ITV PULSAR R290 Range Bike Owner’s Manual

June 15, 2024
ITV

ITV PULSAR R290 Range Bike Owner’s Manual
ITV PULSAR R290 Range Bike

INTRODUCTION

This manual has been created to provide the installer with information to carry out a correct installation and for the effective maintenance of the machine.

Furthermore, the user will find in the document a section referring to the cause of possible incidents, as well as complete information on their resolution.

Therefore, it is recommended to keep the manual in a safe place to resolve any questions related to the operation of the machine during its useful life.

WARNINGS

  • The installation of this equipment must be carried out by the Technical Service.
  • Connect only to a drinking water distribution network.
  • Use the new hoses supplied with the appliance. Old hoses must not be reused.
  • The socket must always be located in an accessible place.
  • When positioning the appliance, make sure that the power cord is not trapped or damaged.
  • Do not place multiple portable power outlets or portable power sources at the rear of the appliance.
  • Always disconnect power to the machine before any cleaning or maintenance service.
  • Any necessary change in the electrical installation for the proper connection of the machine must be carried out exclusively by qualified and certified professional personnel.
  • Modifying or attempting to modify this machine is extremely dangerous and will void the warranty.
  • The appliance must not be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
  • Connect only to potable water supply. This machine is not intended to be used outdoors or exposed to rain.
  • The machine must be connected using the power cord supplied with the equipment. It is not intended to be connected to a fixed pipeline.
  • To avoid danger due to instability of the appliance, it must be fixed in accordance with the instructions.

If the power cable is damaged, it must be replaced with a special mounting cable that will be supplied by the manufacturer or after-sales service. This replacement must be carried out only by a qualified technical service.

It is mandatory to connect the equipment to ground to avoid possible electric shocks to people or damage to the equipment. The machine must be grounded in accordance with local and/or national regulations.
The manufacturer disclaims any responsibility in the event of damage occurring due to the lack of ground installation.

To ensure the proper functioning and efficiency of this equipment, it is very important to follow the manufacturer’s recommendations, especially those related to cleaning and maintenance operations, which must only be carried out by qualified personnel.

ATTENTION: The intervention of unqualified personnel, in addition to being dangerous, can cause serious breakdowns. In case of damage, contact your dealer. We recommend always using original spare parts.

ITV reserves the right to make changes to specifications and design without notice.

WE REMIND YOU THAT MAINTENANCE AND CLEANING OPERATIONS ARE NOT INCLUDED IN THE WARRANTY AND THEREFORE, THEY WILL BE BILLED BY THE INSTALLER.

This sign indicates “Risk of Fire/Flammable Materials” due to the use of flammable refrigerant.

For this reason, the following warnings should be considered:

  • Keep the openings for ventilation of the appliance casing or built-in furniture without obstructing it.
  • Do not use mechanical devices or other means to accelerate defrosting, only those recommended by the manufacturer.
  • Do not damage the refrigerant circuit.
  • Do not use electrical devices inside the food compartments, unless they are recommended by the manufacturer.
  • Explosive substances, such as aerosols with flammable propellant, must not be stored in this appliance.

In case of refrigerant leak:

  • Do not generate a flame in the surroundings of the appliance.
  • Do not turn on/off switches or connect/disconnect plugs in the area of the appliance.
  • Do not use a direct flame.
  • Immediately ventilate the area of the appliance by opening doors and windows.
  • Call an authorized technical service.

Disposal of the ice machine: ITV encourages you to follow the regulations of each country regarding the ecological disposal of electrical and electronic devices such as this. The user who wants to dispose of this equipment must contact the manufacturer and follow the appropriate differentiated collection method for subsequent treatment.

MACHINE RECEPTION

Inspect the outer packaging. In case of damage, make the corresponding claim to the carrier. To confirm the existence of damage, unpack the machine in the presence of the carrier and note any damage to the equipment on the receipt document or transport document.

