Beluk CX Plus Power Factor Controller Instruction Manual

June 12, 2024
Beluk

Rev. 1.0
2023-01

CX Plus Power Factor Controller

Instruction Manual
Gebrauchsanweisung
Please read the operating instructions carefully before operating the unit.
Functional description: Power factor controller in the NV range for controlling capacitor contactors.
Installation place:  Control cabinet installation of compensation systems

Product specifications

Type :CXplus
Voltage range : 90-550 V AC
Fuse :  6 A
Measuring voltage :  90-550 V AC
Measuring current : 5 mA – 5 A
Switching outputs :   6R /12R | 6T/12T
Inputs :Digitaleingang
Communication interfaces : Optional:
This product contains
2x mounting brackets

DANGER

General safety notes

Failure to observe the following instructions may result in serious injury or death!
! DANGER
There is a risk of electric shock during installation!
Therefore, electrical devices may only be installed, operated, serviced and maintained by qualified professionals. A professional is someone who has the ability, experience and knowledge required for the construction, installation and operation of electrical equipment and who has been instructed in identification and avoidance of possible hazards.
During installation and maintenance, the relevant regulations for the installation of switchgear and accident prevention must be observed and adhered to. Devices with damaged or open housings or terminals must not be operated on the power grid and must be
disconnected immediately.
After disconnecting the device, 10 minutes must be waited until the capacitors have been discharged. Subsequently, doors or covers may be removed. It must be checked whether the disconnected area is voltage-free using a standardized measuring instrument.
Ther BELUK GmbH assumes no responsibility or warranty for damage to persons and equipment caused by improper installation and use.Beluk CX Plus Power
Factor Controller - icon

Mounting:|
---|---
Installation location:| in door of switch cabinet
Mounting position:| vertical
IP protection class:| front: IP41 / rear: IP20
Mounting type:| 2x mounting brackets

Connection diagram: CX plus -12R

Beluk CX Plus Power Factor Controller - Connection

NOTE: The CX plus is designed to control capacitive or inductive stages. Operating both stage types simultaneously is not possible.

Installation and commissioning

The working area must be de-energised and secured against unauthorised and unintentional reconnection. The absence of voltage must be determined with a standardised measuring device.
The de-energised system must be earthed and short-circuited. Neighbouring live parts must be covered and/or cordoned off.

  1. Before installation, the connection specifications of the CX plus must be compared with the data of the power grid.

  2. The current transformer must be short-circuited.
    NOTE: A current transformer which has been open-circuited generates a life-threatening voltage. This can lead to a destruction of the current transformer.

  3. Insert the CX plus into the panel cut-out and fix it by using both fixing clamps.

  4. Connect the grounding cable to the intended terminal on the backside of the device.

  5. All cables must be connected as it is depicted in the connection diagram.

  6. Fuse protection of the unit with 6A

  7. Remove the short-circuit bridge at the current transformer.

  8. The voltage can now be switched on.

  9. If the device is connected correctly, the display will light up for one second and all symbols will be displayed during a display test.

First Setup:

www.beluk-qr.de/download/Video_AI_BLR_CXplus_EN_01.mp4

Select: First Setup
YES / No
ENTER -> YES
Make the most important settings!
Un Nominal voltage
Ct Current transformer factor
External current transformer in the supply. Primary and secondary windings result in the factor e.g., 150 | 750/5A.
Pt Voltage transformer factor
In the case that no voltage transformer is connected | 1
Ai Automatic initialization
The phase angle between voltage and current is determined and which stage outputs are used.
YES: ALL stages are connected 3x
All connected stages “AUTO” unused outputs “OFF
10) After a successful First Setup, the display shows AUTO. The control starts after the set discharge time has been expired.

PFC| Control ON, OFF, Hold
Switching on, off or suspend the control
---|---
CP1| Target-cosϕ 1
Compensation target
St| Switching time
Delay between switching different stages
Out| Stage type AUTO, FON, FOFF, Flty

Main menu
A menu can be selected by pushing ; Submenus are entered with

AUTO or
no display: Measurement menu
INFO: Stage database
AUTO: Control is active (no menu item)
MANUAL: Manual mode
SETUP: Controller settings
ALARM: Alarm memory
More Information:

Beluk CX Plus Power Factor Controller - QR 1 http://www.beluk-qr.de/download/Video_AI_BLR_CXplus_EN_01.mp4

www.beluk.de
BELUK GmbH | Taubenstraße
D-86956 Schongau
Tel. +49 8861 2332-0