MASTER MT-DP96HMF Digital Multifunction Meter User Manual
- June 9, 2024
- MASTER
Table of Contents
MT-DP96HMF Digital Multifunction Meter
User Manual
MT-DP96HMF Digital Multifunction Meter
Thanks for choosing our product – MT-DP96HMF, Please read this manual
carefully and pay attention to below caution matters.
CAUTION
This product should be installed and maintained by professional person
Before operating this product inside or outside, please cut off the input
signal and power supply;
Please make sure all parts of the product don’t have voltage by suitable
voltage detection device
The power supply should be within the rated range
The below situation will result in device damage and abnormal working
Auxiliary power source voltage over range
Distribute system frequency over range
Current, voltage input polarity incorrect
Disconnect the communication plug under charged situation
No according requirement to connect terminal
Please don’t touch the terminals when the meter is in operation!
Function introduce
Measure function | Remark |
---|---|
Realtime measure | Three phase voltage (L-L, L-N) |
Three phase current and neutral current
System Frequency
P, Q, S, PF (per phase & total
Electric energry| KWh import
KVARh import
KWh export, KVARh export
Harmonics| THDU per phase
THDI per phase
HDI per phase from 2nd to 31st order
HDU per phase from 2nd to 31st order
Communication| RS485 Port MODBUS-RTU
Maximum Demand/| U,I,P,Q| Expand option/
Analog output/| 0-20mA/ 4-20mA/ 0-5V/ 0-10V
Digital input/| Dry contact type/
Relay output/| AC250V 5A Remote/ Alarm
Display type/| LCD
Technical parameter
Parameter
Signal Input/| Connection system| 3P3W/ 3P4W
Voltage| Measurement range| 519V L-L
Over load| Continuous: 1.2 Vn; Instantaneous: 2Vn
Power consumption| < 1VA
Current| Measurement range| 5A/ 1A
Over load| Continous: 1.2In; Instantaneous: 2In
Power consumption| < 1VA
Frequency| 45 – 65Hz
Auxiliary power supply| AC85-265V DC100-300V
Communication| RS485 communication port, physical layer isolation. According
international standard MODBUS-RTU agreement. Communication speed 1200-38400
(Default 9600)
Test type N81, E81, 081 (Default N81)
Analog output| 0-20mA/ 4-20mA/ 0-5V/ 0-10V
Relay output| Programme remote/ Alarm switching output Capacity 5A at 250VAC/
30VDC
Digital input| Remote switch input signal, dry contact input. Program relate
alarm output
---|---
Measure class| Current, Voltage, Active power, Energy: 0.5S; Reactive power:
1S; Frequency: ±0.1Hz
IP protection| IP53 for indoor type and PI65 for outdoor type
Environment| Working temperature: -10÷55°C Store temperature: -20÷75°C
Relative Humidity:<80%RH
Safe| Isolation: Signal, auxiliary power supply, output terminal crust
resistance >5MW and withstand voltage pulse >AC2KV
Installation and correction
LxH (mm)| AxB (mm)| SxY (mm)| SxY (mm) IP65| N (mm)|
M (mm)
---|---|---|---|---|---
96×96| 90.5×90.5| 91×91| 91.5×91.5| 94| 88
Active Pulse | Reactive Pulse | RS485 | Aux. Power Suply | ||
---|---|---|---|---|---|
Ep- | Ep+ | Ep- | Ep+ | B | |
48 | 47 | 50 | 49 | 59 | |
Relay Output | Digital input | Analog output | |||
--- | --- | --- | |||
DO1 | DO2 | DO3 | DO4 | COM | DI1 |
15 | 16 | 17 | 18 | 19 | 20 |
Display & Buttons
a. Four lines digital display measure information: Three phase voltage, three
phase current, active power, reactive power, power factor, frequency, switch
input, output, other switch input, two way active power, two way reactive
power, analog input, demand
b. K is light mean practice value is display value is 1.000 times. M is light
mean practice value is display value is 1.000.000 times
c. Measure item unit or characteristic: three phase voltage V, three phase
current A, active power W, reactive power VAR…
d. Buttons use in change or programme set:
| is change page button or value increase or decrease button
---|---
| is enter programme status
| is select confirm button
If there is no relative symbol display or the set data not working, It means the product without the relative function
Board | Content | Explain |
---|
DISP=1
-Three phase voltage
-Forward active energy Kwh| | Separate display voltage Ua, Ub, Uc (in the 3P4W)
In left fig.
Ua=5774V
Ub=5774V
Uc=5774V
Forward active energy = 2908.05KWh
DISP=2
-Three phase voltage
-Reverse active energy Kwh| | Separate display voltage Uab, Ubc, Uca (in the 3P4W)
In left fig.