Always indicate the number and model of the machine. This number is printed in three places:

  1. Packaging: On the outside it containt a label with the serial number.
    Machine Reception

  2. Exterior of the unit: On the rear panel of the unit there is a label with the same characteristics as the previous one.
    Exterior of the unit

  3. Nameplate: On the back of the machine

Check that the installation kit inside the machine is complete and includes:

  • Shovel
  • ¾ inch water inlet hose
  • 22mm drain hose
  • Filter gasket
  • User manual
  • Warranty

CAUTION: All packaging elements (plastic bags, cardboard boxes and wooden pallets) must be kept out of the reach of children, as they are a source of potential danger.

INSTALLATION

ICE MACHINE LOCATION

This ice maker is not designed to be used outdoors. The ice maker should not be located next to ovens, grills, or other equipment that produces a lot of heat.

Incorrect installation of the equipment may cause damage to persons, animals or property, for which the manufacturer cannot be held responsible.

PULSAR machines are designed to operate at ambient temperatures between 10ºC and 43ºC (50ºF and 109ºF) and inlet water temperatures between 5ºC and 35ºC (41ºF and 95ºF).

Below the minimum temperatures there may be some difficulties in making the ice flakes. Above the maximum temperature, compressor life is shortened and output is substantially lower.

Airflow on compact air-cooled machines enters through the front grille, entering the right front, and exiting the rear. In addition, the unit is equipped with a rear ventilation grill. Do not obstruct the front grill with any object.
Installation

If the frontal ventilation is not sufficient, the outlet is totally or partially obstructed or due to its location it receives hot air from another appliance, we recommend, if it is not possible to change the location of the machine, INSTALLING A CONDENSED MACHINE BY WATER.

IT IS IMPORTANT THAT THE WATER PIPES DO NOT PASS NEAR HEAT SOURCES SO AS NOT TO LOSE ICE PRODUCTION.

The location should allow sufficient clearance for the water, drain, and electrical connections at the rear of the ice maker.

ICE MACHINE LEVELING

Use a level on the top of the ice maker to ensure the equipment is perfectly level.

Screw the leveling feet into the bottom of the ice maker as far as they will go. Place the machine in its final position.

Use a level on top of the ice maker. Adjust each leg as necessary to level the ice maker from front to back and side to side.
Ice Machine Leveling

MINIMUM DISTANCE TO OBSTACLES

The machines expel hot air through the grilles, which must be discharged into the room and not accumulate.
This is particularly important for the air expelled from the rear of the machines: a space of at least 10cm must be left up to the wall, allowing the air to flow from behind and out so that there is a renewal of this, avoiding the formation of hot air pockets in that area that could reduce the machine’s ice production and even activate its protection against excessive temperature and stopping it.

Connection diagram:
The location should allow sufficient clearance for water drainage and electrical connections at the rear of the ice machine.
Connection diagram

WATER SUPPLY CONNECTION

The quality of the water supplied to the ice maker will influence the time between cleanings and ultimately the life of the product (mainly on water- cooled units). It will also have a notable influence on the appearance, hardness and flavor of the ice.

Local water conditions may require water treatment to inhibit scale formation and improve flavor and clarity. If you are installing a water filtration system, refer to the installation instructions supplied with the filtration system.

The pressure must be between 0.1MPa and 0.6MPa (1 and 6 bar). If the pressure exceeds these values, install a pressure regulator.

The water connection must be dedicated (only equipment hooked to the water line).

ATTENTION: The machine must be connected to the pipeline with adequate backflow protection in accordance with current national and local regulations.

DRAIN CONNECTION

GRAVITY DRAINAGE

The drain must be located lower than the level of the machine, at least 150mm.

