification to controller. If press successfully, the LED will blink one time
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 4 | Z-Wave Plus Lifeline |
---|---|---|
2 | 4 | GROUP 2 allows for sending control commands to associated devices such |
as relay module, lighting, etc. This association group is configured through
the advanced parameters no. 2, 3, 5 and 8. This Group Support: BASIC_SET
3| 4| GROUP 3 allows for Send Notification to associated devices in this
group. This Group Support: NOTIFICATION_REPORT_V4
4| 4| GROUP 4 allows for Send Sensor Binary Report to associated devices in
this group. This Group Support: SENSOR_BINARY_REPORT_V2
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Sensitivity Level Setting
This parameter defines the sensitivity of PIR sensor. Its recommended to
test thesensor with movements from the farthest end of the coverage area at
the first timeof use. If movements cannot be detected sensitively, simply
adjust the sensitivitylevel with this parameter. This parameter can be
configured with the value of 8through 255, where 8 means high sensitivity and
255 means low sensitivity.
Size: 1 Byte, Default Value: 12
SettingDescription
8 – 255 | PIR sensitivity |
---|
Parameter 2: ON/OFF Duration
_This parameter determines how long the associated devices should have ON
status.For instance, if this parameter is set to 30 (sec), the PIR sensor will
send aBASIC_SET command to associated device with value BASICSET level if PIR
sensoris triggered and associated device will be turned on 30 seconds begore
its turnedoff. This parameter value must be large as Parameter #. If user sets
this parameterto default by Configure CC, the parameter # will be set to
default value.
Size: 2 Byte, Default Value: 30
SettingDescription
5 – 600 | Seconds |
---|
Parameter 3: BASIC SET LEVEL
_BASIC_SET command will be sent when PIR sensor is triggered. The receiver
willtake it into consideration; for instance, if a lamp module is receiving
the BASICSETcommand of which value is decisive as to how bright of dim level
of lamp moduleshall be.
Size: 1 Byte, Default Value: 255
SettingDescription
0 – 99 | Dim level |
---|---|
255 | Previous non zero dim level |
Parameter 4: PIR DETECTION FUNCTION ENABLED / DISABLED
This parameter can enable or disable the PIR sensor detecting
function.Function: Enabled / Disabled PIR function
Size: 1 Byte, Default Value: 255
SettingDescription
0 | DISABLE |
---|---|
255 | ENABLE |
Parameter 5: AMBIENT ILLUMINATION LUX LEVEL
_This parameter can set Lux value which determines when the light sensor
isactivated. If the ambient illumination level falls bellow this value and a
person movesacross or within the detection area, PIR sensor will send Z-Wave
ON command (i.e.BASICset (value = parameter 3) to an associated device and
activate it.
Size: 2 Byte, Default Value: 100
SettingDescription
0 – 1000 | Lux |
---|
Parameter 6: RE-TRIGGER INTERVAL SETTING
This parameter can be used to adjust the interval of being re-triggered
after the PIRsensor has been triggered. This parameter value must be less than
Paramater #2.If user sets this parameter to default by Configure CC, the
parameter #2 will be setto default value.
Size: 1 Byte, Default Value: 8
SettingDescription
1 – 8 | Retrigger interval in seconds |
---|
Parameter 7: LIGHT SENSOR POLLING INTERVAL
This parameter can set the light sensor to measure ambient illumination
levelinterval time. NOTE: This value must be less than Wakeup Interval Time!
Size: 2 Byte, Default Value: 180
SettingDescription
60 – 3600 | Seconds |
---|
Parameter 8: 8
_If this parameter is set to 1 and when Lux level is less than the value
defined byparameter #5, PIR sensor will send a BASIC_SET command frame (i.e.
BASIC_SET(value = parameter 3) to an associated device and activate it. If Lux
level is greater than thevalue defined by parameter #5, PIR sensor will not
send BASICSET command frame.
Size: 1 Byte, Default Value: 0
SettingDescription
0 | DISABLE |
---|---|
1 | ENABLE |
Parameter 9: AMBIENT ILLUMINATION LUX LEVEL REPORT
This parameter defines by how much Lux level must change in Lux to be
reported tothe main controller.
Size: 2 Byte, Default Value: 1
SettingDescription
0 – 1000 | lux |
---|
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Notification Sensor |
Network Operation | Reporting Sleeping Slave |
Firmware Version | HW: 66 FW: 3.80 |
Z-Wave Version | 6.51.06 |
Certification ID | ZC10-18015916 |
Z-Wave Product Id | 0x0131.0x0003.0x1089 |
Sensors | Luminance |
Supported Notification Types | Home Security |
Color | White |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Supported Command Classes
- Association Grp Info
- Association V2
- Battery
- Configuration
- Device Reset Locally
- Manufacturer Specific V2
- Notification V4
- Powerlevel
- Sensor Binary V2
- Sensor Multilevel V7
- Version V2
- Wake Up V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>