Uab=10KV
Ubc=10KV
Uac=10KV
Reverse active energy =1000.02 Kwh
DISP=3
-Three phase current
-Forward reactive energy Kvarh| | Separate display current la, lb, lc (in the 3P4W)
In left fig.
la=5A
Ib=5A
Ic=5A
Reverse reactive energy = 50 Kvarh
DISP=4
-Total active power
-Total reactive power
-Total apparent power| | Total active power = 86.6KW
Total reactive power = 0000Kvar
Total apparent power =86.6KVA
Reverse reactive energy =100.08Kvarh
DISP=5
– Active power phase A
-Reactive power phase A
-Apparent power phase A| | Active power of phase A = 28.87KW
Reactive power of phase A = 0000Kvar
Apparent power of phase A =28.87KVA
Forward active energy =2908.05KWh
DISP=6
– Active power phase B
-Reactive power phase B
-Apparent power phase B| | Active power of phase B = 28.87KW
Reactive power of phase B = 0000Kvar
Apparent power of phase B =28.87KVA
Reverse active energy =1000.02KWh
DISP=7
– Active power phase C
-Reactive power phase C
-Apparent power phase C| | Active power of phase C = 28.87KW
Reactive power of phase C = 0000Kvar
Apparent power of phaseCB =28.87KVA
Forward reactive energy =50.00KVARh
DISP=8
– Average current
-Zero sequence current| | Average current = 5A
Zero sequence current = 0.06A
Reverse reactive energy =50.00KVARh
DISP=9
– Three phase total power factor
-Frequency
-Voltage unbalance| | Three phase total power factor =1.000
Frequency = 50Hz
Voltage unbalances = 9V
Forward active energy =2908.05KWh
DISP=10
Split phase power factor| | Power factor of phase A =0.999 (inductive load)
Power factor of phase B =0.999 (inductive load)
Power factor of phase C =0.999 (inductive load)
Reverse active energy =1000.02KWh
DISP=11
Total voltage harmonic| | In the left fig:
a.b.c phase total voltage harmonic =10%
DISP=12
2nd voltage harmonic| | In the left fig:
2nd voltage harmonic of a.b.c phase =10%
DISP= 41
31st voltage harmonic| | In the left fig: 31st voltage harmonic of a, b. c
phase =10%
DISP=42
Total current harmonic| | In the left fig: a.b.c phase total current harmonic
=10%
DISP =43
2nd current harmonic| | In the left fig: 2nd current harmonic of
a, b, c phase =10%
DISP= 72
31st current harmonic| | In the left fig:
31st current harmonic of a, b,c phase =10%
DISP=73
Residue current| | In left fig.
display Residual current value: 10.09mA
DISP=74
Digital input information from 1 to 12 way channel| | First line: 1-4 way channel
Second line: 5-8 way channel
Third line: 9-12 way channel
In left fig.: No.5 way, No.6 way, No.8 way Chanel are ON,other way Chanel is
OFF
DISP=75
Digital output information from 1 to 4 way channel| | In left fig.: No.1 way,
No.3 way, No.4 way Chanel are ON, No.2 way Chanel is OFF
Programme operation
In programme status, digital interface adopt layers structure menu type, meter
supply three lines number display (se fig. 5)
No.1 line is first layer menu information;
No.2 line is second layer menu information;
No.3 line is third layer menu information;
Exp: The fig.5 shown: No.1 layer: INPT = Signal input; No.2 layer: CT =
current transformer; No.3 layer: current value is 5, It means ratio of CT is
25/5A.
The digital display interface menu has the following organizational structure,
the user can choose the appropriate setting parameters according tho the
actual situation.
No.1 Layer | No.2 Layer | No.3 Layer | Description |
---|---|---|---|
System SET | Display DISP | 0000-0017 | 0000 mean automatic cycling display. Each |
board connect see table 6
DISL| 0001-0003 or 0000-0120| 0000-0120 is keening time of LCD back light.
0000 means the backlight keeping ON
Data clear
CL r. E| 1111| 1111 means the data clear other value is invalid
Signal Input
INPT| Wiring type Net| 0000 or other value| 0000 mean 3P4W system. Other value
is mean 3P3W system
---|---|---|---
Voltage trans. ratio PT| 1 ∼ 9999| PT value= PT primary value/ secondary value
Current trans. rato PT| 1 ∼ 9999| CT value= CT primary value/ secondary value
Communication Set CON i (i is 1 ∼ 2)| Address SN| 1 ∼ 247| Meter address range
1 to 247
---|---|---|---
Communication speed BAUD| 0001 ∼ 0004| 0001 is 1200; 0002 is 2400; 0003 is
4800; 0004 is 9600; 00005 is 9200; 00006 is 38400
Data format DATA| 0001 ∼ 0003| 0000 is E,8, 1; 0001 is 0,8,1; 00002 is N,8,1
Digital output Set DO- i (i is 1 ∼ 4)| Choose alarm item or close alarm| Set
alarm item’s specific threshold value| Choose alarm item, and set relative
threshold value (when alarm item is digital value, no need set threshold
value), once meet alarm condition, switch output working
---|---|---|---
Analog output Set
AO—i (i is 1 ∼ 4)| Chosen transmitter item or close analog output (refer to
8.2 analog output)| Set the full scale value of analog item| Choose
transmitter item’s and relative electrical parameter (0-20mA, 4-20mA,
4-12-20mA) For example, set “A0-1″ TYPE”0135″ UAL”5000”, which means A phase
current 0-5A corresponds to the transmitter output signal of first loop 4-20mA
Note: The above menu is applied to the product with complete functions. If you find there is no such menu in the product or the menu is not working, It means the product not supporting the function.
(Analog capacity output: other three ways is similar)
Version 1.0