NIAGARA DELTA 24 FF Wall-Mounted Gas Boiler Instruction Manual

June 2, 2024
NIAGARA DELTA

24 FF Wall-Mounted Gas Boiler

Machine Translated by Google
WALL-MOUNTED GAS BOILER DOUBLE SERVICE built-in accumulation Forced flow sealed model Instructions for installation and use

NIAGARA DELTA 24 FF NIAGARA DELTA 28 FF NIAGARA DELTA 30 FF
FR

C
C

Machine Translated by Google
Name of the boiler: NIAGARA DELTA 24 FF NIAGARA DELTA 28 FF NIAGARA DELTA 30 FF

This installation and user manual is intended for appliances installed in France

Summary

Instructions for the installer

1 – Description ……………………………………….. ………………………………………….. ……… 2 dimensional characteristics ………………………………. ……………………………. 3 – hydraulic characteristics ……………… ………………………………………….. …………… 4 – installation conditions ………………………… ………………………………………….. ……. 5 – installation of the
boiler…………………………. ………………………………………….. … 6 – disassembly and assembly of the casing – maintenance…………………………….. ….. 7 – electrical connections …………………………………. …………………………………. 8 commissioning ….. ………………………………………….. ……………………………………. 9 –
settings…. ………………………………………….. …………………………… ………………….. 10 – operating incidents ……………………… ………………………………………….. ……. 11 – gas
transformation ……………………………….. ………………………………………….. .

Page
3 4 5 6 7 8 9 10 11 16 18

Instructions for the user
Page
12 – commands………………………………………… ………………………………………….. ……. 18 13 driving…………………………………… ………………………………………….. ………………… 19 14 maintenance …………………… ………………………………………….. ……………………………. 20 15 – combustion product evacuation safety ………….. …………………………………. 20 16 warranty …… ………………………………………….. ………………………………………….. …. 21 17 – practical advice……………………………………….. ………………………………………….. …. 21 18 – change of gas……………………………… ………………………………………….. .. 21 19 – technical characteristics……………………………………….. ………………………………. 22 20 – operating faults….. ………………………………………….. …………………… 24

2

Machine Translated by Google
Instructions for the installer

1

Description

9
14
16 17 15
19 21

Fig.1

11

20

24 25 26 30 27 28 29

K
1
3 13 4 5
6
12
7 2
18
8
10

1. – sheet steel frame 2. – pressure expansion vessel 3. – extraction hood 4. – main copper exchanger 5. – waterproof case 6. – stainless steel multigas burner comprising:
· a removable manifold equipped with injectors · two ignition electrodes · a flame detection electrode 7. – gas block comprising: · two safety solenoid valves · a regulation solenoid valve 8. – automatic degasser 9. – stainless steel domestic hot water tank 10. – circulator 11. – electronic unit (fig. 2) 12. – igniter 13. – overheating safety 14. – combustion product control pressure switch 15. – tank thermistor
16. – flow heating thermistor 17. – return heating thermistor 18. – distributing valve
19. – sanitary heat exchanger with stainless steel plates 20. – sanitary flow switch 21. – sanitary thermistor K. – fixing the evacuation kit (see kit instructions)

31
22
Fig.2

32 23

22. – heating switch: Off / min / max 23. – DHW switch: Off / mini / eco / comfort 24. – green power-on light 25. – orange burner operation light 26. – green heating mode light 27. – green DHW mode light 28. – red safety light 29. – reset push button 30. – heating circuit pressure gauge 31. display
32. – installer mode setting pushbuttons
3

Machine Translated by Google
2 Dimensional characteristics
195 500

950

925

470 180

450 min for maintenance 595

135 317

57

54 172 80

54 54 145

38

43

188

42

41 40 39

44

Fig. 3
3 connection solutions to choose from: · type C 12 ou C 42 · type C 32 xx
100 60 143
58
Type C 12 4

Ø 80 Ø 125
Type C 32 xx

280
39 Gas inlet 40 Heating return 41 Heating flow 42 Cold water inlet 43 Cylinder hot water flow 38 Balloon valve 44 Heating valve
250 Poids à vide · 24 kW : 59 kg · 28 kW : 60 kg · 30 kW : 60 kg