It is advisable that the drain hose be 30mm in inner diameter and with a minimum slope of 3cm/meter.
Gravity Drainage

ELECTRIC CONNECTION
  • It is mandatory to connect the equipment to ground. To avoid possible electric shock to persons or damage to the equipment, the machine must be grounded in accordance with local and/or national regulations, as applicable.
  • The manufacturer disclaims any responsibility in the event that damage occurs due to the lack of ground installation.
  • The positioning of the appliance must ensure that the electrical supply is not damaged or choked.
  • Do not install portable multiple sockets or other portable power sources on the rear of the appliance.
  • The machine is supplied with a 1.5 m long cable.
  • If the power cable is damaged, it must be replaced with a special mounting cable that will be supplied by the manufacturer or by the after-sales service. This replacement must be carried out only by a qualified technical service.
  • The machine should be positioned so that there is a minimum of space between the back and the wall to allow easy and safe access to the cord plug.
  • It is advisable to install a remote switch to completely disconnect the machine.
  • Protect the outlet. Install appropriate switches, fuses and differential protector.

The voltage is indicated on the nameplate and in the technical specifications section of this manual. A voltage variation greater than 10% indicated on the nameplate may cause damage or prevent the machine from starting.

PRIOR CONTROL AND START-UP

PRIOR CHECK

a) Is the machine leveled?
b) Do the voltage and frequency match those on the nameplate?
c) Are the drains connected and working?
d) Are the ambient temperature and water temperature maintained in the following range?

| ATMOSPHERE| WATER
---|---|---
MAXIMUM| 43ºC/109.4ºF| 35ºC/95ºF
MINIMUM| 10ºC/50.0ºF| 5ºC/41ºF

e) Is the water pressure adequate?

MINIMUM 0.1MPa (1 bar)
MAXIMUM 0.6 MPa (6 bar)

NOTE: In case the inlet water pressure is greater than 6 bar, install a pressure reducer.

START UP

Once installation instructions have been followed (ventilation, site conditions, temperatures, water quality, etc.), proceed as follows:

  1. Open the water inlet. Verify the no existence of leakages.

  2. Open the door and remove the protection elements on the shield.

  3. Verify that the curtain moves freely.

  4. Connect the machine to the power supply.

  5. Push the switch on the machine front side.

  6. Verify that there are no vibrations or frictions on the elements.

  7. The machine has a timer governing startup, allowing for water to be recharged for the production cycle.

  8. Check that the water tank is filled with water and that the paddles send the water to the evaporator.

  9. Check the cubes after two cycles; they should be uniform in shape. If they do not come out correctly, or the unit does not make ice, contact an authorized service technician.
    Start up

  10. The unit produces ice until the bin is full, using a stop sensor. When the ice is removed from the bin, the unit will once again produce ice.

WARNING: this switch does not disconnect all the voltage inside the machine. Disconnect from the mains before handling.

COMPONENTS DESCRIPTION

REFRIGERATION DIAGRAM

Refrigeration diagram by air condenser
Refrigeration diagram

It consists of the following components:

  1. Compressor: It sucks in gases at low pressure from the cold source and supplies them with pressure and temperature to be discharged to the hot source.
  2. Condenser: receives the gases from the compressor where they give up heat to the mean (air or water).
  3. Evaporator: An evaporator that receives the refrigerant still with liquefied particles where they evaporate by absorbing heat from the mean. It is an isobaric and isothermal process.
  4. Capillar in all the models.
  5. Hot gas valve: is a valve that is installed between the compressor discharge line (high pressure hot gas) and the low pressure line.
  6. Drier: filters and dehydrates the coolant.
  7. Safety pressure switch (high pressure): Stops the machine, in case a pressure higher than this value is reached:
    R290 → OFF 25 bar (362 psi)
    Condensing pressure switch: Controls the fan (air condensation) or valve (water condensation) to keep the high pressure at the stipulated level:
    R290 → OFF11.5 – ON13.5 bar (167- 196 psi).
HYDRAULIC EQUIPMENT
  • Water inlet valve: Controlled by the control board; supplies water from to the tank.

  • Water tank: Maintains the water level by means of a level tube.

  • An overflow allows the water level in the tank to be maintained at the start of a new cycle. A drain plug is also provided to facilitate the draining of the tank and its cleaning.

  • Turbine: A set of blades/vanes arranged on a shaft that projects the water into the moulds of the horizontal evaporators. It is partially submerged in water and is driven by an electric motor.
    Hydraulic Equipment
    Hydraulic Equipment

  • Switch exterior→ Can disconnect the power supply to the equipment or a point in the control system that guarantees the disconnection of the electrical elements.

  • Electronic board (PCB control) → Control board that receives input signals, manages them and returns outputs, normally by activating relays.

  • Water inlet solenoid valve (EW) → Input fresh water for the new cycle.

  • Safety pressure switch (Pt)→ In the event of reaching the set pressure (25 bar), it stops the machine completely and sets it in alarm.

  • Condensing pressure swicth (Pc) → Starts or stops the fan or water inlet to maintain the set high pressure.

  • Stock thermostat→Bulb located inside the bin that allows the ice making cycle to stop when the temperature reaches an adjustable range of 1-4 degrees.

  • Motor-turbine→ Motor that drives the turbine through a pulley and a belt.

  • Compressor → It sucks in gases at low pressure from the cold source and supplies them with pressure and temperature to be discharged to the hot source.

CONTROL BOARD

Control Board

INPUTS

Symbol Description
SC Evaporator temperature NTC probe
P Safety pressure switch
N PCB push button
T Stock thermostat
OUTPUTS
Symbol Description
C Compressor
B Motor-turbine
EA Water inlet valve
GC Hot gas valve.

SIGNALLING LEDs

The following tables describe the signals provided by the different LEDs on the control board.

Input LEDs
The input LEDs are positioned next to each of their corresponding inputs. Orange LED color with active signal.

Output LEDs
The output LEDs are positioned next to their corresponding relays. Orange LED color with active signal.

Status LEDs. Normal work (fixed LEDs)
There are four additional red leds that signals machine status (continuous):

Continuous red LED LE1 LE2 LE3 LE4
Start up delay X
Ice cycle T>Tc X X
Ice cycle T<Tc X
Harvest t<tg X X
Harvest >tg X
Full bin X

Status LEDs. Alarm (Flashing LEDs)
The following table defines the alarm states of the machine, which can be differentiated with the following flashing of the status LEDs:

Flashing red LED DL1 DL2 DL3 DL4
Safety pressure switch X
Ice cycle timeout X
Harvest cycle timeout X
Faulty temperatura probe X

DIP SWITCHES SETTING

The following table describes the functionality of the micro-switches that the table has, that is, the work options that the combinations of these can provide:

DIP Switches DescripTION
1-4 (sw1-1/4) tf – ice production timer. See table
5-7 (sw1-5/7) tw – harvest timer. See table.
8 (sw1-8) Tc (Evaporator temperatura for timer start) ON=-12ºC / OFF=-8ºC
9 (sw2-1) Tg (Hot valve temperature). ON=+4ºC / OFF=+0ºC
10 (sw2-2) Safety high pressure switch trip function.ON= automatic reset

(minimum stop 30 min.) OFF=manual reset (power OFF-ON)
11 (sw2-3)| ON. Timeout alarms operation activated.
12 (sw2-4)| Always ON for these models.

The following table shows the default intensity configuration in each of the possible combinations allowed by the switches on the control board:

SWITCH 1 (SW1) TF (MIN)
1 2
OFF OFF
ON OFF
OFF ON
ON ON
OFF OFF
ON OFF
OFF ON
ON ON
OFF OFF
ON OFF
OFF ON
ON ON
OFF OFF
ON OFF
OFF ON
ON ON

The factory default will be indicated on the machine’s wiring diagram, located on the cover of the electrical panel.

FUNCTIONS OF THE INTERNAL BUTTON ON THE PCB

Function depends on the unit status:

  • Start up timer: Finish initial delay y passes to ice production stage
  • Ice production. Switches to harvest
  • Harvest. Switches to Ice production

Wash cycle activation

Keep pressed the button while switching on main front switch. Wash cycle is activated and only the water recirculation pump is running. There is a maximum time for this cycle of 30 min. After this time, pump stops.

Wash cycle is finished by switching off main power.

Read cleaning and sanitizing instructions for proper usage of this function.

SEQUENCE OF OPERATION

Once you connect the machine there is a time delay of 140” during which the water valve is activated to ensure the water tray is filled. Compressor, pump will be off.
Once the time is up, it continues with a harvest cycle and the compressor starts.

During take-off, the water tank where the turbines are located is filled and the water above the set level goes out through an overflow.
After take-off, ice production starts, so the turbine starts running, the hot gas valve closes and the freezing cycle begins. The blades push the water into the rows of ice cubes in the evaporator, where the water starts to freeze and make ice.
Hydraulic Equipment

When the temperature probe (#3) at the end of the evaporator reaches an adjusted value Tc (-12/-8°C), the fabrication continues the fixed time with the combination of dip-switches 1-4 (see table). This way we can ensure the filling of the ICE CUBE is correct in different working conditions.

Once the production time is over the harvest phase starts. The pump stops, the hot gas and the water inlet valves open. When the evaporator temperature probe (#3) reaches an adjusted value Tg (4/0°C) the harvest continues the fixed time with the combination of dip-switches 5-7 (see table). Water is poured
over the evaporator helping unstick the ice cubes from the plastic frame.
After the harvest cycle, the machine comes back to the production cycle.

At the beginning of each Harvest cycle, the PCB checks if the Thermostat is open or close. Once the ice bin is full and the ice cubes cover the thermostat tube, the contact open, so when the harvest begins, the machine will stop until the contact of the thermostat close again. When it close, it starts with a harvest cycle and then it will continue with the production cycle again.

ALARMS

They detect operational malfunctions. They are indicated with the flashing status Leds LE1-4.
In case that a machine stop has been caused by alarm, the reset is done by switching OFF and ON the main switch. If the dip-switch 11 OFF, time alarms are not to be followed.

SAFETY HIGH PRESSURE SWITCH

When the pressure contact (P) trips, instantly, all outputs switch over to off position.

When it is closed again, there are two possibilities:

  • Dip-switch 10 OFF. Manual reset. The machine remains stopped until reset to Initial start-up.
  • Dip-switch 10 ON. Automatic reset. The machine check pressure switch status every 30 min.

When closed, the machine will continue at the position where it was. Signalling: Flashing LE1.

LONG HARVEST

If the harvest time is longer than 5 min., the harvest is interrupted, switching over to the production cycle. If the same happens again at the next harvest, the machine will stop. Signalling: Flashing LE3.

ICE PRODUCTION CYCLE TIMEOUT
If during the production cycle, evaporator temperature probe has not reached the set temperature Tc in more than 60 min, the machine will stop until reset. Signalling: Flashing LE2.

FAULTY TEMPERATURE PROBE
If PCB detects that evaporator temperature probe is broken or unconnected, the machine will stop Signalling: Flashing LE4.

Probe type is NTC and resistance value must be 10kΩ at 25°C.

MAINTENANCE AND CLEANING PROCEDURES

It is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition. Ice machines also require occasional cleaning of their water systems with a specifically designed chemical.
These chemical dissolves mineral build up that forms during the ice making process.

Sanitize the ice storage bin as frequently as local health codes require, and every time the ice machine is cleaned and sanitized.

The ice machine’s water system should be cleaned and sanitized at least twice a year.

CAUTION: Do not mix Ice Machine Cleaner and Sanitizer solutions together.
WARNING: Wear rubber gloves and safety goggles when handling Ice Machine Cleaner or Sanitizer.
WARNING: Unit should always be disconnected during maintenance/cleaning procedures.

RUBBER GLOVES AND SAFETY GOGGLES SHOULD BE WORN WHEN HANDLING ICE MACHINE CLEANER OR SANITIZER.

CLEANING THE AIR CONDENSER
  1. Disconnect the machine.

  2. Disconnect machine and close water faucet.

  3. Remove the front grid by removing the two screws placed at front side (see figure)
    Hydraulic Equipment

  4. Clean condenser using a vacuum cleaner, soft brush or low pressure air. Clean from top to bottom, not side to side. Be careful not to bend the fins of the condenser.

  5. Open the water inlet valve or tap.

  6. Switch on the power supply to the machine.

CLEANING THE WATER CONDENSER

  1. Disconnect the machine.
  2. Disconnect the water inlet or close the faucet.
  3. Disconnect the water inlet and outlet from the condenser.
  4. Prepare a solution at the 50% of phosphoric acid and distilled or demineralized water.
  5. Make the solution circulate through the condenser. (The solution is more effective if hot – between 35ºC [95ºF] and 40ºC [104ºF]).
CLEANING THE ICE BIN AND EXTERIOR
  1. Disconnect the machine, close water faucet and empty storage bin of ice.
  2. Use the cleaner/water solution to clean all surfaces of the bin. Use a nylon brush or cloth. Then rinse all areas thoroughly with clean water.
  3. Use the sanitizer/water solution to sanitize all surfaces of the bin. Use a nylon brush or cloth.
  4. Rinse with plenty of water, dry, run the machine and open water faucet.
WATER LEAKAGE CHECKING

This must be done whenever maintenance is carried out on the machine: check all water connections, braces, tubes and hoses in order to eliminate leaks and prevent breakages and flooding.

CLEANING THE HYDRAULIC SYSTEM
  1. Set the switch to the OFF position after ice falls from the evaporator at the end of a harvest cycle or set the switch to the OFF position and allow the ice to melt off the evaporator.
    CAUTION: Never use anything to force ice from the evaporator.

  2. Remove all ice from the bin.

  3. Remove the top panel.
    Hydraulic System

  4. Remove the universal Pulsar cap for drain operations near the pump and empty the water tray.
    Return it to their original position to avoid water spill.
    Hydraulic System

  5. Prepare a solution of an appropriate product for the cleaning of ice machines (lime). Do not use hydrochloric acid. We recommend the use of any approved scale removal product prepared according to the manufacturer’s instructions as for example CalKlin.

  6. Fill water tray with the solution

  7. Disconnect power. Turn on the machine pushing SW3 (see picture). Let solution stand for 30-40 minutes and then switch off the machine. Disconnect power.
    Hydraulic System

  8. Remove the universal Pulsar cap to drain and purge out the ice machine scale remover and residue. Replace it.

  9. Mix enough cleaning solution (as in point e) to clean parts and interior food zone surfaces.

  10. Clean all surfaces of the shield (#3) with the cleaner solution using a brush (not a wire brush) or cloth. Rinse all areas with water.

  11. Clean all the interior surfaces of the freezing compartment (including storage bin) with the cleaner solution using a brush or cloth. Rinse all areas with water.

  12. Mix a disinfectant solution using a sanitizer approved for food equipment (following the manufacturer’s instructions for use).

  13. Sanitize all the interior surfaces of the freezing compartment (including the storage bin) applying liberally sanitizer solution, using a cloth or sponge.

  14. Connect power and water supplies.

  15. Fill water reservoir with the sanitizer solution.

  16. Switch on machine in order to run water pump. Let solution stand for 20 minutes and switch off.

  17. Remove the auxiliary cap to drain and purge out the sanitizer solution and residue. Replace it.

  18. Fill the water reservoir with water and switch on the machine to allow water to circulate for 5 minutes and then stop the machine. Repeat this operation two more times to rinse thoroughly (by removing the cap to drain the water and replacing it for each cleaning cycle).

  19. Return the back metal lid and the top panel to their position.

  20. Switch on machine and discard the first two harvests.

MAINTENANCE TABLE

ACTION| MONTHLY| QUARTERLY| SEMESTERLY| ANNUAL| BIENNIAL| T UNIT
---|---|---|---|---|---|---
Cleaning air condenser| | | | | | 30 minutes
Cleaning water condenser| | | | | | 90 minutes
Exterior and stock bin cleaning| | | | | | 30 minutes
Cleaning hydraulic system| | | | | | 30 minutes
General cleaning| | | | | | —

  • Depending on the characteristics of the environment
  • Indispensable/Essential
  • Depending on water quality
  • Performed by owner

Maintenance and cleaning procedures, as well as problems resulting from their non-performance, ARE NOT COVERED BY THE GUARANTEE. Service personnel will bill you for travel expenses, time spent and materials required for maintenance and cleaning of the unit.

TROUBLESHOOTING GUIDE

GENERAL QUESTIONS

Not all cubes are releasedHarvest time too short Low ice productionBlocked condenser or air access tocondenserNo ice productionThe belt is broken

PROBLEMS POSSIBLE CAUSES SOLUTION
None of the electrical systems work. No power Check power supply and

connection
Switch Interruptor OFF| Power on
None of the electrical systems work. Front pilot is ON| Full bin status (LE4 on) with no ice. Thermostat defective or incorrectly set| Check. Replace
PCB alarm.| Check the LED code
PCB ALARMS See section 6
Safety pressure switch| Dirty condenser| Clean condenser
Machine wrong located| Change machine location
Defective fan| Check. Replace
Water machine: Faulty water valve| Check. Replace
Defective safety / cooling switch| Check. Replace
NTC probe error| Defective probe| Check. Replace
Defective probe plug connection| Check.
**Ice cycle timeout| No frozen evaporator| Check refrigeration system
NTC probe faulty contact| Check probe fitting
Faulty hot gas valve/coil| Check. Replace
Harvest cycle timeout| Harvest do not happen| Check water inlet strainer
Faulty hot gas valve/coil| Check. Replace
Wrong cycle sequence| DIP-Switch 2-4 OFF| Set ON
OTHER PROBLEMS
Compressor does not run, but voltage is supplied| Compressor/electrical equipment defective| Check/replace
Compressor runs, but does not cool| Refrigeration system not working properly| Check load and components
Plate is energized, but does not turn on| Internal board fuse open| Replace
Shutdown due to full store, but no ice| Failure of the stock thermostat| Replace
Thermostat NOK placement| Correct positioning
Abnormal noise in the machine| Fan or fan blades in bad condition orloose| Fix or substitute
Deteriorated turbine bearings| Replace complete bin
Vibrating pipes or components| Reposition and/or fix
Noise in compressor| Substitute
White and partially formed cubes.| Dirty nozzles| Clean/Replace
Dirty suction filter| Clean/Replace
Lack of water at cycle´s end| Check water leaks
Too large cubes| Freezing time too large| Adjust by dip-switches 1-4
Probe makes bad contact| Adjust by means of dip switches
Too small cubes| Freezing time too short| Adjust by dip-switches 1-4
Dirty condenser| Clean
Faulty probe| Replace
Adjust by dip-switches
Freezing time too large (Ice slab)| Adjust by dip-switches
Faulty hot gas valve| Check / replace
Lack of water input| Check net pressure and input filters
Clean condenser; improve air circulation
Faulty hot gas valve, doesn t close totaly.| Replace
Low performance refrigeration system| Check
Replace
Tank water cap out of position**| Check and place correctly

TECHNICAL DATA

WIRING DIAGRAM
To see the wiring diagram, please the following QR code or click the link:
https://acortar.link/DHhIhM

OTHER TECHNICAL INFORMATION
For more technical information scan the following QR code or click the link:
https://acortar.link/O8zoKO
QR Code

  • Specification sheets
  • User manual
  • Exploded views
  • CAD / REVIT drawings
  • Technical videos

ITV PULSAR Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals