BOSCH FLM-420-NAC-S Signaling Device Interface Modules Installation Guide
- June 13, 2024
- Bosch
Table of Contents
BOSCH FLM-420-NAC-S Signaling Device Interface Modules
Installation Instructions
A| Xxx| xXx| xxX| FPA-5000
FPA-1200|
BZ 500 LSN
UEZ 2000 LSN
UGM 2020
---|---|---|---|---|---
0 0 0
| 0| 0|
0
|
|
0 0 1 — 2 5 4
| 0 — 2| 0 — 9| 0 — 9| |
CL 0 0| CL| 0|
0
|
|
NOTICE!
Installation must only be performed by authorized and specialized personnel!
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
DANGER!
Live components and stripped cable! Risk of injury from electric shock.
The system must be current-free during connection work.
Functional description
FLM-420-NAC Signaling Device Interface Modules make it possible to connect
sounder, strobes, and horns to LSN fire panels. Each interface offers one
monitored primary line. The control of the signaling device line
(NAC=Notification Appliance Circuit) is performed through polarity reversal.
Interface module variants:
- FLM-420-NAC-S for surface-mounting with housing (see Figure 2 to Figure 6, Page 5 to Page 8).
- FLM-420-NAC-D for installation on a DIN rail with adapter (see Figure 7 and Figure 8, Page 9 to 10).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 1, Page 4).
Address (A) | Operating mode |
---|---|
0 0 0 | Loop/stub in LSN improved version mode with automatic addressing (T-tap |
system not possible)
0 0 1 — 2 5 4| Loop/stub/T-tap system in LSN improved version mode with manual
addressing
CL 0 0| Loop/stub in LSN classic mode
2 5 5 — 2 9 9| Non-permitted address range (error message on fire panel)!
Connection
Terminals | Function | Connection diagram |
---|---|---|
IN: b | a | NAC zone input |
- Stub: see Figure 9, Page 11
- Loop: see Figure 10 , Page 11
OUT: b | a| NAC zone output
0 V | 24 V| Ext. power supply
LSN: a1- | b1+ | a2- | b2+| LSN in / LSN out
FAIL ac | FAIL bat| Fault ext. voltage / Fault ext. battery
Technical specifications
Display elements | 2 LEDs (red = alarm, green = normal operation) |
---|---|
Input voltage | 15 V DC — 33 V DC |
Max. current consumption from LSN | 6,06 mA (standby/during an alarm) |
Max. current consumption from ext. power supply | 15 mA (standby) + output |
current
Ext. power supply| 20,4 V DC — 29 V DC
Max. output current| 3 A (during an alarm, from ext. power supply)
EOL resistance| 3,9 kΩ
Classes of equipment as per IEC 60950| Class III equipment
Protection class as per IEC 60529| FLM-420-NAC-S: IP 54
FLM-420-NAC-D: IP 30
Permitted operating / storage temperature| -20 °C bis +50 °C / -25 °C bis +85
°C
Permitted relative humidity| < 96%, non-condensing
Material interface module housing| PPO (Noryl)
Material surface-mount housing| ABS + PC-Blend
Customer Support
Bosch Sicherheitssysteme GmbH
Werner-von-Siemens-Ring 10
85630Grasbrunn
Germany
www.boschsecurity.com
© Bosch Sicherheitssysteme GmbH, 2010
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>