Machine Translated by Google

3

Hydraulic characteristics

The boiler is supplied as standard with an automatic by-pass and a 2-speed ciculator. The diagram (fig. 4) shows the curve of the pressure available as a function of the flow (at the boiler outlet). The minimum flow rate of the installation to ensure proper operation must be 300 l/h. (Thermostatic taps closed).
Water capacity of the installation. The boiler is fitted with a pressurized expansion vessel. Maximum volume of the expansion tank: 7.1 litres. Inflation pressure: 0.7 bar.
The expansion capacity of the vessel of a pressurized installation varies with (fig. 5): the average operating temperature in °C, – the static height which corresponds to the difference in level in meters, between the highest point top of the installation and the axis of the expansion tank
The filling pressure should always be higher than the static height (expressed in meters) divided by 10 (recommended between 1 and 1.5 bars)

Available pressure
mCE Minimum flow rate (thermostatic valves closed) 6
5
Teacher
4
3 PV
2

1

0

100

300

500

700

200

400

600

800 900 10001100 1200

l/h
Fig. 4

PPf f Cold pressure for the heating circuit (in bar) 2.0

1,9

1,8
1,7
40°C
1,6

1,5
50°C
1,4

1,3
60°C
1,2
70°C
1,1
80°C
1,0

0,9 0,8 0,7
20 40 60 80 100 120

140 160 180 200 220 240

260

Water content diMagaxraimmu.m capacity of the installation (in litres)

C
Fig. 5

– Pf = Pressure of the expansion vessel, in bar – C = Capacity of the installation, in litres.
5

Machine Translated by Google

4

Conditions d’installation

4.1 REMINDER OF THE REGULATIONS
RESIDENTIAL BUILDINGS REGULATORY CONDITIONS FOR INSTALLATION AND EN THIRD The installation and maintenance of the device must be carried out by a qualified professional in accordance with the regulatory texts and rules of the art in force, in particular: – order of August 2, 1977 Technical and Safety Rules applicable to combustible gas and liquefied hydrocarbon installations located inside buildings and their outbuildings. – order of February 5, 1999 amending the order of August 2, 1977
After replacing an identical boiler (axis and footprint of the previous appliance), the installer is required to draw up a “model 4″ certificate of conformity. – standard DTU P 45-204 – Gas installations (formerly DTU
n°61-1 – Gas installations – April 1982 + addendum n°1 of July 1984). – Departmental Health Regulations.
Protection of the drinking water network · the presence on the installation of a CB type disconnection function with uncontrollable different pressure zones meeting the functional requirements of standard NF P 43-011, intended to prevent heating water returning to the network drinking water is required by articles 16-7 and 16-8 of the Departmental Health Regulations.
· an NF backflow preventer is placed on the tap bar of the boiler.
· standard NF C 15-100 – Low voltage electrical installations – Rules.
ESTABLISHMENTS OPEN TO THE PUBLIC REGULATORY INSTALLATION CONDITIONS Installation and maintenance of the device must be carried out by a qualified professional in accordance with the regulatory texts and rules of the art in force, in particular: – safety regulations against fire and panic in establishments
receiving public: a) General requirements for all appliances:
· articles GZ Fuel gas and liquefied hydrocarbon installations. · CH articles

4.2 PRECONISATION D’INSTALLATION
Installation of the boiler – the axis of the external flue must be placed at a distance of
at least 0.40 m from any opening window and at a minimum distance of 0.60 m from any ventilation orifice (depending on the type of outlet chosen, refer to the instructions for the evacuation kit). – when installing a boiler in a bathroom, comply with the special safety rules of standard NF C 15-100 (chapter 7).
– do not install the boiler above the hotplates, the oven, and in general above any equipment producing oily vapors which could, through clogging, affect its operation.
– provide a wall and fixings to support the weight of the boiler (weight: approximately 130 kg). – take precautions to limit
noise pollution.
Domestic hot water circuit
In the case of water hardness greater than TH 25, provide water treatment.
See sanitary DTU standard .
Central heating circuit Flow rate: when sizing, make sure that the minimum flow rate is complied with: 300 I/h, thermostatic valves closed.
Corrosion Precautions
Operating incidents due to corrosion are likely to occur when the installation is made with dissimilar elements.
To avoid these problems it is desirable to use a corrosion inhibitor. Take every precaution to prevent the treated water from becoming aggressive. Old installation: place a settling pot on the return and at the low point, and provide for appropriate treatment of the circuit.
Recommendation: provide air vents on all the radiators and at the high points of the installation; as well as drain cocks at low points.

Heating, ventilation, refrigeration, air conditioning and production of steam and domestic hot water. b) Specific
requirements for each type of establishment open to the public (hospitals, shops, etc.). Recommendation :
If the region is exposed to the risk of lightning (insulated installation at the end of the EDF line, etc.), provide a lightning arrester.
Our warranty is subject to this condition.

6

Machine Translated by Google

5

Installation of the boiler

LAYING TEMPLATE present the paper template provided for the prefabrication to the selected location and follow its recommendations. – take into account the installation conditions § 4. CONNECTING THE PIPING The connection sockets are supplied in a package separate from the device. Various fitting sets are available from wholesalers.
– 1st installation replacement of Chaffoteaux & Maury boilers – replacement of boilers of other brands – wall spacer kit (in the case of passage of the tubes from the rear)
– put in place (fig. 6): – the various taps, 3/4 gas taps (yellow lever tap, minimum tightening torque 10 mN), heating flow and return, 1/2 taps on domestic cold water, and hot water tank outlet hose 46 – seals and connection sockets, 3/4 sockets on gas, heating flow and return, 1/2 socket on cold water and water domestic hot water – an F1 filter gasket is placed on the gas tap, an F2 water filter on the domestic cold water supply and a heating filter F3 on the heating block – The drain pipe of the safety valve 44 (translucent tube), the balloon valve 38 and that of the backflow preventer 45 must be connected to a waste water pipe.
EXHAUST KIT – finish by mounting the exhaust device, at location K (fig. 1), depending on the type of connection chosen, taking
referring to the assembly instructions supplied with the kit. CLEANING AND TREATMENT OF THE INSTALLATION Once the hydraulic connections have been completed, it is essential to clean the installation with an appropriate product (dispersant) in order to remove filings, welds, machining oils and various greases. Prohibit any solvent or aromatic hydrocarbon (gasoline, oil, etc.).
Complete treatment of the installation is recommended from commissioning in order to maintain a pH between 9 and 9.5.
To fit the boiler, it is not necessary to remove the casing.

44 45 46 F2
38 Fig. 6

F3 F1
1/4 7

Machine Translated by Google

6

Disassembly and assembly of the casing – maintenance

A A

Removing the trim – unscrew
the 4 fixing screws A of the trim (fig. 7) – release the clips – remove the trim

A A
detail
Fig. 8
A A
Maintenance
For maintenance of the device, it is possible to move the electrical box without having to disconnect it. Electrical box clipped onto the heating outlet pipe or lower back of the frame – (fig. 9).

A

Fig. 7

A

Fitting the casing Remove the protective film – present the casing (fig. 8) – engage the 2 clips in the casing
(see detail)
– tighten the 4 fixing screws A of the front

Fig. 9 8

Machine Translated by Google
7 Electrical connections
Location of the connections: – the electrical connection of the TA is made under the boiler, on the bottom plate. the arrivals of the mains supply cables and the room thermostat must be provided on the wall at the height defined by
the installation template – the mains supply to the boiler is carried out with a 2 P + E cable supplied with the ‘device. The TA cable is not supplied.
Note: the 2 cables, mains and TA, must be 2 separate cables
Important: – in accordance with the regulations, a bipolar separation device, with a contact opening distance of at least 3 mm, must
be provided in the fixed boiler supply installation
C
Mains connection The 3-conductor cable C is pre-wired in the electrical box of the device. Connect this cable to the protected 230 V distribution network. (fig. 10)
Connecting a room thermostat
Open terminal block B using a screwdriver (fig. 11) A room thermostat is connected to this connector B. (fig. 12) – remove shunt S. – connect the thermostat in place of
shunt S

TAHMEBIRAMNOCSETAT TRHOEORMMOSTAT

Fig. 10
B

TA connection

Connector B

S

Fig. 11

Connection on the pre-wired electrical box side
Fig. 12

9

Machine Translated by Google

8

Commissioning

Pressurization (fig. 13)
Sanitary circuit – open the cold water tap 42 – drain the tank and the installation by drawing from the various hot water taps Heating circuit – check that the heating flow 41 and heating return 40 valves are open – open the filling valves 37 close these valves when the needle of the pressure gauge 30 is at the pressure determined in § 3 bleed the installation and restore the pressure
Gas circuit open the gas tap 39 – bleed the gas circuit – check the seals on the entire gas line

30

Fig. 13

37

40

39

41

42

10

Machine Translated by Google

9

Settings

The device when it leaves the factory is preset. The value of these settings is specified in menus 3 and 4 All settings can be changed by the installer or a qualified professional. The settings and information on the boiler can be accessed by tilting door P of the electrical box and removing cover D (fig. 14).

Display
D

Fig. 14
DISPLAY Element 1

Fig. 15
P
Menu key – key + key Settings key
Element 3 Element 2

To access the menus, press the keys
is displayed.

and

simultaneously for about 5 seconds (fig.15). Menu 1

Menu change: Press the Menu key

(fig.15). The menu number is displayed for 3 seconds

. To access the

next menu, press the Menu button again .

Changing items within a menu:

Push the button

or the key

to move up or down headings.

Note: when you are on the last item, you loop back to the 1st if you execute a +, and when you are on the first, you loop back to

the last if you execute a –

Modifying the parameters of a section (only concerns menus 3 and 4) :

Press the Setup button to change to switch to adjustment mode, elements 2 and 3 flash, then press to validate the

or

the setup parameters. Press the Setup button

modifications

and exit Setting mode, items 2 and 3 stop flashing .

Return to factory configuration:

Position yourself in menus 3 or 4 and press the key

indicates CM

flashing for a few moments when this is done.

and Setting

for 10 seconds. The display

Fault history reset:

Go to menu 1 and press the key

CM

flashing for a few moments when this is done.

and Setting

for 10 seconds. The display shows

Note: To exit installer mode, the display switches back to user mode approximately 1 minute after the last pressing the keys.

11

Machine Translated by Google
ACTION

STATE

DISPLAY

Menu – 1 – Fault history indicates the

5

last 10 faults

rubric Last fault appeared Penultimate fault that appeared x times …

Element 1 Element 2 and 3

code from 01 to 99

code from 01 to 99

code from 01 to 99

Last fault that appeared before the previous one

code from 01 to 99

Note: The display shows — if there was no fault code recorded

1 time

Menu – 2 – Boiler status indicates the status or configuration of the boiler

rubric Display board software version

Element 1 Element 2 and 3

10 to 99

Main board software version x times
Type of smoke evacuation

10 to 99

0 : CF

1 : FF

variable speed

2 : VMC

3 : FF

Fixed speed

4 : condensation

TA request present

0 : non

1 : yes

Theoretical position of the distributing valve
Sanitary outlet temperature (in °C) Tank temperature (in ° C) Heating flow temperature (in ° C) Heating return temperature (in ° C)

0 : sanitary

1 : heating

from 0 to 99

x x

from 0 to 99

x x

from 0 to 99

x x

from 0 to 99

x x

Outside temperature Flashing when negative temperature

from 0 to 99

x x

12

Setting factory

Machine Translated by Google

ACTION

STATE

1 time

Menu – 3 – Boiler settings

rubric Gentle heat module

x times

Sanitary safety temperature DHW setpoint fixed at 60° no setpoint display

Element 1
0 0
1 1

Element 2 and 3 0 : non 1 : yes
0 : non 1 : yes

DISPLAY

Programmer action

2

0 : out of the 2

2

1 : on cylinder heating

2

2 : on heating

2

3 : on none

Max. boiler gas power level from 70% of P nominal to P nominal

3

Value from 0 to 10

13

Setting factory

Machine Translated by Google
ACTION
1 time

STATE
Menu – 4 – Settings for heating

DISPLAY

rubric
Pump shut-off operation x times
Pump speed

Element 1 Element 2 and 3

0

0 : non

0

1 : yes

1

0 : big

1

1 : Small

2

0 mn

Pump post-circulation time 0 to 5 minutes in 1/2 minute steps

2

0,5 mn

2

1,0 mn

2

5 mn

Heating setpoint in

Manuel Automatique

3

0 : manuel

3

1 : auto

Maximum heating setpoint from 50 to 90°C in steps of 1°C

4

85°C

Minimum heating setpoint from 25 to 50°C in steps of 1°C

5

35°C

Setting the time threshold for the closed state

0 to 60 minutes in 1 minute steps

Functioning

Normal

6

x x

from 5 to 60 minutes

6

7

0 : non

All or nothing

7

1 : yes

8

0 mn

TAC

8

0,5 mn

From 0 to 7 minutes in steps of 1/2 minute

8

2,5 mn

8

7 mn

Gas power level max. in heating from P min to P max general NOTE: P max. see menu 3 section 3

Value

9

from 0 to 10

14

Machine Translated by Google

9

Example of settings (continued)

Setting the TAC: If you want to modify the setting of the TAC (Heating Anti Cycle Timer) to 3 minutes.
(reminder: factory setting at 2 min 30 s / see installer table menu 4 section 8).
Proceed as follows:

1 – switch to installer mode,

1

touches

and

pressed for

5 seconds, the display indicates: -1-

then 0·– if there is no fault or a code

corresponding to the last default


5

Display

2 – press the menu key three times to

2

get to menu -4-, the display shows: -4- then

the setting of item 0

either 0 0 or 0 1

x 3 or

3 – go to section 8 (adjustment of the

3

x 8

TAC) by pressing the key 8 times

, the display indicates:

82.5 (which corresponds to the factory

setting 2 min 30 s) 8 = item 8 2.5 = 2.5 min

– i.e. 2 min 30 seconds

4 – press the setting key once, elements

4

2 and 3 flash, then press the key until

3.0 appears on elements 2 and 3, the

display indicates: 83.0 validate by pressing

the setting key once. Elements 2 and 3 no

longer flash.

The setting is complete. The display switches back to mode user after about 1 minute.
Once the various settings have been completed, replace the cover D and close the door P (fig.14).

15

Machine Translated by Google

10

Operating incidents

In the event of an operating or information anomaly, the display flashes a 2-digit code. Refer to the table below to diagnose the problem.
For faults 01 and 03 the device locks, red LED 28 lit (fig.16).

Example: Overheating lockout

28

DEFECT

Fig. 16

Display coding
01 03 05 06 07 08 09 10 11 12 13 14 17 18 19 20 21 22 23 24 25 26 27 31 32
16

Fault title
Overheating lockout Lockout by ignition fault
No water circulation Primary water circulation fault
Sanitary thermistor open Sanitary thermistor shorted
Heating flow thermistor open Heating flow thermistor short-circuited Heating return thermistor open Heating return thermistor short-circuited Flue gas overflow fault shutdown (Spott) (CF) or 1.25 A fuse
Safety by smoke overflow (VMC) Wiring problem (FF) or 1.25A fuse No extraction flow (FF) Extraction detection device (FF) failure Low Extractor Speed (FF) Extractor operating control fault (FF)
Balloon thermistor open
Tank thermistor short circuited
Communication problem with the display card Communication fault with the main board

Information
Pump frost protection Frost protection burner
Restart attempt
Tank temperature out of limit

Machine Translated by Google

Burner gas power adjustment The values given in the tables below are given as an indication for a nominal gas distribution pressure, to make a possible adjustment of the heating power of the boiler according to the needs of the installation.
They cannot be used to calculate the exact boiler output set.

Gas: P. utile
(kW)
8
10 12 14 16 18 20 22 24

G20 Feed pressure (mm WC)
7 11
16 22 28 36 44 53 63

Niagara Delta 24 FF G25
Feed pressure (mm WC)
8
13 19 26 34 43 53 64 76

PROPANE Feed pressure (mm WC)
71 100 153 182 217 269 295 299 302

BUTANE Feed pressure (mm WC)
56 78 115 140 152 168 213 231 235

Gas: P. utile
(kW)
8
10 12 14 16 18 20 22 24 26 28

G20 Feed pressure (mm WC)
7 11
16 22 28 36 44 53 63 74 86

Niagara Delta 28 FF G25
Feed pressure (mm WC)
8
13 19 26 34 43 53 64 76 89 103

PROPANE Feed pressure (mm WC)
71 100 153 182 217 269 295 299 302

BUTANE Feed pressure (mm WC)
56 78 115 140 152 168 213 231 235

Gas: P. utile
(kW)
8
10 12 14 16 18 20 22 24 26 28 30

G20 Feed pressure (mm WC)
10 13 20 25 33 42 50 61 72 84 95 110

Niagara Delta 30 FF G25
Feed pressure (mm WC)
16 20 27 35 46 60 73 87 105 120 136 160

PROPANE Feed pressure (mm WC)
22 40 58 70 88 120 150 180 210 250 280 320

BUTANE Feed pressure (mm WC)
20 30 40 52 70 90 114 135 158 184 210 242
17

Machine Translated by Google

11

Gas transformation

In the event of adaptation to a gas other than that for which the boiler is equipped, the parts supplied with the conversion kit will be replaced.

12 Orders

Instructions for the user

24 25 26

30

27 28 29

31

22

23

Fig. 17

Dashboard

22. – heating switch: 0 / min / max 23. – sanitary switch: 0 / mini / eco / comfort

24. 25. 26. –

green power on light orange burner operating light green heating mode light

18

27. –

sanitary mode green light

28. –

red warning light

29. – reset push button

30. – heating circuit pressure gauge 31. – display

Machine Translated by Google

13

Conduct

Getting started (fig. 17)

1. Check that the pressure in the heating circuit is sufficient: the needle of the manometer at least 1 bar with

1.5 bar cold max. Otherwise see § 3.

2. Make sure that the general gas shut-off valve of the installation is open and that the boiler is energized,

the green light 24

lights up.

3. Open the gas valve 39 (fig.13).

Your boiler is ready to operate.

Warning: when starting up after a prolonged shutdown, the presence of air in the gas pipe may interfere with

the first ignitions. See § 20 “Operating incidents”.

Heating mode authorized only

Indicator 26 is on and the display indicates the heating flow temperature,

ex.

Switch 22 is used to adjust the temperature of the water in the heating flow circuit according to seasonal needs:
– towards maximum in cold weather – towards minimum in mild weather
The TA request is displayed by a dot at the bottom right of the display

Sanitary mode authorized only

Indicator 27 is on and: 1st case: no drawing off and no tank heating

the display indicates

fixed

2nd case: tank heating the display indicates

clockwise segment scrolling

3rd case: drawing

the display indicates

clockwise segment scrolling

Switch 23 is used to adjust the domestic water temperature between the minimum and comfort positions.
During this adjustment, the display flashes and indicates the average domestic hot water storage set point temperature.

When the switch is located in the area

Delta Safe (tank at 60°C minimum), the risk of

development of bacteria of the Legionella type is avoided.

19

Machine Translated by Google

13

Driving (continued)

Sanitary and heating mode authorized LEDs 26 and 27 are on and: 1st case: no drawing off and no tank heating

the display shows the heating flow temperature,

ex.

2nd case: tank heating

the display indicates

clockwise segment scrolling

3rd case: drawing the display indicates

clockwise segment scrolling

Standby

Middle segment fixed + power LED 24 on

Boiler standby and frost protection function Place the heating 22 and hot water 23 switches in position O The green lights 26 and 27 go out
During this mode, the circulator operates for 1 minute and the distributor valve switches over every 23 hours.
Caution: in this mode, the TA frost protection function is inoperative. Boiler frost protection function: at 7°C triggering of the pump
at 4°C burner triggering
To ensure the frost protection function of the TA leave the boiler in the heating position

Complete shutdown of the boiler – place switches 22 and 23 in position O extinguishing green lights 26 and 27 – cut off the power supply to the appliance – close the gas valve 39 (fig. 13)
Note: in this position, frost protection is not guaranteed

14

Maintenance

The annual maintenance of your boiler is compulsory under the terms of the legislation in force. Have it checked once a year by a qualified professional. For all maintenance operations on your boiler, annual maintenance contract formulas may be offered to you by service providers. Consult your installer or our sales department. The manufacturer’s warranty, which covers manufacturing defects, should not be confused with maintenance operations.

15

Combustion product evacuation safety

This boiler is fitted with a burnt gas extraction flow detection system which authorizes burner operation. In the event of a prolonged lack of flow, the boiler is put into safety shutdown; fault code display 21 Warning: this device for controlling the evacuation of combustion products must not be put out of service; nor be the object of inopportune interventions. In case of replacement, only original parts can be used.
20

Machine Translated by Google

16

Guarantee

Your boiler is guaranteed for a period specified on the guarantee certificate which specifies the terms and conditions: make sure that the detachable part of this certificate has been returned to Chaffoteaux & Maury.
To benefit from the guarantee, a qualified professional must have installed, adjusted and commissioned your installation. This gives you the assurance that he has complied with the installation instructions and that the regulatory and safety conditions have been complied with.
The first technical inspection of your boiler can be carried out free of charge at your request by a qualified professional from the “Chaffoteaux & Maury technical station”.

17

Practical advice

Frost Precautions
We advise you to consult your installer or your after-sales service who will tell you which measures are best suited to your situation. · Sanitary circuit
The boiler’s sanitary circuit is drained after having closed the installation’s cold water tap at the water meter, then: – open a hot water tap, – activate the drain valve of the balloon valve 38 (fig. 18). Water flows out of the drain hole. · Heating circuit Take one of the following measures: –

  1. Drain the circuit of the heating installation – 2) Protect the heating installation with an antifreeze product. Periodic verification of the level of protection provided by this antifreeze is an additional guarantee.

– 3) Let your installation run at idle speed by setting the room thermostat to the “frost protection” position (between 5 and 10°C). Caution: leave the boiler in the heating position

41

Fig. 18

38

18

Gas change

These devices are designed to operate either with natural gas or with butane- propane gas. The gas change must be carried out by a qualified professional.

21

Machine Translated by Google

19

Technical characteristics

Model…………………………………….. ………………… Niagara delta 24 FF

Niagara delta 28 FF

Heating power ……………………………………..Pn Power variable domestic hot water …….Pn max
Performance category according to RT 2000 ………………………. Category …………………………………………. ………………………. Forced flow sealed type. – C12 concentric horizontal outlet Ø 100/60 mm …… – C32 «xx» in concentric vertical outlet Ø 125/80 mm – C42 3CE for evacuation ducts of the type: ………. ………….. ………………………………………..· SPIRAL GAS 3CE …………………………………………………………….· ROLUX 3CE

8.2 to 24 kW 24 kW
Low temperature II 2E+3+

8.2 to 28 kW 28 kW
Low temperature II 2E+3+

Fresh air flow required for air supply to combustion………………………………………………………………V

46 m3 /h

56 m3 /h

Specific domestic hot water flow (ÿT: 30 K) …………D Domestic hot water ignition flow ………………………. ………… Minimum flow rate of the central heating circuit ………………………. Minimum DHW cut-in pressure Pw min Maximum DHW circuit pressure ……………Pw max
Maximum heating circuit pressure ………….Pw max Adjustable heating flow temperature ………………………. .. Average DHW storage temperature ……………………………. Sanitary circuit capacity ………………………………………….. .

18.7 I/min. 1.9 l/min.
300 I/h 0,5bar 7 bar 3 bar from 40 to 85°C from 45 to 70°C 60 litres

Electric tension………………………………………… ………… Absorbed electrical power …………………………………….. Electrical protection ………………………………………… ……..

230 volt mono – 50 Hz 150W IP 44

Nominal gas flow (15°C-1013 mbar) …………………..

Max flow.

Qn 26.7 kW 2.83 m3 /

G 20 (GN H – Lacq)……..34.02 MJ/m3 under 20 mbar Vr G 25 (GN L –

h 3.01 m3 /

Groningen) 29.25 MJ/m3 under 25 mbar Vr G 30 (butane) . ……….45.6 MJ/

h 2.11 kg/h

kg at 28-30 mbar Vr G 31 (propane) …………..46.4 MJ/kg at 37 mbar Vr

2.07 kg/h

Minimum flow. 9.5 kW
1.00 m3 /h 1.06 m3 /h 0.74 kg/h 0.72 kg/h

21.0 I/min. 1.9 l/min. 300 I/h 0,5bar 7 bar 3 bar
from 40 to 85°C from 45 to 70°C
60 litres

230 volt mono – 50 Hz 150W IP 44

Max flow. 31.1 kW 3.29 m3 /h 3.50 m3 /h 2.46 kg/h 2.41 kg/h

Minimum flow. 9.5 kW
1.00 m3 /h 1.06 m3 /h 0.74 kg/h 0.72 kg/h

Nat

Prop

Nat

Prop

Nanny location ………………………………………….. ……… G20-G25

G30-G31

G20-G25

G30-G31

Marking ………………………………… ………………………… 1305249 NAT 1305248 PRO 1303601 NAT 1305247 PRO Injectors in 1/100 mm….. ……………………………… 123

No. of injectors……… ………………………………………….. .

68

123

72

18

18

18

18

Diaphragm

Diameter/marking ………………………………………. …….

4,8

Solenoid valve assembly

Tracking………………………………………….. ………………. NAT GAS Color of valve

seat……………………………… ……………..

noir

4
GOAL/PROP yellow

6,2
NAT GAS black

7,0
GOAL/PROP yellow

22

Machine Translated by Google

19

Technical characteristics (continued)

Model…………………………………………. ………………………………………….. …………….
Heating power ………………………………………… ……………………………………….Pn Hot water capacity variable sanitary ………………………………………… …….Pnmax Solution Technique RT 2000………………………………………………………………………………… Category…………………………………………. ………………………………………….. ……………………… Forced flow sealed type. – C12 concentric horizontal outlet Ø 100/60 mm……………………………… ……………. – C32 «xx» in concentric vertical outlet Ø 125/80 mm – C42 3CE for evacuation ducts:……………………………. ………………………………………. · SPIRAL GAS 3CE

· ROLUX 3CE

Fresh air flow required for air supply to combustion …………………………………………………………………………………………………………V

Specific domestic hot water flow rate (ÿT: 30 K) ………………………………… ………………….D Domestic hot water ignition flow ……………… ………………………………………….. ……… Minimum flow rate of the central heating circuit …………………………………….. ………………………… Minimum sanitary cut-in pressure ………………………………………….. ….Pw min Maximum DHW circuit pressure ………………………………………. ………………Pw max
Maximum heating circuit pressure ………………………………………. …………….Pw max Adjustable boiler flow temperature ……………………… ………………………………………. Average DHW storage temperature ………………………………………….. ………………………. Sanitary circuit capacity ……………………………………….. …………………………………………..

Electric tension………………………………………… ………………………………………….. ………….. Absorbed electrical power ……………………………………….. ………………………………………. Electrical protection ………………………………………… ………………………………………….. ……….

Nominal gas flow (15°C-1013 mbar) ……………………………….. ………………………………. ……………………………………………………………………………………………………………………….Qn

G 20 (GN H – Lacq)…………………………………… …………34.02 MJ/m3 under 20 mbar G 25 (GN L –

Vr

Groningen) ………………… ……………………29.25 MJ/m3 at 25 mbar G 30

Vr

(butane) ………… ……………………………………….45.6 MJ /kg under 28-30 mbar G 31

Vr

(propane) ………………………………… …………………..46.4 MJ/kg at 37 mbar

Vr

……………………………………………………………………………………………………………………………
Nanny location ………………………………………….. ………………………………………….. ……….. Marking ………………………………………… ………………………………………….. ……………….. Injectors in 1/100 of mm……………………………………… ………………………………………….. No. of injectors………………………………………….. ………………………………………….. …………….
Diaphragm Diameter/marking ………………………………………. ………………………………………….. ……….
Solenoid valve assembly Marking ………………………………………….. ………………………………………….. ………………….. Color of valve seat ………………………………………. …………………………………………

Niagara delta 30 FF
10.1 to 30 kW 30 kW
Low temperature II 2E+3+

59 m3 /h

22.3 I/min. 1.9 l/min. 300 I/h 0,5bar 7 bar 3 bar
from 40 to 85°C from 45 to 70°C
60 litres

230 volt mono – 50 Hz 150W IP 44

Max flow. 33.3 kW 3.52 m3 /h 3.74 m3 /h 2.62kg/h 2.58 kg/h

Minimum flow. 11.3 kW 1.2 m3 /h 1.27 m3 /h 0.89 kg/h 0.88 kg/h

Nat

Prop

G20-G25

G30-G31

1306949 NAT 1306960 PRO

123

74

18

18

9
NAT GAS black

9
GOAL/PROP yellow

23

Machine Translated by Google

20

Operating incidents

Incidents The boiler does not start
Red light on; secured

Causes
Absence of gas, Absence of water
No electricity
Presence of air in the gas circuit
Shutdown by the room thermostat

Solutions
Make the necessary checks (gas supply, presence of water, circuit breakers, fuses, etc.)
May occur after prolonged downtime. Repeat the commissioning operations, see § 8
Adjust the room thermostat.
Wait a few minutes. Press the reset button 29 (fig. 17): the red light goes out, the ignition cycle starts again. If the “safety” setting persists, have a qualified professional intervene.

Noises in the heating system

Presence of air or insufficient pressure

Heating radiators in SUMMER operation

Thermosiphon phenomenon at the start of the heating circuit

Purge the heating installation or restore the pressure, see § 8
In summer, close the heating outlet tap 41 (fig. 18), do not tfhoergsettatrot oref othpeenseitaasot n.

However, if these solutions remain unsuccessful, call a qualified professional.

-1C1/O2M0L0E1C 1037/025030144h-

C 47 rue Aristide Briand 92532 LEVALLOIS PERRET Cedex Tel. Consumer reception: 01 47 59 80 60 Tel.
Professional Technical Assistance: 01 47 59 80 20 Commercial Services Fax: 01 47 59 80 01
Fax Services Techniques : 01 47 59 80 02 www.chaffoteaux-maury.fr

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals